7.2
Connection instructions
- Use short cable terminations of the EUI-C type (with shells). They are compulsory for
Functional Units PF - PFA - PGC
- The building of the extremity (other than AREVA supply) must be carried out in
accordance with the manufacturer's instructions.
- The earthing braid for each cable must always exit above the bottom plate and the
clamping collar.
- Leave 40mm of free clearance on the lug barrel for fitting the grounding clamp.
- Ensure the correct orientation of the contact plate before crimping it.
- There must be no stress tensioning the cable.
Never stick any phase markers to the cable end reassemblies
--> decrease in the dielectric strength and degradation over time.
- Never clamp the cable by its cable end.
- Never leave a washer in incompatible material between the lug and the connecting plate.
7.3
Preparation of the cables
ÄÄÄÄ
ÄÄÄÄ
F
F
Pull out each cable from the
opening via the front of the
Functional Unit to make up the
extremity.
Example of a connection
terminating in IS.
F
F
Cut out each grommet to the
diameter of the cable.
F
Fit the grommet on to its cable.
Example of a connection
terminating in PF.
19