CHAPTER 8 USER CALIBRATION
8.1 User Calibration
As the product has been calibrated at the factory, it does not need to be calibrated
in normal use.
The product has the capability of analog input calibration, which enables user
calibration as needed.
OMRON assumes no responsibility for the result of user calibration.
Note that, once user calibration is performed, original calibration data is
overwritten and cannot be restored.
Devices and tools necessary for user calibration must be made available by the
user. For handling of these devices, refer to their respective manuals.
Entry of
Calibration
data
First store both of calibration values 1 and 2 temporarily. Then save them while
the product is in the change state.
Calibration data cannot be saved normally unless calibration values 1 and 2 are
both specified.
If calibration data is saved normally, the product keeps a record of the user
calibration. When you enters the user calibration level, a calibration record mark
will appear on the main indicator as shown below.
T
u
0i . 30
USER
CALIBRATION
Calibration record mark