Download Emergency Lighting Transfer System User Manual 1997

Transcript
ELTS
Normal
Load
Emergency
Emergency Lighting Transfer System
User Manual
2
Electronic Theatre Controls, Inc.
Emergency Lighting Transfer System
User Manual
Contents
Introduction................................................................................................... 5
How to use this manual ........................................................................... 5
Codes and standards................................................................................ 5
System Diagram....................................................................................... 6
Installation and setup chapters
Installation..................................................................................................... 7
Unpack and Inspect.................................................................................. 7
ELTS Models............................................................................................ 8
Mounting the ELTS cabinet...................................................................... 9
Installing Remote stations (optional) ...................................................... 11
Connecting power and control wiring to the ELTS cabinet ................... 12
Transfer switch, Normal power and lighting load connections .............. 13
Control and Sensing wire connections................................................... 15
Testing ......................................................................................................... 18
Before you power up for the first time .................................................. 18
Turn on system ...................................................................................... 18
Functional checkout ............................................................................... 19
Settings ....................................................................................................... 21
ELTS timing settings .............................................................................. 21
ELTS voltage and frequency settings..................................................... 24
Use and service chapters
Operation..................................................................................................... 25
Automatic operation............................................................................... 25
Switching power sources manually ....................................................... 26
Service ......................................................................................................... 27
Preventive maintenance......................................................................... 27
Troubleshooting ......................................................................................... 28
Emergency or Normal Power Stable LED does not turn on properly..... 28
The ELTS will not switch between Normal and Emergency.................. 28
Remote stations cannot switch the ELTS.............................................. 29
Appendices
Appendix A: ELTS specifications............................................................... 30
Appendix B: Wire connection schematics and diagrams ....................... 31
Appendix C: Transfer switch control system schematics....................... 33
Appendix D: Transfer switch load switching schematic......................... 34
Appendix E: Test and Maintenance Log ................................................... 35
Emergency Lighting Transfer System User Manual
3
4
Electronic Theatre Controls, Inc.
Emergency Lighting Transfer System
Introduction
Welcome to ETC’s Emergency Lighting Transfer System (ELTS) User Manual.
This manual shows you how to install and use your ELTS system. See ELTS
Models on page 8 for a breakdown of ELTS models and configurations.
How to use this manual
This manual is divided into three sections:
▼
Installation on page 7 tells you how to install and test your system
▼
Operation on page 25 tells you how to use and service your system
▼
The Appendix B: Wire connection schematics and diagrams on page 31
contains additional information you may need
Warnings and notice conventions
These symbols alert you to danger or important information:
Warning! Warns you when electricity may cause injury
Warning! Warns you when there is a possibility of other types of injury
Notice:
Alerts you to important information relating to equipment
performance or reliability
Contacting ETC
For questions about ELTS system delivery or general information, contact ETC
Customer Service at 800/688-4116.
Codes and standards
ELTS systems meet the following regulatory standards for emergency lighting
transfer devices:
Emergency Lighting Transfer System User Manual
▼
ANSI/UL 1008 – Listed, Automatic Transfer Switches
▼
ANSI/NFPA 110 – Emergency and Standby Power Systems
▼
ANSI/NFPA 70 – National Electric Code
Article 701 – Legally Required Standby Systems
Article 700 – Emergency Systems
Article 540 –11(c) – Motion Picture Houses
Article 520 – 7 – Theatres and Similar Locations
Article 518 – 3(c) – Places of Assembly
▼
City of New York, Advisory board, Electrical Department
▼
OSHA
▼
Department of Defense
5
System Diagram
Emergency
generator
Main power
L1 L2 L3 N
Normal loads are connected directly
to the dimming system. If main power
fails, normal loads are dark.
L1 L2 L3 N
Normal loads
Channels 1–6
Normal loads
Generator
Start
L1, L2 and L3
sensing wires
Dimmer rack
Normal/Emergency loads are routed through
the ELTS. Normal load power comes from the
dimming system. If the ELTS detects a loss of
dimmer normal power, it switches the
normal/emergency loads from dimmer normal
power to the emergency power source.
Normal power
Channels 7–12 (into ELTS)
Normal/Emergency loads
Channels 7–12 (from ELTS)
Fire alarm activation
Aux activation
ELTS cabinet
Normal/Emergency loads
Up to ten Remote stations
can be connected to the ELTS
Figure 1: Diagram of a typical ELTS system
6
Electronic Theatre Controls, Inc.
Installation
Unpack and Inspect
Before you begin installation, check your shipment so you know it arrived
complete and undamaged.
1. Check the shipping container for obvious physical damage:
▼
Torn or opened containers
▼
Water stains or wetness
▼
Crushed or punctured boxes
▼
Other shipping-related damage
2. If you find damage, document it to help with a claim against your shipper.
3. Unpack your order and check the contents against the Bill of Materials to
be sure your order is complete.
4. Open the ELTS cabinet door and check for loose connections or broken
components caused by shipping vibration.
5. If you discover a problem with your order, call ETC Customer Service at
800/688-4116.
ELTS 850, 1820, 2420
GROUND
DUE TO SHIPPING, MFG. IS NOT RESPONSIBLE FOR
LOOSE CONNECTIONS, TIGHTEN ALL CONNECTIONS
BEFORE ENERGIZING.
LUG
Control panel
ASCO
PS
Emergency
ground lug
POWER
SUPPLY
ASCO GROUP 9
CONTROL PANEL
6
7
8
9
N
5
C
4
N
3
C
2
B
ELTS 450,
620, 1220
1
A
10
EPDB
A
B
GROUND
DUE TO SHIPPING, MFG. IS NOT RESPONSIBLE FOR
LOOSE CONNECTIONS, TIGHTEN ALL CONNECTIONS
BEFORE ENERGIZING.
LUG
ASCO
PS
POWER
SUPPLY
ASCO GROUP 9
CONTROL PANEL
A
Emergency
ground lug
C
N
7
8
9
10
B
6
A
SR3B
5
SR3B
EPDB
4
SR3B
N
3
SR3B
C
2
ELTS power supply
B
1
Emergency
Line and
Neutral lugs
NL6
EN6
LN6
NN5
EL6
LL6
EN4
NN4
EL4
NL4
NN3
LN4
LL4
T1
T2
3
T3
T4
5
T5
6
T6
7
T7
8
T8
9
T9
10
T10
11
T11
12
T12
1
R1
2
R2
3
R3
4
R4
5
R5
ELTS power supply
SR3B
SR3B
SR3B
SR3B
Isolation relays
6
NL3
EN3
LN3
EL3
LL3
1
2
4
NL5
EN5
LN5
EL5
NN5
NL5
NN4
NL4
LL5
NN6
NL6
EN6
LN6
Emergency
Line and
Neutral lugs
NN2
R5
EN2
R4
LN2
R3
5
EL3
R2
3
LL3
2
4
EN2
R1
LN2
1
NN3
T12
NL3
T11
NN2
T10
11
12
LN3
10
EL6
T9
12 POLE TRANSFER SWITCH
LL6
T8
9
TS2
12 POLE TRANSFER SWITCH
EN5
8
TS1
LN5
T7
EL5
T6
LL5
T5
EN4
T4
6
7
LN4
T3
5
EL4
T2
3
LL4
2
4
EN3
T1
NN6
Isolation relays
1
1
F1
2
F2
TS1
TS2
12 POLE TRANSFER SWITCH
12 POLE TRANSFER SWITCH
NN6
NL2
NN1
EN6
EL2
EN1
LN6
LL2
LN1
NN6
NL2
NN1
EN6
EL2
EN1
A1
A2
1
NL6
EL6
LL6
NL6
EL6
NL1
EL1
LL1
LL6
3
NL1
F2
EL1
F1
LL1
1
2
1
2
LN6
LL2
LN1
3
6
G1
NN5
EN5
NL5
EL5
LL5
NL5
NN4
NL4
LN4
EN4
EL4
LL4
NN4
EN4
NN3
EN3
LN3
NN3
EN3
NL3
EL3
LL3
NL3
EL3
NN2
EN2
LN2
NN2
LN2
EN2
NL2
EL2
LL2
NL2
EL2
LL2
EA
EN1
4
NN1
LN1
EC
EL1
5
NL1
12 POLE TRANSFER SWITCH
NC
LL1
5
NC
NN1
12 POLE TRANSFER SWITCH
4
3
NL1
TS4
EN1
TS3
6
LN5
EN5
NN5
LN5
EN5
NN5
NL5
LL5
EL5
NL5
EC
EL5
3
TS11
TS29
3
2
TB3
5
1
3
4
2
3
TB1
TB2
2
1
2
1
NN6
NL6
LN6
EN6
EL6
LL6
NN6
EL6
NL6
EA
LL6
1
EN6
LN6
6
LL5
Terminal
blocks
NB
1
2
LN1
2
6
EL1
NA
5
LL1
Terminal
blocks
G3
LL3
4
6
3
NB
LN3
3
G2
4
1
NA
2
2
5
NL4
1
EL4
G1
LL4
LN4
G3
1
1
5
6
3
EL5
LL5
2
2
4
1
LN5
G2
3
3
3
A2
NN5
2
A1
EN5
LN5
3
1
2
3
4
5
6
TS30
7
TS10
8
TS12
NN4
EN4
LN4
NN4
EN4
LN4
6
NL4
NN3
EL4
NL3
LL4
LN3
EN3
EL3
NL3
LL3
NL4
NN3
EL4
EN3
LN3
LL3
NN2
NL2
EN2
NN1
NL1
LN2
EN1
EL2
LN1
LL2
NN2
EN2
EL2
LL2
NL2
EL1
TS12
LL1
TS10
NN1
TS30
8
NL1
TS29
7
EN1
TS11
6
LN1
TB3
5
EL1
TB2
3
LN2
TB1
2
4
LL1
1
EL3
LL4
9
3
3
2
2
1
1
9
Transfer switch
assemblies
Figure 2: Identifying ELTS components
Emergency Lighting Transfer System User Manual
7
ELTS Models
Large ELTS cabinet (30" wide x 54" tall x 9" deep)
ELTS 850
8 circuits of 50 amps
ELTS 1820
18 circuits of 20 amps
ELTS 2420
24 circuits of 20 amps
Electronic Theatre Controls Inc.
