< to adjust the display to the reading on the volt/ammeter. The controller should stabilize within one second. Repeat until the volt/ammeter reads 4.000mA. Press . to store the value. 4. Press the Right Key . at the Calibrate Rexmit 1 prompt. At the 20.000mA prompt press . once. Use the Up Key > or the Down Key < to adjust the display to the reading on the volt/ammeter. The controller should stabilize within one second. Repeat until the volt/ammeter reads 20.000mA. Press . to store the value. Volts 5. Connect the volt/ammeter to terminals 48 (+) and 49 (-). 6. Press the Right Key . at the Calibrate Rexmit 1 prompt. At the 1.000V prompt press . once. Use the Up Key > or the Down Key < to adjust the display to the reading on the volt/ammeter. The controller should stabilize within one second. Repeat until the volt/ammeter reads 1.000V. Press . to store the value. 7. Press the Right Key . at the Calibrate Rexmit 1 prompt. At the 10.000V prompt press . once. Use the Up Key > or the Down Key < to adjust the display to the reading on the volt/ammeter. The controller should stabilize within one second. Repeat until the volt/ammeter reads 10.000V. Press . to store the value. 8. Rewire for operation and verify calibration. Retransmit 2 Setup and Calibration 1. Connect the correct power supply to terminals 1, 2 and 3 (see the W iring Chapter and the Appendix). Milliamperes 2. Connect the volt/ammeter to terminals 47 (+) and 46 (-). 3. Press the Right Key . at the Calibrate Rexmit 2 prompt. At the 4.000mA prompt press . once. Use the Up Key > or the Down Key < to adjust the display to the reading on the volt/ammeter. The controller should stabilize within one second. Repeat until the volt/ammeter reads 4.000mA. Press . to store the value. 4. Press the Right Key . at the Calibrate Rexmit 2 prompt. At the 20.000mA prompt press . once. Use the Up Key > or the Down Key < to adjust the display to the reading on the volt/ammeter. The controller should stabilize within one second. Repeat until the volt/ammeter reads 20.000mA. Press . to store the value. Volts 5. Connect the volt/ammeter to terminals 45 (+) and 46 (-). 6. Press the Right Key . at the Calibrate Rexmit 2 prompt. At the 1.000V prompt press . once. Use the Up Key > or the Down Key < to adjust the display to the reading on the volt/ammeter. The controller should stabilize within one second. Repeat until the volt/ammeter reads 1.000V. Press . to store the value. 7. Press the Right Key . at the Calibrate Rexmit 2 prompt. At the 10.000V prompt press . once. Use the Up Key > or the Down Key Calibration Menu Map Calibrate Input 1 Calibrate Input 2 Calibrate Input 3 Calibrate Output 1A Calibrate Output 1B Calibrate Output 2A Calibrate Output 2B Calibrate Rexmit 1 Calibrate Rexmit 2 Restore In1 Cal Restore In2 Cal Restore In3 Cal 9.6 ■ Calibration Watlow Series F4S/D