Download User`s Manual
Transcript
6. Terminal Wiring Diagrams NOTE Do not use unassigned terminals as relay terminals. ■ UT450 Standard Type (Model UT450-0䊐 or UT450-3䊐) or Heating/Cooling Type(Model UT450-2䊐) *Wiring can only be carried out for controllers with 24 V DC loop power supply. 24 V DC loop power supply 21.6-28.0VDC (30 mA DC max.) RS-485 communication * Wiring can only be carried out 23 SDB(+) 24 + 43 SDA(-) - 44 Relay contact output 1 NO 2 COM 3 N 1 41 31 21 11 2 42 32 22 12 3 43 33 23 13 4 44 34 24 14 5 9 45 35 25 13 - 13 - 13 B 46 36 26 16 7 47 37 27 17 8 48 38 28 18 9 49 39 29 19 10 50 40 30 20 Control output Current/voltage pulse output 16 + 17 - Note:Select this option from the OT parameter. Alarm-1 output Relay No function AUTO when DI1=ON MAN when DI1=OFF AUTO when DI1=ON STOP when DI1=ON MAN when DI1=OFF RUN when DI1=OFF When switching target SP 1 to 4: 1.SP2.SP3.SP 4.SP No function STOP when DI2=ON RUN when DI2=OFF 2.SP when DI2=ON 2.SP when DI2=ON 1.SP when DI2=OFF 1.SP when DI2=OFF DI1 OFF ON OFF ON COM 7 Common Alarm-4 output AL4 34 No function No function * If all of the contact inputs are set to OFF, the controller uses the immediately preceding target setpoint. No function Common Remote when R/L=ON Local when R/L=OFF Remote when R/L=ON Local when R/L=OFF Common Common COM 35 Common Relay contact rating: 240 V AC, 1 A 30 V DC, 1 A (resistance load) Transistor contact rating: 24 V DC, 50 mA * OT is a setup parameter. You can change the settings of the parameter OT to change the control output type. See Initial Settings User’s Manual , for more information. COM 50 0% L 11 A 12 + 250 Ω 4-20mA 12 b 26 RDA(-) 27 SG 21 + 22 - 46 45 100% 13 - 13 B Specify in a range of 1-5 V DC, 0-2 V DC, or 0-10 V DC. mV/V input Before carrying out wiring, turn off the power to the controller and check that cables to be connected are not alive with a tester or the like because there is a possibility of electric shock. 9 1 41 31 21 11 2 42 32 22 12 3 43 33 23 13 4 44 34 24 14 5 45 35 25 15 6 46 36 26 16 7 47 37 27 17 8 48 38 28 18 9 49 39 29 19 10 50 40 30 20 13 - Retransmission output DI1 14 + 4-20 mA DC 15 - Load resistance: 600 Ω or less 15 V DC loop power supply 14 + DI2 +5V STOP when DI3=ON AUTO when DI3=ON STOP when DI3=ON RUN when DI3=OFF MAN when DI3=OFF RUN when DI3=OFF AUTO when DI4=ON No function No function MAN when DI4=OFF DI3 40 +5V DI4 39 +5V No function No function No function DI5 38 +5V No function No function No function DI6 37 Common Common Common COM 20 DI2 OFF OFF ON ON DI3 DI4 DI6 Common 40 39 38 37 * Alarm-4 output is optional function COM 20 +5V Remote when R/L=ON Remote when R/L=ON Remote when R/L=ON Local when R/L=OFF Local when R/L=OFF Local when R/L=OFF R/L 28 Common DI5 Alarm-1 output 18 R/L COM COM 30 AL1 6 14.5-18.0VDC (21 mA DC max.) Correspondence between parameter DIS and external contact input functions UT When DIS=0 When DIS=1 (Factory-shipped setting) No function AUTO when DI1=ON MAN when DI1=OFF AUTO when DI1=ON STOP when DI1=ON MAN when DI1=OFF RUN when DI1=OFF When switching target SP 1 to 4: 1.SP2.SP3.SP 4.SP No function STOP when DI2=ON RUN when DI2=OFF 2.SP when DI2=ON 2.SP when DI2=ON 1.SP when DI2=OFF 1.SP when DI2=OFF DI1 OFF ON OFF ON AL2 5 Alarm-2 output Alarm-3 output AL3 4 Common COM 7 Alarm-4 output AL4 34 DI3 ON OFF ON OFF ON OFF ON OFF DI4 OFF ON ON OFF OFF ON ON OFF DI5 OFF OFF OFF ON ON ON ON OFF No function COM 35 Contact rating: 12 V DC, 10 mA or more When DIS=4 DI2 OFF OFF ON ON Contact UT DI1 19 +5V DI2 18 +5V No function No function Common Common Remote when R/L=ON Local when R/L=OFF Remote when R/L=ON Local when R/L=OFF Remote when R/L=ON Local when R/L=OFF +5V DI3 +5V DI4 +5V +5V OT=1 OT=2 OT=3 Time proportional control Relay output (terminals 1 , 2 and 3 ) Time proportional control Voltage pulse output (terminals 16 and 17 ) Current output (terminals 16 and 17 ) On-off control Relay output (terminals 1 , 2 and 3 ) Common