SureCross Wireless I/O Network Manual
Input Units
Units
Description
Definition
LCD: 0000.0F
10
11
Asynchronous
Counter, 32-bit
The 32-bit counter value records counts up to 4.29 billion.
Asynchronous
Counter, 16-bit
The 16-bit counter value records counts up to 65535.
LCD: 0000 0000
LCD: 0000
Output Units
Units
0
Description
Definition
Raw
Displays the raw A/D conversion data with data ranges from 0 to 65535. This units type is typically used only for factory calibration.
LCD: Raw A/D hex value
1
4 to 20 mA
Analog unit. Modbus register contents are scaled such that 0 represents 4 mA and 65535 represents 20 mA.
LCD: 4.00mA–20.00mA
2
0 to 20 mA
Default analog input unit. Modbus register contents are scaled such that 0 represents 0 mA and
65535 represents 20 mA.
LCD: 0.00mA–20.00mA
3
Discrete (ON/OFF)
Default discrete unit.
LCD: ON/OFF
4
0 to 10V (Volts)
Analog unit using 0 to 10V instead of current. Modbus register contents are scaled such that 0
represents 0V and 65535 represents 10V.
LCD: 0.00V–10.00V
5
Signed Analog, 0 to For a signed value, such as temperature, that is to be converted to a voltage out value. Use null
10V
to set the start point and span to define the range. The null value is the starting temperature to be
associated with 0V. The span is the entire temperature range that is to be associated with 0 to
10V.
LCD: 0.00V–10.00V
6
Signed Analog, 0 to For a signed value, such as temperature, that is to be converted to a mA out value. Use null to
20 mA
set the start point and span to define the range. The null value is the starting temperature to be
associated with 0 mA. The span is the entire temperature range that is to be associated with 0 to
20 mA.
LCD: 0.00mA–20.00mA
7
Unsigned Analog, 0 For unsigned values, such as a counter, that is to be converted to a mA out value. Use the null to
to 20 mA
set the start point and span to define the range. The null value is the distance to be associated
with 0 mA. The span is the entire distance range that is to be associated with 0 to 20 mA.
LCD: 0.00mA–20.00mA
8
96
Signed Analog, 4 to In older models, this units type is for degree Celsius conversions only. Use null to set the start
20 mA (A)
point and span to define the range. The null value is the starting temperature to be associated
with 4 mA. The span is the entire temperature range that is to be associated with 4 to 20 mA. For
newer firmware models, type codes 8 and 9 are treated the same.