Download LogicView for FFB

Transcript
User Manual
Freeze in
– In this mode the inputs are not scanned, the ladder executes and the outputs are
updated. By clicking the icon the next message will appear confirming the operation:
Fig 3. 157 – Confirming the Freeze In mode
Is possible to change the Toggle Value of the discrete inputs and FFB. Just right-click the input, then
Toggle Value and the input value will be inverted. The CPU can be in Run or Stop mode.
– In this mode the inputs are scanned, the ladder executes and the outputs are
Freeze out
not updated. They keep the last value. By clicking the icon the next message will appear confirming
the operation:
Fig 3. 158 – Confirming the Freeze Out mode
Is possible to change the Toggle Value of the discrete outputs. Just right-click the output, then
Toggle Value and the output value will be inverted. The CPU can be in Stop mode.
- In this mode the inputs are scanned, the ladder executes, but the outputs keep
Safe Mode
the safe values set by user. By clicking the icon the next message will appear confirming the
operation:
Fig 3. 159 – Confirming the Safe mode
– In this mode the hardware inputs are scanned, the ladder executes, the outputs
Force Mode
are updated and the user can act over the inputs which no exist in hardware. By clicking the icon the
next message will appear confirming the operation:
3.82