Download Battery Powered Optical Smoke Alarm

Transcript
FHB1 (27-7-11) User Manual:Layout 1
27/7/11
08:21
Page 1
OWNERS MANUAL
Recommend siting of smoke alarms in
single storey home with two sleeping areas
LOUNGE
Battery Powered
Optical Smoke Alarm
KITCHEN
BEDROOM
BEDROOM
K
BEDROOM
SMOKE ALARMS FOR MINIMUM PROTECTION
SMOKE ALARMS FOR INCREASED PROTECTION
HEAT ALARMS
BEDROOM
S
Recommend siting
of smoke alarms
in multi storey
R
homes
B
BEDROOM
BEDROOM
BEDROOM
LOUNGE
KITCHEN
GARAGE
B
BASEMENT
5. Where smoke alarms are located in a hallway,
corridor or landing, the alarm should be no further
than three metres from any bedroom door to assist
audibility behind closed doors
6. No point on the ceiling in any room, hallway or
corridor should be further than 7.5 metres from any
smoke alarm.
7. Heat alarms should not be used in escape routes
from the building. Where used in other areas, heat
alarms should be no more than 5.3 metres from
other heat or smoke alarms.
8. Do not install heat alarms in sleeping areas; for
example, bedrooms, nurseries, playrooms or areas
where the elderly and disabled may spend long
periods of time.
9. Do not install heat alarms on walls.
10. To give the earliest warning of a developing fire,
smoke alarms should be installed in all the rooms of
your home (other than those in point 2 of Choice
and Location of Alarms above).
SMOKE DETECTORS FOR MINIMUM PROTECTION
SMOKE DETECTORS FOR MORE PROTECTION
HEAT ALARMS
FHB1
Installation Procedure
Recommend position of alarms in a room, corridor or escape route.
300mm MINIMUM
FHB1 Product Description
Separate the alarm from the mounting plate. The product is
shipped with the batteries disconnected and the mounting
plate loose.
MINIMUM 600MM
All FireHawk Photoelectric type smoke alarms are
approved to EN14604-2005, the most recent and
rigorous European Smoke Alarm Standard. The
Photoelectric sensing chamber is particularly sensitive
to slow smouldering fires typically originating in living
rooms, bedrooms and hallways whilst being highly
resistant to nuisance alarms.
The life of the product can be significantly
reduced by adverse environments, incorrect
location and a failure to regularly clean and
maintain it according to the following
instructions. Incorrect location and a lack of
reasonable care may also cause it to malfunction
and will invalidate the warranty.
Product Features
• 9 volt PP3 type battery.
• Approved to EN14604:2005, Smoke alarm devices.
• Red LED flashes approximately every 40 seconds
confirming unit is receiving power and ready to
detect fire conditions. (Quiescent Mode)
• Low Battery Warning – Alarm gives one beep every
40 seconds.
• Test Button tests for sensitivity, circuitry, battery and
alarm sounder.
• Loud 85 Decibel Piezo Electric Alarm – Automatically
resets when hazardous condition has passed and
chamber is clear.
Choice and Location of Alarms
Ionisation type smoke alarms are best at detecting fast
flaming fire such as loose burning paper, however, their
operation can be significantly delayed the farther they
are from the source of the fire and smoke according to
recommendations in the British Standard 5839-pt6.
Unless there is a significant risk of fast, clean burning
fires in a particular area, photoelectric smoke alarms are
recommended by that Standard for living
accommodation where most fires originate in electrical
equipment and smoundering material such as furniture,
clothing, curtains and carpets.
Optical Smoke Alarms are best for sensing smouldering
fires and are therefore best suited for rooms containing
furniture, bedding and clothes such as escape routes,
lounges, bedrooms and other living rooms.
Heat Alarms are most suitable for kitchens, boiler rooms,
workshops and garages where dust, dirt and moisture
would contribute to nuisance alarms. NOTE – Heat
alarms should not be used in escape routes and should
always be interlinked to smoke alarms.
For minimum protection, install at least one smoke alarm
on each level of your home. They should be installed in
hallways, corridors and all escape routes from the
building and within 3 meters of all bedroom doors. All
alarms should be interconnected if supplied with the
interlink function.
Recommended siting of smoke alarms in single
storey home with one sleeping area.
