PEC Plus user manual Testing settings and equipment To acknowledge alarms Press Select. If there was only one alarm message, the PEC Plus clears the message and returns to the main display. If there are additional alarm messages, the PEC Plus displays the next message. For a list of alarm messages, their descriptions, and possible resolutions, read Alarm and error messages on page 75. Acknowledging alarms clears the alarm message; it does not deactivate the alarm relay. To deactivate the alarm relay, resolve the problem causing the alarm condition. If you acknowledge the alarm, but do not resolve the problem causing the alarm condition, the alarm message displays again after five minutes without any key presses. If the condition causing the alarm returns to normal (for example, the temperature drops below the high alarm setting), the alarm relay and LED deactivate, but the alarm message remains. Testing settings and equipment There are four test utilities. Stage test mode Temperature test mode Actuator 1 Actuator 2 Using stage test mode Stage test mode allows you to test each variable stage or relay individually. When you enter stage test mode, all variable stages and relays switch off. You can change the output of variable stages or state of relays. Variable stages and relays (that are not assigned to actuators or curtains) remain at the state you set them until you leave stage test mode. 31040004 61