NOTE: External Contact Input If the power is turned on when the external contact input is OFF, the mode (SPN, R/L, or A/M) existing before the power is turned off will be continued. (except for RUN/STOP) Note: Select this option from the OT parameter. Cooling-side control Cooling-side control output output Current/voltage pulse output Relay contact output NC 4-20 mA DC, voltage pulse (12 V) + 46 NO 49 - 47 COM 50 Contact rating: 250 V AC, 3 A 30 V DC, 3 A (resistance load) L N 8 CAUTION Before carrying out wiring, turn off the power to the controller and check that cables to be connected are not alive with a tester or the like because there is a possibility of electric shock. 9 25 RDB(+) RDA(-) 21 + SG 22 - 11 A mV/V input 31 21 11 42 32 22 12 43 33 23 13 44 34 24 14 13 - 25 15 6 46 36 26 16 7 47 37 27 17 8 48 38 28 18 9 49 39 29 19 50 40 30 16 + 17 - 20 Relay AL2 5 Alarm-3 output AL3 4 14 + No function AUTO when DI1=ON MAN when DI1=OFF COM 7 Transistor No function Alarm-4 output AL4 34 Common COM 35 No function No function Relay contact rating: 240 V AC, 1 A 30 V DC, 1 A (resistance load) Transistor contact rating: 24 V DC, 50 mA L N NOTE: External Contact Input If the power is turned on when the external contact input is OFF, the mode (SPN, R/L, or A/M) existing before the power is turned off will be continued. (except for RUN/STOP) * OT is a setup parameter. You can change the settings of the parameter OT to change the control output type. See Initial Settings User’s Manual , for more information. Remote when R/L=ON Local when R/L=OFF 1.SP2.SP 3.SP4.SP 5.SP6.SP7.SP 8.SP DI5 OFF OFF OFF ON ON ON ON OFF No function DI6 OFF OFF OFF OFF OFF OFF OFF ON * If all of the contact inputs are set to OFF, the controller uses the immediately preceding target setpoint. No function DI1 OFF ON OFF ON DI2 OFF OFF ON ON UT DI1 19 DI2 18 No function No function No function No function Common Common Remote when R/L=ON Remote when R/L=ON Remote when R/L=ON Local when R/L=OFF Local when R/L=OFF Local when R/L=OFF Remote when R/L=ON Local when R/L=OFF Common Common DI5 38 Contact +5V Transistor contact DI1 +5V DI2 Common RDA(-) +5V DI3 +5V DI4 +5V +5V DI5 DI6 DI6 37 27 SG Common R/L 28 COM 30 COM Note:Select this option from the OT parameter. *Time proportional PID relay contact output is configured at factory before shipment. R/L COM COM 30 28 30 Contact rating: 12 V DC, 10 mA or more 8 Before carrying out wiring, turn off the power to the controller and check that cables to be connected are not alive with a tester or the like because there is a possibility of electric shock. 9 Alarm-1 output 40 39 AL1 6 Alarm-2 output AL2 5 Alarm-3 output AL3 4 Common COM 7 38 37 11 A Specify in a range of 1-5 V DC, 0-2 V DC, or 0-10 V DC. 12 + 12 + 250 Ω 4-20mA 12 b 13 - 13 - 13 B 1 21 11 2 22 12 3 23 13 4 24 14 5 25 15 6 26 16 7 27 17 8 28 18 9 29 30 15 V DC Power Supply Wiring to Two-wire Sensor Retransmission output * PV retransmission is configured at factory before shipment. Control output Current/voltage pulse output 16 + 19 17 - 4-20 mA DC 15 - Note:Select this option from the OT parameter. 14 + 20 15 - * If 15 V DC loop power supply is used, retransmission output cannot be used. 14.5-18.0VDC (21 mA DC max.) UT No function No function AUTO when DI1=ON MAN when DI1=OFF STOP when DI2=ON RUN when DI2=OFF Common No function When DIS=2 When DIS=3 When switching target SP 1 to 4: 1.SP 2.SP3.SP 4.SP 2.SP when DI2=ON 2.SP when DI2=ON 1.SP when DI2=OFF 1.SP when DI2=OFF DI1 OFF ON OFF ON DI2 OFF OFF ON ON Common Common STOP when DI3=ON AUTO when DI3=ON RUN when DI3=OFF MAN when DI3=OFF No function No function Remote when R/L=ON Local when R/L=OFF Remote when R/L=ON Local when R/L=OFF When DIS=4 AUTO when DI1=ON STOP when DI1=ON MAN when DI1=OFF RUN when DI1=OFF Remote when R/L=ON Local when R/L=OFF Remote when R/L=ON Local when R/L=OFF Common Common Common UT DI1 19 +5V Common STOP when DI3=ON RUN when DI3=OFF DI3 29 