Download ControlLogix System User Manual, 1756-UM001N-EN-P

Transcript
User Manual
ControlLogix System User Manual
Catalog Numbers 1756-L61, 1756-L62, 1756-L63, 1756-L63XT, 1756-L64, 1756-L65, 1756-L71, 1756-L72, 1756-L73,
1756-L73XT, 1756-L74, 1756-L75
Important User Information
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from
your local Rockwell Automation® sales office or online at http://www.rockwellautomation.com/literature/) describes some
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
IMPORTANT
Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, CompactLogix, ControlLogix, DriveLogix, FLEX, Kinetix, MessageView, MicroLogix, POINT I/O, PhaseManager, PowerFlex, RSFieldbus, RSLinx, RSLogix, RSNetWorx, Rockwell Software, Rockwell
Automation, Compact I/O, RediSTATION, Series 9000, FlexLogix, PanelView, FactoryTalk, ArmorPOINT, Stratix 8000, SLC, ControlFLASH, DH+, Data Highway Plus, Integrated Architecture, Logix5000,
ControlLogix-XT, GuardLogix, RSView, Encompass, 1336 FORCE, 1336 PLUS, 1336 IMPACT, SMC, RSBizWare, FLEX Ex, ArmorBlock, ArmorBlock MaXum, Guard PLC, and TechConnect are trademarks of Rockwell
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Summary of Changes
This manual contains new and updated information. Changes throughout this
revision are marked by change bars, as shown to the right of this paragraph.
New and Updated
Information
This table contains the changes made to this revision.
Topic
Page
Studio 5000™ Logix Designer application is the rebranding of RSLogix™ 5000 software
11
Added an Attention statement to the section about installing the ESM
25
Added Integrated Motion to motion control options
141
Added section about extended properties
154
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
3
Summary of Changes
Notes:
4
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Table of Contents
Preface
Studio 5000 Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ControlLogix Controllers Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Standard ControlLogix Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Redundant ControlLogix Controllers. . . . . . . . . . . . . . . . . . . . . . . . . .
Extreme Environment ControlLogix Controllers . . . . . . . . . . . . . . .
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Required Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
11
12
12
12
13
13
14
Chapter 1
Install the 1756-L7x Controller
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1756-L7x Controller Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts Included with the 1756-L7x Controller . . . . . . . . . . . . . . . . . . .
Parts Available for Use with the 1756-L7x Controller . . . . . . . . . . .
1756-L7x Controller Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Insert the Controller into the Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Insert the Key. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Install the SD Card. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Remove the SD Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Install the ESM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Uninstall the ESM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
17
17
17
18
18
19
20
21
23
25
26
Chapter 2
Install the 1756-L6x Controller
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1756-L6x Controller Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts Not Included with the 1756-L6x Controller. . . . . . . . . . . . . . .
1756-L6x Controller Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CompactFlash Card Installation and Removal . . . . . . . . . . . . . . . . . . . . . .
Battery Connection and Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Insert the Controller into the Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Remove the Controller from the Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . .
31
31
31
32
32
36
39
41
Chapter 3
Start Using the Controller
Make Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1756-L7x Connection Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1756-L6x Connection Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connect to the 1756-L7x Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Set Up the USB Driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connect to the 1756-L6x Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configure the Serial Driver. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Upgrade Controller Firmware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Determine Required Controller Firmware. . . . . . . . . . . . . . . . . . . . . .
Obtain Controller Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Use ControlFLASH Utility to Upgrade Firmware . . . . . . . . . . . . . .
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
43
43
44
44
45
47
48
50
50
51
51
5
Table of Contents
Use AutoFlash to Upgrade Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . .
Set the Communication Path. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Go Online with the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Download to the Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Use the Who Active Dialog Box to Download . . . . . . . . . . . . . . . . . .
Use the Controller Status Menu to Download . . . . . . . . . . . . . . . . . .
Upload from the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Use the Who Active Dialog Box to Upload . . . . . . . . . . . . . . . . . . . . .
Use the Controller Status Menu to Upload . . . . . . . . . . . . . . . . . . . . .
Choose the Controller Operation Mode . . . . . . . . . . . . . . . . . . . . . . . . . . .
Use the Mode Switch to Change the Operation Mode . . . . . . . . . . .
Use Logix Designer to Change the Operation Mode . . . . . . . . . . . . .
Load or Store to the Memory Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Store to the Memory Card. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Load from the Memory Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Other Memory Card Tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Use ControlLogix Energy Storage Modules (ESMs) . . . . . . . . . . . . . . . . .
Save the Program to On-board NVS Memory . . . . . . . . . . . . . . . . . . .
Clear the Program from On-board NVS Memory . . . . . . . . . . . . . . .
Estimate the ESM Support of the WallClockTime . . . . . . . . . . . . . . . . . .
Maintain the Battery (1756-L6x controllers only) . . . . . . . . . . . . . . . . . . .
Check the Battery Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1756-BA1 or 1756-BATA Battery Life . . . . . . . . . . . . . . . . . . . . . . . . .
1756-BATM Battery Module and Battery Life . . . . . . . . . . . . . . . . . .
Estimate 1756-BA2 Battery Life . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Estimate 1756-BA2 Battery Life after Warnings. . . . . . . . . . . . . . . . .
Battery Storage and Disposal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
54
56
57
58
58
59
59
59
60
61
61
63
64
64
67
69
69
70
71
71
72
72
73
74
74
75
76
Chapter 4
ControlLogix System and Controllers ControlLogix System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Configuration Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Design a ControlLogix System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ControlLogix Controller Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System, Communication, and Programming Features . . . . . . . . . . . .
Memory Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
77
80
81
81
82
Chapter 5
Communication Networks
6
Networks Available. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EtherNet/IP Network Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ControlLogix EtherNet/IP Module Features. . . . . . . . . . . . . . . . . . . .
ControlLogix EtherNet/IP Communication Modules . . . . . . . . . . .
Software for EtherNet/IP Networks. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connections over an EtherNet/IP Network . . . . . . . . . . . . . . . . . . . .
Double Data Rate (DDR) Backplane Communication. . . . . . . . . . .
ControlNet Network Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ControlLogix ControlNet Module Features . . . . . . . . . . . . . . . . . . . .
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
83
84
84
85
86
86
87
87
89
Table of Contents
ControlLogix ControlNet Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Software for ControlNet Networks . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connections over a ControlNet Network . . . . . . . . . . . . . . . . . . . . . .
DeviceNet Network Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ControlLogix DeviceNet Module Features . . . . . . . . . . . . . . . . . . . . .
ControlLogix DeviceNet Bridge Module and Linking Devices . . .
Software for DeviceNet Networks . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connections over DeviceNet Networks . . . . . . . . . . . . . . . . . . . . . . . .
ControlLogix DeviceNet Module Memory . . . . . . . . . . . . . . . . . . . . .
Data Highway Plus (DH+) Network Communication . . . . . . . . . . . . . .
Communicate over a DH+ Network. . . . . . . . . . . . . . . . . . . . . . . . . . .
Universal Remote I/O (RIO) Communication . . . . . . . . . . . . . . . . . . . . .
Communicate over a Universal Remote I/O Network . . . . . . . . . . .
Foundation Fieldbus Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HART Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
89
89
90
90
91
91
92
92
92
92
93
94
95
96
97
Chapter 6
Serial Communication
on 1756-L6x Controllers
1756-L6x Controller Serial Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ControlLogix Chassis Serial Communication Options . . . . . . . . .
Communication with Serial Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DF1 Master Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DF1 Point to Point Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DF1 Radio Modem Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DF1 Radio Modem Advantages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DF1 Radio Modem Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DF1 Radio Modem Protocol Parameters . . . . . . . . . . . . . . . . . . . . . .
DF1 Slave Protocol. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DH-485 Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ASCII Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configure the 1756-L6x Controller for Serial Communication . . . . .
Broadcast Messages over a Serial Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configure Controller Serial Port Properties . . . . . . . . . . . . . . . . . . .
Program the Message Instruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modbus Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
100
100
101
101
101
102
103
103
104
104
105
107
107
109
110
111
111
Chapter 7
Manage Controller Communication
Connection Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Produce and Consume (interlock) Data. . . . . . . . . . . . . . . . . . . . . . . . . . .
Connection Requirements of a Produced or Consumed Tag . . . .
Send and Receive Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Determine Whether to Cache Message Connections . . . . . . . . . . .
Calculate Connection Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Local Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Remote Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connections Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
113
114
114
116
116
117
117
118
119
7
Table of Contents
Chapter 8
I/O Modules
Selecting ControlLogix I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Local I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Add Local I/O to the I/O Configuration . . . . . . . . . . . . . . . . . . . . . .
Remote I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Add Remote I/O to the I/O Configuration . . . . . . . . . . . . . . . . . . . .
Distributed I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Add Distributed I/O to the I/O Configuration . . . . . . . . . . . . . . . .
Reconfigure an I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reconfigure an I/O Module via the Module Properties . . . . . . . . .
Reconfigure an I/O Module via a Message Instruction . . . . . . . . . .
Add to the I/O Configuration While Online . . . . . . . . . . . . . . . . . . . . . .
Modules and Devices that Can be Added While Online. . . . . . . . .
Online Additions - ControlNet Considerations . . . . . . . . . . . . . . . .
Online Additions—EtherNet/IP Considerations . . . . . . . . . . . . . .
Determine When Data Is Updated . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
121
122
123
124
125
128
129
131
131
132
132
133
135
138
139
Chapter 9
Develop Motion Applications
Motion Control Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motion Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Obtain Axis Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Program Motion Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
141
142
142
143
143
144
Chapter 10
Develop Applications
8
Elements of a Control Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Task Priority . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Scheduled and Unscheduled Programs . . . . . . . . . . . . . . . . . . . . . . . .
Routines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tags. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Extended Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Access Extended Properties in Logic. . . . . . . . . . . . . . . . . . . . . . . . . . .
Programming Languages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Add-On Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Monitoring Controller Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Monitoring I/O Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Determine if I/O Communication has Timed Out . . . . . . . . . . . . .
Determine if I/O Communication to a
Specific I/O Module has Timed Out . . . . . . . . . . . . . . . . . . . . . . . . . .
Interrupt the Execution of Logic and Execute the Fault Handler.
System Overhead Time Slice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configure the System Overhead Time Slice . . . . . . . . . . . . . . . . . . . .
Sample Controller Projects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
145
146
149
149
151
152
153
154
154
156
157
158
159
160
160
161
162
163
164
Table of Contents
Chapter 11
Using the PhaseManager Tool
PhaseManager Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Minimum System Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
State Model Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How Equipment Changes States. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Manually Change States . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PhaseManager Tool versus Other State Models . . . . . . . . . . . . . . . . . . . .
Equipment Phase Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
165
167
167
168
169
170
170
Chapter 12
Redundant Systems
ControlLogix Redundancy Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Enhanced versus Standard Redundancy . . . . . . . . . . . . . . . . . . . . . . .
Build a Redundant System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ControlNet Considerations in Redundant Systems . . . . . . . . . . . . . . . .
EtherNet/IP Considerations in Redundant Systems . . . . . . . . . . . . . . .
IP Address Swapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Redundancy and Scan Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
171
173
174
175
175
176
176
176
177
Chapter 13
SIL 2 Certification
Introduction to SIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Programming and Debugging Tool (PADT). . . . . . . . . . . . . . . . . . .
Typical SIL2 Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fail-safe Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
High-availability Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fault-tolerant Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
179
179
180
181
182
183
Appendix A
Status Indicators
1756-L7x Controller Status Display and Indicators . . . . . . . . . . . . . . . .
1756-L7x Controller Status Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Status Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fault Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Major Fault Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I/O Fault Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1756-L7x Controller Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RUN Indicator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FORCE Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SD Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
OK Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1756-L6x Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RUN Indicator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I/O Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FORCE Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RS232 Indicator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
185
185
186
187
188
190
193
193
193
193
194
194
194
195
195
195
9
Table of Contents
BAT Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196
OK Indicator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196
Appendix B
Using Electronic Keying
Electronic Keying . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Exact Match . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Compatible Keying . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Disabled Keying . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
197
198
199
201
Appendix C
History of Changes
1756-UM001M-EN-P, February 2012 . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1756-UM001L-EN-P, November 2011 . . . . . . . . . . . . . . . . . . . . . . . . . . .
1756-UM001K-EN-P, May 2011. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1756-UM001J-EN-P, July 2010 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1756-UM001I-EN-P, January 2007. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1756-UM001H-EN-P, July 2008 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1756-UM001G-EN-P, January 2007. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1756-UM001F-EN-P, May 2005 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1756-UM001E-EN-P, August 2002 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1756-UM001D-EN-P . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1756-UM001C-EN-P, June 2001 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1756-UM001B-EN-P, November 2000 . . . . . . . . . . . . . . . . . . . . . . . . . . .
Index
10
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
206
206
206
207
207
207
207
207
208
208
208
208
Preface
Studio 5000 Environment
The Studio 5000™ Engineering and Design Environment combines engineering
and design elements into a common environment. The first element in the
Studio 5000 environment is the Logix Designer application. The Logix Designer
application is the rebranding of RSLogix™ 5000 software and will continue to be
the product to program Logix5000™ controllers for discrete, process, batch,
motion, safety, and drive-based solutions.
The Studio 5000 environment is the foundation for the future of
Rockwell Automation® engineering design tools and capabilities. It is the one
place for design engineers to develop all the elements of their control system.
ControlLogix Controllers
Overview
There are three types of ControlLogix® controllers available. These types include
the following:
• Standard ControlLogix controllers
• Extreme environment ControlLogix controller
• Safety GuardLogix® controllers
This manual explains how to use standard and extreme environment
ControlLogix controllers.
For more information about using safety GuardLogix controllers, see the
GuardLogix Controller Systems Safety Reference Manual, publication
1756-RM093, or the GuardLogix Controllers User Manual, publication
1756-UM020.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
11
Preface
Standard ControlLogix Controllers
Two lines of standard ControlLogix controllers are now available. These
controllers are identified as 1756-L6x controllers and 1756-L7x controllers
according to abbreviations of their full catalog numbers.
Table 1 - ControlLogix Catalog Numbers
Abbreviated Cat. No.
Cat. No.
1756-L6x
1756-L61, 1756-L62,1756-L63, 1756-L64,1756-L65
1756-L7x
1756-L71, 1756-L72, 1756-L73,1756-L74, 1756-L75
The standard ControlLogix controllers share many similar features, but also have
some differences. Table 2 provides a brief overview the differences between the
controllers. For further details about these features and differences, see the
appropriate chapters of this manual.
Table 2 - Differences Between 1756-L7x and 1756-L6x Controllers
Feature
1756-L7x
1756-L6x
Clock support and backup used for
memory retention at powerdown
Energy Storage Module (ESM)
Battery
Communication ports (built-in)
USB
Serial
Connections, controller
500
250
Memory, nonvolatile
Secure Digital (SD) card
CompactFlash card
Status display and status indicators
Scrolling status display and four
status indicators
Six status indicators
Unconnected buffer defaults
20 (40, max)
10 (40, max)
Redundant ControlLogix Controllers
Certain ControlLogix controllers are also supported for use in redundant
systems. For more information about controllers and redundant systems, see
Chapter 12.
Extreme Environment ControlLogix Controllers
The extreme environment ControlLogix controllers, catalog numbers
1756-L73XT and 1756-L63XT, provide the same functionality as the 1756-L73
and 1756-L63 controllers, but are designed to withstand temperatures -25...70 °C
(-13...158 °F).
12
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Preface
Before You Begin
Before you begin using your ControlLogix controller, verify that you have the
applications required to configure and program the controller.
Required Software
Use this table to identify the minimum software versions required to use your
ControlLogix controller.
Table 3 - Required Software for Controller Use
Cat. No.
Studio 5000 Environment
RSLogix 5000 Software
RSLinx® Classic
1756-L61/A
—
Version 12.06.00 or later
Any version
1756-L61/B
—
Version 13.04.00 or later
1756-L62/A
—
Version 12.06.00 or later
1756-L62/B
—
Version 13.04.00 or later
1756-L63/A
—
• If not using a CompactFlash
card, version 10.07.00 or
later
• If using a CompactFlash
card, version 11.16.00 or
later
1756-L63/B
—
Version 13.04.00 or later
1756-L63XT/B
—
Version 13.04.00 or later
Version 2.55.00 or later
1756-L64/B
—
Version 16.03.00 or later
Any version
1756-L65/B
—
Version 17.01.02 or later
1756-L71/A
Version 21.00.00 or later
Version 20.01.02
Version 2.59.00 or later
1756-L72/A
Version 21.00.00 or later
Version 19.01.00 or later
Version 2.57.00 or later
1756-L73/A
Version 21.00.00 or later
Version 19.01.00 or later
1756-L73XT/A
Version 21.00.00 or later
Version 19.01.00 or later
1756-L74/A
Version 21.00.00 or later
Version 19.01.00 or later
1756-L75/A
Version 21.00.00 or later
Version 19.01.00 or later
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
13
Preface
Additional Resources
These documents contain additional information concerning related products
from Rockwell Automation.
Resource
Description
1756 ControlLogix Controllers Technical Data, publication
1756-TD001
Provides specifications for ControlLogix controllers.
1756 ControlLogix I/O Modules Technical Data,
publication 1756-TD002
Provides specifications for ControlLogix I/O modules.
ControlLogix Peer I/O Control Application Technique,
publication 1756-AT016
Describes typical peer control applications and provides
details about how to configure I/O modules for peer
control operation.
Integrated Architecture and CIP Sync Configuration
Application Technique, publication IA-AT003
Describes how to configure CIP Sync with Integrated
Architecture™ products and applications.
ControlLogix Chassis and Power Supplies Installation
Instructions, publication 1756-IN005
Describes how to install and troubleshoot standard and
ControlLogix-XT™ versions of the 1756 chassis and power
supplies, including redundant power supplies.
Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1
Provides general guidelines for installing a Rockwell
Automation industrial system.
Product Certifications website, http://ab.com
Provides declarations of conformity, certificates, and other
certification details.
You can view or download publications at
http://www.rockwellautomation.com/literature/. To order paper copies of
technical documentation, contact your local Allen-Bradley distributor or
Rockwell Automation sales representative.
14
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Chapter
1
Install the 1756-L7x Controller
Topic
Page
Before You Begin
17
1756-L7x Controller Parts
17
1756-L7x Controller Installation
18
Insert the Controller into the Chassis
19
Insert the Key
20
Install the SD Card
21
Remove the SD Card
23
Install the ESM
25
Uninstall the ESM
26
ATTENTION: Personnel responsible for the application of safety-related programmable electronic systems (PES) shall be
aware of the safety requirements in the application of the system and shall be trained in using the system.
ATTENTION: Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as
defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is not intended for use in residential environments and may not provide adequate protection to radio
communication services in such environments.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for
those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting
from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread
of flame, complying with a flame spread rating of 5VA or be approved for the application if nonmetallic. The interior of the
enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional
information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
• Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication 1770-4.1, for additional
installation requirements
• NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosure
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
15
Chapter 1
Install the 1756-L7x Controller
North American Hazardous Location Approval
The following information applies when operating this equipment in
hazardous locations.
Informations sur l’utilisation de cet équipement en environnements
dangereux.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups
A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied
with markings on the rating nameplate indicating the hazardous location temperature
code. When combining products within a system, the most adverse temperature code
(lowest "T" number) may be used to help determine the overall temperature code of the
system. Combinations of equipment in your system are subject to investigation by the
local Authority Having Jurisdiction at the time of installation.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en
environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux.
Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent
le code de température pour les environnements dangereux. Lorsque plusieurs produits
sont combinés dans un système, le code de température le plus défavorable (code de
température le plus faible) peut être utilisé pour déterminer le code de température
global du système. Les combinaisons d'équipements dans le système sont sujettes à
inspection par les autorités locales qualifiées au moment de l'installation.
WARNING: EXPLOSION HAZARD
• Do not disconnect equipment unless power has
been removed or the area is known to be
nonhazardous.
• Do not disconnect connections to this
equipment unless power has been removed or
the area is known to be nonhazardous. Secure
any external connections that mate to this
equipment by using screws, sliding latches,
threaded connectors, or other means provided
with this product.
• Substitution of components may impair
suitability for Class I, Division 2.
• If this product contains batteries, they must only
be changed in an area known to be
nonhazardous.
WARNING: RISQUE D’EXPLOSION
• Couper le courant ou s'assurer que
l'environnement est classé non dangereux avant
de débrancher l'équipement.
• Couper le courant ou s'assurer que
l'environnement est classé non dangereux avant
de débrancher les connecteurs. Fixer tous les
connecteurs externes reliés à cet équipement à
l'aide de vis, loquets coulissants, connecteurs
filetés ou autres moyens fournis avec ce produit.
• La substitution de composants peut rendre cet
équipement inadapté à une utilisation en
environnement de Classe I, Division 2.
• S'assurer que l'environnement est classé non
dangereux avant de changer les piles.
European Hazardous Location Approval
The following applies when the product bears the Ex Marking.
This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to comply with the Essential Health and
Safety Requirements relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15 and EN 60079-0.
ATTENTION: This equipment is not resistant to sunlight or other sources of UV radiation.
WARNING:
• This equipment shall be mounted in an ATEX certified enclosure with a minimum ingress protection rating of at least IP54
(as defined in IEC60529) and used in an environment of not more than Pollution Degree 2 (as defined in IEC 60664-1) when
applied in Zone 2 environments. The enclosure must utilize a tool removable cover or door.
• This equipment shall be used within its specified ratings defined by Rockwell Automation.
• This equipment must be used only with ATEX certified Rockwell Automation backplanes.
• Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other
means provided with this product.
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
16
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Install the 1756-L7x Controller
Before You Begin
1756-L7x Controller Parts
Chapter 1
Complete these tasks using the appropriate resources listed as references before
you install your controller and power supply.
Task
Resources
Install a ControlLogix Chassis and Power Supply
Refer to ControlLogix Chasis and Power Supplies,
publication 1756-IN005
These sections describe parts that are included with the L7x controllers, as well as
available accessory parts.
Parts Included with the 1756-L7x Controller
These parts are included with the controller:
• 1756-ESMCAP capacitor-based energy storage module (ESM)
• 1784-SD1 Secure Digital (SD) card, 1 GB
• 1747-KY controller key
Figure 1 - Parts with the 1756-L7x Controller
1756-L7x Controller
Logix 5575
RUN FORCESD
OK
SD Card (installed)
1756-ESMCAP
(installed)
1747-KY Key
IMPORTANT
32016-M
The 1756-L7x controllers ship with an SD card installed. We recommend that
you leave the SD card installed.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
17
Chapter 1
Install the 1756-L7x Controller
Parts Available for Use with the 1756-L7x Controller
In addition to parts included with the controller, you may choose to use these
parts specific to your application.
If your application requires
Then use this part
USB connection from a computer to the controller
USB cable(1)
Nonvolatile memory
1784-SD1 (1 GB) or 1784-SD2 (2 GB)
ESM without WallClockTime back-up power
1756-ESMNSE
This ESM does not have WallClockTime back-up power.
Use this ESM if your application requires that the installed
ESM deplete its residual stored energy to 40 μJoule or less
before transporting it into or out of your application.(2)
Additionally, you can use this ESM with a 1756-L73 (8 MB)
or smaller memory-sized controller only.
ESM that secures the controller by preventing the USB
connection and SD card use(2)
This ESM provides your application an enhanced degree of
security.
1756-ESMNRM
(1) The USB port is intended for temporary local programming purposes only and not intended for permanent connection. The USB
cable is not to exceed 3.0 m (9.84 ft) and must not contain hubs.
(2) For information about the hold-up time of the ESMs, see Hold-up Time (in days) on page 71 and stored energy depletion rate on
page 26.
WARNING: Do not use the USB port in hazardous locations.
ATTENTION:
• The USB port is intended for temporary local programming purposes only and
not intended for permanent connection.
• The USB cable is not to exceed 3.0 m (9.84 ft) and must not contain hubs.
1756-L7x Controller
Installation
18
These sections explain how to install the 1756-L7x controller. To install the
1756-L7x controller, complete the tasks summarized in this table.
Task
Page
Insert the Controller into the Chassis
19
Insert the Key
20
Remove the SD Card
21
Install the SD Card
21
Install the ESM
25
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Install the 1756-L7x Controller
Insert the Controller
into the Chassis
Chapter 1
When installing a ControlLogix controller, you can do the following:
• Place the controller in any slot.
• Use multiple controllers in the same chassis.
You can install or remove a ControlLogix controller while chassis power is on and
the system is operating.
WARNING: When you insert or remove the module while backplane power
is on, an electrical arc can occur. This could cause an explosion in hazardous
location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Repeated electrical arcing causes excessive wear to contacts on both the
controller and its mating connector on the chassis. Worn contacts may create
electrical resistance that can affect controller operation.
ATTENTION: Prevent Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal
damage and affect normal operation. Follow these guidelines when you handle
this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
IMPORTANT
The ESM begins charging when one of these actions occurs:
• The controller and ESM are installed into a powered chassis.
• Power is applied to the chassis that contains a controller with the ESM
installed.
• An ESM is installed into a powered controller.
After power is applied, the ESM charges for up to two minutes as indicated by
CHRG or ESM Charging on the status display.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
19
Chapter 1
Install the 1756-L7x Controller
1. Align the circuit board with the top and bottom guides in the chassis.
Top Circuit Board
Aligned
Logix 55xx
RUN FORCESD
Bottom Circuit Board
Aligned
OK
31997-M
2. Slide the module into the chassis until it snaps into place.
3. Verify that the controller is flush with the power supply or other installed
modules.
After you have inserted the controller into the chassis, reference the Status
Indicators on page 185 for information about interpreting the status indicators.
Insert the Key
After the controller is installed, insert the key.
Logix 55xx
RUN FORCESD
20
OK
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Install the 1756-L7x Controller
Install the SD Card
Chapter 1
Complete these steps to install the SD card in the 1756-L7x controllers.
WARNING: When you insert or remove the Secure Digital (SD) memory
card while power is on, an electrical arc can occur. This could cause an
explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
1. Verify that the SD card is locked or unlocked according to your preference.
Unlocked
Locked
32005-M
For more information about the lock/unlock memory settings, see the
Load or Store to the Memory Card on page 64.
2. Open the door for the SD card.
Logix 55xx
RUN FORCESD
OK
32002-M
3. Insert the SD card into the SD card slot.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
21
Chapter 1
Install the 1756-L7x Controller
4. Gently press the card until it clicks into place.
Logix 55xx
RUN FORCESD
OK
32004-M
5. Close the SD card door.
Logix 55xx
RUN FORCESD
OK
32006-M
22
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Install the 1756-L7x Controller
Remove the SD Card
Chapter 1
The 1756-L7x controller ships with an SD card installed. Complete these steps to
remove the SD card from the 1756-L7x controller.
WARNING: When you insert or remove the Secure Digital (SD) memory
card while power is on, an electrical arc can occur. This could cause an
explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
IMPORTANT
• Verify that the SD card status indicator is off and that the card is not in use
before removing it.
• We recommend that you do the following:
–Leave an SD card installed.
– Use the SD cards available from Rockwell Automation (catalog number
1784-SD1 or 1784-SD2).
• While other SD cards may be used with the controller,
Rockwell Automation has not tested the use of those cards with the
controller. If you use an SD card other than those available from
Rockwell Automation, you may experience data corruption or loss.
• Also, SD cards not provided by Rockwell Automation do not have the same
industrial, environmental, and certification ratings as those available from
Rockwell Automation.
1. Verify that the SD card is not in use by checking to be sure the
SD indicator is Off.
You may also put the controller into Hard Run mode to keep the
TIP
controller from writing to the SD card while it is removed.
2. Open the door to access the SD card.
Logix 55xx
RUN FORCESD
OK
32015-M
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
23
Chapter 1
Install the 1756-L7x Controller
3. Press and release the SD card to eject it.
Logix 55xx
RUN FORCESD
OK
32004-M
4. Remove the SD card and close the door.
24
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Install the 1756-L7x Controller
Install the ESM
Chapter 1
To install an ESM in the 1756-L7x controller, complete these steps.
ATTENTION: To avoid potential damage to the product when inserting the
ESM, align it in the track and slide forward with minimal force until the ESM
snaps into place.
1. Align the tongue-and-groove slots of the ESM and controller.
Logix 55xx
RUN FORCESD
OK
2. Slide the ESM back until it snaps into place.
The ESM begins charging after installation. Charging status is indicated by
one of these status messages:
• ESM Charging
• CHRG
After you install the ESM, it may take up to 15 seconds for the charging
status messages to display.
IMPORTANT
TIP
Allow the ESM to finish charging before removing power from the controller.
Failure to do so can result in the loss of the application program. A type 1,
code 40 major fault will be logged on powerup.
To verify that the ESM is fully charged, check the status display to confirm that
messages CHRG or ESM charging are no longer indicated.
We recommend that you check the WallClockTime object attributes after
installing an ESM to verify that time of the controller is correct.
The ESM contains a real-time clock. If the ESM is new or came from another
controller, your controller’s WallClockTime object attributes may change.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
25
Chapter 1
Install the 1756-L7x Controller
Uninstall the ESM
WARNING: If your application requires the ESM to deplete its residual stored
energy to 40 μJoule or less before you transport it into or out of the application,
use the 1756-(SP)ESMNSE(XT) module only. In this case, complete these steps
before you remove the ESM.
1. Turn power off to the chassis.
After you turn power off to the chassis, the controller’s OK status indicator
transitions from green to solid red to OFF.
2. Wait at least 20 minutes for the residual stored energy to decrease to
40 μJoule or less before you remove the ESM.
There is no visual indication of when the 20 minutes has expired. You must
track that time period.
WARNING: When you insert or remove the energy storage module while
backplane power is on, an electrical arc can occur. This could cause an explosion
in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Repeated electrical arcing causes excessive wear to contacts on both the module
and its mating connector.
IMPORTANT
Before you remove an ESM, make necessary adjustments to your program
to account for potential changes to the WallClockTime attribute.
Consider these points before removing the ESM:
• The following ESM modules may be currently installed in your 1756-L7x
or 1756-L7xXT controller:
–
–
–
–
1756-ESMCAP
1756-ESMNSE
1756-ESMCAPXT
1756-ESMNSEXT
• The 1756-L7x controllers come with the 1756-ESMCAP module already
installed. The 1756-L7xXT extreme temperature controller ships with a
1756-ESMCAPXT module already installed. For more information on
how to use a 1756-ESMNSE, 1756-ESMNRM, 1756-ESMNSEXT, or
1756-ESMNRMXT module, see page 25.
• After the 1756-L7x or 1756-L7xXT controllers lose power, either because
the chassis power is turned off or the controller has been removed from a
powered chassis, do not remove the ESM immediately.
Wait until the controller’s OK status indicator transitions from Green to
Solid Red to OFF before you remove the ESM.
• You can use the 1756-ESMNSE module with a 1756-L73 (8MB) or
smaller memory-sized controller only.
26
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Install the 1756-L7x Controller
Chapter 1
• Use the 1756-ESMNSE module if your application requires that the
installed ESM deplete its residual stored energy to 40 μJoule or less before
transporting it into or out of your application.
• Once it is installed, you cannot remove the 1756-ESMNRM or
1756-ESMNRMXT module from a 1756-L7x or 1756-L7xXT controller.
Complete these steps to remove an ESM module from the controller.
1. Remove the key from the mode switch.
IMPORTANT
The next step depends on which of the following conditions applies to your
application.
• If you are removing the ESM from a powered 1756-L7x controller, go to
step 2.
• If you are removing the ESM from a 1756-L7x controller that is not
powered, either because the chassis power is turned off or the
controller has been removed from a powered chassis, do not remove
the ESM immediately.
Wait until the controller’s OK status indicator transitions from Green to
Solid Red to OFF before you remove the ESM.
After the OK status indicator transitions to Off, go to step 2.
2. Use your thumb to press down on the black release and pull the ESM away
from the controller.
Logix 55xx
RUN FORCESD
OK
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Logix 55xx
RUN FORCESD
OK
27
Chapter 1
Install the 1756-L7x Controller
Notes:
28
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Chapter
2
Install the 1756-L6x Controller
Topic
Page
Before You Begin
31
1756-L6x Controller Parts
31
1756-L6x Controller Installation
32
CompactFlash Card Installation and Removal
32
Battery Connection and Replacement
36
Insert the Controller into the Chassis
39
Remove the Controller from the Chassis
41
ATTENTION: Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as
defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is not intended for use in residential environments and may not provide adequate protection to radio
communication services in such environments.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those
specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from
accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of
flame, complying with a flame spread rating of 5VA or be approved for the application if nonmetallic. The interior of the
enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional
information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
• Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for additional installation requirements.
• NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
29
Chapter 2
Install the 1756-L6x Controller
North American Hazardous Location Approval
The following information applies when operating this equipment in
hazardous locations.
Informations sur l’utilisation de cet équipement en environnements
dangereux.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups
A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied
with markings on the rating nameplate indicating the hazardous location temperature
code. When combining products within a system, the most adverse temperature code
(lowest "T" number) may be used to help determine the overall temperature code of the
system. Combinations of equipment in your system are subject to investigation by the
local Authority Having Jurisdiction at the time of installation.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en
environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux.
Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent
le code de température pour les environnements dangereux. Lorsque plusieurs produits
sont combinés dans un système, le code de température le plus défavorable (code de
température le plus faible) peut être utilisé pour déterminer le code de température
global du système. Les combinaisons d'équipements dans le système sont sujettes à
inspection par les autorités locales qualifiées au moment de l'installation.
WARNING: EXPLOSION HAZARD
• Do not disconnect equipment unless power has
been removed or the area is known to be
nonhazardous.
• Do not disconnect connections to this
equipment unless power has been removed or
the area is known to be nonhazardous. Secure
any external connections that mate to this
equipment by using screws, sliding latches,
threaded connectors, or other means provided
with this product.
• Substitution of components may impair
suitability for Class I, Division 2.
• If this product contains batteries, they must only
be changed in an area known to be
nonhazardous.
WARNING: RISQUE D’EXPLOSION
• Couper le courant ou s'assurer que
l'environnement est classé non dangereux avant
de débrancher l'équipement.
• Couper le courant ou s'assurer que
l'environnement est classé non dangereux avant
de débrancher les connecteurs. Fixer tous les
connecteurs externes reliés à cet équipement à
l'aide de vis, loquets coulissants, connecteurs
filetés ou autres moyens fournis avec ce produit.
• La substitution de composants peut rendre cet
équipement inadapté à une utilisation en
environnement de Classe I, Division 2.
• S'assurer que l'environnement est classé non
dangereux avant de changer les piles.
European Hazardous Location Approval
The following applies when the product bears the Ex Marking.
This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to comply with the Essential Health and
Safety Requirements relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15 and EN 60079-0.
ATTENTION: This equipment is not resistant to sunlight or other sources of UV radiation.
WARNING:
• This equipment shall be mounted in an ATEX certified enclosure with a minimum ingress protection rating of at least IP54
(as defined in IEC60529) and used in an environment of not more than Pollution Degree 2 (as defined in IEC 60664-1) when
applied in Zone 2 environments. The enclosure must utilize a tool removable cover or door.
• This equipment shall be used within its specified ratings defined by Rockwell Automation.
• This equipment must be used only with ATEX certified Rockwell Automation backplanes.
• Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other
means provided with this product.
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
ATTENTION: Personnel responsible for the application of safety-related programmable electronic systems (PES) shall be
aware of the safety requirements in the application of the system and shall be trained in using the system.
30
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Install the 1756-L6x Controller
Before You Begin
1756-L6x Controller Parts
Chapter 2
Complete these tasks using the appropriate resources listed as references before
you install your controller and power supply.
Task
Resources
Install a ControlLogix® Chassis and
Power Supply
Refer to ControlLogix Chassis and Power Supplies, publication 1756-IN005
These sections describe parts that are included with the 1756-L6x controllers, as
well as available accessory parts:
• One of the following batteries is included with your controller:
– For series A controllers, catalog number 1756-BA1
– For series B controllers, catalog number 1756-BA2
• Key, catalog number 1747-KY
Figure 2 - Parts Included with the 1756-L6x Controller
1756-L6x Controller
1756-BA1 or 1756-BA2
Logix 5563
RUN
I/O
FORCE
RS232
BAT
RUN
OK
REM
PROG
1747-KY Key
Parts Not Included with the 1756-L6x Controller
In addition to parts included with the controller, you may choose to use these
parts specific to your application.
If your application requires
Then use this component
RS-232 connection to the controller
1756-CP3 serial cable
Nonvolatile memory
1784-CF128 CompactFlash card
Expanded battery life for extended memory retention
1756-BATM battery module(1)
(1) The 1756-BATM can be used with series A controllers, but it cannot be used with series B controllers. Series B controllers
use battery power differently than previous controllers and therefore battery considerations for this series controller
vary. For more information about determining what battery to use, see the ControlLogix Controllers Selection Guide,
publication 1756-SG001.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
31
Chapter 2
Install the 1756-L6x Controller
1756-L6x Controller
Installation
CompactFlash Card
Installation and Removal
These sections explain how to install a 1756-L6x controller. To install the
1756-L6x controller, complete the tasks summarized in this table.
Task
Page
CompactFlash Card Installation and Removal
32
Battery Connection and Replacement
36
Insert the Controller into the Chassis
39
Remove the Controller from the Chassis
41
The installation and removal of a CompactFlash card depends on the controller.
WARNING: When you insert or remove the CompactFlash Card while power
is on, an electrical arc can occur. This could cause an explosion in hazardous
location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
• If you are using a series A controller, reference these sections:
– Install a CompactFlash Card in a Series A Controller on page 33.
– Remove a CompactFlash Card from a Series A Controller on page 33.
• If you are using a series B controller, reference these sections:
– Install a CompactFlash Card in a Series B Controller on page 34.
– Remove a CompactFlash Card from a Series B Controller on page 35.
32
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Install the 1756-L6x Controller
Chapter 2
Install a CompactFlash Card in a Series A Controller
Complete these steps to install a CompactFlash card in a series A controller
.
2
4
1
3
1. Lay the controller on its side with the front facing to the left.
2. Raise the locking clip.
3. Insert the CompactFlash card into the slot at the bottom of the controller.
4. Pull the clip forward and then downward until it snaps into place over the
card.
Remove a CompactFlash Card from a Series A Controller
Complete these steps to remove a CompactFlash card from a series A controller.
2
1
3
1. Lay the controller in its side with the mode switch facing left.
2. Raise the locking clip.
3. Gently pull the card out of the slot.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
33
Chapter 2
Install the 1756-L6x Controller
Install a CompactFlash Card in a Series B Controller
Complete these steps to install a CompactFlash card in a series B controller.