MODEL ELTS
AUTOMATIC TRANSFER SWITCH FOR EMERGENCY SYSTEMS
ISSUE NO. 934
Small ELTS cabinet (30" wide x 36" tall x 9" deep)
ELTS 450
4 circuits of 50 amps
ELTS 620
6 circuits of 20 amps
ELTS 1220
12 circuits of 20 amps
Operational Current: 200A Max 3 Phase
Operational Voltage: 120/208v (3p+N+ )
Frequency: 50/60Hz.
NORMAL POWER
Short-circuit current: 10,000 AIC
STABLE
Electronic Theatre Controls Inc.
Middleton, WI Made in USA
®
C
®
UL1008 Listed
EMERGENCY POWER
STABLE
NORMAL
OPERATION
EMERGENCY
OPERATION
GENERATOR
START
FIRE ALARM
TRANSFER SIGNAL
EMERGENCY
POWER
AUTO
NORMAL
POWER
AUXILIARY
TRANSFER SIGNAL
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Electronic Theatre Controls Inc.
MODEL ELTS
AUTOMATIC TRANSFER SWITCH FOR EMERGENCY SYSTEMS
ISSUE NO. 934
Operational Current: 200A Max 3 Phase
Operational Voltage: 120/208v (3p+N+ )
Frequency: 50/60Hz.
NORMAL POWER
Short-circuit current: 10,000 AIC
STABLE
Electronic Theatre Controls Inc.
Middleton, WI Made in USA
®
C
®
UL1008 Listed
EMERGENCY POWER
STABLE
NORMAL
OPERATION
EMERGENCY
OPERATION
GENERATOR
START
FIRE ALARM
TRANSFER SIGNAL
EMERGENCY
POWER
AUTO
NORMAL
POWER
AUXILIARY
TRANSFER SIGNAL
1
2
3
4
5
6
7
8
9
10
11
12
Figure 3: Large and small ELTS cabinets
Remote station (part # 1093A2023)
NORMAL
OPERATION
NORMAL
POWER
EMERGENCY
OPERATION
AUTO
▼
Provides front panel keyswitch control at remote locations.
▼
Link up to ten stations with parallel wiring.
▼
Normal and Emergency LEDs indicate ELTS status.
EMERGENCY
POWER
Figure 4: Remote station
8
Electronic Theatre Controls, Inc.
Mounting the ELTS cabinet
Mount the ELTS on a load-bearing wall, in a location where it will not be
subject to tampering or vandalism. If possible, install the ELTS where it is
most secure from damage by a fire, flood or other incident likely to require its
use. Do not install the ELTS inside any other electrical enclosure.
Physical requirements for mounting
You must mount either size ELTS cabinet with sufficient front clearance (30
inches) to allow the door to open completely.
Electronic Theatre Controls Inc.
MODEL ELTS
AUTOMATIC TRANSFER SWITCH FOR EMERGENCY SYSTEMS
ISSUE NO. 934
Operational Current: 200A Max 3 Phase
Operational Voltage: 120/208v (3p+N+ )
Frequency: 50/60Hz.
NORMAL POWER
Short-circuit current: 10,000 AIC
STABLE
Electronic Theatre Controls Inc.
Middleton, WI Made in USA
®
C
®
UL1008 Listed
EMERGENCY POWER
STABLE
NORMAL
OPERATION
EMERGENCY
OPERATION
GENERATOR
START
FIRE ALARM
TRANSFER SIGNAL
EMERGENCY
POWER
AUTO
NORMAL
POWER
AUXILIARY
TRANSFER SIGNAL
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Electronic Theatre Controls Inc.
MODEL ELTS
AUTOMATIC TRANSFER SWITCH FOR EMERGENCY SYSTEMS
ISSUE NO. 934
55.187"
(bolts)
Operational Current: 200A Max 3 Phase
Operational Voltage: 120/208v (3p+N+ )
54.000"
(cabinet)
Frequency: 50/60Hz.
NORMAL POWER
Short-circuit current: 10,000 AIC
STABLE
Electronic Theatre Controls Inc.
Middleton, WI Made in USA
®
C
®
UL1008 Listed
EMERGENCY POWER
STABLE
NORMAL
OPERATION
EMERGENCY
OPERATION
GENERATOR
START
FIRE ALARM
TRANSFER SIGNAL
EMERGENCY
POWER
AUTO
NORMAL
POWER
AUXILIARY
TRANSFER SIGNAL
1
2
3
4
5
6
7
8
9
10
11
12
36.000"
(cabinet)
37.187"
(bolts)
24.250" (bolts)
30.000" (cabinet)
9.375"
24.250" (bolts)
30.000" (cabinet)
9.375"
Small cabinet
Large cabinet
Figure 5: ELTS cabinet mounting dimensions
Notice:
Emergency Lighting Transfer System User Manual
When planning your installation, make sure to leave space
around the cabinet for entry and exit wire conduit. Emergency
line and neutral conduit may require extra space due to
increased bend radius requirements for larger cables.
9
Planning wire entry into the ELTS cabinet
The Emergency power connections must enter the cabinet from the top or
side of the cabinet within six inches of the top left corner.
Control, Normal power sensing and options wires connect most easily if they
enter above the Remote station terminal or just below the Emergency sensing
terminal on the left side of the cabinet.
Note: Do not run the control, normal power sensing and options wiring in the
same conduit as Emergency phase or load power wiring.
Load wires in from the dimmer rack and out to the lighting loads connect most
easily if they enter through the bottom of the cabinet either between or beside
the transfer switch assemblies.
Note: Except for the emergency power supply wires, which must enter near
the top left corner of the cabinet, recommended conduit entry locations
may be changed based on the requirements of your installation.
Control panel
GROUND
DUE TO SHIPPING, MFG. IS NOT RESPONSIBLE FOR
LOOSE CONNECTIONS, TIGHTEN ALL CONNECTIONS
BEFORE ENERGIZING.
LUG
ASCO
PS
POWER
SUPPLY
ASCO GROUP 9
CONTROL PANEL
6
7
8
9
N
5
C
4
N
3
C
2
B
1
A
10
EPDB
Emergency power
conduit entry area
A
B
Isolation relays
Emergency power lugs
ELTS power supply
SR3B
SR3B
SR3B
SR3B
Transfer switch
assembly
NL6
EN6
LN6
NN5
EL6
LL6
NL5
EN5
LN5
NN4
EL5
LL5
NL4
EN4
LN4
NN3
EL4
LL4
NL3
EN3
LN3
NN2
EL3
LL3
NL2
EN2
LN2
EL2
LL2
NN6
NL6
NN5
NL5
NN4
EL4
LL4
EN3
LL3
EL3
LN3
R5
EN2
R4
LN2
R3
EL2
R2
5
LL2
R1
3
NN1
NL1
EN1
LN1
EL1
F2
LL1
F1
2
NN1
1
NL1
LN1
EN1
6
EL1
Fire alarm transfer
1
2
4
LL1
Remote stations
NL4
T12
NN3
T11
NL3
T10
NN2
T9
NL2
T8
9
11
12
EN6
8
10
12 POLE TRANSFER SWITCH
LN6
T7
TS2
12 POLE TRANSFER SWITCH
EL6
7
TS1
LL6
T6
EN5
T5
LN5
T4
EL5
T3
6
LL5
T2
5
EN4
T1
3
LN4
Recommended
control conduit
location
1
2
4
NN6
Factory wired terminal
3
2
A1
A2
2
1
2
1
1
Auxiliary transfer
3
3
3
1
Generator start
G1
2
3
G2
4
5
G3
6
1
NA
2
Normal sensing
3
NB
TS3
TS4
12 POLE TRANSFER SWITCH
12 POLE TRANSFER SWITCH
4
5
NC
NN6
Transfer switch
manual operation
handle
NL6
LN6
EN6
EL6
LL6
NN6
EL6
NL6
EA
LL6
1
NN5
EN5
LN5
NN5
EC
EN5
3
LN5
2
NL5
EL5
LL5
LL5
5
NL5
4
EL5
Emergency sensing
EN6
LN6
6
NN4
NL4
NN3
LN4
EN4
EL4
LL4
NL3
LL3
EL3
NL3
NN2
LN2
EN2
NN2
EN3
NN3
EL3
EN2
LN3
NN4
NL4
EN4
EL4
LL4
LL3
LN2
LN3
NL2
NL1
NN1
EL2
LL2
EN1
EL2
NL2
LN1
TS12
EL1
8
LL1
TS10
NN1
TS30
NL1
TS29
7
EN1
TS11
6
LN1
TB2
TB3
5
LL2
TB1
3
EL1
1
2
4
LL1
Recommended
control conduit
location
EN3
LN4
6
3
2
1
1
Factory wired terminal
2
3
9
Recommended
load input and
output conduit
locations
Figure 6: ELTS components
10
Electronic Theatre Controls, Inc.
Mounting the cabinet
After determining where you want to install the cabinet, follow these
instructions.
1. Install two 3/8" bolts 24.25 inches apart for the lower two support slots
(the installer must supply the mounting hardware).
2. Use the mounting dimensions from Figure 5 : ELTS cabinet mounting
dimensions on page 9 to drill the holes for the upper two 3/8" bolts.
3. Place the ELTS cabinet on the wall supported by the two lower bolts.
Notice:
ELTS cabinets are very heavy. Make sure you have adequate
equipment (or help) to lift the cabinet into place and support it
while you secure the top two bolts.
4. Secure the ELTS to the wall with the two upper 3/8" bolts.
Installing Remote stations (optional)
1. Install a standard two gang backbox (4" x 4" x 3.5") and run wire conduit
from it to the ELTS cabinet.
2. Pull five conductor, Class 2 (12 Vdc) wiring through from the backbox to
the cabinet.
3. Connect the wires to the terminal strip on the back of the remote station.
Note which terminal each wire connects to.
4. Install the Remote station onto the backbox with four 6 - 32 x 1/2" oval
head machine screws (provided).
