PICED Programmer's Guide
11.4.184 Warning 14186
Message
"Some Network Properties are invalid.
Click on Show to see the errors.
Click on Default to set the default Network properties.
Click on Continue to ignore the error."
Cause
Some of the C-Bus Network properties as set up in the C-Bus Network Manager appear to be invalid.
Solution
Click on Show to show a list of possible errors. After reviewing the errors, correct any problems.
Click on Default to set the default properties for all C-Bus Networks.
Click on Continue to ignore this error.
11.4.185 Error 14187
Message
"Could not connect to C-Gate at IP Address.
Reason.
PICED can not operate without a valid C-Gate connection.
Click on Close to close PICED
Click on Continue to select an alternative C-Gate server
Click on Help for more information"
Cause
There was an error when trying to connect to the C-Gate server.
Solution
Click on Close to close PICED.
Click on Continue to attempt to connect to an alternative C-Gate server. This option is not normally
recommended.
If the error reason contains the message "Unable to determine server version", then the PICED
software has been unable to read the version from C-Gate. This may be due to the computer being
too slow or too busy, causing a delay in the connection to C-Gate. Check Computer Requirements
in the FAQ. If this problem persists, you may need to start C-Gate prior to starting PICED (see
Starting Up Automatically in FAQ).
Otherwise, if the error reason is "The version of C-Gate could not be found or is not compatible with
this version of PICED", the problem is caused by the versions of C-Gate and PICED being
incompatible with each other. You will need to either :
Install a version of C-Gate which is compatible with PICED; OR
Change to a different version of PICED