Download agent`s MIB description
Transcript
agent’s MIB description référence : reference n° indice : index 34003597XT page 23/26 : AA 7. Traps monitored by UM-Client UM-Client are distributed basic management applications running on host systems, that provide domain alarm messages and shutdown script initiation activated by acknowledged SNMP traps received from MGE UPS SYSTEMS agents. UM-Client provides provides reliable cross-platform fail-safe shutdown of multiple distributed hosts powered by mid-range and large MGE UPS SYSTEMS SNMP instrumented UPS’s. It is recommended to use UM-Link configured with Auto-Learning disabled, in order to work easily with UMClient. Following is a list of MGE traps which are monitored by the UM-Client : Trap Level 1 : 9 upsAtLowCondition 31:upsOffInProgress 37:upsCommunicationFailure 38:upsCommunicationRestored UPS battery minimum condition status UPS off procedure under way State of serial communication with UPS Trap Level 2 : 1:upsBatteryFault 13:upsOnByPass 17:upsUtilityFailure 18:upsUtilityRestored 29:upsOffToStart UPS battery fault status UPS on bypass status UPS mains input failure indicator UPS mains input restored UPS off procedure initiated UM-Client acknoledges reception of these traps. For more information, please refer to the UM-Client User Manual. MGE UPS Systems agent’s MIB description 23