5. To install multiple Remote stations, repeat steps 1 – 4, wiring in parallel
between Remote station terminal blocks.
Refer to Connecting Remote stations to the ELTS on page 16 for instructions
for connecting Remote station wiring inside the ELTS cabinet.
Emergency Lighting Transfer System User Manual
11
Connecting power and control wiring to the ELTS cabinet
Warning! To prevent death or injury due to electrical shock, Normal and
Emergency power to the ELTS must be turned off any time you
are connecting or servicing any ELTS.
Connecting Emergency power
The Emergency power lugs are in the upper left of the ELTS cabinet. The ELTS
is available in one or three phase power configurations.
1. Cut a hole within six inches of the top left corner of the ELTS cabinet
2. Install conduit and pull the Emergency power cables into the cabinet.
Note: Top conduit connections are recommended to reduce the cable bending
necessary to connect to the lugs.
Table 1: Emergency power lug wire sizes and connection torques
Connection type
Wire size
Torque
Phase and Neutral lugs (3 phase)
6 AWG to 2/0
275 in/lbs
Phase and Neutral lugs (single phase) 6 AWG to 250 MCM
275 in/lbs
Ground lug (both phase types)
50 in/lbs
14 AWG to 2/0
Three phase (4 wire) connections
1. Connect each phase power cable to the correct lug. See Figure 7, below,
to identify the lugs.
2. Connect the Neutral cable to the Neutral lug.
3. Connect the Ground cable to the Ground lug.
GROUND
DUE TO SHIPPING, MFG. IS NOT RESPONSIBLE FOR
LOOSE CONNECTIONS, TIGHTEN ALL CONNECTIONS
BEFORE ENERGIZING.
LUG
Phase C lug
(Three phase
ELTS only)
Ground lug
Phase A lug
A
B
C
N
A
B
C
N
Phase B lug
Neutral lug
Figure 7: Connecting Emergency power to the ELTS
Single phase connection (3 wire)
1. Connect one phase cable to the Phase A lug and one to the Phase B lug.
See Figure 7, above, to identify lugs.
2. Connect the Neutral cable to the Neutral lug.
3. Connect the Ground cable to the Ground lug
12
Electronic Theatre Controls, Inc.
Transfer switch, Normal power and lighting load connections
Each transfer switch can have up to six 20 amp circuits or two 50 amp circuits
connected to it. You need to connect Line and Neutral inputs from the dimmer
rack and outputs to the emergency lighting loads. The Line and Neutral input
from Emergency power are delivered prewired.
Table 2Switch assembly wire sizes and connection torques
Circuits Circuits
1–6
7 – 12
Circuits
13 – 18
Wire size
Torque
Wire size
Torque
14 – 10 AWG
35 in/lbs
8 AWG
40 in/lbs
6 – 4 AWG
45 in/lbs
3 AWG to 2/0
50 in/lbs
20 amp dimmer rack Load and Neutral wire input connections
Circuits
19 – 24
1. Attach the conduit for the wires from the dimmer rack to the bottom of
the ELTS cabinet (recommended.)
2. Connect a Neutral wire for each dimmer circuit to terminals NN1 through
NN6 on the right side of the transfer switch assembly. See Figure 8, left,
to match switch assemblies to loads.
Figure 8: 20 amp Transfer
switch circuit assignments
3. Connect a Line wire for each dimmer circuit to terminals NL1 through NL6
on the right side of the transfer switch assembly.
4. Repeat steps 2 and 3 for the other transfer switch assemblies.
NN6
NL6
EN6
NN5
NL5
NN4
NL4
EN3
NN3
NL3
NN2
Neutral wire
from dimmer
NL2
NN1
NL1
EL2
NN2
LL6
EL6
EN5
LN5
LL5
EL5
EN4
LN4
LN3
EL3
LL2
EN1
Line wire
from dimmer
Prewired Emergency Line and
Neutral input terminals
NL1
1
2
Prewired Emergency
feeds
NN1
3
LL1
LN1
LN2
LL3
LL4
EN6
EL6
EN5
EL5
EN2
LN6
LL6
LN5
LL5
EL4
LN6
12 POLE TRANSFER SWITCH
EL1
Lighting load
Line output
wire
Input connections for Line and
Neutral wires from the
dimmer rack (Normal power)
TS1
NL2
Lighting load Line
and Neutral
terminals
Lighting load
Neutral output
wire
Figure 9: 20 amp Transfer switch connections for Line and Neutral wires
20 amp lighting load Line and Neutral output connections
1. Attach the conduit for the wires to the lighting loads through the bottom
of the ELTS cabinet (recommended).
2. Connect a Neutral wire for each lighting load to terminals LN1 through
LN6 on the left side of the transfer switch assembly. See Figure 8, above,
to match switch assemblies to loads.
3. Connect a Line wire for each lighting load to terminals LL1 through LL6 on
the left side of the transfer switch assembly
4. Repeat steps 2 and 3 for the other transfer switch assemblies.
Emergency Lighting Transfer System User Manual
13
50 amp dimmer rack Load and Neutral wire input connections
1. Attach the conduit for the wires from the dimmer rack to the bottom of
the ELTS cabinet (recommended.)
2. Connect a Neutral wire for each dimmer circuit to terminals NN1 and NN2
on the right side of the transfer switch assembly. See Figure 10, left, to
match switch assemblies to loads.
Circuits Circuits
1&2
3&4
3. Connect a Line wire for each dimmer circuit to terminals NL1 and NL2 on
the right side of the transfer switch assembly.
4. Repeat steps 2 and 3 for the other transfer switch assemblies.
50 amp lighting load Line and Neutral output connections
Circuits
5&6
Circuits
7&8
Figure 10: 50 amp transfer
switch circuit assignments
1. Attach the conduit for the wires to the lighting loads through the bottom
of the ELTS cabinet (recommended.)
2. Connect a Neutral wire for each lighting load to terminals LN1 and LN2 on
the left side of the transfer switch assembly. See Figure 10, to match
switch assemblies to loads.
3. Connect a Line wire for each lighting load to terminals LL1 and LL2 on the
left side of the transfer switch assembly
4. Repeat steps 2 and 3 for the other transfer switch assemblies.
Lighting load Line
and Neutral
terminals
Input connections for Line and
Neutral wires from the
dimmer rack (Normal power)
TS1
Lighting load
Neutral output
wire
Neutral wire
from dimmer
NN2
NL2
EN2
EN1
NN1
EL1
NL1
3
LN1
LL1
LL2
Lighting load
Line output
wire
EL2
LN2
4 POLE TRANSFER SWITCH
1
2
Prewired Emergency
feeds
Line wire
from dimmer
Prewired Emergency
Line and Neutral
input terminals
Figure 11: 50 amp Transfer switch connections for Line and Neutral wires
14
Electronic Theatre Controls, Inc.
Control and Sensing wire connections
Door control and
indicator connections
(prewired)
1
T1
2
T2
3
T3
4
T4
5
T5
6
T6
7
T7
8
T8
9
T9
10
T10
11
T11
12
T12
Control and power sensing wires connect to terminal blocks on the left side of
the ELTS cabinet.
Terminals can accept from 8 to 22 AWG wires. Torque terminal screws to
18 in/lbs.
1. Install control and sensing wire conduit on the left side of the ELTS cabinet
above the remote station connection terminals or below the Emergency
power sensing terminals (recommended conduit location).
2. Pull the wires into the cabinet.
Connecting the Normal power sensing wires
Remote station
connections
1
R1
2
R2
3
R3
4
R4
5
R5
6
Fire alarm signal
transfer
1
F1
2
F2
3
Auxiliary
signal transfer
1
A1
2
A2
3
1
Engine/
generator start
G1
2
3
G2
4
5
Normal power
sensing
Emergency
power sensing
(prewired)
EA
2
3
EC
4
5
Connect phase A to terminal 1 (across from wire NA)
▼
Connect phase B to terminal 3 (across from wire NB)
▼
Connect phase C to terminal 5 (across from wire NC)
Note: On single phase (three wire) systems, terminal 5 will not be used.
Connecting the Emergency power sensing wires
Emergency power sensing wires on ELTS systems with front panel circuit
breaker or fuse panels are wired from the Emergency power lugs to the
correct terminals on the Emergency power terminal block at the factory.
6
Transfer switch
connections
(prewired)
▼
NC
6
1
3. Pull the wires from the circuit breakers through wire conduit to the Normal
power sensing terminal block in the ELTS cabinet.
NB
4
5
2. Connect each sensing wire to a 15 amp circuit breaker close to the
dimmer rack. Circuit breakers CANNOT be inside the ELTS cabinet.
4. Connect the sensing wires to the Normal power sensing terminal block:
NA
2
3
Note: Power sensing wires must be 12 AWG or larger.
1. Connect a sensing wire to each phase lug of the dimmer rack connected
to the ELTS. Mark each wire to identify its phase at the ELTS rack.
G3
6
1
Normal power sensing wires connect to the phase lugs of the dimmer rack
connected to the ELTS. They attach to the Normal power sensing terminal
block. Each sensing wire must connect to the ELTS through a 15 amp circuit
breaker located outside the ELTS cabinet.
1
TB1
2
TB2
3
TB3
4
TS11
5
TS29
6
TS30
7
TS10
8
TS12
9
Figure 12: Control and Sensing
wire terminal connections
Sensing wires on systems without front panel circuit breakers must be wired
into the ELTS cabinet.
Note: Emergency power sensing wires must be 12 AWG or larger.
1. Connect a sensing wire to phase A and C (A and B on single phase
systems) of the Emergency power supply. Mark each wire to identify its
phase at the ELTS rack.
2. Pull the wires through the conduit to the Emergency power sensing
terminal block in the ELTS cabinet.
3. Connect the sensing wires to the Emergency sensing terminal block:
▼
Connect phase A to terminal 1 (across from wire NA)
▼
Connect phase C to terminal 5 (across from wire NC)
Note: On single phase (three wire) systems, connect phase B to terminal 5.
Emergency Lighting Transfer System User Manual
15
Connecting the Engine/generator starting wires
Closed start
signal
1
G1
1. Connect two wires to the terminals of your engine/generator starting
circuit.