1
3
2
4
1. Open the door of the controller and push the CompactFlash latch to the
left.
2. Insert the CompactFlash card with the Allen-Bradley® logo pointing left.
3. Release the latch and secure it over the CompactFlash card.
34
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Install the 1756-L6x Controller
Chapter 2
Remove a CompactFlash Card from a Series B Controller
Complete these steps to remove a CompactFlash card from a series B controller.
1
3
2
1. Verify that the OK indicator is solid green then open the door of the
controller.
2. Push and hold the CompactFlash latch to the left.
3. Push the eject button and remove the card.
4. Release the latch.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
35
Chapter 2
Install the 1756-L6x Controller
Battery Connection
and Replacement
This product contains a hermetically-sealed lithium battery that may need to be
replaced during the life of the product.
At the end of its life, the battery contained in this product should be collected
separately from any unsorted municipal waste.
The collection and recycling of batteries helps protect the environment and
contributes to the conservation of natural resources as valuable materials are
recovered.
WARNING: When you connect or disconnect the battery an electrical arc can
occur. This could cause an explosion in hazardous location installations. Be sure
that power is removed or the area is nonhazardous before proceeding.
For safety information on the handling of lithium batteries, including handling
and disposal of leaking batteries, see Guidelines for Handling Lithium Batteries,
publication AG-5.4.
IMPORTANT: To prevent program loss, replace a 1756-BA1 or 1756-BA2 battery
according to the schedule below even if the BAT status indicator is Off.
If the temperature 2.54 cm (1 in.) below the chassis is Replace the battery within
-25…35 °C (-13…95 °F)
No replacement required
36…40 °C (96.8…104 °F)
3 years
41…45 °C (105.8…113 °F)
2 years
46…50 °C (114.8…122 °F)
16 months
51…55 °C (123.8…131 °F)
11 months
56…70 °C (132.8…158 °F)
8 months
ATTENTION: Store batteries in a cool, dry environment. We recommend 25 °C
(77 °F) with 40…60% relative humidity. You may store batteries for up to 30
days between -45…85 °C (-49…185 °F), such as during transportation. To
avoid leakage or other hazards, do not store batteries above 60 °C (140 °F) for
more than 30 days.
Connection of the battery varies depending on your controller series:
• If you are using a series A controller, see page 37.
• If you are using a series B controller, see page 38.
36
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Install the 1756-L6x Controller
Chapter 2
Install the Battery on a Series A Controller
Complete these steps to install a 1756-BA1 battery on a series A controller.
For information about installing a 1756-BATM battery module or replacing a
1756-BATM assembly, see the ControlLogix Battery Module Installation
Instructions, publication 1756-IN578.
ATTENTION: For a series A controller, connect only a 1756-BA1 battery or a
1756-BATM battery module. The use of other batteries may damage the
controller.
DATE
Wire Terminal Location
Connected Wire
Top
No connection
Middle
Black lead (-)
Bottom
Red lead (+)
1. Connect the battery connector to the port to the right of the battery slot.
2. Snap the battery into the battery slot.
3. Write the date on the battery label.
4. Attach the label to the inside of the controller door.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
37
Chapter 2
Install the 1756-L6x Controller
Install the Battery on a Series B Controller
Complete these steps to install the battery on a series B controller.
ATTENTION: For a series B controller, connect only a 1756-BA2 battery. The
use of other batteries may damage the controller.
COMPACT
FLASH
1-DCD
2-RXD
3-TXD
4-DTR
5-GND
DSR-6
RTS-7
CTS-8
N/C-9
RS232
1
To
Insert 1
2
To Eject
1+2
1
2
UP
BATTERY
DATE
1
DATE
2
BATTERY
PORT
30563-M
1. Insert the battery, with the arrow pointing up, into the battery slot.
2. Plug the battery connector into the battery port (+ Red, - Black).
3. Write the date on the battery label.
4. Attach the label to the inside of the controller door.
38
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Install the 1756-L6x Controller
Insert the Controller
into the Chassis
Chapter 2
When installing a ControlLogix controller, you can do the following:
• Place the controller in any slot.
• Use multiple controllers in the same chassis.
You can install a ControlLogix controller while chassis power is on and the
system is operating.
WARNING: When you insert or remove the module while backplane power is
on, an electrical arc can occur. This could cause an explosion in hazardous
location installations. Be sure that power is removed or the area is nonhazardous
before proceeding.
Repeated electrical arcing causes excessive wear to contacts on both the controller
and its mating connector on the chassis. Worn contacts may create electrical
resistance that can affect controller operation.
ATTENTION: Prevent Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal
damage and affect normal operation. Follow these guidelines when you handle
this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
ATTENTION: If this equipment is used in a manner not specified by the
manufacturer, the protection provided by the equipment may be impaired.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
39
Chapter 2
Install the 1756-L6x Controller
Complete these steps to insert the controller into the chassis.
1. Insert the key into the controller.
2. Turn the key to the PROG position.
3. Align the circuit board with the top and bottom guides in the chassis.
4. Slide the module into the chassis.
5. Verify that the controller is flush with the power supply or other installed
modules.
6. Verify that the top and bottom latches are engaged.
After you have inserted the controller into the chassis, you may need to reference
the Status Indicators on page 185 for more information related to the state of the
controller.
40
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Install the 1756-L6x Controller
Remove the Controller
from the Chassis
Chapter 2
You can remove a controller while chassis power is on and the system is operating.
If you remove the controller, all of the devices owned by the controller go to their
configured fault state.
WARNING: When you insert or remove the module while backplane power is
on, an electrical arc can occur. This could cause an explosion in hazardous
location installations. Be sure that power is removed or the area is
nonhazardous before proceeding.
Repeated electrical arcing causes excessive wear to contacts on both the controller
and its mating connector in the chassis. Worn contacts may create electrical
resistance that can affect controller operation.
Complete these steps to remove the controller from the chassis.
1. Press the locking tabs on the top and bottom of the controller.
2. Slide the controller out of the chassis.
1
2
20880
1
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
41
Chapter 2
Install the 1756-L6x Controller
Notes:
42
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Chapter
3
Start Using the Controller
Make Connections
Topic
Page
Make Connections
43
Connect to the 1756-L7x Controller
44
Connect to the 1756-L6x Controller
47
Upgrade Controller Firmware
50
Set the Communication Path
56
Go Online with the Controller
57
Download to the Controller
58
Upload from the Controller
59
Choose the Controller Operation Mode
61
Use the Mode Switch to Change the Operation Mode
61
Use Logix Designer to Change the Operation Mode
63
Load or Store to the Memory Card
64
Use ControlLogix Energy Storage Modules (ESMs)
69
Estimate the ESM Support of the WallClockTime
71
Maintain the Battery (1756-L6x controllers only)
72
Before you can begin using your controller, you must make a connection to the
controller.
1756-L7x Connection Options
Connection options with the 1756-L7x include the following:
• Connect using a USB cable as described in Connect to the
1756-L7x Controller on page 44.
• Install and configure a communication module in the chassis with the
controller as described in the installation instructions for the
communication module.
For information on Double Data Rate (DDR) backplane communication usage,
see Double Data Rate (DDR) Backplane Communication on page 87.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
43
Chapter 3
Start Using the Controller
1756-L6x Connection Options
Connection options with the 1756-L6x include the following:
• Connect using a serial cable as described in Connect to the
1756-L6x Controller on page 47.
• Install and configure a communication module in the chassis with the
controller as described in the installation instructions for the
communication module.
TIP
Connect to the
1756-L7x Controller
When upgrading your 1756-L6x controller firmware, we recommend you use a
network connection other than the serial cable. Serial connections are much
slower than other communication connections.
The controller has a USB port that uses a Type B receptacle. The port is USB 2.0
compatible and runs at 12 Mbps.
To use the USB port of the controller, you must have RSLinx software,
version 2.56 or later, installed on your workstation. Use a USB cable to connect
your workstation to the USB port. With this connection, you can upgrade
firmware and download programs to the controller directly from your
workstation.
ATTENTION: The USB port is intended for temporary local programming
purposes only and not intended for permanent connection. The USB cable is
not to exceed 3.0 m (9.84 ft) and must not contain hubs.
WARNING: Do not use the USB port in hazardous locations.
Figure 3 - USB Connection
Logix 55xx
RUN FORCESD
OK
32007-M
32007-M
44
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Start Using the Controller
Chapter 3
Set Up the USB Driver
To configure RSLinx software to use a USB port, you need to first set up a USB
driver.
To set up a USB driver, perform this procedure.
1. Connect your controller and workstation by using a USB cable.
The Found New Hardware Wizard dialog box appears.
2. Click any of the Windows Update connection options and click Next.
If the software for the USB driver is not found and the installation is
TIP
canceled, verify that you have installed RSLinx Classic software,
version 2.57 or later.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
45
Chapter 3
Start Using the Controller
3. Click Install the software automatically (Recommended) and click Next.
The software is installed.
4. Click Finish to set up your USB driver.
To browse to your controller in RSLinx software, click the RSWho icon.
The RSLinx Workstation organizer appears.
Virtual Chassis Driver
USB Port Driver
Your controller appears under two different drivers, a virtual chassis and the USB
port. You can use either driver to browse to your controller.
46
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Start Using the Controller
Connect to the
1756-L6x Controller
Chapter 3
The 1756-L6x ControlLogix controller uses a serial port for workstation
connections.
WARNING: If you connect or disconnect the serial cable with power applied to
this module or the serial device on the other end of the cable, an electrical arc
can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
To connect a workstation to the serial port, you can make your own serial cable or
use one of these cables:
• 1756-CP3 serial cable
• 1747-CP3 cable from the SLC™ product family (if you use this cable, the
controller door may not close)
To Workstation
To Controller
42576
Follow these guidelines if you make your own serial cable:
• Limit the length to 15.2 m (50 ft).
• Wire the connectors as shown.
• Attach the shield to both connectors.
To Workstation
To Controller
1 CD
1 CD
2 RDX
2 RDX
3 TXD
3 TXD
4 DTR
COMMON
4 DTR
COMMON
6 DSR
6 DSR
7 RTS
7 RTS
8 CTS
8 CTS
9
9
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
42231
47
Chapter 3
Start Using the Controller
Plug the controller end of the serial cable into the RS-232 port on the front of the
controller.
COMPACT
FLASH
1-DCD
2-RXD
3-TXD
4-DTR
5-GND
DSR-6
RTS-7
CTS-8
N/C-9
RS232
1
To
Insert 1
2
To Eject
1+2
1
2
UP
BATTERY
DATE
1
2
BATTERY
PORT
Configure the Serial Driver
Use RSLinx software to configure the RS232 DF1 device driver for serial
communication.
To configure the driver, perform this procedure.
1. In RSLinx software, from the Communications menu, choose Configure
Drivers.
48
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Start Using the Controller
Chapter 3
2. From the Available Driver Types pull-down menu, choose the RS-232
DF1 device driver.
3. Click Add New.
The Add New RSLinx Driver dialog box appears.
4. Type the driver name and click OK.
5. Specify the serial port settings.
a. From the Comm Port pull-down menu, choose the serial port on the
workstation to which the cable is connected.
b. From the Device pull-down menu, choose Logix 5550/
CompactLogix™.
c. Click Auto-Configure.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
49
Chapter 3
Start Using the Controller
6. If the auto configuration is successful, click OK.
If the auto configuration is not successful, verify that the correct Comm
Port was selected.
7. Click Close.
Upgrade Controller Firmware
You may choose to upgrade controller firmware by using either of these tools:
• ControlFLASH™ software packaged with the Studio 5000 environment
• AutoFlash feature of the Logix Designer application
To upgrade your controller firmware, complete the tasks listed in this table.
Task
Page
Determine Required Controller Firmware
50
Obtain Controller Firmware
51
Use ControlFLASH Utility to Upgrade Firmware
51
Use AutoFlash to Upgrade Firmware
54
Determine Required Controller Firmware
IMPORTANT
The controller must be in Remote Program or Program mode and all major
recoverable faults cleared to accept upgrades.
Use this table to determine what firmware revision is required for your controller.
Table 4 - Firmware Required For Controllers
Controller
Series
Use this firmware revision
1756-L61
A
12.x or later
B
13.40 or later
A
12.x or later
B
13.40 or later
A
• If not using a CompactFlash card, 10.x or later
• If using a CompactFlash card, 11.x or later
B
13.40 or later
1756-L63XT
B
13.40 or later
1756-L64
B
16 or later
1756-L65
B
17 or later
1756-L71
A
20 or later
1756-L72
A
19 or later
1756-L73
A
19 or later
1756-L73XT
A
19 or later
1756-L74
A
19 or later
1756-L75
A
19 or later
1756-L62
1756-L63
50
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Start Using the Controller
Chapter 3
Obtain Controller Firmware
Controller firmware is packaged with the Studio 5000 environment. In addition,
controller firmware is also available for download from the Rockwell Automation
Technical Support website at http://www.rockwellautomation.com/support/.
Use ControlFLASH Utility to Upgrade Firmware
To upgrade your controller firmware with ControlFLASH software, complete
these steps.
IMPORTANT
If the SD card is locked and the stored project’s Load Image option is set to
On Power Up, the controller firmware is not updated as a result of these steps.
The previously-stored firmware and project are loaded instead.
1. Verify that the appropriate network connection is made and the network
driver has been configured in RSLinx software.
2. Start ControlFLASH software and click Next to begin the upgrade
process.
3. Select the catalog number of your controller and click Next.
1756-L7x Controllers
1756-L6x Controllers
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
51
Chapter 3
Start Using the Controller
4. Expand the network driver to locate your controller.
1756-L7x Controller with USB Network Driver
1756-L6x Controller with Ethernet Network Driver
5. Select the controller and click Next.
6. Select the firmware revision you want to upgrade to and click Next.
1756-L7x Controller Upgrade
52
1756-L6x Controller Upgrade
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Start Using the Controller
TIP
Chapter 3
If you are using a 1756-L7x controller and experience a Script File Error after selecting the firmware revision number (see the
example below), there is likely an anomaly with your firmware files.
To recover, take these actions:
• Go to http://www.rockwellautomation.com/support/ and download the firmware revision you are trying to upgrade.
Replace the firmware revision you have previously installed with that posted on the Technical Support website.
• If replacing your firmware revision does not resolve the anomaly, contact Rockwell Automation Technical Support.
7. Click Finish.
8. When a confirmation dialog box appears, click Yes.
The progress dialog box indicates the progress of the firmware upgrade.
1756-L7x controllers indicate progress in updates and blocks. 1756-L6x
controllers indicate progress only in blocks.
1756-L7x Controller Progress
1756-L6x Controller Progress
WARNING: Allow the firmware update to fully complete before cycling power
or otherwise interrupting the upgrade.
TIP
If the ControlFLASH upgrade of the controller is interrupted, the 1756-L6x and
1756-L7x controllers revert to boot firmware, that is firmware revision 1.xxx.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
53
Chapter 3
Start Using the Controller
When the upgrade is complete, the Update Status dialog box indicates that
the upgrade is complete.
9. Click OK.
10. Close ControlFLASH software.
Use AutoFlash to Upgrade Firmware
To upgrade your controller firmware with the AutoFlash feature, complete these
steps.
IMPORTANT
If the SD card is locked and the stored project’s Load Image option is set to
On Power Up, the controller firmware is not updated as a result of these steps.
The previously-stored firmware and project are loaded instead.
1. Verify that the appropriate network connection is made and your network
driver is configured in RSLinx software.
2. Use the Logix Designer application to create a controller project at the
version you need.
3. Click RSWho to specify the controller path.
54
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Start Using the Controller
Chapter 3
4. Select your controller and click Update Firmware.
1756-L7x Controller with USB Driver
1756-L6x Controller with Ethernet Driver
5. Select the firmware revision to upgrade to and click update.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
55
Chapter 3
Start Using the Controller
6. Click Yes.
The firmware upgrade begins.
Allow the firmware upgrade to complete without interruption.
When the firmware upgrade is complete, the Who Active dialog box
opens.
Set the Communication Path
To get online with the controller, you must specify a communication path in the
Logix Designer application. You specify the communication path after you create
a controller program.
Complete these steps to specify the communication path after you have created
your program.
1. Click Who Active.
2. Expand the communication path and select the controller.
3. Click Set Project Path.
56
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Start Using the Controller
Go Online with the Controller
Chapter 3
Use one of these methods to go online with the controller:
• After setting the communication path, click Go Online in the Who Active
dialog box.
• From the Controller Status menu, choose Go Online.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
57
Chapter 3
Start Using the Controller
Download to the Controller
Downloading a project to the controller moves the project from the Logix
Designer application onto the controller. You can download a project in two
ways:
• Use the Who Active Dialog Box to Download on page 58
• Use the Controller Status Menu to Download on page 59
Use the Who Active Dialog Box to Download
You can use the features of the Who Active dialog box to download to your
controller after you have set the communication path. Complete these steps to
download to the controller.
1. After setting the communication path, click Download in the Who Active
dialog box.
2. Click Download after reading the warnings in the Download dialog box.
58
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Start Using the Controller
Chapter 3
Use the Controller Status Menu to Download
After you set a communication path in the Logix Designer application, you can
use the Controller Status menu to download to the controller. To download,
from the Controller Status menu, choose Download.
Figure 4 - Download via the Controller Status Menu
TIP
Upload from the Controller
After the download completes on a 1756-L7x controller, the project name is
indicated on the scrolling status display.
Uploading a project to the controller copies the project from the controller to the
Logix Designer application. To upload a project, use one of these methods:
• Use the Who Active Dialog Box to Upload, page 59
• Use the Controller Status Menu to Upload, page 60
Use the Who Active Dialog Box to Upload
You can use the features of the Who Active dialog box to upload from your
controller after you have set the communication path. Complete these steps to
upload from the controller.
1. After setting the communication path, click Upload in the Who Active
dialog box.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
59
Chapter 3
Start Using the Controller
2. Click Upload after verifying the project you are uploading in the
Connected to Upload dialog box.
Use the Controller Status Menu to Upload
After you have set a communication path in the project, you can use the
Controller Status menu to upload from the controller. To upload, from the
Controller Status menu, choose Upload.
Figure 5 - Upload via the Controller Status Menu
60
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Start Using the Controller
Choose the Controller
Operation Mode
Chapter 3
Use this table as a reference when determining your controller Operation mode.
Table 5 - Controller Operation Modes and Meanings
Select one of these modes
If you want to
Run
Remote
Run
Turn outputs to the state commanded by the
logic of the project
X
X
Test
Program
X
X
X
Turn outputs to their configured state for
Program mode
Execute (scan) tasks
Program
X
X
X
Change the mode of the controller via Logix
Designer application
X
X
X
Download a project
X
X
X
X
X
X
X
X
Schedule a ControlNet network
While online, edit the project
X
X
Send messages
X
X
X
Send and receive data in response to a message
from another controller
X
X
X
X
X
Produce and consume tags
X
X
X
X
X
Use the Mode Switch to Change the Operation Mode
Use the mode switch to change the operation mode. The controller mode switch
provides a mechanical means to enhance controller and control system security.
You must physically move the controller’s mode switch to change its operating
mode from RUN, to REM, or to PROG. When the controller’s mode switch is
set to RUN mode, features like online editing, program downloads, and firmware
upgrades will be prohibited. See Table 5 for a complete list of prohibited features.
