Download WOLVERTON
Transcript
V. HEARTH AND FIRE SURROUND In conformity with Building Regulations, the stove should be installed on a solid, non-combustible surface such as concrete or masonry. This must be at least 125mm (5”) thick. The specified depth may include the thickness of any solid non-combustible floor beneath the hearth. Combustible material should not be placed beneath constructional hearths unless there is an air-space of at least 50mm between the underside of the hearth and the combustible material, or the combustible material is at least 250mm (10”) below the top of the hearth. Dimensions of the hearth should project at least 300mm (12”) forward of the front of the appliance and 150mm (6”) at the sides. The stove must be situated at least 1000mm (40”) from any combustible material including furniture, magazine rack and clothing etc. Do not dry clothes on or within this proximity of the stove. Fire recesses must be constructed from non-combustible material. The minimum clearance between the stove and the recess wall should be 76mm (3”). IMPORTANT: Do not install the stove in closets or alcoves. Central locations are desirable; however the minimum run of pipe to the chimney should be the deciding factor when choosing a location. Do not store flammable liquids in the same room as the stove. Minimum wall clearance must be maintained as illustrated below. BACK WALL A SIDE WALL B ADJACENT WALL SIDE WALL A SIDE WALL SIDE WALL B BACK WALL ADJACENT WALL C C C SIDE WALL A - 229 mm / 9” SIDE WALL A - 229 mm / 9” BACK WALL B - 76 mm / 3” CORNER C -B 26-mm 1” BACK WALL 76/ mm / 3” CORNER C - 26 mm / 1” C