2
Always
connected
3
G2
4
Open start
signal
5
The ELTS system can provide both normally open and normally closed starting
circuits for engine generator activation.
G3
6
Note: Consult your generator installation manual for start signal wiring
information.
2. Pull the wires through the conduit to the engine/generator start terminal
block.
3. Connect one of the starting wires to terminal 3 (across from wire G2).
Figure 13: Connections
for Engine/generator
starting wires
4. Connect the other starting wire to terminal 1 or 5:
▼
For a closed start signal, connect the wires to terminal 1 (across from
wire G1)
▼
For an open start signal, connect the wires to terminal 5 (across from
wire G3)
Connecting Remote stations to the ELTS
You can connect up to 10 Remote stations to the ELTS with parallel wiring. For
Remote station installation instructions see page 11.
Remote 1
1
R1
Remote 2
2
R2
1. Pull the Remote station wires the Remote station terminal.
Remote 3
3
R3
2. Connect the Remote wire 1 (Common) to terminal 1
(across from wire R1).
Remote 4
4
R4
Remote 5
5
R5
3. Connect the Remote wire 2 (Emergency Select) to terminal 4
(across from wire R2).
6
Figure 14: Connections
for Remote stations
4. Connect the Remote wire 3 (Normal Select) to terminal 5
(across from wire R3).
5. Connect the Remote wire 4 (Normal indicator LED) to terminal 2
(across from wire R4).
6. Connect the Remote wire 5 (Emergency indicator LED) to terminal 3
(across from wire R5).
16
Electronic Theatre Controls, Inc.
Connecting fire alarm activation
You can connect your ELTS to your fire alarm system so it switches to
Emergency when the alarm is triggered. Your fire alarm system must be able
to provide an open signal when it activates.
Remove Fire
alarm shorting
wire and install
Fire alarm circuit
wires in terminals
1 and 2
1. Connect two wires to the terminals of your fire alarm activation circuit.
2. Pull the wires through the conduit to the fire alarm terminal block.
1
F1
3. Remove the shorting wire between terminal 1 and terminal 2.
2
F2
4. Connect one wire to terminal 1 (across from wire F1).
5. Connect the other wire to terminal 2 (across from wire F2).
3
Remove Aux.
shorting wire
and install Aux.
circuit wires in
terminals 1 and 2
1
A1
2
A2
3
Figure 15: Connecting
fire alarm and auxiliary
circuit wires
Note: If you do not use the fire alarm activation feature, leave the shorting wire
in place or the ELTS will not operate properly.
Connecting auxiliary activation
You can connect your ELTS to an auxiliary circuit so it switches to Emergency
when the circuit is triggered. Your auxiliary circuit must provide an open signal
when it activates.
1. Connect two wires to the terminals of your auxiliary circuit.
2. Pull the wires through the conduit to the auxiliary terminal block.
3. Remove the shorting wire between terminal 1 and terminal 2.
4. Connect one wire to terminal 1 (across from wire A1).
5. Connect the other wire to terminal 2 (across from wire A2).
Note: If you do not use the auxiliary activation feature, leave the shorting wire
in place or the ELTS will not operate properly.
Emergency Lighting Transfer System User Manual
17
Testing
Before you power up for the first time
Checking transfer switch operation manually
By checking transfer switch manual operation before you apply power, you
reduce the possibility of failure caused by mechanically frozen, damaged or
obstructed switches. Each switch should rotate without catching or binding.
Warning! Normal and Emergency power should be off when you open
the ELTS cabinet for to check switch operation. Opening the
cabinet with power applied exposes you to death or injury from
electrical shock.
1. Open the ELTS cabinet.
Warning! Rotating the transfer switch assemblies manually with Normal
or Emergency power applied may result in the assemblies
switching automatically, causing severe hand injuries.
2. Turn the manual operation handle 90° clockwise. E (Emergency) should be
visible on the assembly about 1.5 inches above the handle.
3. Rotate the handle 180° counter-clockwise. N (normal) should be visible.
Note: If you have difficulty operating the switch, check for installation debris
that may be blocking switch operation.
4. Repeat steps 2 and 3 with the remaining transfer switch assemblies.
Turn on system
Voltage checkout
1. Apply power to the ELTS and connected dimmer rack at the main circuit
breaker. The green Normal LED lights.
2. Apply emergency power. The red Emergency light turns on.
Warning! ELTS voltage tests should only be performed by qualified
personnel using EXTREME caution. Opening the cabinet with
power applied exposes you to death or injury from electrical
shock.
3. Open the ELTS cabinet.
4. Use a digital voltmeter (DVM) to test the feed voltage at the Normal power
sensing terminal block (Figure 12 on page 15 for location). Phase A is on
terminal 1, phase B on terminal 3 and phase C on terminal 5. Voltage must
be within ± 10 percent of the rated voltage for the ELTS.
5. Use the DVM to test the feed voltage at the Emergency power lugs.
Phase lugs are labeled either A, B or C. Voltage values must be within ± 10
percent of the rated voltage for the ELTS.
6. Close the ELTS cabinet.
18
Electronic Theatre Controls, Inc.
Functional checkout
After verifying the Normal and Emergency voltages, check the ELTS system
functions.
Lit if Normal power
is acceptable
Lights when
Emergency power is
used
Lit if Emergency
power is acceptable
Electronic Theatre Controls Inc.
MODEL ELTS
AUTOMATIC TRANSFER SWITCH FOR EMERGENCY SYSTEMS
Lights when
Normal power is
used
ISSUE NO. 934
Operational Current: 200A Max 3 Phase
Operational Voltage: 120/208v (3p+N+ )
Frequency: 50/60Hz.
Short-circuit current: 10,000 AIC
NORMAL POWER
STABLE
Electronic Theatre Controls Inc.
Middleton, WI Made in USA
®
©
®
UL1008 Listed
NORMAL
OPERATION
EMERGENCY
OPERATION
EMERGENCY POWER
STABLE
GENERATOR
START
Keyswitch selects
ELTS preference
between Normal
and Emergency
NORMAL
POWER
AUTO
EMERGENCY
POWER
FIRE ALARM
TRANSFER SIGNAL
AUXILIARY
TRANSFER SIGNAL
Lights when ELTS
sends a Generator
start signal
Lights when ELTS
receives a fire alarm
activation
Lights when ELTS
receives a auxiliary
activation
Figure 16: Local control operation and LED indications
Switch function
1. Insert the key into the keyswitch on the front panel of the ELTS.
2. Turn the key to EMERGENCY POWER. The red light above EMERGENCY
OPERATION turns on and the emergency loads go to full brightness. If
Emergency power is provided by an engine/generator, there will be a
short delay as the generator turns on and the voltage and frequency
stabilize.
3. Release the key. The keyswitch returns to AUTO (center) and the
EMERGENCY OPERATION light remains on.
4. Turn the key to the NORMAL POWER position. The green light below
NORMAL OPERATION turns on if the system is functioning correctly.
5. Release the key. The keyswitch returns to AUTO and the NORMAL
OPERATION light remains on.
Remote switch functions
After confirming correct function of the keyswitch on the front of the ELTS
cabinet, repeat the switch function checkout procedure at EVERY remote
station installed on your system.
Emergency Lighting Transfer System User Manual
19
Automatic function
The automatic function tests the ELTS’s ability to switch back and forth from
Normal to Emergency when Normal power is interrupted or restored.
1. Make sure the NORMAL OPERATION LED is lit on the ELTS front panel.
2. Turn off the normal power to the dimmer rack connected to the ELTS. The
NORMAL OPERATION and NORMAL POWER STABLE LEDs on the
ELTS front panel goes out and the ELTS switches to Emergency power
(the EMERGENCY OPERATION and EMERGENCY POWER STABLE
LEDs light, and the emergency loads go to full brightness.) If Emergency
power is provided by an engine/generator, there will be a short delay
before switching as the generator turns on and the voltage and frequency
stabilize.
3. Turn the Normal power back on. The ELTS switches back to Normal
power after the retransfer delay times out (the default setting is one
minute). On the front of the ELTS, the EMERGENCY OPERATION and
EMERGENCY POWER STABLE LEDs turn off and the NORMAL
OPERATION and NORMAL POWER STABLE LEDs light. If used, the
Emergency power engine/generator turns off when the cool down time is
complete.
Options function
ELTS systems can also be activated by fire alarm and auxiliary circuits. Both
are operated by a normally closed circuit controlled by the fire alarm or auxiliary
relays. When the fire alarm or auxiliary circuit activates, the relay opens,
causing the ELTS to switch to Emergency power. To test option relay function,
either:
▼
Activate the fire alarm or auxiliary relay. The ELTS should switch to
Emergency power and the emergency loads should go to full.
▼
If you do not wish to activate the fire alarm or auxiliary circuit, generate an
open circuit at the ELTS connection to the fire alarm or auxiliary circuit by
disconnecting one of the two wires to the ELTS cabinet. The ELTS will
switch to Emergency power and the emergency loads should go to full.
Note: The second method tests the ELTS response to an open circuit, but
does not confirm the fire alarm or auxiliary relay’s ability to open the
circuit to the ELTS.
20
Electronic Theatre Controls, Inc.
Settings
ELTS timing settings
ELTS timing settings for momentary outage override, transfer to Emergency
delay, return to Normal delay, and generator cool down are set at the factory.
You can adjust settings for specific applications any time after installation.
Caution: Only make changes to ELTS timing settings if you are familiar
with the system and know the reason for making the change.
Table 3: ELTS timing settings
Latch
Cover
Delay type
Default
setting
Range
DIP Switch
Adjustment
Pot.
Momentary Outage
override
1 second
0.5 - 6 seconds
Transfer to Emergency
delay
0
0 - 60 seconds
0 - 8 minutes
SW2 up
SW2 down
P2
Return to Normal delay
30 minutes
0
0.5 - 30 minutes
SW1 up
SW1 down
P1
Generator cool down
cycle
5 minutes
0 - 8 seconds
0.5 - 30 minutes
SW3 up
SW3 down
P3
P4
Getting access to the ELTS control panel
Figure 17: Removing
the control panel cover
To make adjustments, you must access the ELTS control panel.