The physical mode switch can complement other authorization and
authentication methods that similarly control user-access to the controller, such
as the following:
• Logix CPU Security tool
• FactoryTalk Security service
IMPORTANT
During runtime, we recommend that you place the controller mode switch in
RUN mode and remove the key (if applicable) from the switch. This can help
discourage unauthorized access to the controller or potential tampering with
the controller’s program, configuration, or device firmware. Place the mode
switch in REM or PROG mode during controller commissioning and
maintenance and whenever temporary access is necessary to change the
product’s program, configuration, or firmware.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
61
Chapter 3
Start Using the Controller
The mode switch on the front of the controller can be used to change the
controller to one of these modes:
• Run (RUN)
• Remote (REM)
• Program (PROG)
1756-L7x
1756-L6x
Logix557x
Logix556x
RUN FORCE SD
OK
REM PR
OG
RUN
Mode Switch
ATTENTION:
Mode Switch
Position
Available Controller Modes
RUN
Run mode—The controller is actively controlling
the process/machine. Projects cannot be edited in
the Logix Designer application when in Run mode.
Run mode should only be used when all
conditions are safe.
REM
Remote Run mode—This mode is identical to
Run mode except you can edit the project online.
Users are able to modify a project file online in
Remote Run mode.
Be sure to control outputs with care to avoid
injury to personnel and damage to equipment.
Remote Program mode—This mode is identical
to Program mode.
Remote Test mode—The controller mode during
which code is executing. I/O is not controlled, and
limited editing operations are available.
Output modules are commanded to their Program
mode state (on, off, or hold).
Outputs are commanded to their Program
mode state, which could cause a dangerous
situation.
Note: The mode of the controller can be changed
from within the Logix Designer application.
PROG
62
Program mode—The controller mode during
which programming language is not executing. I/O
is not controlled, and limited editing operations are
available.
Output modules are commanded to their Program
mode state (On, Off, or Hold).
In this position, controller modes cannot be
changed through the Logix Designer application.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Do not use Program mode as an emergency
stop (E-stop). Program mode is not a safety
device.
Outputs are commanded to their Program
mode state, which could cause a dangerous
situation.
Start Using the Controller
Chapter 3
Use Logix Designer to Change the Operation Mode
Depending on the mode of the controller you specify by using the mode switch,
you can change the Operation mode of the controller in the Logix Designer
application.
After you are online with the controller and the controller mode switch is set to
Remote (REM or the center position), you can use the Controller Status menu in
the upper-left corner of the application window to specify these operation
modes:
• Remote Program
• Remote Run
• Remote Test
Figure 6 - Operation Mode
TIP
For this example, the controller mode switch is set to Remote mode. If your
controller mode switch is set to Run or Program modes, the menu options
change.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
63
Chapter 3
Start Using the Controller
Load or Store to the
Memory Card
The memory card that is compatible with your ControlLogix controller is used to
load or store the contents of user memory for the controller.
Store to the Memory Card
After you are online with the controller and have changed the controller to
Program or Remote Program mode, complete these steps to store a project to the
memory card.
1. Open the Controller Properties dialog box and click the
Nonvolatile Memory tab.
2. Click Load/Store.
TIP
If Load/Store is dimmed (unavailable), verify the following:
• You have specified the correct communication path and are online with the
controller in Program mode.
• The memory card is installed.
• With the 1756-L7x controllers, if the SD card is locked, Store is dimmed
(unavailable) and the locked status is indicated in the bottom-left corner of
the Nonvolatile memory/Load Store dialog box. See step 4.
If the memory card is not installed, the missing card is indicated by a message
in the lower-left corner of the Nonvolatile Memory tab as shown here.
3. Change the Load Image, Load Mode, and Automatic Firmware Update
properties according to your application requirements.
64
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Start Using the Controller
Chapter 3
The table below describes the Load Image options you can choose for the
project.
IMPORTANT
If the SD card is locked and the stored project’s Load Image option is set
to On Power Up, the controller firmware is not updated as a result of
conducting a firmware upgrade. The previously-stored firmware and
project are loaded instead.
If you want the image (project) to load when
Then choose
Power to the controller is applied or cycled
On Power Up
The controller has lost the project and power has been cycled or
applied
On Corrupt Memory
Initiated via the Logix Designer application
User Initiated
The table below describes the Load Mode options you can choose for the
project.
If you want the controller to go to this mode after
loading
Then choose
Program
Program (remote only)
Run
Run (remote only)
The table below describes the Automatic Firmware Update options you
can choose for the project. The Automatic Firmware Update property is
also referred to as the Firmware Supervisor feature.
If you want to
Then choose
Enable automatic firmware updates so I/O devices in the
configuration tree of the controller that are configured to use
Exact Match Keying are updated as required
Enable and Store Files to Image(1)
Disable automatic firmware updates and remove any I/O
firmware files that are stored with the image
Disable and Delete Files from Image
Disable automatic firmware updates when there are no
firmware files are stored with the image
Disable
(1) The devices used with this option must support the version of firmware being updated to.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
65
Chapter 3
Start Using the Controller
4. Click Store, then click OK in the confirmation dialog box that appears.
Indicates the SD card is locked.
Store is dimmed (unavailable).
After clicking Store, the project is saved to the memory card as indicated
by the controller status indicators.
With these controllers
These indications show the store status
1756-L6x
While the store is in progress, the following occurs:
• OK indicator on the controller is solid red
• A dialog box in the Logix Designer application indicates the store is in
progress
When the store is complete, the following occurs:
• OK indicator on the controller is momentarily red, then solid green
1756-L7x
While the store is in progress, the following occurs:
• OK indicator is flashing green
• SD indicator is flashing green
• SAVE is shown on the status display
• A dialog box in the Logix Designer application indicates the store is in
progress
When the store is complete, the following occurs:
• OK indicator on the controller is momentarily red, then solid green
• SD indicator on the controller is Off
IMPORTANT
66
Allow the store to complete without interruption. If you interrupt the
store, data corruption or loss may occur.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Start Using the Controller
Chapter 3
Load from the Memory Card
After you have set the communication path, are online with the controller, and
have changed the controller to Program mode, complete these steps to load a
project to the controller from the memory card.
1. Open the Controller Properties and click the Nonvolatile Memory tab.
2. Click Load/Store.
TIP
If Load/Store is dimmed (unavailable), verify the following:
• You have specified the correct communication path and are online with the
controller.
• The memory card is installed.
If the memory card is not installed, the missing card is indicated by a message
in the lower-left corner of the Nonvolatile Memory tab as shown here.
3. Verify that the image in nonvolatile memory (that is, the project on the
memory card) is the project you want to load.
TIP
If no project is stored on the memory card, a message in the lower-left corner
of the Nonvolatile Memory tab indicates that an image (or project) is not
available as shown here.
TIP
For information about changing the project that is available to load from
nonvolatile memory, see the Logix5000™ Controllers Nonvolatile Memory
Programming Manual, publication 1756-PM017.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
67
Chapter 3
Start Using the Controller
4. Click Load.
After clicking Load, the project is loaded to the controller as indicated by
the controller status indicators.
With these controllers
These indications show the store status
1756-L6x
While the load is in progress, the following occurs:
• OK indicator on the controller is flashing green
• A dialog box in the Logix Designer application indicates the store is in
progress
When the load is complete, the following occurs:
• OK indicator on the controller is momentarily red, then solid green
1756-L7x
While the load is in progress, the following occurs:
• OK indicator is solid red
• SD indicator is flashing green
• LOAD is shown on the status display
• UPDT may be shown on the status display if the firmware is also updating
with the load
• A dialog box in the Logix Designer application indicates the store is in
progress
When the load is complete, the following occurs:
• OK indicator on the controller is momentarily red, then solid green
• SD indicator on the controller is Off
IMPORTANT
68
Allow the load to complete without interruption. If you interrupt the
load, data corruption or loss may occur.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Start Using the Controller
Chapter 3
Other Memory Card Tasks
Other tasks that you may need to complete by using the memory cards of the
controller include the following:
• Changing the image that is loaded from the card
• Checking for a load that was completed
• Clearing an image from the memory card
• Storing an empty image
• Changing load parameters
• Reading/writing application data to the card
For more information about completing any of these tasks, see the Logix5000
Controllers Memory Card Programming Manual, publication 1756-PM017.
Use ControlLogix Energy
Storage Modules (ESMs)
You can use the ControlLogix ESMs to execute either of the following tasks:
• Provide power to 1756-L7x controllers to save the program to the
controller’s on-board nonvolatile storage (NVS) memory after power is
removed from the chassis or the controller is removed from a powered
chassis.
IMPORTANT
When you are using an ESM to save the program to on-board NVS
memory, you are not saving the program to the SD card installed in the
controller.
• Clear the program from the 1756-L7x controller’s on-board NVS memory.
For more information, see Clear the Program from On-board NVS
Memory.
The following table describes the ESMs.
Cat. No.
Description
1756-ESMCAP
Capacitor-based ESM
The 1756-L7x controllers come with this ESM installed.
1756-ESMNSE
Capacitor-based ESM without WallClockTime back-up power
Use this ESM if your application requires that the installed ESM deplete its residual stored energy
to 40μjoules or less before transporting it into or out of your application. Additionally, you can
use this ESM with a 1756-L73 (8MB) or smaller memory-sized controller only.
1756-ESMNRM
Secure capacitor-based ESM (non-removable)
This ESM provides your application an enhanced degree of security by preventing physical access
to the USB connector and the SD card.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
69
Chapter 3
Start Using the Controller
Save the Program to On-board NVS Memory
Follow these steps to save the program to NVS memory when the controller loses
power.
1. Remove power from the controller.
You can remove power in either of two ways:
• Turn power off to the chassis while the controller is installed in the
chassis.
• Remove the controller from a powered chassis.
Immediately after the controller is no longer powered, the program starts
saving while the OK status indicator is green (this green is a dimmer green
than normal operation), then turns red after program save is complete.
Once the ESM stops operating, it turns off.
The following graphic shows the controller’s OK status indicator.
Logix557x
RUN FORCE SD
OK
N REM PRO
RU
G
2. Leave the ESM on the controller until the OK status indicator is Off.
70
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Start Using the Controller
Chapter 3
Clear the Program from On-board NVS Memory
If your application allows it, follow these steps to clear the program from the
1756-L7x controller’s on-board NVS memory.
1. Remove the ESM from the controller.
2. Remove power from the controller.
You can remove power in either of the following two ways:
• Turn power off to the chassis while the controller is installed in the
chassis.
• Remove the controller from a powered chassis.
3. Reinstall the ESM into the controller.
4. Restore power to the controller in one of these two ways:
• If the controller is already installed in the chassis, turn power back onto
the chassis.
• If the controller is not installed into the chassis, reinstall the controller
into the chassis and turn power back onto the chassis.
Estimate the ESM Support
of the WallClockTime
The ESM provides support for the maintenance of the WallClockTime of the
controller when power is not applied. Use this table to estimate the hold-up time
of the ESM based on the temperature of the controller and installed ESM.
Hold-up Time (in days)
Temperature
1756-ESMCAP
1756-ESMNRM
1756-ESMNSE
20 °C (68 °F)
12
12
0
40 °C (104 °F)
10
10
0
60 °C (140 °F)
7
7
0
IMPORTANT
Any action causing the 1756-L7x controller to reset (hard or soft), without an
ESM installed, will result in the controller’s wall clock time being reset to the
factory default of 01/01/1998.
To check the status of the ESM, refer to General Status Messages on page 186.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
71
Chapter 3
Start Using the Controller
Maintain the Battery
(1756-L6x controllers only)
This section explains how to monitor and maintain the lithium batteries
supported by ControlLogix controllers.
Table 6 - 1756-L6x Controllers and Compatible Batteries
Cat. No.
Series
Compatible Battery
1756-L61
1756-L62
1756-L63
A
1756-BA1
or
1756-BATA
or
1756-BATM
1756-L61
1756-L62
1756-L63
1756-L64
1756-L65
B
1756-BA2
1756-L63XT
B
For additional resources, see the table below.
Table 7 - Additional Resources for Battery Maintenance
Resource
Description
Guidelines for Handling Lithium Batteries, publication
AG-5.4
Provides information regarding storage, handling,
transportation, and disposal of lithium batteries.
Programmable Controllers Battery Reference,
http://www.ab.com/programmablecontrol/batteries.html
Provides Material Safety Data Sheets (MSDS) for
individual replacement batteries.
Check the Battery Status
When the battery is approximately 95% discharged, these low-battery warnings
are indicated:
• The BAT is solid red.
• A minor fault (type 10, code 10) is logged.
IMPORTANT: To prevent possible battery leakage, even if the BAT status
indicator is off, replace a battery according to this schedule.
72
If the temperature 2.54 cm (1 in.)
below the chassis is
Replace the battery within
-25…35 °C (-13…95 °F)
No replacement required
36…40 °C (96.8…104 °F)
3 years
41…45 °C (105.8…113 °F)
2 years
46…50 °C (114.8…122 °F)
16 months
51…55 °C (123.8…131 °F)
11 months
56…70 °C (132.8…158 °F)
8 months
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Start Using the Controller
Chapter 3
1756-BA1 or 1756-BATA Battery Life
To estimate how long a 1756-BA1 or 1756-BATA battery will support controller
memory on 1756-L6x, series A controllers, perform this procedure.
1. Determine the temperature 2.54 cm (1 in.) below the chassis.
2. Determine the weekly percentage of time that the controller is turned on.
EXAMPLE
If a controller is Off either one of these times:
• 8 hr/day during a 5-day work week
• All day Saturday and Sunday
Then the controller is off 52% of the time:
• Total hours per week = 7 x 24 = 168 hrs
• Total off hours per week = (5 days x 8 hr/day) + Saturday +
Sunday = 88 hrs
• Percentage off time = 88/168 = 52%
3. Determine the estimated worst-case battery life before and after the BAT
status indicator turns on.
4. For each year of battery life, decrease the time before the BAT status
indicator turns on by the percentage that is shown in the table.
Do not decrease the time after the BAT status indicator turns on.
IMPORTANT
If the BAT status indicator turns on when you apply power to the
controller, the remaining battery life may be less than this table
indicates. Some of the battery life may have been used up while the
controller was off and unable to turn on the BAT status indicator.
Table 8 - Worst-case Estimates of 1756-BA1 Battery Life
Temperature
Battery Life Before BAT Status Indicator Turns On
Power Off 100% Power Off 50% Yearly Decrease
Battery Life after BAT Status
Indicator Turns On and Power is Off
60 °C (140 °F)
22 days
43 days
23%
6 hrs
25 °C (77 °F)
21 days
42 days
17%
28 hrs
0 °C (32 °F)
14 days
28 days
17%
2.5 days
Table 9 - Worst-case Estimates of 1756-BATA Battery Life
Temperature Battery Life Before BAT Status Indicator Turns On
Power Off 100% Power Off 50% Yearly
Decrease
Battery Life after BAT Status
Indicator Turns On and Power is Off
60 °C (140 °F)
98 days
204 days
11%
104 days
25 °C (77 °F)
146 days
268 days
5%
157 days
0 °C (32 °F)
105 days
222 days
6%
113 days
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
73
Chapter 3
Start Using the Controller
1756-BATM Battery Module and Battery Life
Use the 1756-BATM battery module with any 1756-L6x/A controller. The
battery module is highly recommended for higher-memory controllers.
IMPORTANT
If your project is not stored in nonvolatile memory, the use of the battery
module is highly recommended.
When the 1756-BATA battery within the 1756-BATM module is approximately
50% discharged, these low-battery warnings are indicated:
• The BAT is solid red.
• A minor fault (type 10, code 10) is logged.
Estimate 1756-BA2 Battery Life
The 1756-BA2 batteries are for use in 1756-L6x/B controllers. Use this table to
estimate how much time will elapse before the battery becomes low.
Table 10 - Worst-case Estimates of 1756-BA2 Life According to Temperatures and Power Cycles
Temperature 2.54 cm (1 in.) Below
the Chassis, max
Power Cycles
Battery Life Before the BAT Status Indicator Turns Red
Project Size
1 MB
2 MB
4 MB
8 MB
16 MB
3 per day
3 years
3 years
26 months
20 months
10 months
2 per day or less
3 years
3 years
3 years
31 months
16 months
3 per day
2 years
2 years
2 years
20 months
10 months
2 per day or less
2 years
2 years
2 years
2 years
16 months
46...50 °C (105.8...113 °F)
3 per day or less
16 months
16 months
16 months
16 months
10 months
51...55 °C (123.8...131 °F)
3 per day or less
11 months
11 months
11 months
11 months
10 months
56…70 °C (132.8…158 °F)
3 per day or less
8 months
8 months
8 months
8 months
8 months
-25…35 °C (-13…95 °F)
41...45 °C (105.8...113 °F)
74
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Start Using the Controller
Chapter 3
Estimate 1756-BA2 Battery Life after Warnings
Use this table to estimate the battery life after the low-battery warnings are
indicated. Use these times even if the controller does not have power because
there is always a small power-drain on the battery.
IMPORTANT
Temperature 2.54 cm (1 in.)
Below the Chassis, max
0...20 °C (32...68 °F)
21...40 °C (69.8...104 °F)
41...45 °C (105.8...113 °F)
46...50 °C (105.8...113 °F)
51...55 °C (123.8...131 °F)
56...60 °C (132.8...140 °F)
Power Cycles
When you power up the controller, see if there is a low-battery warning. If
you get a low-battery warning for the first time, you have less battery life
than this table shows. While powered down, the controller still drains the
battery but it cannot give the low-battery warning.
Battery Life After the BAT Status Indicator Turns Red (worst case)
Project Size
1 MB
2 MB
4 MB
8 MB
16 MB
3 per day
26 weeks
18 weeks
12 weeks
9 weeks
5 weeks
1 per day
26 weeks
26 weeks
26 weeks
22 weeks
13 weeks
1 per month
26 weeks
26 weeks
26 weeks
26 weeks
26 weeks
3 per day
18 weeks
14 weeks
10 weeks
8 weeks
5 weeks
1 per day
24 weeks
21 weeks
18 weeks
16 weeks
11 weeks
1 per month
26 weeks
26 weeks
26 weeks
26 weeks
26 weeks
3 per day
12 weeks
10 weeks
7 weeks
6 weeks
4 weeks
1 per day
15 weeks
14 weeks
12 weeks
11 weeks
8 weeks
1 per month
17 weeks
17 weeks
17 weeks
17 weeks
16 weeks
3 per day
10 weeks
8 weeks
6 weeks
6 weeks
3 weeks
1 per day
12 weeks
11 weeks
10 weeks
9 weeks
7 weeks
1 per month
12 weeks
12 weeks
12 weeks
12 weeks
12 weeks
3 per day
7 weeks
6 weeks
5 weeks
4 weeks
3 weeks
1 per day
8 weeks
8 weeks
7 weeks
7 weeks
5 weeks
1 per month
8 weeks
8 weeks
8 weeks
8 weeks
8 weeks
3 per day
5 weeks
5 weeks
4 weeks
4 weeks
2 weeks
1 per day
6 weeks
6 weeks
5 weeks
5 weeks
4 weeks
1 per month
6 weeks
6 weeks
6 weeks
6 weeks
6 weeks
EXAMPLE
Under these conditions, the battery will last at least 20 months before the
BAT status indicator turns red:
• The maximum temperature 2.54 cm (1 in.) below the chassis = 45 °C
(113 °F).
• You cycle power to the controller three times per day.
