Download Security Escort 2.15 Hardware Installation Manual
Transcript
Security Escort Testing and troubleshooting | en Symptoms 65 Probable Cause Possible Solutions\ No power to receiver. Check power for 10.5 V DC to 13.5 V DC. If lower than 10 V DC or no voltage present, check wiring (PWR+ to PWR-) on power side of receiver, repair, or replace cable. Close lightning hit. Power down transponder (AC and battery) for 30-sec., then turn power back on. If bus failure does not clear, probable cause would be bad bus on transponder. Bad bus on transponder. Remove cable from bus, meter terminals with VOM. If voltage is lower then 9 V DC on BUS+ or lower then 12 V DC on PWR+, replace transponder. Table 6.3: EA500 transponder bus faults Symptoms Probable Cause Possible Solutions\ Single receiver not Address switch in wrong Rotate switch to correspond responding. position. with transponder database location. Open on the bus wires. Put meter across bus wire. Should be reading between 7.5 V DC to 10.5 V DC. If voltage is not present or lower than 9 V, check wiring (BUS+ to BUS-) for possible ground or open. No power to receiver. Check power for 10.5 V DC to 13.5 V DC. If lower than 10 V or no voltage present, check wiring (PWR+ to PWR-) on power side of receiver repair or replace cable. Defective receiver. If power is present on BUS+ and PWR+ and rotary switch is set to correct address, replace receiver. Robert Bosch (SEA) Pte Ltd Hardware Installation Manual 2015.05 | V2.15.0 | DOC