Download User Manual - LUCKINSlive

Transcript
General Rules for Installation
The following summary table shows the acceptable line capacity values.
Module
Maximum coupling capacity
24 to 125 VDC inputs
BMX DDI 1602
BMX DDI 1603
BMX DDI 1604T
BMX DDM 16022
BMX DDM 16025
45 nF (1)
BMX DDI 3202 K
BMX DDI 6402 K
BMX DDM 3202 K
25 nF (1)
24 to 140 VAC inputs
BMX DAI 0805
50 nF
BMX DAI 1602
50 nF
BMX DAI 1603
60 nF
BMX DAI 0814
BMX DAI 1604
70 nF
(1) max. admissible coupling capacity with a 240 VAC / 50 Hz line
Example: A standard cable of 1 m in length has a coupling capacity that falls within 100 and 150
pF.
Outputs
For the outputs of discrete I/O modules, follow the recommendations described here.
WARNING
UNEXPECTED EQUIPMENT OPERATION
Use wires of a sufficient diameter to avoid drops in voltage, overheating, and unexpected
equipment operation.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
40
35012474 10/2013