• The controller contains an 8 MB project.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
75
Chapter 3
Start Using the Controller
Battery Storage and Disposal
Follow these general rules to store your batteries:
• Store batteries in a cool, dry environment. We recommend
25 °C (77 °F) with 40…60% relative humidity.
• You may store batteries for up to 30 days in temperatures from -45...85
°C (-49...185 °F), such as during transportation.
• To avoid leakage or other hazards, do not store batteries above
60 °C (140 °F) for more than 30 days.
This product contains a sealed lithium battery that needs to be replaced
during the life of the product.
At the end of its life, the battery contained in this product should be
collected separately from any unsorted municipal waste.
The collection and recycling of batteries helps protect the environment and
contributes to the conservation of natural resources as valuable materials
are recovered.
76
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Chapter
4
ControlLogix System and Controllers
ControlLogix System
Topic
Page
ControlLogix System
77
Design a ControlLogix System
80
ControlLogix Controller Features
81
The ControlLogix system is chassis-based and provides the option to configure a
control system that uses sequential, process, motion, and drive control in addition
to communication and I/O capabilities.
Configuration Options
This section describes some of the many system configuration options that are
available with ControlLogix controllers.
Standalone Controller and I/O
One of the simplest ControlLogix configurations is a standalone controller with
I/O assembled in one chassis.
Figure 7 - Standalone Controller and I/O
Output
Output
Input
L75
32044-MC
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
77
Chapter 4
ControlLogix System and Controllers
Multiple Controllers in One Chassis
For some applications, multiple controllers may be used in one ControlLogix
chassis. For example, for better performance, multiple controllers can be used in
motion applications.
Figure 8 - Multiple Controllers in One Chassis
EN2T
EN2T
L75
L75
FactoryTalk ®Server
Ethernet
Ethernet
Stratix 8000™ Switch
Kinetix 6500 Drive
Kinetix® 6500 Drive
Motor
Motor
Motor
Kinetix 6500 Drive
78
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
32045-MC
ControlLogix System and Controllers
Chapter 4
Multiple Devices Connected via Multiple Networks
For some applications, a variety of devices may be connected to the ControlLogix
chassis via multiple communication networks. For example, a system might be
connected to the following:
• Distributed I/O via an Ethernet network
• A PowerFlex® drive connected via a DeviceNet network
• Flowmeters connected via a HART connection
Figure 9 - Multiple Devices Connected via Multiple Networks
HART
IF8H
EN2T
EN2T
CN2
DNB
L75
Endress + Hauser Flowmeters
HART
DeviceNet
Ethernet
ControlNet
PowerFlex Drive
FactoryTalk Server
FLEX™ I/O
Ethernet Device-level
Ring Network
POINT I/O™
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
32046-MC
79
Chapter 4
ControlLogix System and Controllers
Design a ControlLogix System
When you design a ControlLogix system, there are several system components to
consider for your application. Some of these components include the following:
• I/O devices
• Motion control and drive requirements
• Communication modules
• Controllers
• Chassis
• Power supplies
• Studio 5000 environment
For more information about designing and selecting components for your
ControlLogix system, see the ControlLogix Selection Guide, publication
1756-SG001.
In addition, if you are designing your ControlLogix System for any of the specific
applications listed in this table, see the appropriate resources for more
information.
80
For this type of application
See this publication
Motion with Integrated Motion on the
EtherNet/IP network
Integrated Motion on the EtherNet/IP Network Configuration and
Startup User Manual, publication MOTION-UM003
Motion with the use of a coordinate system
Motion Coordinated Systems User Manual, publication MOTION-UM002
Motion with Sercos or analog motion
SERCOS Motion Configuration and Startup User Manual, publication
MOTION-UM001
Enhanced redundancy
ControlLogix Enhanced Redundancy System User Manual,
publication 1756-UM535
Standard redundancy
ControlLogix Redundancy System User Manual,
publication 1756-UM523
SIL2
Using ControlLogix in SIL2 Applications Safety Reference Manual,
publication 1756-RM001
SIL2 fault-tolerant I/O with RSLogix 5000
subroutines
ControlLogix SIL2 System Configuration Using RSLogix 5000
Subroutines Application Technique, publication 1756-AT010
SIL2 fault-tolerant I/O with RSLogix 5000
Add-On Instructions
ControlLogix SIL2 System Configuration Using SIL2 Add-On Instructions
Application Technique, publication 1756-AT012
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
ControlLogix System and Controllers
ControlLogix Controller
Features
Chapter 4
The ControlLogix controllers are part of the Logix5000 family of controllers
offered by Rockwell Automation. The sections that follow describe the
differentiating features of the ControlLogix controllers.
System, Communication, and Programming Features
This table lists the system, communication, and programming features available
with ControlLogix controllers.
Table 11 - ControlLogix Controller Features
Feature
1756-L61, 1756-L62, 1756-L63,
1756-L64, 1756-L65
1756-L71, 1756-L72, 1756-L73,
1756-L74, 1756-L75
Controller tasks
• 32 tasks
• 100 programs/task
• Event tasks: all event triggers
Communication ports
1 port - RS-232 serial
Communication options
•
•
•
•
•
•
•
EtherNet/IP
ControlNet
DeviceNet
Data Highway Plus™
Remote I/O
SynchLink
Third-party process and device networks
Serial port communication
•
•
•
•
•
ASCII
DF1 full/half-duplex
DF1 radio modem
DH-485
Modbus via logic
Controller connections supported, max
250
Network connections, per network
module
•
•
•
•
Controller redundancy
Full support except for motion applications
Integrated motion
• Integrated Motion on the EtherNet/IP network
• SERCOS interface
• Analog options:
– Encoder input
– LDT input
– SSI input
Programming languages
•
•
•
•
1 port - USB, 2.0 full-speed, Type B
N/A
500
100 ControlNet (1756-CN2/A)
40 ControlNet (1756-CNB)
256 EtherNet/IP; 128 TCP (1756-EN2x)
128 EtherNet/IP; 64 TCP (1756-ENBT)
Relay ladder
Structured text
Function block
Sequential Function Chart (SFC)
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
81
Chapter 4
ControlLogix System and Controllers
Memory Options
The ControlLogix controller is available in different combinations of user
memory. Use this table to determine which controller meets your memory
requirements.
Table 12 - ControlLogix Controller Memory Options
Controller
Memory for Data and Logic
I/O
Back-up Memory
1756-L61
2 MB
478 KB
CompactFlash card(1)
1756-L62
4 MB
1756-L63, 1756-L63XT
8 MB
1756-L64
16 MB
1756-L65
32 MB
1756-L71
2 MB
0.98 MB (1006 KB)
SD card
1756-L72
4 MB
1756-L73, 1756-L73XT
8 MB
1756-L74
16 MB
1756-L75
32 MB
(1) These nonvolatile memory cards are optional and do not come with the controller.
82
IMPORTANT
The 1756-L7x controllers ship with an SD card installed. We recommend that
you leave the SD card installed, so if a fault occurs, diagnostic data is
automatically written to the card and can be used by Rockwell Automation to
troubleshoot the anomaly.
IMPORTANT
We recommend that you use the SD cards available from Rockwell Automation
(catalog numbers 1784-SD1 or 1784-SD2).
While other SD cards may be used with the controller, Rockwell Automation
has not tested the use of those cards with the controller. If you use an SD card
other than those available from Rockwell Automation, you may experience
data corruption or loss.
Also, SD cards not provided by Rockwell Automation may not have the same
industrial, environmental, and certification ratings as those available from
Rockwell Automation and may not survive in the same industrial environments
as the industrially rated versions available from Rockwell Automation.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Chapter
5
Communication Networks
Networks Available
Topic
Page
Networks Available
83
EtherNet/IP Network Communication
84
ControlNet Network Communication
87
DeviceNet Network Communication
90
Data Highway Plus (DH+) Network Communication
92
Universal Remote I/O (RIO) Communication
94
Foundation Fieldbus Communication
96
HART Communication
97
Several communication networks are available for use with ControlLogix
systems. This table describes typical network applications used with
ControlLogix systems and lists the networks available to support such
applications.
Table 13 - Applications and Supported Networks
Application Type
Supported Networks
Integrated Motion
EtherNet/IP
Integrated Motion on the EtherNet/IP network for time
synchronization
EtherNet/IP
Control of distributed I/O
•
•
•
•
•
•
Produce/consume data between controllers
• ControlNet
• EtherNet/IP
Messaging to and from other devices, including access to
the controller via Logix Designer application
•
•
•
•
•
•
ControlNet
DeviceNet
EtherNet/IP
Foundation Fieldbus
HART
Universal remote I/O
ControlNet
DeviceNet (only to devices)
Data Highway Plus (DH+)
DH-485
EtherNet/IP
Serial
For additional information about network design for your system, see the
Ethernet Design Considerations Reference Manual, publication ENET-RM002.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
83
Chapter 5
Communication Networks
The EtherNet/IP network offers a full suite of control, configuration, and data
collection services by layering the Common Industrial Protocol (CIP) over the
standard Internet protocols, such as TCP/IP and UDP. This combination of
well-accepted standards provides the capability required to both support
information data exchange and control applications.
EtherNet/IP Network
Communication
The EtherNet/IP network uses commercial, off-the-shelf Ethernet components
and physical media, providing you with a cost-effective plant-floor solution.
Figure 10 - EtherNet/IP Network Example
ControlLogix
Controller with
1756-EN2T Module
Distributed I/O
LINK NET OK
LINK NET OK
1756-EN2T Module (as an adapter)
with 1756 I/O Modules
CompactLogix™ Controller with
Integrated EtherNet/IP Port
1794-AENT Adapter with 1794
I/O Modules
Switch
1734-AENT Adapter with 1734
I/O Modules
PowerFlex® 700S AC Drive
with DriveLogix™ Software
Workstation
For more information about using EtherNet/IP modules, see the EtherNet/IP
Modules in Logix5000 Control Systems User Manual, publication
ENET-UM001.
ControlLogix EtherNet/IP Module Features
The ControlLogix EtherNet/IP communication modules provide these features:
• Support for messaging, produced/consumed tags, HMI, and
distributed I/O
• The ability to encapsulate messages within the standard TCP/UDP/IP
protocol
• A common application layer with ControlNet and DeviceNet networks
• Network connections via an RJ45 cable
• Support half/full duplex 10 MB or 100 MB operation
• Support standard switches
84
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Communication Networks
Chapter 5
ControlLogix EtherNet/IP Communication Modules
For EtherNet/IP network communication in a ControlLogix system, you have
several modules to choose from. This table lists modules and their primary
features.
Table 14 - EtherNet/IP Communication Modules and Capabilities
Module
Is used to
1756-ENBT
•
•
•
•
1756-EN2T
• Perform the same functions as a 1756-ENBT module, with twice the capacity for more
demanding applications.
• Provide a temporary configuration connection via the USB port.
• Configure IP addresses quickly by using rotary switches.
1756-EN2F
• Perform the same functions as a 1756-EN2T module.
• Connect fiber media by an LC fiber connector on the module.
1756-EN2TR
• Perform the same functions as a 1756-EN2T module.
• Support communication on a ring topology for a Device Level Ring (DLR) single-fault
tolerant ring network.
1756-EN3TR
• Perform the same functions as the 1756-EN2TR module.
• Extended Integrated Motion on EtherNet/IP network.
• Support of up to 128 motion axes.
1756-EN2TXT
• Perform the same functions as a 1756-EN2T module.
• Operate in extreme environments with -25…70 °C (-13…158 °F) temperatures.
1756-EWEB
• Provide customizable web pages for external access to controller information.
• Provide remote access via an Internet browser to tags in a local ControlLogix controller.
• Communicate with other EtherNet/IP devices (messages).
• Bridge EtherNet/IP nodes to route messages to devices on other networks.
• Support Ethernet devices that are not EtherNet/IP-based with a socket interface.
This module does not provide support for I/O or produced/consumed tags.
Connect controllers to I/O modules (requires an adapter for distributed I/O).
Communicate with other EtherNet/IP devices (messages).
Serve as a pathway for data sharing between Logix5000 controllers (produce/consume).
Bridge EtherNet/IP nodes to route messages to devices on other networks.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
85
Chapter 5
Communication Networks
Software for EtherNet/IP Networks
This table lists software that is used with the EtherNet/IP networks and modules.
Table 15 - Software for Use with EtherNet/IP Networks
Software
Is used to
Required or Optional
Logix Designer application
• Configure ControlLogix projects.
• Define EtherNet/IP communication.
Required
RSLinx Classic or RSLinx®
Enterprise
• Configure communication devices.
• Provide diagnostics.
• Establish communication between devices.
Required
BOOTP/DHCP Utility
Assign IP addresses to devices on an EtherNet/IP network.
Optional
RSNetWorx™ for EtherNet/IP • Configure EtherNet/IP devices by IP addresses and/or
host names.
• Provide bandwidth status.
Connections over an EtherNet/IP Network
You indirectly determine the number of connections the controller uses by
configuring the controller to communicate with other devices in the system.
Connections are allocations of resources that provide more reliable
communication between devices compared to unconnected messages.
All EtherNet/IP connections are unscheduled. An unscheduled connection is
triggered by the requested packet interval (RPI) for I/O control or the program,
such as a MSG instruction. Unscheduled messaging lets you send and receive data
when needed.
86
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Communication Networks
Chapter 5
Double Data Rate (DDR) Backplane Communication
DDR communication can be achieved with the 1756-L7x controller. The
following communication modules support DDR when used in conjunction
with the 1756-L7x controller. Minimum series are indicated:
• 1756-EN2T/C
• 1756-EN2TR/B
• 1756-EN2TF/B
• 1756-EN2TXT/C
• 1756-EN3TR/A
• 1756-RM/B
DDR communication is achieved most efficiently when all modules in the
communication path are DDR modules, or, in other words, as a single
conversation (connection) only between DDR modules.
DDR communication is achievable in a chassis with a mix of DDR and nonDDR modules. The DDR communication occurs between the modules that
support it. If non-DDR modules are also in the chassis, communication between
those modules will be at the non-DDR rate.
For example, you could have a chassis with two 1756-L7x controllers in slots 0
and 1 communicating with each other using DDR, and two 1756-L6x controllers
in slots 2 and 3 communicating using non-DDR.
When multicast communication is used within a chassis to multiple modules, the
transmission rate is limited to the slowest module—or at the non-DDR rate.
For example, if a 1756-L7x controller is producing a tag to a 1756-L7x controller
and a 1756-L6x controller on the same multicast connection, it must use the
non-DDR rate.
ControlNet Network
Communication
The ControlNet network is a real-time control network that provides high-speed
transport of both time-critical I/O and interlocking data and messaging data.
This includes uploading and downloading of program and configuration data on
a single physical-media link. The ControlNet network’s highly-efficient data
transfer capability significantly enhances I/O performance and peer-to-peer
communication in any system or application.
The ControlNet network is highly deterministic and repeatable and is unaffected
when devices are connected or disconnected from the network. This quality
results in dependable, synchronized, and coordinated real-time performance.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
87
Chapter 5
Communication Networks
The ControlNet network often functions as the following:
• A substitute/replacement for the remote I/O (RIO) network because the
ControlNet network adeptly handles large numbers of I/O points
• A backbone for multiple distributed DeviceNet networks
• A peer interlocking network
Figure 11 - ControlNet Network Overview
Workstation
Distributed I/O
CompactLogix Controller
PowerFlex 700S AC Drive
with DriveLogix Software
1756-CNB Module
(as an adapter) with
1756 I/O Modules
ControlNet Network
1794-ACN15 Adapter
with 1794 I/O Modules
FlexLogix Module
PanelView Terminal
1734-ACNR Adapter with
1734 I/O Modules
PLC-5/40C15 Controller
In this example, these actions occur via the ControlNet network:
• The controllers produce and consume tags.
• The controllers initiate MSG instructions that do the following:
– Send and receive data.
– Configure devices.
• The workstation is used to do the following:
– Configure both the ControlNet devices and the ControlNet network.
– Download and upload projects from the controllers.
For more information about using ControlNet modules, see ControlNet
Modules in Logix5000 Control Systems User Manual, publication
CNET-UM001.
88
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Communication Networks
Chapter 5
ControlLogix ControlNet Module Features
The ControlNet communication modules provide these features:
• Support for messaging, produced/consumed tags, and distributed I/O
• Use a common application layer with DeviceNet and EtherNet/IP
networks
• Requires no routing tables
• Support the use of coax and fiber repeaters for isolation and increased
distance
• Support redundant media (1756-CNBR, 1756-CN2R, and
1756-CN2RXT modules only)
ControlLogix ControlNet Modules
This table lists the available ControlLogix ControlNet modules and their
primary features.
Table 16 - ControlNet Modules and Capabilities
Module
Is used to
1756-CNB
•
•
•
•
1756-CNBR
• Perform the same functions as a 1756-CNB module.
• Support redundant ControlNet media.
1756-CN2
• Perform the same functions as a 1756-CNB module.
• Provide twice the capacity for more demanding applications.
1756-CN2R
• Perform the same functions as a 1756-CN2 module.
• Support redundant ControlNet media.
1756-CN2RXT
• Perform same functions as a 1756-CN2R module.
• Operate in extreme environments with -25…70 °C (-13…158 °F) temperatures.
Control I/O modules.
Communicate with other ControlNet devices (messages).
Share data with other Logix5000 controllers (produce/consume).
Bridge ControlNet links to route messages to devices on other networks.
Software for ControlNet Networks
This table lists software that is used with the ControlNet networks and modules.
Table 17 - Software for Use with ControlNet Networks
Software
Is used to
Required or Optional
Logix Designer application
• Configure ControlLogix projects.
• Define ControlNet communication.
Required
RSNetWorx™ for ControlNet™
• Configure ControlNet devices.
• Schedule a network.
RSLinx Classic or Enterprise
• Configure communication devices.
• Provide diagnostics.
• Establish communication between devices.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
89
Chapter 5
Communication Networks
Connections over a ControlNet Network
You indirectly determine the number of connections the controller uses by
configuring the controller to communicate with other devices in the system.
Connections are allocations of resources that provide more reliable
communication between devices compared to unconnected messages.
Table 18 - ControlNet Connections
Connection
Definition
Scheduled
(unique to a
ControlNet
network)
A scheduled connection is unique to ControlNet communication. A scheduled connection lets you
send and receive data repeatedly at a predetermined interval, which is the requested packet
interval (RPI). For example, a connection to an I/O module is a scheduled connection because you
repeatedly receive data from the module at a specified interval.
Other scheduled connections include connections to the following:
• Communication devices
• Produced/consumed tags
On a ControlNet network, you must use RSNetWorx for ControlNet software to enable all scheduled
connections and establish a network update time (NUT). Scheduling a connection reserves
network bandwidth specifically to handle the connection.
Unscheduled
An unscheduled connection is a message transfer between devices that is triggered by the
requested packet interval (RPI) or the program, such as a MSG instruction. Unscheduled messaging
lets you send and receive data when you need to:
Unscheduled connections use the remainder of network bandwidth after scheduled connections
are allocated.
ControlNet Module Connections
The 1756-CNB and 1756-CNBR communication modules support 64 CIP
connections over a ControlNet network. However, for optimal performance,
configure a maximum of 48 connections for each module.
The 1756-CN2, 1756-CN2R, and 1756-CN2RXT communication modules
support 128 connections over a ControlNet network, all of which can be
configured without risk of performance degradation.
