Download Micrologic Control units
Transcript
Setting load shedding / reconnection Protection settings P Load shedding On On Pick up Pick up Pick up 1000kW 1000kW 3600s 3600s 3600s Drop out Confirm. Load shedding P E71676A P 1000kW 10s Select: b Off: load shedding disabled b On: load shedding enabled. E71675A Load shedding On On On Pick up Pick up Pick up P 1000kW 1000kW 1000kW 3600s 3600s 3600s Drop out 985kW Drop out 980kW 10s 10s then Select the existing dropout threshold. 10s Confirm. Adjust. P E71677A Load shedding Drop out 985kW Load shedding On On Pick up Pick up P 1000kW 1000kW 3600s 3600s Drop out Do you want to save new settings? Drop out 985kW 985kW 10s 10s then Set the other parameters. E71657A E71674A Load shedding Drop out 1000kW 10s then Select the first setting. E71677A P 1000kW 1000kW 10s 04443728AA - 01/2009 Load shedding Off Drop out When all the settings have been made, quit the screen by pressing one of the menu-access buttons. This saves the new values. P E71672A Load shedding E71671A E71670A Example: Take load shedding / reconnection depending on power. Quit the setting screen. no yes Confim. 67