Download AVV Installation Instructions

Transcript
●
●
●
●
m
6m
~
●
Power cable entry
Arrow showing
wall installation
direction
Locking
pins
m
7
6
5
4
3
2
1 L1 -
●
Position the Room Thermostat Unit on a wall where it will be
most convenient for the customer.
Gently pull out the temperature knob and the ON/OFF handle.
Open the screw on the bottom of the Room Thermostat Unit.
(See Fig. 8).
Pull the cover of the Room Thermostat Unit and drill the appropriate holes in the wall.
After positioning the Room Thermostat unit on the wall, replace the cover gently and ensure that the locking pins are in
the correct position. .
When positioning the Thermostatic Room on the wall, remember that the connecting cable between the Room Thermostat unit and the indoor unit is only three meters long.
Cover plate for the cable entry passage
way. Remove this plate when installing
a wall duct for the power cable.
-6m
10
30
Positioning the Room Thermostat Unit
Temperature
Knob
ON
STBY
OFF
ON/OFF
Locking Screw
Fig. 8
Inter-unit
Electric Cable
Clamp
Indoor Unit Electrical Connections (Fig. 9)
Installing the Outdoor Unit Installation
and location
●
●
●
The outdoor unit must be installed a least 5 cm (2") above a
solid surface.
Drainage
Make sure that the unit is horizontal leveled.
Tube
Fasten the outdoor unit supports to the base, as shown in Fig.
10. Place the rubber absorption cushions (supplied) under the
unit’s legs to prevent vibrations.
Wiring the outdoor unit
●
●
●
●
Power Supply
Cable
Inter Unit
Cable
10
30
●
Remove the outdoor unit plastic side cover.
Attach the inter-unit electric cable with mating connectors,
using the electrical terminals supplied with the air-conditioner.
Connect the wires in accordance with the color coding which
appears in Fig. 11.
Secure the inter-unit electric cable to the outdoor unit using
the clamp shown in Fig. 10.
Reassemble the plastic side cover.
ON
STBY
OFF
Fig. 9
Room Thermostat Unit
1PH ~
NEUTRAL
Notes:
● A drainage tube can be connected to the outdoor unit to remove condensation formed during heating mode operation.
● When possible, lead the indoor unit drainage tube to the outdoor unit.
● Make sure that the inter-unit electric cable is properly connected to the outdoor unit, in accordance with the color coding in the wiring diagram attached to the air conditioner.
● Make sure that all screws and wires are properly fastened.
Loose wires or connections can cause damage and present a
fire hazard!
L1 - ~
L2- 0
COMP.
S(3p
T(3p
INTER-UNIT
ELECTRIC
CABLE CLAMP
4 ABSORPTION
CUSHION TO BE
PUT UNDER EACH
LEG
Fig. 10