DeviceNet Network
Communication
The DeviceNet network uses the Common Industrial Protocol (CIP) to provide
the control, configuration, and data collection capabilities for industrial devices.
The DeviceNet network uses the proven Controller Area Network (CAN)
technology, which lowers installation costs and decreases installation time and
costly downtime.
A DeviceNet network provides access to the intelligence present in your devices
by letting you connect devices directly to plant-floor controllers without having
to hard wire each device into an I/O module.
With a ControlLogix system, DeviceNet communication requires the use of a
1756-DNB DeviceNet communication module.
90
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Communication Networks
Chapter 5
Figure 12 - ControlLogix DeviceNet Network Overview
ControlLogix Controller with
1756-ENBT Module
EtherNet/IP Network
CompactLogix Controller
FLEX I/O Adapter
and Modules
1788-EN2DN
DeviceNet Network
Personal Computer
Sensor
Pushbutton
Cluster
PWR
PWR
STS
Motor
Starter
Input/output Devices
STS
PORT
MOD
PORT
NET A
MOD
NET B
NET A
NET B
PowerFlex AC
Drive
Indicator
Lights
Bar Code
Scanner
In this example, the ControlLogix controller is connected to the DeviceNet
network and devices via the 1788-EN2DN linking device.
For more information about using DeviceNet modules and devices, see
DeviceNet Modules in Logix5000 Control Systems User Manual, publication
DNET-UM004.
ControlLogix DeviceNet Module Features
The DeviceNet communication module provides these features:
• Supports messaging to devices (not controller to controller)
• Shares a common application layer with ControlNet and EtherNet/IP
networks
• Offers diagnostics for improved data collection and fault detection
• Requires less wiring than standard, hard-wired systems
ControlLogix DeviceNet Bridge Module and Linking Devices
This table lists the available ControlLogix DeviceNet bridge module and linking
devices that can be used with the DeviceNet network.
Table 19 - DeviceNet Communication Modules and Capabilities
Module/Device
Is used to
1756-DNB
• Control I/O modules.
• Communicate with other DeviceNet devices (via messages).
1788-EN2DN
Link an EtherNet/IP network to a DeviceNet network.
1788-CN2DN
Link a ControlNet network to a DeviceNet network.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
91
Chapter 5
Communication Networks
Software for DeviceNet Networks
This table lists software that is used with the DeviceNet networks and modules.
Table 20 - Software for Use with DeviceNet Networks
Software
Is used to
Required or Optional
Logix Designer application
• Configure ControlLogix projects.
• Define DeviceNet communication.
Required
RSNetWorx™ for DeviceNet™
• Configure DeviceNet devices.
• Define the scan list for those devices.
RSLinx Classic or Enterprise
• Configure communication devices.
• Provide diagnostics.
• Establish communication between devices.
Connections over DeviceNet Networks
The ControlLogix controller requires two connections for each 1756-DNB
module. One connection is for module status and configuration. The other
connection is a rack-optimized connection for the device data.
ControlLogix DeviceNet Module Memory
The 1756-DNB module has fixed sections of memory for the input and output
data of the DeviceNet devices on the network. Each device on your network
requires either some input or output memory of the scanner. Some devices both
send and receive data, so they need both input and output memory. The 1756DNB module supports up to add the following:
• 124 DINTs of input data
• 123 DINTs of output data
Data Highway Plus (DH+)
Network Communication
For DH+ network communication, use a 1756-DHRIO module in the
ControlLogix chassis to exchange information between these controllers:
• PLC and SLC controllers
• ControlLogix controllers and PLC or SLC controllers
• ControlLogix controllers
In addition to data exchange between controllers, the DH+ network also
provides the ability to regularly share data both plant-wide and at a cellular level.
You can connect a maximum of 32 stations to a single DH+ link:
• Channel A supports 57.6 Kbps, 115.2 Kbps, and 230.4 Kbps.
• Channel B supports 57.6 Kbps and 115.2 Kbps.
92
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Communication Networks
Chapter 5
Figure 13 - ControlLogix DH+ Network Communication Example
Data Collection and Recipe
Management
Workstation
EtherNet/IP Network
ControlLogix
Controller
ControlLogix
Controller
DH+ Network
DH+ Network
PLC-5 Controller
SLC™ 500 Controller
RSView® Station
PLC-5 Controller
SLC 500 Controller
RSView Station
Communicate over a DH+ Network
For the controller to communicate to a workstation or other device over a
DH+ network, use RSLinx Classic software to do the following:
• Specify a unique link ID for each ControlLogix backplane and additional
network in the communication path.
• Configure the routing table for the 1756-DHRIO module.
The 1756-DHRIO module can route a message through up to four
communication networks and three chassis. This limit applies only to the routing
of a message and not to the total number of networks or chassis in a system.
For more information about configuring and using a DH+ network via the
1756-DHRIO module, see the Data Highway Plus-Remote I/O
Communication Interface Module User Manual, publication 1756-UM514.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
93
Chapter 5
Communication Networks
Universal Remote I/O (RIO)
Communication
For universal remote I/O communication, you have two module options for use
in the ControlLogix chassis. This table lists the RIO modules and capabilities.
Table 21 - RIO Modules and Capabilities
RIO Module
Is used to
1756-RIO
• Function as an RIO scanner and adapter.
• Support connections to 32 racks in any combination of rack size or block transfers.
• Update data to the ControlLogix controller by using scheduled connections.
1756-DHRIO
•
•
•
•
Function as an RIO scanner.
Support either 32 logical rack connections or 16 block-transfer connections per channel.
Establish connections between controllers and I/O adapters.
Distribute control so that each controller has its own I/O.
When a channel on the 1756-DHRIO module is configured for remote I/O, the
module acts as a scanner for a universal remote I/O network. The controller
communicates to the module to send and receive the I/O data on the universal
remote I/O network.
The 1756-RIO module can act as a scanner or adapter on a remote I/O network.
In addition to digital and block-transfer data, the 1756-RIO module transfers
analog and specialty data without message instructions.
Figure 14 - ControlLogix Universal Remote I/O Communication Example
ControlLogix Controller
1771-ASB and I/O Modules
1746-ASB and I/O Modules
Universal Remote I/O Network
PLC-5 Controller in Adapter Mode
1794-ASB and I/O Modules
94
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Communication Networks
Chapter 5
Communicate over a Universal Remote I/O Network
For the controller to control I/O over a universal remote I/O network, you must
complete these tasks.
1. Configure the remote I/O adapter.
2. Lay out the remote I/O network cable.
3. Connect the remote I/O network cable.
4. Configure the scanner channel.
For more information about configuring a remote I/O network with the
1756-RIO or 1756-DHRIO modules, see these publications:
• Data Highway Plus-Remote I/O Communication Interface Module User
Manual, publication 1756-UM514
• ControlLogix Remote I/O Communication Module User Manual,
publication 1756-UM534
As you design your remote I/O network, remember the following:
• All devices connected to a remote I/O network must communicate using
the same communication rate. These rates are available for remote I/O:
– 57.6 Kbps
– 115.2 Kbps
– 230.4 Kbps
• You must assign unique partial and full racks to each channel used in
Remote I/O Scanner mode.
Both channels of a 1756-DHRIO module cannot scan the same partial or
full rack address. Both module channels can communicate to 00...37 octal
or 40...77 octal, but each channel can communicate only with one address
at a time in whichever of these two ranges it falls.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
95
Chapter 5
Communication Networks
Foundation Fieldbus
Communication
Foundation Fieldbus is an open interoperable fieldbus designed for process
control instrumentation. The fieldbus devices described in the table can be
connected to the ControlLogix controller via another network as shown in the
example below.
Table 22 - Fieldbus Devices and Capabilities
Fieldbus Device
Is used to
1757-FFLD
• Bridge an EtherNet/IP network to Foundation Fieldbus.
• Connect via a low-speed serial (H1) and high-speed Ethernet (HSE) network
connections.
• Access devices directly via an OPC server.
1788-CN2FF
• Connect via low-speed serial (H1) connections.
• Bridge a ControlNet network to a Foundation Fieldbus.
• Support redundant ControlNet media.
Foundation Fieldbus distributes and executes control in the device. The
Foundation Fieldbus linking device does the following:
• Bridges from an EtherNet/IP network to an H1 connection
• Accepts either HSE or EtherNet/IP messages and converts them to the H1
protocol
Figure 15 - Foundation Fieldbus Example
ControlLogix Controller with a
1756-ENBT Module
RSFieldbus™ Software
1757-FFLD Linking Device
24V DC
Power
Supply
Power
Conditioner
Field Device
Field Device
For more information about using the Foundation Fieldbus devices available
from Rockwell Automation, see these publications:
• Foundation Fieldbus Linking Device User Manual, publication
1757-UM010
• ControlNet Foundation Fieldbus Linking Device User Manual,
publication 1757-UM011
• RSFieldbus User Manual, publication RSBUS-UM001
96
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Communication Networks
HART Communication
Chapter 5
HART (Highway Addressable Remote Transducer) is an open protocol designed
for process control instrumentation.
Device
Is used to
1756 analog I/O modules:
• 1756-IF8H
• 1756-OF8H
• Act as HART master to allow communication with HART field devices.
• Interface directly with field devices (through built-in HART modems),
eliminating need for external hardware and additional wiring.
• Provide access to more field device data, including voltage and current
measurements.
• Directly connect asset management software to HART devices.
• Support differential wiring for environments where improved noise immunity is
needed (input modules).
ProSoft interface
MVI56-HART
• Acquire data or control application with slow update requirements, such as a
tank farm.
• Does not require external hardware to access HART signal.
• Does not provide a direct connection to asset management software.
The HART protocol combines digital signals with analog signals to ready the
digital signal for the Process Variable (PV). The HART protocol also provides
diagnostic data from the transmitter.
Figure 16 - HART Protocol Example
ControlLogix Controller with 1756-IF8H or
1756-OF8H Modules
HART Field Devices
For more information about using the HART I/O modules, see the
ControlLogix HART Analog I/O Modules User Manual, publication
1756-UM533.
For more information about the ProSoft HART interface, see the
ProSoft Technologies website at http://www.prosoft-technology.com.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
97
Chapter 5
Communication Networks
Notes:
98
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Chapter
6
Serial Communication on 1756-L6x Controllers
Topic
Page
1756-L6x Controller Serial Port
100
Communication with Serial Devices
101
DF1 Master Protocol
101
DF1 Point to Point Protocol
101
DF1 Radio Modem Protocol
102
DF1 Slave Protocol
104
DH-485 Protocol
105
ASCII Protocol
107
Configure the 1756-L6x Controller for Serial Communication
107
Broadcast Messages over a Serial Port
109
Modbus Support
111
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
99
Chapter 6
Serial Communication on 1756-L6x Controllers
1756-L6x Controller
Serial Port
The 1756-L6x ControlLogix controllers have a built-in RS-232 port that can be
used in a variety of serial-based applications. The potential serial communication
applications include the following:
• DF1 modes (including broadcast message support)
• DF1 radio modem
• ASCII device communication
Figure 17 - ControlLogix DF1 Device Communication Example
DH+ Connection
EtherNet/IP
Network
RS-232 Connection
RS-232 Connection
RS-232 Connection
Modem
Modem
Modem
ControlLogix Chassis Serial Communication Options
You can use the serial port of the ControlLogix controller and/or use ProSoft
modules in the ControlLogix to achieve serial communication. Options specific
to the ControlLogix controller serial port are described in this chapter.
For more information about ProSoft modules that can be used to establish serial
communication, see the ProSoft Technology website or go to
http://www.prosoft-technology.com and browse available products.
100
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Serial Communication on 1756-L6x Controllers
Chapter 6
When configuring the controller for serial communication, you first specify a
Serial Port mode (System or User), then a protocol.
Communication with
Serial Devices
Figure 18 - Serial Port Mode in the Controller Properties
This table describes the serial communication protocols for use with each mode.
Table 23 - Serial Port Modes, Protocols, and Uses
Mode
Protocol
Is used to
See page
System
DF1 Master
Control polling and message transmission between the master and slave nodes.
101
DF1 Point to Point
• Communicate between the controller and one other DF1-protocol-compatible device.
• Program the controller via the serial port.
101
DF1 Radio Modem
• Communication with SLC 500 and MicroLogix™ 1500 controllers.
• This protocol supports master/slave and store/forward configurations.
102
DF1 Slave
Setup the controller as a slave station in a master/slave serial communication network.
104
DH-485
Communication with other DH-485 devices via a multi-master and token-passing network that enables
programming and peer-to-peer messaging.
105
ASCII
• Communicate with ASCII devices.
• Use ASCII instructions to read and write data from and to an ASCII device.
107
User
DF1 Master Protocol
The master/slave network includes one controller configured as the master node
and up to 254 slave nodes. Link slave nodes by using modems or line drivers.
A master/slave network can have node numbers from 0...254. Each node must
have a unique node address. Also, at least two nodes, one master and one slave,
must exist to define your link as a network.
DF1 Point to Point Protocol
The DF1 Point to Point protocol is used when connecting from the controller to
one DF1 device. This is the default System mode protocol. Default parameters
are listed in this table.
Table 24 - Default DF1 Point to Point Parameters
Parameter
Value
Baud Rate
19,200
Data Bits
8
Parity
None
Stop Bits
1
Control Line
No Handshake
RTS send Delay
0
RTS Off Delay
0
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
101
Chapter 6
Serial Communication on 1756-L6x Controllers
DF1 Radio Modem Protocol
Your ControlLogix controller includes a driver that allows it to communicate
over the DF1 Radio Modem protocol. This driver implements a protocol,
optimized for use with radio modem networks, that is a hybrid between DF1
full-duplex protocol and DF1 half-duplex protocol, and therefore is not
compatible with either of these protocols.
The DF1 radio modem driver should be used only among devices that
support and are configured for the DF1 Radio Modem protocol.
Additionally, there are some radio modem network configurations that will
not work with the DF1 radio modem driver. In these configurations,
continue to use DF1 half-duplex protocol.
IMPORTANT
Figure 19 - DF1 Radio Modem Network Example
EtherNet/IP Network
RS-232
Modem
Power
OUT
L1
L2/N
Modem
Modem
Modem
Like DF1 full-duplex protocol, the DF1 radio modem allows any node to initiate
to any other node at any time (that is, if the radio modem network supports fullduplex data-port buffering and radio-transmission collision avoidance). Like
DF1 half-duplex protocol, a node ignores any packets received that have a
destination address other than its own, with the exception of broadcast packets
and passthru packets.
Unlike either DF1 full-duplex or DF1 half-duplex protocols, the DF1 radio
modem protocol does not include ACKs, NAKs, ENQs, or poll packets. Data
integrity is ensured by the CRC checksum.
102
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Serial Communication on 1756-L6x Controllers
Chapter 6
DF1 Radio Modem Advantages
The primary advantage of using the DF1 radio modem protocol for radio
modem networks is in transmission efficiency. Each read/write transaction
(command and reply) requires only one transmission by the initiator (to send the
command) and one transmission by the responder (to return the reply). This
minimizes the number of times the radios need to key-up to transmit, which
maximizes radio life and minimizes radio power consumption.
In contrast, DF1 half-duplex protocol requires five transmissions for the DF1
master to complete a read/write transaction with a DF1 slave—three by the
master and two by the slave.
The DF1 radio modem driver can be used in a pseudo master/slave mode with
any radio modems, as long as the designated master node is the only node
initiating MSG instructions, and as long as only one MSG instruction is triggered
at a time.
For modern serial radio modems that support full-duplex data port buffering and
radio transmission collision avoidance, the DF1 radio modem driver can be used
to set up a masterless peer-to-peer radio network, where any node can initiate
communication to any other node at any time, as long as all of the nodes are
within radio range so that they receive each other’s transmissions.
DF1 Radio Modem Limitations
These considerations must be made if you can implement the new DF1 radio
modem driver in your radio modem network:
• If all of the devices on the network are ControlLogix controllers, you must
configure them with the DF1 radio modem driver via
RSLogix 5000 software, version 17.01.02 or later or Logix Designer
application, version 21.00.00 or later. If not, then make sure that all of the
nodes can support the DF1 radio modem protocol.
• If each node receives the radio transmissions of every other node, being
both within radio transmission/reception range and on a common
receiving frequency (either via a Simplex radio mode or via a single,
common, full-duplex repeater) the radio modems must handle full-duplex
data port buffering and radio transmission collision avoidance.
If this is the case, you can take full advantage of the peer-to-peer message
initiation capability in every node (for example, the ladder logic in any
node can trigger a MSG instruction to any other node at any time).
If not all modems can handle full-duplex data port buffering and radio
transmission collision avoidance, you may still be able to use the DF1 radio
modem driver, but only if you limit MSG instruction initiation to a single
master node whose transmission can be received by every other node.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
103
Chapter 6
Serial Communication on 1756-L6x Controllers
• If not all nodes receive the radio transmission of every other node, you
may still be able to use the DF1 radio modem driver, but only if you limit
MSG instruction initiation to the node connected to the master radio
modem whose transmissions can be received by every other radio modem
in the network.
• You can take advantage of the ControlLogix controller channel-to-channel
passthru to remotely program the other nodes via RSLinx Classic and
Logix Designer applications running on a personal computer connected to
a local ControlLogix controller via DH-485, DH+, or Ethernet network.
DF1 Radio Modem Protocol Parameters
Use this table as a reference when setting the parameters for the use of the DF1
Radio Modem Protocol.
Table 25 - DF1 Radio Protocol Parameters
Parameter
Description
Station Address
Specifies the node address of the controller on the serial network. Select a number 1…254 decimal, inclusive.
To optimize network performance, assign node addresses in sequential order. Initiators, such as personal computers, should be assigned the
lowest address numbers to minimize the time required to initialize the network.
Error Detection
Click one of the radio buttons to specify the error detection scheme used for all messages.
• BCC - the processor sends and accepts messages that end with a BCC byte.
• CRC - the processor sends and accepts messages with a 2 byte CRC.
Enable Store and Forward
Check ’Enable Store and Forward’ if you want to enable the store and forward functionality. When enabled, the destination address of any
received message is compared to the Store and Forward tag table. If there is a match, the message is then forwarded (re-broadcasted) out the
port.
From the Store and Forward Tag pull-down menu, choose an integer (INT[16]) tag.
Each bit represents a station address. If this controller reads a message destined for a station that has its bit set in this table, it forwards the
message.
DF1 Slave Protocol
With the DF1 slave protocol, a controller uses DF1 half-duplex protocol. One
node is designated as the master and it controls who has access to the link. All the
other nodes are slave stations and must wait for permission from the master
before transmitting.
Make these considerations when using the DF1 Slave protocol:
• If multiple slave stations are used on the network, link slave stations by
using modems or line drivers to the master.
• If you are using a single slave station on the network, you do not need a
modem to connect the slave station to the master.
• Control parameters can be configured without handshaking.
• 2...255 nodes can be connected to a single link.
104
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Serial Communication on 1756-L6x Controllers
DH-485 Protocol
Chapter 6
The controller can send and receive messages to and from other controllers on a
DH-485 network. The DH-485 connection supports remote programming and
monitoring via the Logix Designer application. However, excessive traffic over a
DH-485 connection can adversely affect overall controller performance and lead
to timeouts and decreased performance of the configuration.
You can also use a 1756-DH485 module to connect the ControlLogix chassis to a
DH-485 network with multiple controllers. For more information, see the
ControlLogix DH-485 Communication Module User Manual, publication
1756-UM532.
