Download User manual
Transcript
SureCross Wireless I/O Network Manual Input Units Units Description Definition LCD: 0000.0F 10 11 Asynchronous Counter, 32-bit The 32-bit counter value records counts up to 4.29 billion. Asynchronous Counter, 16-bit The 16-bit counter value records counts up to 65535. LCD: 0000 0000 LCD: 0000 Output Units Units 0 Description Definition Raw Displays the raw A/D conversion data with data ranges from 0 to 65535. This units type is typically used only for factory calibration. LCD: Raw A/D hex value 1 4 to 20 mA Analog unit. Modbus register contents are scaled such that 0 represents 4 mA and 65535 represents 20 mA. LCD: 4.00mA–20.00mA 2 0 to 20 mA Default analog input unit. Modbus register contents are scaled such that 0 represents 0 mA and 65535 represents 20 mA. LCD: 0.00mA–20.00mA 3 Discrete (ON/OFF) Default discrete unit. LCD: ON/OFF 4 0 to 10V (Volts) Analog unit using 0 to 10V instead of current. Modbus register contents are scaled such that 0 represents 0V and 65535 represents 10V. LCD: 0.00V–10.00V 5 Signed Analog, 0 to For a signed value, such as temperature, that is to be converted to a voltage out value. Use null 10V to set the start point and span to define the range. The null value is the starting temperature to be associated with 0V. The span is the entire temperature range that is to be associated with 0 to 10V. LCD: 0.00V–10.00V 6 Signed Analog, 0 to For a signed value, such as temperature, that is to be converted to a mA out value. Use null to 20 mA set the start point and span to define the range. The null value is the starting temperature to be associated with 0 mA. The span is the entire temperature range that is to be associated with 0 to 20 mA. LCD: 0.00mA–20.00mA 7 Unsigned Analog, 0 For unsigned values, such as a counter, that is to be converted to a mA out value. Use the null to to 20 mA set the start point and span to define the range. The null value is the distance to be associated with 0 mA. The span is the entire distance range that is to be associated with 0 to 20 mA. LCD: 0.00mA–20.00mA 8 96 Signed Analog, 4 to In older models, this units type is for degree Celsius conversions only. Use null to set the start 20 mA (A) point and span to define the range. The null value is the starting temperature to be associated with 4 mA. The span is the entire temperature range that is to be associated with 4 to 20 mA. For newer firmware models, type codes 8 and 9 are treated the same. www.bannerengineering.com - tel: 763-544-3164 rev. H