Transistor contact DI1 +5V DI2 DI2 18 COM 20 OT=5 OT=6 OT=7 OT=8 OT=9 OT=10 OT=11 OT=12 Heating side: Voltage pulse output (terminals 16 and 17 ) Cooling side: Relay output (terminals 48 , 49 and 50 ) Heating side: Current output (terminals 16 and 17 ) Cooling side: Relay output (terminals 48 , 49 and 50 ) Heating side: Relay output (terminals 1 , 2 and 3 ) Cooling side: Voltage pulse output (terminals 46 and 47 ) Heating side: Voltage pulse output (terminals 16 and 17 ) Cooling side: Voltage pulse output (terminals 46 and 47 ) Heating side: Current output (terminals 16 and 17 ) Cooling side: Voltage pulse output (terminals 46 and 47 ) Heating side: Relay output (terminals 1 , 2 and 3 ) Cooling side: Current output (terminals 46 and 47 ) Heating side: Voltage pulse output (terminals 16 and 17 ) Cooling side: Current output (terminals 46 and 47 ) Heating side: Current output (terminals 16 and 17 ) Cooling side: Current output (terminals 46 and 47 ) 14 COM * OT is a setup parameter. You can change the settings of the parameter OT to change the control output type. See Initial Settings User’s Manual , for more information. 19 * Wiring can only be carried out for controllers with 24 V DC loop power supply. 18 24 V DC Power Supply Wiring to Two-wire Sensor 20 12 DI3 +5V COM 30 Loop power supply 14.5 to 18.0 V DC Note: Connecting a 100 resistor to the terminals is optional. Model: X010-100-2 (resistor with M3.5 crimp-on terminal lugs) +5V Remote when R/L=ON R/L 28 Local when R/L=OFF Common Contact R/L COM Contact rating: 12 V DC, 10 mA or more NOTE: External Contact Input If the power is turned on when the external contact input is OFF, the mode (SPN, R/L, or A/M) existing before the power is turned off will be continued. (except for RUN/STOP) OT=4 (factory-set default) Two-wire transmitter 4-20mADC Correspondence between parameter DIS and external contact input functions When DIS=0 When DIS=1 (Factory-shipped setting) 30 Heating side: Relay output (terminals 1 , 2 and 3 ) Cooling side: Relay output (terminals 48 , 49 and 50 ) 13 Load resistance: 600 Ω or less 15 V DC loop power supply 4-20 mA DC, voltage pulse (12 V) PV input 0.4 to 2.0 V DC signal 15 Common Correspondence between parameter OT and heating-side/cooling-side output types 12 External resistor 100 (Note) 14 + * DIS is a setup parameter. Changing DIS setpoint allows you to change the function of external contact input. Relay contact rating: 240 V AC, 1 A 30 V DC, 1 A (resistance load) Transistor contact rating: 24 V DC, 50 mA 28 Note: Connecting a 250 Ω resistor to the terminals is optional. Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs) 13 - 10 Allowable range: 100 to 240 V AC (10%) (free voltage) 50/60 Hz shared 18 set the PV input type to 1-5 V DC (setpoint “41”). 12 + Contact rating: 12 V DC, 10 mA or more The control output types, “relay output” and “voltage pulse output” shown in the table above refer to those of time proportional control. To change the type to a relay output for on-off control, select “Relay Terminals” and change the setpoint of the proportional band to “0.” 37 * When receiving 4-20 mA DC current signals, RTD input +5V R/L 38 䊏 Receiving 4-20 mA DC Current Signals by the Controller mV/V input Alarm output 20 COM 20 Common Common Common TC input Default: 1-5 V DC 10 19 COM Common Common Common When DIS=4 STOP when DI3=ON AUTO when DI3=ON STOP when DI3=ON DI3 40 RUN when DI3=OFF MAN when DI3=OFF RUN when DI3=OFF AUTO when DI4=ON No function DI4 39 No function MAN when DI4=OFF DI3 ON OFF ON OFF ON OFF ON OFF DI4 OFF ON ON OFF OFF ON ON OFF No function When DIS=3 26 22 - CAUTION Power supply 14.5-18.0VDC (21 mA DC max.) 2.SP when DI2=ON 2.SP when DI2=ON 1.SP when DI2=OFF 1.SP when DI2=OFF When switching target SP 1 to 8: 3 * If 15 V DC loop power supply is used, retransmission output cannot be used. switching target AUTO when DI1=ON STOP when DI1=ON When SP 1 to 4: MAN when DI1=OFF RUN when DI1=OFF 