IMPORTANT
Use Logix5000 controllers on DH-485 networks only when you want to add
controllers to an existing DH-485 network.
For new applications with Logix5000 controllers, we recommend that you
use networks in the NetLinx open architecture.
The DH-485 protocol uses RS-485 half-duplex as its physical interface. RS-485
is a definition of electrical characteristics, not a protocol. You can configure the
RS-232 port of the ControlLogix controller to act as a DH-485 interface.
To connect the controller to the DH-485 network, you must use these
components:
• A 1761-NET-AIC converter (two controllers can be connected to one
converter)
• An RS-232 cable (catalog number 1756-CP3 or 1747-CP3) for each
controller to connect to the converter
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
105
Chapter 6
Serial Communication on 1756-L6x Controllers
Figure 20 - DH-485 Network Communication Overview
Computer with Studio 5000 environment
ControlLogix Controller
ControlLogix Controller
1756-DH485 Module
1756-ENBT Module
AIC+ Link Coupler
AIC+ Link Coupler
EXTERNAL
TE
EXTERNAL
TE
DH-485 Network
AIC+ Link Coupler
AIC Link Coupler
T
TERM
A
AIC Link Coupler
MicroLogix
AIC Link Coupler
PanelView Display
SLC™ 5/03 Controller
SLC 5/03 Controller
IMPORTANT
106
A DH-485 network consists of multiple cable segments. Limit the total length
of all the segments to 1219 m (4000 ft).
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Serial Communication on 1756-L6x Controllers
ASCII Protocol
Chapter 6
When you configure the serial port for User mode and the ASCII protocol, you
can use it to do the following:
• Read ASCII characters from a weigh scale module or bar code reader.
• Send and receive messages from an ASCII-triggered device, such as a
MessageView™ terminal.
After you configure the controller for use with the ASCII protocol, program the
controller using the ASCII instructions. Reference the Logix5000 Controllers
General Instruction Reference Manual, publication 1756-RM003, for
information about the ASCII instructions.
Configure the 1756-L6x
Controller for Serial
Communication
Complete these steps to configure your 1756-L6x controller for serial
communication after creating a controller project in the Logix Designer
application.
1. Open the Controller Properties and click the Serial Port tab.
2. From the Mode pull-down menu, choose the mode that corresponds to
your intended protocol.
Use this table as a reference.
For this protocol
Choose this mode
DF1 Master
System
DF1 Point to Point
DF1 Radio Modem
DF1 Slave
DH-485
ASCII
User
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
107
Chapter 6
Serial Communication on 1756-L6x Controllers
3. Specify the remaining properties in the Serial Port tab according to your
communication preferences.
4. If you are using the System mode protocols, click the System Protocol tab
and specify the protocol parameters.
a. From the Protocol pull-down, choose the protocol you need.
b. Specify the parameters for the protocol.
108
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Serial Communication on 1756-L6x Controllers
Chapter 6
5. If you are using the User mode protocol (ASCII), click the User Protocol
tab and specify the ASCII parameters.
After you have configured the controller for ASCII protocol
communication, reference the Logix5000 Controllers General Instruction
Reference Manual, publication 1756-RM003, for the available ASCII
instructions.
Broadcast Messages over
a Serial Port
You can broadcast messages over a serial port connection from a master controller
to all of its slave controllers by using several communication protocols. These
protocols include the following:
• DF1 Master
• DF1 Radio Modem
• DF1 Slave
Broadcasting over a serial port is achieved by using the ‘message’ tag. Because
messages are sent to receiving controllers, only the ‘write’ type messages can be
used for broadcasting.
The broadcast feature can be set up by using ladder logic or structured text. The
broadcast feature can also be set by modifying the path value of a message tag in
the tag editor.
To configure and program the controller to broadcast messages via the serial port,
complete these procedures:
• Configure Controller Serial Port Properties on page 110
• Program the Message Instruction on page 111
For these procedure examples, ladder logic programming is used.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
109
Chapter 6
Serial Communication on 1756-L6x Controllers
Configure Controller Serial Port Properties
First, set the System Protocol by following these steps.
1. In the Controller Organizer, right-click the controller and choose
Properties.
2. On the Controller Properties dialog box, from the System Protocol tab,
choose the settings for the controller, then click OK.
110
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Serial Communication on 1756-L6x Controllers
Chapter 6
Use this table when specifying settings for the protocols listed.
Field
DF-1 Master Protocol
DF-1 Slave Protocol
DF-1 Radio Modem Protocol
Station Address
Controller station address number
Controller station address number
Controller station address number
Transmit Retries
3
3
N/A
ACK Timeout
50
N/A
N/A
Slave Poll Timeout
N/A
3000
N/A
Reply Message Wait
5
N/A
N/A
Polling Mode
Message: polls the slave by using the Message
instruction
Slave: initiates messages for slave-to-slave
broadcast
Standard: schedules polling for the slave
N/A
N/A
EOT Suppression
N/A
Disable
N/A
Error Detection
BCC
BCC
BCC
Duplicate Detection
Enabled
Enabled
N/A
Enable Store and Forward
N/A
N/A
Choose enable if you want to use the store
and forward tag.
The last bit of the INT[16] Enable Store and
Forward array must be ’enabled.’ For
example, say you create an INT[16] tag
named EnableSandF. Then
EnableSandF[15].15 must be set to 1 for
broadcast to work on radio modem.
Program the Message Instruction
Add and configure the Message instruction according to the protocol you are
using. For more information about specifying the configuration details, see the
Logix5000 Controllers General Instruction Reference Manual, publication
1756-RM003.
IMPORTANT
Modbus Support
When using structured text, broadcast over a serial port is set by typing
MSG(aMsg) and right-clicking an MSG to display the Message Configuration
dialog box.
To use ControlLogix controllers with the Modbus protocol, establish a serial port
connection and execute a specific ladder-logic routine.
Two controller projects specific to the Modbus network are available as sample
programs within the Logix Designer application:
• ModbusMaster.ACD
• ModbusSlave.ACD
For information about using these sample programs, see the Using Logix5000
Controllers as Masters or Slaves on Modbus Application Solution, publication
CIG-AP129.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
111
Chapter 6
Serial Communication on 1756-L6x Controllers
Notes:
112
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Chapter
7
Manage Controller Communication
Connection Overview
Topic
Page
Connection Overview
113
Produce and Consume (interlock) Data
114
Send and Receive Messages
116
Calculate Connection Use
117
A Logix5000 system uses a connection to establish a communication link
between two devices. The types of connections include the following:
• Controller-to-local I/O modules or local communication modules
• Controller-to-remote I/O or remote communication modules
• Controller-to-remote I/O (rack-optimized) modules
• Produced and consumed tags
• Messages
• Controller access via the Logix Designer application
• Controller access via RSLinx Classic or RSLinx Enterprise applications for
HMI or other applications
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
113
Chapter 7
Manage Controller Communication
Produce and Consume
(interlock) Data
ControlLogix controllers let you produce (transmit) and consume (receive)
system-shared tags.
Figure 21 - Illustration of Produced and Consumed Tags
Controller_1
Controller_2
Produced Tag
Consumed Tag
Controller_3
Consumed Tag
Controller_4
Consumed Tag
The system-shared tags are explained in this table.
Table 26 - Produced and Consumed Tag Definitions
Tag
Definition
Produced tag
A tag that a controller makes available for use by other controllers. Multiple controllers
can simultaneously consume (receive) the data. A produced tag sends its data to one or
more consumed tags (consumers) without using logic.
Consumed tag
A tag that receives the data of a produced tag. The data type of the consumed tag must
match the data type (including any array dimensions) of the produced tag. The RPI of
the consumed tag determines the period at which the data updates.
For two controllers to share produced or consumed tags, both must be attached
to the same network. You cannot bridge produced and consumed tags over two
networks.
Produced and consumed tags use connections of both the controller and the
communication modules being used. For a ControlNet network, produced and
consumed tags use scheduled connections.
Connection Requirements of a Produced or Consumed Tag
Produced and consumed tags each require connections. As you increase the
number of controllers that can consume a produced tag, you also reduce the
number of connections the controller has available for other operations, like
communication and I/O.
IMPORTANT
114
If a consumed-tag connection fails, all of the other tags being consumed from
that remote controller stop receiving new data.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Manage Controller Communication
Chapter 7
Each produced or consumed tag uses the number of connections listed in this
table. Adding status information to a produced/consumed tag does not impact
the number of connections used.
Table 27 - Produced and Consumed Tag Connections
This Type of Tag
Uses This Many Connections
Of This Module
Produced tag
number_of_configuredconsumers + 1
Controller
Consumed tag
1
Produced or consumed tag
1
EXAMPLE
Communication
Calculations of connections for produced or consumed tags:
• A ControlLogix controller producing 4 tags for 1 controller uses 8
connections.
Each tag uses 2 connections (1 consumer + 1 = 2).
2 connections per tag x 4 tags = 8 connections.
• Consuming 4 tags from a controller uses 4 connections (1 connection per
tag x 4 tags = 4 connections).
The number of available connections limits the number of tags that can be
produced or consumed. If the controller uses all of its connections for I/O and
communication devices, no connections are left for produced and consumed tags.
Table 28 - ControlLogix Modules and Available Connections
Module Type
Cat. No.
Available Connections
Controller
1756-L7x
500
1756-L6x
250
•
•
•
•
256
EtherNet/IP
ControlNet
1756-EN2F
1756-EN2T
1756-EN2TXT
1756-EN2TR
• 1756-ENBT
• 1756-EWEB
128
• 1756-CN2
• 1756-CN2R
• 1756-CN2RXT
128
• 1756-CNB
• 1756-CNBR
64
For more information about produced/consumed tags, see the Logix5000
Controllers Produced and Consumed Tags Programming Manual, publication
1756-PM011.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
115
Chapter 7
Manage Controller Communication
Send and Receive Messages
Messages transfer data to other devices, such as other controllers or operator
interfaces. The MSG instruction is a ladder logic output instruction that
asynchronously reads or writes a block of data to or from another module over
the backplane or a network. The size of the instruction depends on the data types
and message command programmed by the user.
Messages use connection resources to send or receive data. Messages can leave the
connection open (cache) or closed when the message is done transmitting.
Each message uses one connection out of the controller, regardless of how many
devices are in the message path. To conserve connections, configure one message
to read from or write to multiple devices.
Table 29 - Message Types
Message Type
Communication
Method
Connected Message
Message Can Be
Cached
CIP data table read or write
N/A
Configurable
Yes
PLC-2®, PLC-3®, PLC-5®, or SLC
(all types)
CIP
No
No
CIP with Source ID
No
No
DH+
Yes
Yes
CIP generic
N/A
Optional (1)
Yes(2)
Block-transfer read or write
N/A
Yes
Yes
(1) You can connect CIP generic messages. However, for most applications we recommend you leave CIP generic messages
unconnected.
(2) Consider caching only if the target module requires a connection.
For more information about using messages, see these publications:
• Logix5000 Controllers Messages, publication 1756-PM012
• Logix5000 Controllers General Instructions, publication 1756-RM003
Determine Whether to Cache Message Connections
When you configure a MSG instruction, you can choose whether to cache the
connection. Use this table to determine if you should cache connections.
Table 30 - Options for Caching Connections
If the message executes
Then
Repeatedly
Cache the connection.
This keeps the connection open and optimizes execution time. Opening a
connection each time the message executes increases execution time.
Infrequently
Do not cache the connection.
This closes the connection upon completion of the message, which frees up that
connection for other uses.
TIP
116
Cached connections transfer data faster than uncached connections.The
controller only supports 32 cached messages.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Manage Controller Communication
Chapter 7
The total connection requirements of a ControlLogix system include both local
and remote connections.
Calculate Connection Use
Local Connections
Local connections refer to connections used to communicate between modules
housed in the same ControlLogix chassis (that is, the local modules). Use this
table to calculate the number of local connections based on the configuration of
your local chassis.
Table 31 - Local Chassis Connections
Local Connection To
Device Quantity
Connections per
Device
Local I/O module (always a direct connection)
1
1756-M16SE, 1756-M08SE, or 1756-M02AE servo module
3
• 1756-CN2, 1756-CN2R, 1756-CN2RXT ControlNet communication module
• 1756-CNB, 1756-CNBR ControlNet communication module
0
• 1756-EN2F, 1756-EN2T, 1756-EN2TXT, or 1756-EN2TR EtherNet/IP communication module
• 1756-ENBT EtherNet/IP communication module
0
1756-EWEB EtherNet/IP web server module
0
1756-DNB DeviceNet communication module
2
1756-RIO remote I/O communication module (Connection count depends on module configuration
and could be as many as 10 per module.)
1
1756-DHRIO DH+/universal remote I/O communication module
Each adapter associated with the module
1
1
1756-DH485 DH-485 communication module
1
Total Connections
Total
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
117
Chapter 7
Manage Controller Communication
Remote Connections
Use remote connections when the communication module is in a chassis that is
remote from the controller. The number of connections a communication
module supports determines how many remote connections the controller can
access through that module.
Table 32 - Remote Connections
Remote Connection Type
Device Quantity
Connections per
Device
Remote ControlNet communication module
I/O configured as direct connection (none)
I/O configured as rack-optimized connection
0
1
Remote I/O module over a ControlNet network (direct connection)
1
Remote EtherNet/IP communication module
I/O configured as direct connection (none)
I/O configured as rack-optimized connection
0
1
Remote I/O module over a EtherNet/IP network (direct connection)
1
Remote device over a DeviceNet network
(accounted for in rack-optimized connection for local 1756-DNB)
0
DeviceNet module in a remote chassis
2
Other remote communication adapter
1
Produced tag
Each consumer
1
1
Consumed tag
1
Message (see Table 29 for message types)
Connected
Unconnected
1
0
Block-transfer message
1
Total
118
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Total Connections
Manage Controller Communication
Chapter 7
Connections Example
In this example system, the 1756 ControlLogix controller does the following:
• Controls local digital I/O modules in the same chassis
• Controls remote I/O devices on a DeviceNet network
• Sends and receives messages to and from a CompactLogix controller on an
EtherNet/IP network
• Produces one tag that the 1794 FlexLogix controller consumes
• Is programmed via the Logix Designer application
RediSTATION™
Operator Interface
1769-ADN Adapter with Compact I/O™ Modules
Series 9000™
Photoeye
DeviceNet Network
ControlLogix Controller with
1756-ENBT and 1756-DNB
Modules
1769-L35E CompactLogix
with 1769-SDN Module
EtherNet/IP Network
FlexLogix Controller with 1788-DNBO Daughtercard
Workstation
The ControlLogix controller in this example uses these connections.
Table 33 - Connections Example Calculation
Connection Type
Device Quantity
Connections per
Device
Total Connections
Controller to local I/O modules
4
1
4
Controller to 1756-ENBT module
1
0
0
Controller to 1756-DNB module
1
2
2
Controller to Logix Designer application
1
1
1
Message to CompactLogix controller
2
1
2
Produced tag
Consumed by FlexLogix controller
1
1
1
1
1
1
Total 11
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
119
Chapter 7
Manage Controller Communication
Notes:
120
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Chapter
8
I/O Modules
Selecting ControlLogix
I/O Modules
Topic
Page
Selecting ControlLogix I/O Modules
121
Local I/O Modules
122
Remote I/O Modules
124
Distributed I/O
128
Reconfigure an I/O Module
131
Reconfigure an I/O Module
131
Determine When Data Is Updated
139
Rockwell Automation offers several ControlLogix I/O modules for use in
ControlLogix systems. When you select your I/O modules, remember the
following:
• A wide variety of digital, analog, and specialty I/O modules are available
from Rockwell Automation. Some features of these I/O modules include
the following:
– Field-side diagnostics
– Electronic fusing
– Individually-isolated inputs/outputs
• Removable terminal blocks (RTBs) or 1492 wiring systems are required
for use with I/O modules.
• 1492 PanelConnect™ modules and cables can be used to connect input
modules to sensors.
For more information about ControlLogix I/O module features, specifications,
and wiring options, see the ControlLogix Selection Guide,
publication 1756-SG001.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
121
Chapter 8
I/O Modules
Local I/O Modules
The ControlLogix chassis you choose affects how many local I/O modules you
can use. Several ControlLogix chassis sizes are available to suit your configuration
requirements. You can fill the slots of your chassis with any combination of
controllers, communication modules, and I/O modules.
This table lists the available ControlLogix chassis and the number of slots
available with each.
Table 34 - ControlLogix and ControlLogix- Chassis and Slots
Chassis
Slots
1756-A4
4
1756-A4LXT
1756-A5XT
5
1756-A7
7
1756-A7LXT
1756-A7XT
1756-A10
10
1756-A13
13
1756-A17
17
If you have empty slots in your chassis, use the 1756-N2 or 1756-N2XT slot-filler
module.
122
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
I/O Modules
Chapter 8
Add Local I/O to the I/O Configuration
If you are adding local I/O, add the I/O module to the backplane with the
controller. To add an I/O module to the local chassis, complete these steps.
1. Right-click the backplane and choose New Module.
2. Select the I/O module you want to add and click OK.
3. Specify the configuration properties according to the module and network
configuration you are using.
For more information about the module configuration properties, see the
user manual for the I/O module you are adding.
For this type of module
See this user manual
Analog I/O
ControlLogix Analog I/O Modules User Manual, publication
1756-UM009
Configurable flowmeter
ControlLogix Configurable Flowmeter Module User Manual,
publication 1756-UM010
Digital I/O
ControlLogix Digital I/O Modules User Manual, publication
1756-UM058
HART analog I/O
ControlLogix HART Analog I/O Modules User Manual, publication
1756-UM533
High-speed analog I/O
ControlLogix High-speed Analog I/O Module User Manual,
publication 1756-UM005
High-speed counter
ControlLogix High-speed Counter Module User Manual, publication
1756-UM007
Low-speed counter
ControlLogix Low-speed Counter Module User Manual, publication
1756-UM0536
Programmable limit switch
ControlLogix Programmable Limit Switch Module User Manual,
publication 1756-UM002
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
123
Chapter 8
I/O Modules
Remote I/O Modules
Remote I/O refers to I/O that is not located in the local chassis and is connected
to the controller via a communication network.
The ControlLogix controller supports the use of remote I/O via these networks:
• EtherNet/IP
• ControlNet
• DeviceNet
• Universal remote I/O
For more information about the network configurations that can be used to
connect remote I/O, see Communication Networks on page 83.
Figure 22 - ControlLogix Controller and Remote I/O Example
ControlLogix Controller Chassis
ControlLogix Remote I/O
ControlNet Network
124
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
I/O Modules
Chapter 8
Add Remote I/O to the I/O Configuration
If you are adding remote I/O, add the I/O modules to the backplane of the
remote communication module that is connected to the controller. To add a
remote I/O to the I/O Configuration folder in the Logix Designer application,
complete these steps.
1. Add a communication module to the backplane that contains the
controller.
2. Specify the communication module properties according to your network
configuration.
For more information about the communication module and network
properties, see the user manual for the network you are using:
– ControlNet Modules in Logix5000 Control Systems User Manual,
publication CNET-UM001
– DeviceNet Modules in Logix5000 Control Systems User Manual,
publication DNET-UM004
– EtherNet/IP Modules in Logix5000 Control Systems User Manual,
publication ENET-UM001
3. Right-click the communication network and choose New Module.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
125
Chapter 8
I/O Modules
4. Add the remote communication module you are using.
5. Specify the chassis and connection properties according to your network
configuration.
