Download User Manual for Motion Controllers - Extension Module
Transcript
Extension Module for Moog Ruggedized Motion Controller (MSC-R-IO) 5 Project Planning and Installation 5 Project Planning and Installation The following instructions must be observed in order to ensure that the M3000® automation system will be safely integrated into its application environment: Project Planning and Installation • IEC 61131 Especially the information contained in IEC 61131-4 • Safety All safety and accident prevention regulations applicable to the specific application (such as machinery directives, safety instructions contained in documentation, etc.) • Emergency stop The emergency stop devices (EN 60204) must remain in effect during all of the system's or facility's operational modes. • Restarting Unlocking of the emergency stop devices must not lead to uncontrolled or undefined restarting. Dangerous operational conditions of any kind must not arise following interruption or failure of the power supply. • Voltage Deviations and fluctuations of the supply and load voltages must not fall below or exceed the specified tolerances. Deviations outside the specified operating range might lead to dangerous conditions and functional disturbances in the automation system. • Power supply 24 V DC M3000® modules must be supplied only with 24 V DC SELV (Safety Extra-Low Voltage) according to EN 60950-1. -"5.2.1-Power Supply Characteristics" on page 16 • Wire fault A cable or wire fault must not lead to undefined conditions. All necessary safety precautions must be taken in the hardware and software. • Connection All connection and signal cables must be installed in such a way that inductive or capacitive interferences will not impair the M3000® automation system. Rev. A, May 2014 14