1.SP2.SP3.SP 4.SP STOP when DI2=ON RUN when DI2=OFF COM Relay No function When DIS=2 2 Power supply Correspondence between parameter DIS and external contact input functions When DIS=1 (Factory-shipped setting) NO Load resistance: 600 Ω or less 15 V DC loop power supply 39 +5V Remote when R/L=ON Remote when R/L=ON Local when R/L=OFF Local when R/L=OFF R/L 28 PV input * Not configured at factory before shipment See Initial Settings User’s Manual , for more information. * Wiring can only be carried out for 21 + Contact rating: 250 V AC, 3 A 30 V DC, 3 A (resistance load) 4-20 mA DC 15 - 4-20 mA DC, voltage pulse (12 V) When DIS=0 No function Common * PV retransmission is configured at factory before shipment. 14 + Heating-side control output Note:Select this option Current/voltage from the OT pulse output parameter. Alarm output Alarm-2 output 1 NC 35 UT Control output Relay contact output * DIS is a setup parameter. Changing DIS setpoint allows you to change the function of external contact input. AL1 6 Note: Connecting a 250 Ω resistor to the terminals is optional. Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs) Retransmission output SDA(-) 25 RDB(+) 13 - 12 + 41 24 250 Ω 4-20mA 13 B Common for controllers with communication controllers with remote input. functions. Remote input Maximum baud rate: 9600 bps 23 SDB(+) 12 + 12 b 15 - Alarm-1 output set the PV input type to 1-5 V DC (setpoint “41”). 12 + Specify in a range of 1-5 V DC, 0-2 V DC, or 0-10 V DC. RS-485 communication * Wiring can only be carried out * When receiving 4-20 mA DC current signals, RTD input Default: 1-5 V DC 45 Allowable range: 100 to 240 V AC (10%) (free voltage) 50/60 Hz shared * Alarm-4 output is optional function TC input 40 ■ UT420 Standard Type (Model UT420-0䊐) 䊏 Receiving 4-20 mA DC Current Signals with the Controller 13 - 5 10 10 * Wiring can only be carried out for controllers with remote input. Remote input SDA(-) 27 Heating-side control output Relay contact output Note: Select this option from the OT parameter. *Time proportional PID relay contact 1 NC 1 output is configured at factory before shipment. 2 NO 2 3 COM 3 4 Power supply 24 26 Contact rating: 250 V AC, 3 A 30 V DC, 3 A (resistance load) Power supply for controllers with communication functions. Maximum baud rate: 9600 bps 23 SDB(+) *Time proportional PID relay contact output is configured at factory before shipment. 48 PV input * Not configured at factory before shipment See Initial Settings User’s Manual , for more information. RS-485 communication * Wiring can only be carried out 18 20 COM 20 Common Common NOTE: External Contact Input If the power is turned on when the external contact input is OFF, the mode (SPN, R/L, or A/M) existing before the power is turned off will be continued. (except for RUN/STOP) ■ UT450 Heating/Cooling Type (Model UT450-2䊐) 19 COM Correspondence between parameter OT and control output types OT=0 (factory-set default) DI5 DI6 DI6 37 No function No function Transistor contact DI1 DI2 DI5 38 No function No function No function DI6 OFF OFF OFF OFF OFF OFF OFF ON * If all of the contact inputs are set to OFF, the controller uses the immediately preceding target setpoint. No function 30 When DIS=3 STOP when DI3=ON AUTO when DI3=ON STOP when DI3=ON DI3 40 RUN when DI3=OFF MAN when DI3=OFF RUN when DI3=OFF AUTO when DI4=ON DI4 39 No function No function MAN when DI4=OFF 1.SP2.SP 3.SP4.SP 5.SP6.SP7.SP 8.SP No function Common When DIS=2 When switching target SP 1 to 8: No function Relay contact rating: 240 V AC, 1 A 30 V DC, 1 A (resistance load) Transistor contact rating: 24 V DC, 50 mA 28 * If 15 V DC loop power supply is used, retransmission output cannot be used. * DIS is a setup parameter. Changing DIS setpoint allows you to change the function of external contact input. Alarm output 19 * PV retransmission is configured at factory before shipment. 15 - Transistor contact +5V Note: Connecting a 250 Ω resistor to the terminals is optional. Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs) 12 + Allowable range: 100 to 240 V AC (10%) (free voltage) 50/60 Hz shared +5V DI2 18 Common 8 N Contact UT DI1 19 When DIS=4 set the PV input type to 1-5 V DC (setpoint “41”). 12 + Remote input 47 CAUTION Transistor Transistor * Alarm-4 output is optional function DI3 DI4 DI5 DI6 No function 1.SP2.SP 3.SP4.SP 5.SP6.SP7.SP 8.SP ON OFF ON OFF ON OFF ON OFF OFF ON ON OFF OFF ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF ON 49 Relay When switching target SP 1 to 8: No function When DIS=3 * When receiving 4-20 mA DC current signals, RTD input 10 When DIS=1 (Factory-shipped setting) AL3 4 Alarm-3 output L (Reverse) 14.5-18.0VDC (21 mA DC max.) When DIS=0 AL2 5 Alarm-2 output 48 Power supply * If 15 V DC loop power supply is used, retransmission output cannot be used. Correspondence between parameter DIS and external contact input functions AL1 6 H (Direct) Power supply * DIS is a setup parameter. Changing DIS setpoint allows you to change the function of external contact input. When DIS=2 TC input Default: 1-5 V DC Contact rating: 250 V AC, 3 A Resistance: 100 to 2.5 k 30 V DC, 3 A (resistance load) Load resistance: 600 Ω or less 15 V DC loop power supply 4-20 mA DC, voltage pulse (12 V) SDA(-) Feedback input 4-20 mA DC 15 - UT - 44 25 RDB(+) Relay contact output * PV retransmission is configured at factory before shipment. 15 - 14 + Alarm output 24 14 + 10 Allowable range: 100 to 240 V AC (10%) (free voltage) 50/60 Hz shared + 43 䊏 Receiving 4-20 mA DC Current Signals with the Controller PV input * Not configured at factory before shipment See Initial Settings User’s Manual , for more information. for controllers with communication functions. Maximum baud rate: 9600 bps * Wiring can only be carried out for controllers with remote input. 23 SDB(+) Position proportional control output 13 - Retransmission output RS-485 communication * Wiring can only be carried out 13 - Note: Connecting a 250 Ω resistor to the terminals is optional. Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs) 15 6 21.6-28.0VDC (30 mA DC max.) 250 Ω 4-20mA 12 + Before carrying out wiring, turn off the power to the controller and check that cables to be connected are not alive with a tester or the like because there is a possibility of electric shock. 8 12 + 12 b mV/V input CAUTION L set the PV input type to 1-5 V DC (setpoint “41”). 12 + SG *Wiring can only be carried out for controllers with 24 V DC loop power supply. 24 V DC loop power supply * When receiving 4-20 mA DC current signals, RTD input Default: 1-5 V DC Contact rating: 250 V AC, 3 A 30 V DC, 3 A (resistance load) Power supply TC input Specify in a range of 1-5 V DC, 0-2 V DC, or 0-10 V DC. 22 - Note: Select this option from the OT parameter. *Time proportional PID relay contact output is configured at factory before shipment. Power supply 䊏 Receiving 4-20 mA DC Current Signals with the Controller PV input * Not configured at factory before shipment See Initial Settings User’s Manual , for more information. 11 A RDA(-) 27 Control output * Wiring can only be carried out for controllers with remote input. Remote input 21 + 25 RDB(+) 26 NC for controllers with communication functions. Maximum baud rate: 9600 bps ■ UT450 Position Proportional Type (Model UT450-1䊐 or UT450-4䊐) External resistor 250 (Note) 29 28 PV input 1 to 5 V DC signal 13 30 Two-wire transmitter 43 Loop power supply 21.6 to 28.0 V DC 4-20mADC 44 Correspondence between parameter OT and control output types OT=0 (factory-set default) OT=1 OT=2 OT=3 Time proportional control Relay output (terminals 1 , 2 and 3 ) Time proportional control Voltage pulse output (terminals 16 and 17 ) Current output (terminals 16 and 17 ) On-off control Relay output (terminals 1 , 2 and 3 ) Note: Connecting a 250 resistor to the terminals is optional. Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs) IM 05D01C12-01E (2)