1. Disconnect Normal and Emergency power to the ELTS.
Warning! Opening the ELTS cabinet with power on may result in death or
injury from electrical shock.
2. Open the ELTS cabinet.
3. Release the two latches on the control panel cover and remove it. See
Figure 17, left.
Potentiometer P1
SW1, SW2 and SW3
Potentiometer P3
Potentiometer P2
Potentiometer P4
Figure 18: Adjustment potentiometer and DIP switch locations
Emergency Lighting Transfer System User Manual
21
Changing the momentary outage override
The momentary outage override is the interval the ELTS will tolerate a Normal
power voltage fault without switching to Emergency power. It can be set from
0.5 to 6 seconds using adjustment potentiometer P4.
1. Follow the instructions on page 21 to remove the control panel cover.
2. Locate P4 using Figure 18 : Adjustment potentiometer and DIP switch
locations on page 21.
3. Turn P4 clockwise to increase the interval or counterclockwise to
decrease it. P4 has a 270° adjustment range.
Note: Potentiometer adjustments change timing as a fractions of the
adjustment range. For example, turning the pot half its range changes
the timing value by 50%. You will need to use some trial and error and
a timing device to achieve exact values.
Clockwise to increase
Counterclockwise to decrease
Figure 19: Changing adjustment potentiometer settings
Changing the Transfer to Emergency delay
DIP switch in
Up position
SW 1
2
•1
3
•2
•
•3
•
1. Follow the instructions on page 21 to remove the control panel cover.
•4
•
•
DIP switch in
Down position
Figure 20: Setting DIP
switches
22
The Transfer to Emergency delay sets the time the ELTS waits before
switching to Emergency after the Emergency power voltage and frequency
stabilize. You can set the delay in two time ranges, from zero to 60 seconds
or zero to 8 minutes, using DIP switch SW2 and adjustment potentiometer P2.
2. Locate SW2 using Figure 18 : Adjustment potentiometer and DIP switch
locations on page 21.
3. To select the zero to 60 second adjustment range put SW2 up. To select
the zero to 8 minute range, put SW2 down.
4. Locate P2 using Figure 18 : Adjustment potentiometer and DIP switch
locations on page 21.
5. After setting the range, turn P2 clockwise to increase the interval or
counterclockwise to decrease it. P2 has a 270° adjustment range.
Electronic Theatre Controls, Inc.
Changing the Return to Normal delay
The Return to Normal delay sets the time the ELTS waits before switching
from Emergency to Normal after Normal power is restored. The delay can be
turned off, or set from 0.5 to 30 minutes using DIP switch SW1 and
adjustment potentiometer P1.
Note:To disable the delay on a one-time basis (to quickly restart an interrupted
performance or for testing purposes) switch the ELTS back to Normal
with the front panel Local switch or a Remote keyswitch station.
1. Follow the instructions on page 21 to remove the control panel cover.
2. Locate SW1 using Figure 18 : Adjustment potentiometer and DIP switch
locations on page 21.
3. To turn off the delay put SW1 up. To set the range from 0.5 to 30 minutes,
put SW1 down.
4. If SW1 is down, locate P2 using Figure 18 : Adjustment potentiometer and
DIP switch locations on page 21.
5. Turn P2 clockwise to increase the interval or counterclockwise to
decrease it. P2 has a 270° adjustment range.
Changing the Generator cool down interval
The Generator cool down interval sets the time the ELTS waits before shutting
off the Emergency power generator after switching back to Normal power. It
can be set from zero to 8 seconds or 0.5 to 30 minutes using DIP switch SW3
and adjustment potentiometer P3.
Caution: Consult your generator user manual for proper cool down times
before changing the Generator cool down interval.
1. Follow the instructions on page 21 to remove the control panel cover.
2. Locate SW3 using Figure 18 : Adjustment potentiometer and DIP switch
locations on page 21.
3. To make the adjustment range zero to 8 seconds put SW3 up. To make
the range 0.5 to 30 minutes, put SW3 down.
4. Locate P3 using Figure 18 : Adjustment potentiometer and DIP switch
locations on page 21.
5. After setting the range, turn P3 clockwise to increase the interval or
counterclockwise to decrease it. P3 has a 270° adjustment range.
Emergency Lighting Transfer System User Manual
23
ELTS voltage and frequency settings
Voltage and frequency settings are set at the factory and should only be
adjusted by an authorized ETC representative.
Caution: Indiscriminate changes to voltage and frequency sensing
settings may affect normal operation of the ELTS and result in
switching function failure.
Table 4: 120 volt ELTS voltage and frequency settings
Description
Factory setting Adjustment range
Normal source voltage pickup
108 volts
102 – 120 volts
Normal source voltage dropout
102 volts
81 – 106 volts
Emergency source voltage pickup
108 volts
102 – 120 volts
Emergency source voltage dropout
92 volts
No adjustment: 15% below pickup setting
Emergency source frequency pickup
57 hertz
57 – 60 hertz
Emergency source frequency dropout 50 hertz
No adjustment: 12% below pickup setting
Table 5: 277 volt ELTS voltage and frequency settings
Description
Factory setting Adjustment range
Normal source voltage pickup
249 volts
235 - 277 volts
Normal source voltage dropout
235 volts
187 - 244 volts
Emergency source voltage pickup
249 volts
235 – 277 volts
Emergency source voltage dropout
212 volts
No adjustment: 15% below pickup setting
Emergency source frequency pickup
57 hertz
57 – 60 hertz
Emergency source frequency dropout 50 hertz
24
No adjustment: 12% below pickup setting
Electronic Theatre Controls, Inc.
Operation
Automatic operation
During automatic operation the ELTS system switches back and forth from
Normal to Emergency when either power supply is interrupted or restored.
Lit if Normal power
is acceptable
Lights when
Emergency power is
used
Lit if Emergency
power is acceptable
Electronic Theatre Controls Inc.
MODEL ELTS
AUTOMATIC TRANSFER SWITCH FOR EMERGENCY SYSTEMS
ISSUE NO. 934
Lights when
Normal power is
used
Operational Current: 200A Max 3 Phase
Operational Voltage: 120/208v (3p+N+ )
Frequency: 50/60Hz.
Short-circuit current: 10,000 AIC
NORMAL POWER
STABLE
Electronic Theatre Controls Inc.
Middleton, WI Made in USA
®
©
®
UL1008 Listed
NORMAL
OPERATION
EMERGENCY POWER
STABLE
EMERGENCY
OPERATION
GENERATOR
START
Keyswitch selects
ELTS preference
between Normal
and Emergency
NORMAL
POWER
AUTO
EMERGENCY
POWER
FIRE ALARM
TRANSFER SIGNAL
AUXILIARY
TRANSFER SIGNAL
Lights when ELTS
sends a Generator
start signal
Lights when ELTS
receives a fire alarm
activation
Lights when ELTS
receives a auxiliary
activation
Figure 21: Local control LED indications
Selecting the preferred power source: Normal or Emergency
Using the local keyswitch on the front of the ELTS cabinet or a Remote
keyswitch station installed in your facility, you can select either Normal or
Emergency as the preferred power source.
1. Insert the key into the keyswitch and select the desired power source:
▼
To select Normal power, turn the key left. The green NORMAL
OPERATION LED lights.
▼
To select Emergency power, turn the key right. The red EMERGENCY
OPERATION LED lights and the emergency loads go to full. If Emergency
power is provided by an engine/generator, there will be a short switching
delay as the generator turns on and voltage and frequency stabilize.
2. Release the key. The keyswitch returns to center and the indicator light
you selected remains on. The ELTS uses the selected power source. If the
selected source’s voltage or frequency drops below the limit, the ELTS
will switch to the other source.
3. When the voltage and frequency of the selected source returns to
acceptable levels, the ELTS will switch back to it.
Remote Station
Remote Keyswitch station operation is identical to the local station. Refer to
Selecting the preferred power source: Normal or Emergency for instructions.
Fire alarm or Aux signal switching
If desired, the ELTS system can be activated by fire alarm or auxiliary circuits.
When the ELTS receives the fire alarm or auxiliary circuit activation, it will
switch to Emergency power.
Note: If you have selected Emergency as the preferred power with either the
Local or Remote keyswitch, the ELTS will not switch power sources
after receiving a fire alarm or auxiliary activation.
Emergency Lighting Transfer System User Manual
25
Switching power sources manually
If you need to switch the ELTS from one power source to another when the
electronic switching circuits will not function (for example, if you needed to
use either Normal or Emergency power, but the voltage or frequency was
below the limit) you can set the transfer switch assemblies manually.
1. Disconnect Normal AND Emergency power.
Warning! Turn off Normal and Emergency power to the ELTS at the main
circuit breaker.Opening the cabinet with power applied
exposes you to death or injury from electrical shock.
2. Open the ELTS cabinet.
3. Disconnect the large brown connector on the lower left side of the control
panel.
Squeeze the release
tabs on both sides of
the socket together and
pull the plug out
ASCO GROUP 9
CONTROL PANEL
Figure 22: Removing the control panel connector
Warning! Operating switch assemblies manually without disconnecting
the control panel connector may result in the assemblies
switching back automatically, causing severe hand injuries.
▼
To switch from Normal to Emergency power: Turn the manual operation
handle on the bottom of each transfer switch assembly 90° clockwise.
E (Emergency) should be visible just above the handle.
▼
To switch from Emergency to Normal: Turn the manual operation handle
on the bottom of each transfer switch assembly 90° counter-clockwise.
N (normal) should be visible just above the handle.
4. Close the cabinet door and restore power to the ELTS.
Note: Do not plug the control panel connector back in until you want the ELTS
to resume automatic operation.
Restoring automatic operation
1. Disconnect Normal AND Emergency power.
Warning! Turn off Normal and Emergency power to the ELTS at the main
circuit breaker.Opening the cabinet with power applied
exposes you to death or injury from electrical shock.
2. Open the ELTS cabinet.
3. Reconnect the large brown connector on the lower left side of the control
panel.
4. Close the cabinet door and restore power to the ELTS.
26
Electronic Theatre Controls, Inc.
