3-36 Programming and Parameters Advanced Program Group (continued) A130 [PID Trim Hi] Sets the maximum positive value that is added to a PID reference when PID trim is used. Values Default 60.0 Min/Max: 0.0/400.0 Display: 0.1 A131 [PID Trim Lo] Sets the minimum positive value that is added to a PID reference when PID trim is used. Values Default 0.1 Min/Max: 0.0/400.0 Display: 0.1 A132 [PID Ref Select] Related Parameter(s): P038, A122 Stop drive before changing this parameter. Enables/disables PID mode and selects the source of the PID reference. Refer to Appendix F for details. Options 0 “PID Disabled” (Default) 1 “PID Setpoint” 2 “0-10V Input” 3 “4-20mA Input” 4 “Comm Port” 5 “Setpnt, Trim” 6 “0-10V, Trim” 7 “4-20mA, Trim” 8 “Comm, Trim” A133 [PID Feedback Sel] Select the source of the PID feedback. Refer to Appendix F for details. Options 0 “0-10V Input” (Default) The PID will not function with a bipolar input. Negative voltages are treated as 0 volts. 1 “4-20mA Input” 2 “Comm Port” A134 [PID Prop Gain] Sets the value for the PID proportional component when the PID mode is enabled by A132 [PID Ref Sel]. Values Default 0.01 Min/Max: 0.00/99.99 Display: 0.01