Download Par ti tions

Transcript
A Zone event can be restored to standby by:
Ø changing the status (Armed/Disarmed) of a Partition
the Zone is associated with;
Ø running Alarm Reset from a Keypad (the entered
User Code and Keypad must be jointly enabled on a
Partition the Zone is associated with);
Ø running Alarm Stop from the Keypad (the entered
User Code and Keypad must be jointly enabled on a
Partition the Zone is associated with);
Ø Using a valid Digital Key/Card at a Reader (both Digital Key and Reader must be jointly Enabled on a Partition the Zone is associated with).
Partition Events Table 6 shows the Partition Events.
The Partition Events encase the Zone Events (Fire, 24h,
Burglar, etc.). Each Zone event will in turn generate a
Partition event (on the Partition the Zone is associated
with). The Partition event will not terminate until all the
Zone events end, as follows:
conditions which terminate Partition Events
+ The
(ENDS WHEN ... column) are valid ONLY when
the Partition Event is NOT associated with a Monostable Output.
Zone Events which are associated with a Monostable
Output will not terminate until the Output OFF Timeout
has expired (see Figure 41).
Partition Events can be restored to standby by:
Ø changing the Partition status (Armed/Disarmed);
Ø running Alarm Reset from a Keypad (the entered
User Code and Keypad must be jointly enabled on
the Partition concerned);
Ø running Alarm Stop from the Keypad (the entered
User Code and Keypad must be jointly enabled on
the Partition concerned)
Ø Using a valid Digital Key/Card at a Reader (both Digital Key and Reader must be jointly enabled on the
Partition concerned).
Control Panel Events Table 7 shows the Control
panel Events. The Control panel events comprise all
the Zone Events (Fire, 24h, Burglar, etc.) but are totally
independent of the Partitions. Control panel events will
be generated when the events they comprise occur,
and will not terminate until all the events they comprise
have ended.
conditions which terminate the Control Panel
+ The
Events (ENDS WHEN ... column) are valid ONLY
when the Control Panel Event is NOT associated
with a Monostable Output.
Control Panel Events associated with Monostable Outputs will not terminate until the Output OFF Timeout has
expired (see Figure 41).
Control Panel Events can be restored to standby by:
Ø running Alarm Reset from a Keypad (the entered
User Code must be enabled for Control Panel Reset
— refer to “Keypad codes - Codes types”);
Ø running Alarm Stop from a Keypad (the entered
User Code must be enabled for Stop alarms — refer to “Digital keys”);
Ø using a Digital Key/Card at a Reader (the Digital
Key/Card must be enabled for Stop alarms, refer to
“Digital keys”).Generic Events
These are Control
Panel-generated warnings (e.g. Power Failure).
The conditions which end a Generic Event
+ (ENDS
WHEN ... column) are only valid when the
Generic Event is NOT associated with a Monostable Output.
0001
0280
0281
EVENT
OCCURS WHEN...
Alarm on ... the zone detects Alarm conditions12
zone no.11
0344
0345
0624
0625
0688
ENDS WHEN...
... the zone restores to standby status
Alarm on ... the Wireless zone detects Alarm13 condi- ... the Wireless zone restores to standby
zone no. – tions
Wireless
... Tamper conditions are no longer present
Tamper on ... the zone detects Tamper conditions
on the zone
zone no.11
Tamper on … the Wireless Zone detects Tamper con- ... Tamper conditions are no longer present
Zone no. – ditions
on the Wireless zone
Wireless
Table 5 Zone Events
11 Zone Events relating to terminals T1 and T2 of M-IN/OUT Expanders programmed as Expanders with 4 Zones
+ 2 Outputs, and Zone Events relating to terminals T1, T2, T3 and T4 of M-IN/OUT Expanders programmed as
Expanders with 4 Outputs + 2 Zones, are NOT usable.
12 The conditions that trigger Alarm and Tamper status on Hardwired Zones depend on the settings programmed
on the BPI Zones page.
13 The conditions that trigger Alarm and Tamper status on Wireless Zones depend on the settings programmed on
the Wireless page.
KYO 320
PROGRAMMING FROM THE PC
59