DINING ROOM
KITCHEN
BEDROOM BEDROOM
LIVING ROOM
BEDROOM
SMOKE ALARMS FOR MINIMUM PROTECTION
SMOKE ALARMS FOR INCREASED PROTECTION
HEAT ALARMS
FHB1 Ver.1 16/5/11
L
150mm MINIMUM
300mm MINIMUM
ABOVE HEIGHT OF DOORS.
WINDOWS AND VENTS
Base Plate
NOTE: DO NOT MOUNT HEAT
ALARMS ON WALLS
Test Button
& LED/Light
Do Not Install Smoke Alarms
The life of this alarm can be significantly reduced by adverse
environments, incorrect location and a failure to regularly
clean and maintain it according to the following instructions.
Incorrect location and a lack of reasonable care may also
cause it to malfunction and will invalidate the warranty.
1. Do not locate near fans or extractors. These can pull
smoke and heat away from the alarms.
2. Do not install in or near high humidity areas such as
showers, bathrooms or kitchens where humidity
levels exceed 85% or the room temperature
exceeds 40O of falls below 0OC. These may cause
nuisance alarms and damage the detector.
3. Do not install in the peak of an “A” frame or sloping
ceiling. This may delay smoke and heat reaching
them due to the presence of still air.
4. Do not install less than 300mm from walls and light
fittings when mounted on the ceiling where heat and
still air may prevent smoke reaching the alarm.
5. Do not install in insect infected areas.
6. Do not install in areas subjected to heavy
concentrations of cigarette smoke that will cause
nuisance alarms and the alarm to become
contaminated.
Select desired location, refer
to the Section above. Connect the
battery and insert it into the battery
bay in the back of the alarm. Screw the mounting
base to ceiling using the fixings provided. Line up the slots
on the back of the alarm with the two catches inside
the mounting plate and mount the alarm.
Once the alarm is on the mounting plate twist it clockwise to
lock it into place. The alarm will not twist unless the battery
is fitted into its bay.
Testing the Alarm
Press the test button for at least 10 seconds to test the alarm.
The alarm should sound with a flashing red light then stop.
After testing check that the red light flashes approximately
every 40 seconds.
Test the alarm once a week to ensure correct operation.
WARNING – The electronic test button provides a full test of
the alarms functionality. Do not try to test the alarm using
either heat, smoke, or naked flame as damage will occur.
User Information
Protect your Home Against Fire
7. Do not install smoke alarms in kitchens, boiler
rooms and garages where fumes and dust may
cause nuisance alarms.
Contact your local Fire Brigade for a home safety check. This
information is free and will identify potential fire hazards in
and around your home.
8. Do not install heat alarms in sleeping areas; for
example, bedrooms, nurseries, playrooms or areas
where the elderly and disabled may spend long
periods of time.
Make sure all occupants of the home know what a fire alarm
sounds like. Prove and practise and fire escape plan and
arrange a suitable and safe assembly point.
Ensure everyone leaves the building as soon as possible.
• Do not run.
• Do not stop to collect belongings.
• If it is safe to do so, close all windows and doors as you
escape to prevent the spread of fire.
• Smoke is the main cause of death from fire. If trapped
inside the building, cover your mouth, conserve breath, and
crawl to safety.
9. Do not install on poorly insulated walls and ceilings
where cold air boundary layers could prevent smoke
reaching the alarm.
10. Do not install near objects that could prevent smoke
and heat reaching the alarm.
11. Do not install within 1500mm of fluorescent light
fitting that could trigger nuisance alarms.
12. Do not paint the alarm.
The location of the alarms must be in accordance with
applicable building regulations, in particular Part B. Further
help and guidance can also be found in BS5839 part 6.
Further Detailed Information on Alarm Location
The battery will last approximately one year. At the end of the
battery’s life the alarm will beep once every minute for a
minimum of one month.
To replace the battery, twist the alarm anticlockwise to
remove from the baseplate. Disconnect battery from the
alarm and replace with Duracell MN1604 or GP1604A. Fit
the battery into its bay and refit the alarm to the baseplate.
Test the alarm for correct operation using the test facility
whenever the battery is replaced.
The life of the battery can be significantly shortened by
periods of storage or use in temperatures below 5 degrees C
or above 30 degrees C. It will also be shortened by frequent
or extended periods in full alarm often caused by conditions
such as cigarette smoke, steam, aerosol spray and
condensation.
Problems are indicated in four ways:
1. The battery beeps once every 40 seconds indicating
a low battery.
2. The full alarm sounds for no reason. (A repeating
series of three beeps with flashing light).
3. The alarm does not sound when pressing the test
button.
