Download FGM160-I Complete User Manual
Transcript
FGM 160 – HART Output Interface Specification Notes: 1) : Data from HART Transmitters is only applicable for FGM 160 systems configured for HART Pressure and Temperature transmitters. 2) Data from HART Transmitter 2 is only applicable for FGM 160 systems configured for double HART transmitters. *) Optional units: : : Table 7 – HART output parameter, optional units. Parameter Volume flowrate Mass flowrate Velocity Pressure Temperature Acc./totalized volume Acc./totalized mass Optional units MMCFD (Million Cubic Foot per Day), MMSCFD (Million Standard Cubic Foot per Day) lbs/h ft/s kPa A, psi A, kg/cm2 Abs F MMCF, MMSCF lbs For configuration of HART output parameters units, the FGM 160 Operator & Service Console must be used. All HART variable values will be transmitted as floating-point numbers, 32-bit single precision (IEEE 754), according to HART specification HCF_SPEC-127. 4.8.1 HART Variable Unit Codes The HART variable unit code(s) is included in the reply of HART command 1 (read primary variable) and HART command 3 (read current and four dynamic variables). The following HART unit codes are implemented in FGM 160: Table 8 - HART unit codes. Engineering unit m3/h MMCFD kg/h lbs/h m/s ft/s kg/m3 g bar A kPa A psi A kg/cm2 Abs C F m3 MMCF kg lbs % -- (none) 72.120.605/C HART unit code 19 242 75 82 21 20 92 60 7 12 6 10 32 33 43 243 61 63 57 251 *) *) Note: *) : Unit codes 242 and 243 are manufacturer specific definitions. Page 138 of 188