Positioning with digital outputs 4.2 Parameter configuration Monitoring Time Parameter Parameters Value range Monitoring time 0 to 100 000 ms Default 2000 0 = No monitoring Rounded up by the CPU in 4-ms steps. The CPU uses this monitoring time to monitor ● actual value of the position ● target approach Actual value and target approach monitoring is switched off when the value is set to "0". Actual Value Parameter Parameters Actual value monitoring Value range Yes No Default Yes The moving axis must cover a distance of least one pulse in specified direction within the monitoring time. Actual value monitoring is switched on at the start of a run. It remains active until the cut-off position is reached. Actual value monitoring is switched off when the monitoring time is set to "0". The run is canceled when the monitoring facility responds. The CPU does not detect the failure of a digital input. You can enable actual value monitoring for indirect detection of encoder or drive failure. Target Approach Monitoring Parameter Parameters Value range Target approach monitoring Yes No Default No The axis must reach the target range within the monitoring time after it has reached the cutoff position. Target approach monitoring is switched off when the monitoring time is set to "0". CPU 31xC: Technological functions Operating Instructions, 03/2011, A5E00105484-05 107
Related documents
1 2 3 4 5 6 7 8 AB FM 352-5 Boolean - Service, Support
SIMATIC Standard PID Control
CPU 31xC: Technologische Funktionen - Service
CPU 31xC Technologische Funktionen - kleissler
Dejan Bucar
Point-to-point Link CP 441 Installation and
Papyrus User Manual - Papyrus Library Administration System
SODIMM-PLC7001 User Manual
Descarga - Industry Support Siemens
- ISI D. Gatermann
PID Control for S7-300 and S7-400
PID Self-Tuner