Download Adjustable Frequency AC Drive
Transcript
Installation/Wiring Input/Output Connection Example 2 Wire SRC Control - Internal Supply (SRC) Run FWD/Run REV 11 P036 [Start Source] = 2, 3 or 4 Stop-Run Input must be active for Forward the drive to run. When input is opened, the Stop-Run drive will stop as Reverse specified by P037 [Stop Mode]. If both Run Forward and Run Reverse inputs are closed at the same time, an undetermined state could occur. 2 Wire SNK Control - Internal Supply (SNK) Run FWD/Run REV Stop-Run Forward 1-17 External Supply (SRC) 01 02 03 Stop-Run Forward 01 02 03 04 Stop-Run Reverse +24V Common Each digital input draws 6 mA. 01 02 03 04 Stop-Run Reverse 3 Wire SRC Control - Internal Supply (SRC) Non-Reversing P036 [Start Source] = 1 Stop 11 A momentary input will start the drive. A stop Start input to I/O Terminal 01 will stop the drive as specified by P037 [Stop Mode]. External Supply (SRC) Stop 01 02 Start +24V 01 02 04 Common Each digital input draws 6 mA. 3 Wire SNK Control Non-Reversing Internal Supply (SNK) Stop Start 01 02 03 04