4. The test button light remains steadily on or off
(i.e. does not flash approximately once every minute,
when the unit is not in alarm).
Inspect for obvious damage. Check that the alarm has been
installed in accordance with the instructions. In the case of
repeated nuisance alarms, check that it is free from dust,
cobwebs and external contamination from such things as
cigarette smoke, drying paint, spray from household aerosols
and steam that will ultimately shorten the life of the battery
and invalidate the warranty.
If this does not correct the problem, do NOT attempt to repair.
There are no user serviceable parts internally. If the smoke
alarm is within the warranty period and terms, indicate the
nature of the problem and return the unit with proof of
purchase to the address at the end of this manual. Units
beyond warranty cannot be economically repaired.
Warranty
Fireblitz guarantees to you, as the purchaser, that the enclosed
fire alarm will be free from defects in material, workmanship or
design under normal use and service for a period of 5 years.
This Guarantee is not assignable. Our liability to you under this
guarantee is limited to repairing or replacing any part which we
find to be defective in material, workmanship or design, free of
charge to the customer, upon sending the alarm with proof of
date of purchase, postage paid to Fireblitz Extinguisher Ltd,
Units 15/17 Manford Industrial Estate, Manor Road,
Erith, Kent DA8 2AJ.
The terms of this guarantee will not apply in the following
circumstances: If the alarm has been modified, dismantled,
contaminated, damaged, neglected or otherwise abused or
altered following the date of purchase, or if it fails to operate
due to incorrect siting, installation, maintenance or flat battery,
or damage caused by failure to abide by the instructions
supplied. It is specifically drawn to the users attention that
substantial periods in alarm will shorten battery life, during
which time the fire alarm will have provided valuable protection;
no Claim under the guarantee will be entertained.
The liability of Fireblitz Ltd, arising from the sale of this alarm
or under the terms of this guarantee shall not in any case
exceed the cost of replacement of the alarm. In no case,
shall Fireblitz Ltd be liable for consequential loss or damage
resulting from the failure of the alarm or the breach of this
or any other guarantee, express or implied or for damage
caused by failure to abide by the instructions supplied.
This guarantee does not affect your statutory rights.
Do not silence a fire alarm until you know the cause of
the alarm and when all occupants are safely outside the
building.
Alarm Maintenance
2. The detection element of smoke alarms should be in
between 25mm and 600mm below the ceiling, or in
the case of heat alarms between 25mm and
150mm.
WARNING – Do not store alarms in temperatures below 5
degrees and above 30 degrees, and in low humidity; this
may cause beeping and nuisance alarms when first installed.
These will clear after a short time when the alarm has
become acclimatised. Extended periods under these
conditions will reduce the life of the alarms and invalidate the
warranty.
3. Smoke and heat alarms should be at least 300mm
from any wall or light fitting.
A regular program of fire alarm maintenance will help to
keep your alarm in good working order.
4. If ceiling mounting is impractical smoke alarms may
be installed on walls provided that the area is no
longer or wider than 10 metres and the total area
does not exceed 50m2 and that:a. The detection element is between 150mm and
300mm below the ceiling.
b. The bottom of the detection element is above
openings such as vents, doors and opening
windows.
c. They are not mounted close to or above heaters
or air-conditioning vents.
• Test the alarms weekly making sure that all alarms in the
system sound within 10 seconds.
1. At least one smoke alarm should be installed in the
escape route on all floors of the building.
Troubleshooting
Contact Information for FireHawk
If you require any further help or information please
contact FireBlitz at the following address:Fireblitz Extinguisher Ltd
Units 15/17 Manford Industrial Estate
Manor Road, Erith, Kent DA8 2AJ
Email: [email protected]
www.fireblitz.co.uk
Tel: +44 (0)1322 342238 Fax: +44 (0)1322 331532
PLEASE KEEP THIS HANDBOOK IN A SAFE PLACE
• Vacuum the alarms every six months and wipe them with a
damp cloth.
• Do not paint the alarm.
A smoke alarm is a sensitive life-saving device. The life of
this alarm can be significantly reduced by adverse
environments, incorrect location and a failure to regularly
clean and maintain it according to the instructions. Incorrect
location and a lack of reasonable care may also cause it to
malfunction and will invalidate the warranty.
Fireblitz
Extinguisher Ltd
10
????-CPD-???? (Model FHB1)
EN 14604:2005 Smoke Alarm Devices
Technical Data: See Product Handbook.