Service
Preventive maintenance
Regular testing and simple maintenance of your ELTS system will result in
long service life and reliable performance. To assist in documenting your test
and maintenance schedule, a blank Test and Maintenance Log is included on
page 35. We suggest you post a copy near your ELTS cabinet.
Warning! Turn off Normal and Emergency power to the ELTS at the main
circuit breaker.Opening the cabinet with power applied
exposes you to death or injury from electrical shock.
Warning! Rotating the transfer switch assemblies manually with Normal
or Emergency power applied may result in the assemblies
switching automatically, causing severe hand injuries.
Monthly testing
1. Manually test the ELTS’s transfer function at the local keyswitch on the
front of ELTS cabinet. See Switch function on page 19 for keyswitch
instructions and indications.
2. Note the test results in the test and maintenance log.
Quarterly testing and maintenance
1. Manually test the ELTS’s transfer function at the local keyswitch on the
front of ELTS cabinet. See Switch function on page 19 for keyswitch
instructions and indications.
2. Test the ELTS Auto transfer function. See Automatic function on page 20
for automatic transfer instructions and indications.
3. Visually inspect the ELTS cabinet for loose wires or component damage.
4. Note the test results in the test and maintenance log.
Annual testing and maintenance
1. Manually test the ELTS’s transfer function at the local keyswitch on the
front of ELTS cabinet. See Switch function on page 19 for keyswitch
instructions and indications.
2. Test the ELTS Auto transfer function. See Automatic function on page 20
for automatic transfer instructions and indications.
3. Visually inspect the ELTS cabinet for loose wires or component damage.
4. Retighten ELTS phase, neutral and ground lugs using values in Table 1 :
Emergency power lug wire sizes and connection torques on page 12.
5. Vacuum the ELTS cabinet to remove dust and debris that may have
collected.
6. Note the test results in the test and maintenance log.
Emergency Lighting Transfer System User Manual
27
Troubleshooting
If you have trouble with an installed ELTS system, you can contact ETC
Technical Service at 800/775-4382.
Warning! Trouble shooting usually involves opening the ELTS cabinet
and metering voltages. Opening the ELTS cabinet with power
applied exposes you to death or injury from electrical shock.
Use extreme caution during all troubleshooting activities.
Emergency or Normal Power Stable LED does not turn on properly
During normal operation, either the Normal Power Stable or Emergency
Power Stable LED should be lighted. If one or the other does not light, the
problem may be with the LED, Normal or Emergency sensing wiring, or
Normal or Emergency power.
1. Switch between Normal and Emergency power on the ELTS control panel
keyswitch and observe the results. The ELTS should switch between
Normal and Emergency power.
▼
The ELTS switches between Normal and Emergency
1. Check for loose LED wire connections or defective LEDs.
2. Make sure the Control Panel connector is properly seated.
▼
The ELTS does not switch between Normal and Emergency. Go to the
next ELTS troubleshooting section.
The ELTS will not switch between Normal and Emergency
If the system will not switch from Emergency power
1. check for tripped Normal power sensing wire circuit breakers.
2. If the circuit breakers are not tripped, meter Normal power using the
procedures in Voltage checkout on page 18.
If the system will not switch from Normal power
1. Meter Emergency power using the procedures in Voltage checkout on
page 18.
2. If no fire alarm or auxiliary circuits are connected to the ELTS, make sure
the terminal jumpers are in place.
3. If fire alarm or auxiliary circuits are connected, meter between the wires
to be certain the circuit is closed. An open circuit switches the ELTS to
Emergency power.
If the system does not seem to function in either Normal or Emergency power mode
1. Make sure the control panel connector is properly seated.
2. Check other wire connections for loose terminals or broken wires.
3. Use the procedures in Checking transfer switch operation manually on
page 18 to test the switching mechanism for mechanical problems.
28
Electronic Theatre Controls, Inc.
Remote stations cannot switch the ELTS
1. Switch between Normal and Emergency power on the ELTS control panel
keyswitch and observe the results.
If the ELTS does not switch locally
Follow the instructions in The ELTS will not switch between Normal and
Emergency on page 28.
If the ELTS switches locally
Try switching the ELTS from other Remote station, if multiple stations have
been installed
1. If the other stations function, check the wire terminal connections on the
problem station. See Installing Remote stations (optional) on page 11 for
station connection requirements.
2. If the other stations do not function, or there is only one Remote station
installed.
3. Check the wire connections on the Remote station terminal block.
4. Check the Remote station fuse in the ELTS cabinet
Remove this cover
on the left side of the
Isolation relays to
check the Remote
station fuse
SR3B
SR3B
SR3B
SR3B
Figure 23: Locating the Remote station fuse
5. Inspect the wiring between the ELTS cabinet and the stations for defects.
See Connecting Remote stations to the ELTS on page 16 for ELTS
connection requirements.
Some ELTS circuits do not switch when the system changes sources
Partial switching of ELTS circuits indicates one or more transfer switch
assemblies, or the wiring to them, is defective.
1. Use the procedures in Checking transfer switch operation manually on
page 18 to locate any transfer switch assemblies that have not switched
and to manually test their function.
2. If an assembly cannot be switched manually, check for something that
could be physically obstructing it. If you find something, remove it and
manually test the switch again. If you cannot find and remove the cause
of the switching failure, the assembly is defective and must be replaced.
3. If the assembly switches manually, check for loose wire connections to
the assembly and look for damaged wires between the assembly and the
control panel. Repair any wire problems you find and test the system.
Emergency Lighting Transfer System User Manual
29
Appendix A: ELTS specifications
Dimensions
Small cabinet: ELTS 450, ELTS 620, ELTS1220
36" x 30" x 9"
Large cabinet: ELTS 850, ELTS 1820, ELTS 2420
54" x 30" x 9"
Weight
ELTS 450, ELTS 620, ELTS1220 – 305 pounds
ELTS 850, ELTS 1820, ELTS 2420 – 370 pounds
Electrical
Operational voltage
120/240V single phase 250 amp maximum
120/208V three phase 175 amp maximum
277/480V three phase 175 amp maximum
Frequency: 50 – 60Hz
Short circuit current: 10 kA @ 120/240V
100,000 kA @ 277/480V
(5 kA with 50 amp circuit breakers)
Electrical Compliance
▼
ANSI/UL 1008 – Listed, Automatic Transfer Switches
▼
ANSI/NFPA 110 – Emergency and Standby Power Systems
▼
ANSI/NFPA 70 – National Electric Code
Article 701 – Legally Required Standby Systems
Article 700 – Emergency Systems
Article 540 –11(c) – Motion Picture Houses
Article 520 – 7 – Theatres and Similar Locations
Article 518 – 3(c) – Places of Assembly
▼
City of New York, Advisory board, Electrical Department
▼
OSHA
▼
Department of Defense
Environment
Ambient temperature between 32° F and 104°F (0°C and 40°C)
Humidity between 30 and 95 percent (non-condensing)
Altitude below 6500 feet (2000 meters)
30
Electronic Theatre Controls, Inc.
Appendix B: Wire connection schematics and diagrams
Wire connection schematics and diagrams are included to help you
understand the internal wiring of your ELTS system.
+
N
ØA
ØB
ØC
1 2 3 4
1 2 3 4
1 2 3 4
A A A A
B B B B
C C C C
1
2
3
4
5
6
1
1
1
1
1
51
51
69
69
+
N N N N N N N N N N N N
PS
10 9 8 7 6 5 4 3 2
1
11 14 17 20 12 15 18 21 13 16 19 22 T1 T1 T1 T1 T1 T1 T2 T2 T2 T2 T2 T2
3 F2 4 T9 6 2 EC EA NC NA
31 34 37 40 32 35 38 41 33 36 39 42 T3 T3 T3 T3 T3 T3 T4 T4 T4 T4 T4 T4
#12 WIRE
GND LUG
CP1
CP2
CP3
CP4
CP5
CP6
CP7
CP8
CP9
CP10
CP11
CP12
CP13
CP14
CP15
CP16
CP17
CP18
CP-PLUG
53 1 53 1 62 61 1 1 1 1
52 52 52 52
G
G1
R4
R5
15
G3
EC
EA
20
17
21
22
23
24
17
18
19
20
13
14
15
16
9
10
11
12
5
6
7
8
1
2
3
4
19
NB
NA
EA
G2
18
NC
69
1
51
69
1
1
51
TB
51
2
24VDC
FUSE
CR1
65
1
2
3
4
5
6
G1
52
TO CUSTOMER
"EMERGENCY"
BRANCH PANEL
T1
T1
T1
T4
T1
T1
T1
T1
TB1
TB2
TB3
TS11
TS29
TS30
TS10
TS12
G3
52
1
2
3
4
5
6
NA
69
NB
52
NC
69
1
2
3
4
5
6
EA
69
EC
69
1
2
3
4
5
6
7
8
9
1
18
16
15
G2
G3
R5
R4
69
52
69
52
1
1
1
1
1 62
1 63
52 52
1
52
R1 8
T2 14
T3 10
19 20
1
17
1
X2 X3
X4 X5
X6 X7
A1 13 51 23 61 33 71 43 81
6 3 5 2 4
1
1
6 3 5 2 4
1
6 3 5 2 4
B 9 8 7 A
CR2
CR3
B 9 8 7 A
TO LAMP
LOADS
1
1
CR4
B 9 8 7 A
D3
X13
TR
A2 14 52 24 62 34 72 44 82
F1 12
6 6
A1 12
6
T6
R3
R2
EC EA NA
NC 16
67 63
51 63
62 66
68
62 64
1 65
63 65
1 64
64
1
1
1
1 1 1
1 1
TB
N
TS6
EN6 NN6
TB
N
TS5
EN5 NN5
52
TB
N
TS4
EN4 NN4
TB
N
TS3
EN3 NN3
TB
N
TS2
EN2 NN2
TB
N
TS1
EN1 NN1
15
14
13
12
11
EL6 NL6
EL5 NL5
EL4 NL4
NORMAL
SOURCE
TO LAMP
LOADS
EL3 NL3
EL2 NL2
EL1 NL1
TRANSFER SWITCH
12 POLE
51
X12
6 6
TB1
51
D2
10 8
16
51
X11
6 6
31 12 29 11 10 30 13 32
LN6
LL6
LN5
LL5
LN4
LL4
LN3
LL3
LN2
LL2
LN1
LL1
D1
B 9 8 7 A
14 10
TB2
TB3
TB1
TB2
TB3
1
1
1
T2
T2
T2
LN6
LL6
LN5
LL5
LN4
LL4
LN3
LL3
LN2
LL2
LN1
LL1
TB
N
TS112
TB
N
21 TS111
TB
N
20 TS110
TB
N
19
TS9
TB
N
18
TS8
TB
N
17
TS7
22
EN6 NN6
EL6 NL6
EN5 NN5
EL5 NL5
EN4 NN4
EL4 NL4
EN3 NN3
NORMAL
SOURCE
EL3 NL3
EN2 NN2
EL2 NL2
EN1 NN1
EL1 NL1
TB1
TRANSFER SWITCH
12 POLE
T2
T4
T2
T4
T2
T4
T2
T4
52
61 63
T12
TS2A
TS29
TS3B
TS2B
TS30
TS3A
TO CUSTOMER
"NORMAL"
MAIN PANEL
G2
1
13
31 12 29 11 10 30 13 32
TB2
TB3
TB1
TB2
TB3
T2
T1
T2
T1
T2
T1
51
31 12 29 11 10 30 13 32
TO LAMP
LOADS
LN6
LL6
LN5
LL5
LN4
LL4
LN3
LL3
LN2
LL2
LN1
LL1
N
TS18
EN6 NN6
TB
N
TS17
EN5 NN5
TB
N
TS16
EN4 NN4
TB
N
TS15
EN3 NN3
TB
N
TS14
EN2 NN2
TB
N
TS13
EN1 NN1
35
34
33
32
31
31 12 29 11 10 30 13 32
TB
36
#12 WIRE
TO ENGINE
GENERATOR
CONTROL
53
T11
T3
T3
1
A1
A2
1
11
TS3B
TS30
TS11
1
2
3
63
11
T1
T3
T1
T3
T1
T3
T1
T3
TO CUSTOMER
AUX. STATION
(AS)
64
9
TS1A
TS29
TS2B
TS1B
TS30
TS2A
64
51
62
#12 WIRE
F1
F2
1 1 1
7
1
T2
1
T2
1
T2
1
T2
1
2
3
FACTORY JUMPER
REMOVE
AS REQUIRED
T1 T8 T7
1
53
TS12
TS29
TS1B
TS10
TS30
TS1A
TO CUSTOMER
FIRE ALARM CNTRL.
