Download Vision Cable - Phase to Phase
Transcript
21 4.3.2 09-150 pmo Circuits A circuit can exist of: · a single 3-core cable · three 1-core cables New circuits can be added using the menu New | Circuit. Because of the IEC 60287 standard, it is not always possible to calculate more than one circuit: Under ground: No drying of ground Partial drying of ground Prevent drying of ground Multiple circuits possible One circuit only Multiple circuits possible In air: No solar radiation Solar radiation Configurations from standard Configurations from standard In the dialog used to add a circuit, certain properties can be set. These are: · cable type 21 · lay 22 · current 25 · duct 26 · trough 27 A circuit can also be given a name and a circuit number. The same dialog is also using to change a circuit. 4.3.2.1 Cable type On this tab a specific cable type can be chosen. A filter can be used to narrow down the selection of cables from the cable type database. Filters can be used with 3 criteria: · isolation (plastic or no plastic) · number of cores (1 or 3) · voltage level Filter for the voltage level: The voltage levels are line voltages, however, in the cable type database, the phase voltage is stored. Some PILC cables have a higher phase voltage (8/10 and 10/10 kV), so these cables will be in a higher voltage range. If a cable type is chosen, a graphical representation of the cable is automatically shown. The maximum allowed conductor temperature of the chosen cable can be adjusted if necessary.