STATION (FA)
TO CUSTOMER
REMOTE CONTROL
STATION (RC)
66
#12 WIRE
61
67
68
52
1
52
1
T10
1 62
5
1
R1
R2
R3
R4
R5
T4 7
65 1 51 51
9
6 3 5 2 4
R1
1
2
3
4
5
6
13 T5 3 4
63
T3
T3
53
67
68
53
53
66
53
53
51
53
64
65
TS3A
TS29
1 T1
2 T2
3 T3
4 T4
5 T5
6 T6
7 T7
8 T8
9 T9
10 T10
11 T11
12 T12
EL6 NL6
EL5 NL5
EL4 NL4
NORMAL
SOURCE
TO LAMP
LOADS
EL3 NL3
EL2 NL2
EL1 NL1
TB1
TRANSFER SWITCH
12 POLE
TB2
TB3
TB1
TB2
TB3
T4
T2 T4
T2 T4
T2
LN6
LL6
LN5
LL5
LN4
LL4
LN3
LL3
LN2
LL2
LN1
LL1
TB
N
TS24
EN6 NN6
TB
N
TS23
EN5 NN5
TB
N
TS22
EN4 NN4
TB
N
TS21
EN3 NN3
TB
N
TS20
EN2 NN2
TB
N
TS19
EN1 NN1
42
41
#12 WIRE
10
10
10
9
8
4
3
4
7
5
6
7
CONTROL PANEL
CT1
CT2
CT3
CT4
CT5
CT6
CT7
CT8
CT9
CT10
CT11
CT12
CT13
CT14
CT15
CT16
CT17
CT18
CT19
CT20
POWER TB
INCOMING POWER
40
39
38
37
EL6 NL6
EL5 NL5
EL4 NL4
NORMAL
SOURCE
EL3 NL3
EL2 NL2
EL1 NL1
TB1
TRANSFER SWITCH
12 POLE
TB2
TB3
TB1
TB2
TB3
T3
T3
T3
BACKWALL
Figure 24: ELTS cabinet wire connection location diagram
Emergency Lighting Transfer System User Manual
31
NORMAL POWER
STABLE
G
T7
1
T6
4
EMERGENCY POWER
STABLE
G
T8
1
T6
1
#12 WIRE
3
GENERATOR
START
G
EMERGENCY
OPERATION
T10
T9
R
1
TB
TB
TB
TB
TB
TB
TB
TB
TB
TB
TB
A
B
C
A
B
C
A
B
C
A
B
C
NORMAL
OPERATION
T5
6
TB
G
1
T1
10
T4
9
T1
CB1
1
8
CB2
CB3
CB4
CB5
CB6
CB7
CB8
CB9
CB10
CB11
CB12
TS1
TS2
TS3
TS4
TS5
TS6
TS7
TS8
TS9
TS10
TS11
TS12
T1
T1
T1
T1
T1
T1
T2
T2
T2
T2
T2
T2
#12 WIRE
FIRE ALARM
TRANSFER SIGNAL
R
#12 WIRE
T11
1
T9
7
5
TB
TB
TB
TB
TB
TB
TB
TB
TB
TB
TB
TB
A
B
C
A
B
C
A
B
C
A
B
C
KEYSWITCH CIRCUIT
AUXILIARY
TRANSFER SIGNAL
R
T12
T9
8
1
1
N
1
A
CB13
E
T1
6
T2
1
T3
1
CB14
CB15
CB16
CB17
CB18
CB19
CB20
CB21
CB22
CB23
CB24
TS13
TS14
TS15
TS16
TS17
TS18
TS19
TS20
TS21
TS22
TS23
TS24
T3
T3
T3
T3
T3
T3
T4
T4
T4
T4
T4
T4
#12 WIRE
Breaker bracket schematic
Door panel schematic
Figure 25: ELTS door panel and breaker bracket wire connection schematics
13
11
31
TS1A
TS2A
TS3A
TS1B
TS2B
TS3B
29
13
T1
TB1
TB2
11
31
29
13
T2
TB3
12
10
32
30
TB1
TB2
11
31
29
T3
TB3
12
10
32
30
TB1
TB2
13
11
31
29
12
10
32
30
T4
TB3
12
10
32
30
TB1
TB2
TB3
TERMINAL BLOCK
TS12
TS10
TS30
TS29
TS11
TB3
TB2
TB1
8
TS12
7
TS10
6
TS30
5
TS29
4
TS11
3
TB3
2
TB2
1
TB1
FACTORY CONNECTIONS
TO CONTROL MODULE
SEE CONTROL SCHEMATIC DIAGRAM
Figure 26: Transfer switch assembly control wire connections schematic
32
Electronic Theatre Controls, Inc.
Appendix C: Transfer switch control system schematics
EXPLANATION:
CP
CR1- CR4
PS
TR
PL1- PL7
NA
- CONTROL PANEL
- CONTROL RELAY
- POWER SUPPLY
- TRANSFER RELAY
- INDICATING LIGHT
EA
TR
52
TR
TR
20
13
51
14
24
S4
SS - SELECTOR SWITCH, KEY OPERATED
3
61 62
S6
S3
1
TR
1
23
S1
THIS
DRAWING
S2
PS
EC
208 VAC CKT.
FROM EMERGENCY BRANCH PANEL
D1- D3 - DIODE BLOCKS
- TRANSFER SWITCH TERMINAL CONNECTION
- TERMINAL BLOCK
XX - CONNECTOR PLUG TO CONTROL PANEL
S1 - CONNECTION POINT
NC
208 VAC CKT.
FROM NORMAL MAIN PANEL
S5
4
( 208 VAC INPUT )
2
DUAL INPUT POWER SUPPLY
INTERNAL JUMPER
INTERNAL JUMPER
FACTORY JUMPERS
REMOVE AS REQUIRED
+ 9
7 +
( 24 Vdc OUTPUT )
5 +
F2
F2
F2
F1
F1
F1
CR3
B
A1
A1
CR4
B
A
X10
REMOTE
CONTROL
STATION
FAULT
FUSE
LOCAL DIAGNOSTIC PNL. (LD)
R
FIRE ALARM
TRANSFER SIGNAL
R
GENERATOR
START
G
EMERG POWER
STABLE
G
NORMAL POWER
STABLE
G
AUX T12
T12
FIRE T11
T11
JMPR
1
T11
7
CR3
1
7
TEST-NC
CT6
T10
T10
NR
NR
CT12
T9
T9
T9
TS
CT2
E
T8
T8
T8
E-OK
CT18
N
T7
T7
T7
N-OK
CT19
T6
EMERG.
PL2
R
T5
T5
T5
NORM.
PL1 T4
G
T4
T4
N A E
T2
T2
T2
T3
T3
T3
T1
T1
T1
SS
(KEY OPER)
ET-NC
CT1
+24VDC
CT17
X11
G
X3
13
8
CR4
12
6
9
CR2
9
9
6
CR1
3
11
6
CR2
1
7
10
9
B CR2 A
TRANSFER
MANUAL RELAY
B CR1 A
RETRANSFER
MANUAL RELAY
X7
X13
X5
14
X12
R5
R5
N
R4
R4
R4
E
R2
R2
R2
THIS
DRAWING S2
NA
N
R3
R3
R3
THIS
DRAWING S6
NC
R1
CR3
9
E
R1
7
JMPR
X2
X6
D2
4
GND
CT15
TS-NORM
CT9
D3
CR1
7
INHIBIT
CT11
X4
R
BYPASS
CT10
DELAY
TEST-EMG
CT8
D1
REMOTE CONTROL STATION (RC)
MAN-X
CT4
CT14
T6
LOCAL CONTROL STATION (LC)
GND
CT3
TEST-NC
CT7
GEN T10
T6
AUX. STATION
ISOLATION RELAY
CP
GND
CT16
CR4
T12
6
4
FIRE ALARM
ISOLATION RELAY
X1
5A
A2
A1
6 -
A
AUXILIARY STATION (AS)
A2
8 -
3
2
FIRE ALARM STATION (FA)
AUXILIARY
TRANSFER SIGNAL
10 -
R5
CONTROL PANEL
R1
FROM NORMAL MAIN PANEL
TO
ENGINE-GENERATOR
CONTROL
NB
NB
NORMALLY
CLOSED CONTACT
G1
ENGINE-GEN.
START-RUN
COMMAND
NORMALLY
OPEN CONTACTS
G2
G2
G3
G3
CP12
NA SENSE
CP4
NC SENSE
CP13
TS-NO
CP14
TS-NC
CP11
NB SENSE
NR
G1
CP17
CP8
NR
CP9
CP7
TS12
EA
THIS
DRAWING S3
EA SENSE
SE
CP5
TS10
CP15
TS30
A2
FACTORY CONNECTION
TO TRANSFER SWITCH(ES)
SEE TRANSFER SWITCH
SCHEMATIC DIAGRAM
TS29
19
A1
EC
THIS
DRAWING S5
TS11
15
TB3
TR
16
34
TB2
TB1
Emergency Lighting Transfer System User Manual
TR
17
33
18
1
THIS
THIS
S1 DRAWING DRAWING S4
20
ER
SE
CP16
CP6
EC SENSE
CP10
TS-COM
ER SE
CP1
SE
CP3
CP2
33
Appendix D: Transfer switch load switching schematic
EMERG. SOURCE
EMERG. SOURCE
EMERG. SOURCE
EMERG. SOURCE
EMERG. SOURCE
CIRCUIT 1
CIRCUIT 2
CIRCUIT 3
CIRCUIT 4
CIRCUIT 5
N
ØA
#12
ØB
#12
CB1
20A
N
ØC
#12
ØA
#12
CB3
20A
CB2
20A
TS1
N
ØB
#12
CIRCUIT 6
N
ØC
#12
CB5
20A
CB4
20A
TS3
TS2
N
EMERG. SOURCE
TS4
N
CB6
20A
TS5
TS6
#12 WIRE
LOAD
AC1
REC
+
-
LOAD
CIRCUIT 2
CIRCUIT 1
LL1
LOAD
LN3
LL3
LOAD
CIRCUIT 4
CIRCUIT 3
LN2
LL2
LN1
LOAD
LL4
LOAD
CIRCUIT 6
CIRCUIT 5
LN4
LL5
LN5
LN6
LL6
AC2
TS1
A
COIL
E
B CKT
71
9
70
6
72
8
69
7
E
L
L
N
TB1
TB2
E
L
N
E
N
NN4
E
L
N
NL5
N
NN5
31
29
32
13
30
11
TS1
12
10
TS1
E
L
L
N
NL4
E
L
L
N
NN3
NL3
NN2
E
L
N
N
N
NL2
E
L
L
L
N
NN1
NL1
E
E
E
N
NL6
NN6
NORMAL SOURCE
NORMAL SOURCE
NORMAL SOURCE
NORMAL SOURCE
NORMAL SOURCE
NORMAL SOURCE
CIRCUIT 1
CIRCUIT 2
CIRCUIT 3
CIRCUIT 4
CIRCUIT 5
CIRCUIT 6
EMERG. SOURCE
EMERG. SOURCE
EMERG. SOURCE
TS1
12 POLE UNIT
TB3
EMERG. SOURCE
EMERG. SOURCE
CIRCUIT 7
ØA
#12
EMERG. SOURCE
CIRCUIT 8
N
ØB
#12
CB7
20A
CIRCUIT 9
N
ØC
#12
ØA
#12
TS8
CIRCUIT 11
N
ØB
#12
TS10
TS9
CIRCUIT 12
N
ØC
#12
CB11
20A
CB10
20A
CB9
20A
CB8
20A
TS7
CIRCUIT 10
N
N
CB12
20A
TS11
TS12
#12 WIRE
LOAD
AC1
REC
+
-
LOAD
CIRCUIT 8
CIRCUIT 7
LL7
LOAD
LL9
LOAD
CIRCUIT 10
CIRCUIT 9
LN8
LL8
LN7
LOAD
LL10
LN9
LOAD
CIRCUIT 12
CIRCUIT 11
LN10
LL11
LN11
LN12
LL12
AC2
TS1
A
COIL
E
B CKT
71
9
70
6
72
8
69
7
E
L
L
N
TB1
TB2
E
L
N
NN9
NL9
NN8
E
L
L
E
L
E
L
L
31
29
32
13
30
11
TS2
12
10
TS2
E
L
N
N
N
N
N
N
NL10
NN10
NL11
NN11
NL12
NN12
N
N
N
NL8
E
E
L
L
L
N
NN7
NL7
E
E
E
NORMAL SOURCE
NORMAL SOURCE
NORMAL SOURCE
NORMAL SOURCE
NORMAL SOURCE
NORMAL SOURCE
CIRCUIT 7
CIRCUIT 8
CIRCUIT 9
CIRCUIT 10
CIRCUIT 11
CIRCUIT 12
TS2
12 POLE UNIT
TB3
EMERG. SOURCE
EMERG. SOURCE
CIRCUIT 13
ØA
#12
EMERG. SOURCE
CIRCUIT 14
N
ØB
#12
CB13
20A
CIRCUIT 15
N
ØC
#12
ØA
#12
EMERG. SOURCE
CIRCUIT 16
N
ØB
#12
CIRCUIT 17
N
ØC
#12
CB16
20A
CB15
20A
TS15
TS14
EMERG. SOURCE
CIRCUIT 15
N
CB15
20A
CB14
20A
TS13
EMERG. SOURCE
TS15
N
CB17
20A
TS16
TS17
#12 WIRE
LOAD
AC1
REC
+
-
LOAD
CIRCUIT 14
CIRCUIT 13
LL13
LOAD
LN15
LL15
LOAD
CIRCUIT 16
CIRCUIT 15
LN14
LL14
LN13
LOAD
LL16
LOAD
CIRCUIT 18
CIRCUIT 17
LN16
LL17
LN17
LN18
LL18
AC2
TS1
A
COIL
E
B CKT
71
9
70
6
72
8
69
7
TB1
TB2
E
L
E
L
L
E
E
E
L
L
L
E
E
L
E
L
E
L
E
L
L
31
29
32
13
30
11
TS3
12
10
TS3
E
L
N
N
N
N
N
N
N
N
N
N
N
N
NL13
NN13
NL14
NN14
NL14
NN14
NL15
NN15
NL16
NN16
NL17
NN17
NORMAL SOURCE
NORMAL SOURCE
NORMAL SOURCE
NORMAL SOURCE
NORMAL SOURCE
NORMAL SOURCE
CIRCUIT 13
CIRCUIT 14
CIRCUIT 14
CIRCUIT 15
CIRCUIT 16
CIRCUIT 17
TS3
12 POLE UNIT
TB3
EMERG. SOURCE
EMERG. SOURCE
EMERG. SOURCE
EMERG. SOURCE
EMERG. SOURCE
CIRCUIT 19
CIRCUIT 20
CIRCUIT 21
CIRCUIT 22
CIRCUIT 23
ØA
#12
N
ØB
#12
CB19
20A
N
ØC
#12
ØA
#12
CB21
20A
CB20
20A
TS19
N
ØB
#12
CIRCUIT 24
N
ØC
#12
CB23
20A
CB22
20A
TS21
TS20
N
EMERG. SOURCE
TS22
N
CB24
20A
TS24
TS23
#12 WIRE
LOAD
AC1
REC
++
--
LOAD
CIRCUIT 20
CIRCUIT 19
LL19
LOAD
LN21
LL21
LOAD
CIRCUIT 22
CIRCUIT 21
LN20
LL20
LN19
LOAD
LL22
LOAD
CIRCUIT 24
CIRCUIT 23
LN22
LL23
LN23
LN24
LL24
AC2
TS1
A
COIL
E
B CKT
71
9
70
6
72
8
69
7
TB1
34
TB2
TB3
E
L
L
L
L
L
L
E
E
E
E
E
L
E
L
E
L
E
E
L
L
L
N
N
N
N
N
N
N
N
N
N
N
N
NL19
NN19
NL20
NN20
NL21
NN21
NL22
NN22
NL23
NN23
NL24
NN24
NORMAL SOURCE
NORMAL SOURCE
NORMAL SOURCE
NORMAL SOURCE
NORMAL SOURCE
NORMAL SOURCE
CIRCUIT 19
CIRCUIT 20
CIRCUIT 21
CIRCUIT 22
CIRCUIT 23
CIRCUIT 24
12 POLE UNIT
31
29
32
13
30
11
TS4
12
10
TS41
E
TS4
Electronic Theatre Controls, Inc.
Appendix E: Test and Maintenance Log
Date installed ___________________________________________
System address _________________________________________
________________________________________________________
Service contact __________________________________________
Date
Inspected by
Manual transfer Automatic transfer Visual inspection Vacuumed
Emergency Lighting Transfer System User Manual
35
Electronic Theatre Controls
North America
Europe
3030 Laura Lane
5 Victoria Industrial Estate • Victoria Road
Middleton, Wisconsin 53562 • USA
London W3 6UU • England
Tel: (+1) 608 831 4116 • Fax: (+1) 608 836 1736 Tel: (+44) 181 896 1000 • Fax: (+44) 181 896 2000
World Wide Web: http://www.etcconnect.com • Email: [email protected]
Asia
Room 1619-20 • 16/F Metro Centre II • 21 Lam Hing Street
Kowloon Bay • Hong Kong
Tel: (+852) 2799 1220 • Fax: (+852) 2799 9325
Copyright ©1997 revised 8/97
Specifications subject to change. 1093M1101