6. Right-click the backplane of the newly-added communication module and
choose New Module.
7. Select the I/O module you want to add and click OK.
126
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
I/O Modules
Chapter 8
8. Specify the Module Properties according to your module and application.
For more information about the module configuration properties, see the
user manual for the I/O module you are adding.
For this type of module
See this user manual
Analog I/O
ControlLogix Analog I/O Modules User Manual, publication
1756-UM009
Configurable flowmeter
ControlLogix Configurable Flowmeter Module User Manual,
publication 1756-UM010
Digital I/O
ControlLogix Digital I/O Modules User Manual, publication
1756-UM058
HART analog I/O
ControlLogix HART Analog I/O Modules User Manual, publication
1756-UM533
High speed analog I/O
ControlLogix High Speed Analog I/O Module User Manual,
publication 1756-UM005
High speed counter
ControlLogix High Speed Counter Module User Manual, publication
1756-UM007
Low-speed counter
ControlLogix Low-speed Counter Module User Manual, publication
1756-UM0536
Programmable limit switch
ControlLogix Programmable Limit Switch Module User Manual,
publication 1756-UM002
9. Add any other I/O modules you are using in the remote chassis.
10. Complete steps 1…9 until your remote I/O network and I/O modules are
configured.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
127
Chapter 8
I/O Modules
Distributed I/O refers to I/O that is located remote from the controller and is
not designed for use with a specific controller. Examples of distributed I/O that
can be used with Logix5000 controllers include the following:
• 1794 FLEX I/O modules
• 1734 POINT I/O modules
• 1797 FLEX Ex™ I/O modules
• 1738 ArmorPOINT® I/O modules
• 1732 ArmorBlock® I/O modules
• 1753 GuardPLC™ Safety I/O modules
• 1790 CompactBlock™ LDX I/O modules
• 1791 CompactBlock Guard Safety I/O modules
• 1791 CompactBlock I/O modules
• 1732DS ArmorBlock Guard Safety I/O modules
• 1792 ArmorBlock® MaXum™ I/O modules
Distributed I/O
Distributed I/O is connected to the ControlLogix controller via a
communication network. The ControlLogix controller supports the use of
distributed I/O via these networks:
• EtherNet/IP
• ControlNet
• DeviceNet
Figure 23 - ControlLogix System with Distributed I/O Example
ControlLogix Controller Chassis
EtherNet/IP™
Logix5575
FORCE
RUN FORCE SD
OK
EtherNet/IP
POINT I/O
FLEX I/O
COMM
A
STATUS
REDUNDANT MEDIA
ADAPTER
1794-ACNR15
B
ControlNet
128
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
I/O Modules
Chapter 8
Add Distributed I/O to the I/O Configuration
If you are adding distributed I/O, add the I/O modules to the communication
adapter of the I/O. To add distributed I/O to the I/O Configuration folder for
the ControlLogix controller, complete these steps.
1. Add a communication module to the backplane that contains the
controller.
2. Specify the communication module properties according to your network
configuration.
For more information about the communication module and network
properties, see the user manual for the network you are using:
– ControlNet Modules in Logix5000 Control Systems User Manual,
publication CNET-UM001
– DeviceNet Modules in Logix5000 Control Systems User Manual,
publication DNET-UM004
– EtherNet/IP Modules in Logix5000 Control Systems User Manual,
publication ENET-UM001
3. Right-click the communication network and choose New Module.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
129
Chapter 8
I/O Modules
4. Add the communication adapter for the distributed I/O platform you are
using.
5. Specify the module and connection properties according to your network
configuration.
6. Right-click the bus of the newly-added communication adapter and
choose New Module.
7. Select the I/O module you want to add and click OK.
8. Specify the Module Properties according to your module and application.
For more information about the module configuration properties, see the
user manual for the I/O module you are adding.
9. Add any other I/O modules you are using in this bus.
10. Complete steps 1…9 until your remote I/O network and distributed I/O
modules are configured.
130
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
I/O Modules
Reconfigure an I/O Module
Chapter 8
If an I/O module supports reconfiguration, you can reconfigure the module via
the following:
• The Module Properties dialog box in the I/O Configuration folder
• A MSG instruction in program logic.
IMPORTANT
Use care when changing the configuration of an I/O module. You could
inadvertently cause the I/O module to operate incorrectly.
Use a MSG instruction of type Module Reconfigure to send new configuration
information to an I/O module. During the reconfiguration, consider the
following:
• Input modules continue to send input data to the controller
• Output modules continue to control their output devices
Reconfigure an I/O Module via the Module Properties
To reconfigure an I/O module using the module properties, right-click the
module in the I/O Configuration tree and choose Properties. Then, edit the
properties you need to change and click Apply.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
131
Chapter 8
I/O Modules
Reconfigure an I/O Module via a Message Instruction
To reconfigure an I/O module via a message instruction, use this procedure.
1. Set the required member of the configuration tag of the module to the new
value.
2. Send a Module Reconfigure message to the module.
EXAMPLE
Reconfigure an I/O module
When reconfigure[5] is on, the MOV instruction sets the high alarm to 60 for the local module in slot 4. The Module
Reconfigure message then sends the new alarm value to the module. The ONS instruction prevents the rung from sending
multiple messages to the module while the reconfigure[5] is on.
For more information about using Message instructions, see the Logix5000
Controllers General Instruction Reference Manual, publication 1756-RM003.
Add to the I/O Configuration
While Online
With RSLogix 5000 software, version 15.02.00 or later, and Logix Designer
application, version 21.00.00 or later, you can add I/O and other devices to the
controller configuration while you are online and in Run mode.
The specific modules and devices you can add while online depends on the
version of the software you are using. Later versions have more modules and
devices that can be added while online.
You can add these modules and devices to the local or remote chassis via the
unscheduled portion of a ControlNet network or via an EtherNet/IP network.
For more information about adding to the I/O Configuration while online, see
the Runtime/On-line Addition of ControlLogix (1756) I/O over ControlNet
and EtherNet/IP White Paper, publication LOGIX-WP006.
132
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
I/O Modules
Chapter 8
Modules and Devices that Can be Added While Online
These modules and devices can be added to the ControlLogix controller I/O
configuration while online as of RSLogix 5000 software, version 19.01.00 or later
and Logix Designer application, version 21.00.00 or later.
ControlLogix Modules that Can be Added While Online
•
•
•
•
•
•
1756 controllers
1756 ControlNet modules
1756 DeviceNet bridge modules
1756 EtherNet/IP modules
1756 I/O and speciality modules
1756-DHRIO
IMPORTANT
These ControlLogix modules cannot be added while online:
• Motion modules (1756-MO2AE, 1756-HYD02, 1756-MO2AS, 1756-MO3SE,
1756-MO8SE, 1756-MO8SEG, 1756-M16SE)
• 1756-RIO
• 1756-SYNCH
• 1756-ENBF
• 1756-56AMXN
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
133
Chapter 8
I/O Modules
PowerFlex Drives that Can be Added While Online
134
• PowerFlex® 4 Class Multi-E
• PowerFlex® 7000-Q
• PowerFlex 700S-200V-Q
• PowerFlex 400-E
• PowerFlex® 700-200V-C
• PowerFlex 700S-400V-C
• PowerFlex 400P-E
• PowerFlex 700-200V-E
• PowerFlex 700S-400V-E
• PowerFlex® 40-E
• PowerFlex 700-200V-Q
• PowerFlex 700S-400V-Q
• PowerFlex® 40P-E
• PowerFlex 700-400V-C
• PowerFlex 700S-600V-C
• PowerFlex 4-E
• PowerFlex 700-400V-E
• PowerFlex 700S-600V-E
• PowerFlex 4M-E
• PowerFlex 700-400V-Q
• PowerFlex 700S-600V-Q
• PowerFlex 70® EC-C
• PowerFlex 700-600V-C
• PowerFlex 70-C
• PowerFlex 70 EC-C
• PowerFlex 700-600V-E
• PowerFlex 70-E
• PowerFlex 70 EC-E
• PowerFlex 700-600V-Q
• PowerFlex 70-E
• PowerFlex 70 EC-E
• PowerFlex 700AFE-C
• PowerFlex 70-Q
• PowerFlex 70 EC-Q
• PowerFlex 700AFE-E
• PowerFlex 70-Q
• PowerFlex 70 EC-Q
• PowerFlex 700AFE-Q
• PowerFlex® 753-CNETC
• PowerFlex 700 AC-C
• PowerFlex® 700H-C
• PowerFlex 753-NET-C
• PowerFlex 700 AC-E
• PowerFlex 700H-E
• PowerFlex 753-NET-E
• PowerFlex 700 AC-Q
• PowerFlex 700H-Q
• PowerFlex 753-NET-Q
• PowerFlex 700 Vector-200V-C
• PowerFlex 700S 2-200V
• PowerFlex® 755-CNETC
• PowerFlex 700 Vector-200V-E
• PowerFlex 700S 2-400V
• PowerFlex 755-EENET
• PowerFlex 700 Vector-200V-Q
• PowerFlex 700S 2-600V
• PowerFlex 755-NET-C
• PowerFlex 700 Vector-400V-C
• PowerFlex 700S 2P-200V-C
• PowerFlex 755-NET-E
• PowerFlex 700 Vector-400V-E
• PowerFlex 700S 2P-200V-E
• PowerFlex 755-NET-Q
• PowerFlex 700 Vector-400V-Q
• PowerFlex 700S 2P-200V-Q
• PowerFlex DC-200V-C
• PowerFlex 700 Vector-600V-C
• PowerFlex 700S 2P-400V-C
• PowerFlex DC-200V-E
• PowerFlex 700 Vector-600V-E
• PowerFlex 700S 2P-400V-E
• PowerFlex DC-200V-Q
• PowerFlex 700 Vector-600V-Q
• PowerFlex 700S 2P-400V-Q
• PowerFlex DC-400V-C
• PowerFlex 7000 2-C
• PowerFlex 700S 2P-600V-C
• PowerFlex DC-400V-E
• PowerFlex 7000 2-E
• PowerFlex 700S 2P-600V-E
• PowerFlex DC-400V-Q
• PowerFlex 7000 2-Q
• PowerFlex 700S 2P-600V-Q
• PowerFlex DC-600V-C
• PowerFlex 7000-C
• PowerFlex 700S-200V-C
• PowerFlex DC-600V-E
• PowerFlex 7000-E
• PowerFlex 700S-200V-E
• PowerFlex DC-600V-Q
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
I/O Modules
Chapter 8
Other Devices that Can be Added While Online
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
1305-BAXXA drives
1336E-IMPACT™Drive-EN1 drive
1336F-PLUS™IIDrive-EN1drive
1336R-REGENBrake-EN1 brake
1336S-PLUSDriveLG-EN1 drive
1336S-PLUSDriveSM-EN1 drive
1336T-FORCE™DriveCNA-EN1 drive
1336T-FORCEDrivePLC-EN1 drive
1336T-FORCEDriveStd-EN1 drive
1397DigitalDCDrive-EN1 drive
150 SMC™ FLEX motor controller
150-SMC™DialogPlus-EN1 motor controller
1757-FFLDC ControlNet Foundation Fieldbus device
2364F RGU-EN1 bus supply
48MS-SN1PF1-M2 Multivision Sensor
5XRF RFID interface device
Online Additions - ControlNet Considerations
ControlNet considerations that must be made depend upon the ControlLogix
ControlNet modules you are using.
1756-CNB and 1756-CNBR Modules
When you add I/O to the ControlNet network via the 1756-CNB or
1756-CNBR modules while online, these considerations must be made:
• Digital I/O modules can be added as rack-optimized connections if the
parent module is already configured with rack-optimized connections.
TIP
While you can add a new digital I/O module to an existing rack-optimized
connection, you cannot add rack-optimized connections while online.
• Digital I/O modules can also be added as direct connections.
• Analog I/O modules can be added only as direct connections.
• Disable the Change of State (COS) feature on digital input modules
because it can cause inputs to be sent more quickly than the RPI.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
135
Chapter 8
I/O Modules
• If you plan to add large amounts of I/O to the ControlNet network,
dedicate one ControlNet network for I/O. For the dedicated
ControlNet network, verify that there is little or none of the following:
– HMI traffic
– MSG traffic
– Programming workstations
• Requested Packet Intervals (RPIs) faster than 25 ms for unscheduled
modules can overload the 1756-CNB or 1756-CNBR communication
module. To avoid the overload, make these considerations:
– Use a NUT of 10 ms or more.
– Keep the SMAX and UMAX values as small as possible.
• If the module has a Real Time Sample (RTS), it should be disabled or set
to a rate that is greater than the RPI.
• You can add I/O modules until you reach these limits:
– 75% of CPU utilization of the 1756-CNB or 1756-CNBR
communication module.
– Plan for a CPU-use increase of 1...4% of the 1756-CNB or
1756-CNBR module for each I/O module you add, depending on the
RPI.
– 48 connections on the 1756-CNB or 1756-CNBR communication
module.
– Less than 400,000 unscheduled bytes per second are displayed in
RSNetWorx for ControlNet software after the network has been
scheduled.
1756-CN2, 1756-CN2R, 1756-CN2RXT Modules
The use of 1756-CN2/B, 1756-CN2R/B, and 1756-CN2RXT modules
provides increased capacity for adding I/O while online compared to 1756-CNB
or 1756-CNBR modules. With this increased capacity, you can easily add I/O
and increase ControlNet connections used with significantly less impact on the
overall system.
136
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
I/O Modules
Chapter 8
This table demonstrates the performance factors of the 1756-CN2/B,
1756-CN2R/B, and 1756-CN2RXT modules when adding I/O online.
Table 35 - 1756-CN2, 1756-CN2R, and 1756-CN2RXT Performance Example(1)
No. of Direct
Analog I/O
Connections
Added Online
RPI = 2 ms
CPU %(2)
RPI = 4 ms
Avg.
API(3)
CPU %
Avg.
API(3)
CPU %
Avg.
API(3)
CPU %
0
1.50%
N/A
1.50%
N/A
1.50%
N/A
1
4.80%
2.0
3.70%
4.0
2.50%
2
7.00%
2.0
5.00%
4.0
3
9.00%
2.0
6.10%
4
11.20%
2.2
5
11.50%
6
(2)
RPI = 10 ms
(2)
RPI = 20 ms
(2)
RPI = 50 ms
(2)
RPI = 100 ms
Avg.
API(3)
CPU %
Avg.
API(3)
CPU %(2)
Avg.
API(3)
1.50%
N/A
1.50%
N/A
1.50%
N/A
10.0
2.30%
20.0
1.90%
50.0
1.70%
100.0
3.30%
10.0
2.70%
20.0
2.10%
50.0
1.90%
100.0
4.0
3.80%
10.0
3.00%
20.0
2.20%
50.0
2.00%
100.0
7.40%
4.0
4.40%
10.0
3.40%
20.0
2.40%
50.0
2.10%
100.0
3.3
8.70%
4.0
5.00%
10.0
3.70%
20.0
2.60%
50.0
2.20%
100.0
12.80%
3.3
9.70%
4.0
5.50%
10.0
4.00%
20.0
2.70%
50.0
2.30%
100.0
7
13.80%
3.4
10.80%
4.0
5.90%
10.0
4.30%
20.0
2.90%
50.0
2.30%
100.0
8
15.10%
3.4
11.90%
4.0
6.40%
10.0
4.50%
20.0
3.00%
50.0
2.50%
100.0
9
15.00%
3.3
13.20%
4.0
7.00%
10.0
4.80%
20.0
3.20%
50.0
2.60%
100.0
10
15.60%
3.6
13.20%
4.0
7.50%
10.0
5.20%
20.0
3.40%
50.0
2.70%
100.0
11
16.40%
3.8
13.50%
4.0
8.20%
10.0
5.50%
20.0
3.50%
50.0
2.70%
100.0
12
17.00%
3.8
14.00%
4.0
8.80%
10.0
5.80%
20.0
3.70%
50.0
2.80%
100.0
13
17.80%
3.7
14.60%
4.0
9.30%
10.0
6.10%
20.0
3.80%
50.0
2.90%
100.0
14
18.50%
3.7
15.20%
4.0
9.90%
10.0
6.40%
20.0
4.00%
50.0
2.90%
100.0
15
19.40%
3.9
15.80%
4.0
10.50%
10.0
6.70%
20.0
4.10%
50.0
3.00%
100.0
(1) Example assumes that adequate unscheduled bandwidth is available.
(2) Approximate use of the module’s central-processing unit (CPU) in percent.
(3) The average Actual Packet Interval with 2000 samples (shown in ms).
Because of the increased performance provided by the 1756-CN2, 1756-CN2R,
and 1756-CN2RXT modules, many of the considerations that must be made
with the 1756-CNB and 1756-CNBR modules are not applicable. With the
1756-CN2, 1756-CN2R, and 1756-CN2RXT modules, you can add I/O while
online as long as you use reasonable RPI settings and remain within the CPU
limitations of the ControlNet module.
When adding to the I/O Configuration with 1756-CN2, 1756-CN2R, and
1756-CN2RXT modules, make these considerations:
• Digital I/O modules can be added as rack-optimized connections if the
parent module is already configured with rack-optimized connections.
TIP
While you can add a new digital I/O module to an existing rackoptimized connection, you cannot add rack-optimized connections
while online.
• Digital I/O modules can also be added as direct connections.
• Analog I/O modules can be added only as direct connections.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
137
Chapter 8
I/O Modules
• Disable the Change of State (COS) feature on digital input modules
because it can cause inputs to be sent more quickly than the RPI.
• If you plan to add large amounts of I/O to the ControlNet network,
dedicate one ControlNet network for I/O. For the dedicated ControlNet
network, verify that there is little or none of the following:
– HMI traffic
– MSG traffic
– Programming workstations
• If the module has a Real Time Sample (RTS), it should be disabled or set
to a rate that is greater than the RPI.
• You can add I/O modules until you reach these limits:
– 80% of CPU utilization of the 1756-CN2, 1756-CN2R, or
1756-CN2RXT communication module.
– Less than 400,000 unscheduled bytes per second are displayed in
RSNetWorx for ControlNet software after the network has been
scheduled.
Online Additions—EtherNet/IP Considerations
When you add I/O modules to the EtherNet/IP network, make these
considerations:
• The EtherNet/IP I/O modules you add can be added as these connection
types:
– Rack-optimized connections, including new and existing connections
– Direct connections
• You can add I/O modules until you reach the limits of the communication
module’s connections.
For EtherNet/IP module limitations, see the EtherNet/IP Modules in
Logix5000 Control Systems User Manual, publication ENET-UM001.
138
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
I/O Modules
Chapter 8
ControlLogix controllers update date asynchronously with the execution of logic.
Use this flowchart to determine when a producer, such as a controller, input
module, or bridge module, will send data.
Determine When Data Is
Updated
Figure 24 - Data Update Flowchart
Output
Input or Output Data?
Input
Analog or Digital?
Digital
Analog or Digital?
Analog
Digital
Remote or Local?
Analog
Remote
COS for Any Point on the Module?
Local
No
No
RTS ≤ RPI?
Yes
Yes
Data is sent to the backplane at the
RTS.
Data is sent to the backplane at the RTS
and RPI.
Data is sent to the backplane at the RPI and at
the change of a specified point.
Data is sent to the backplane at the RPI.
• Over a ControlNet network, remote data is sent at the actual packet interval.
• Over an EtherNet/IP network, remote data is usually sent close to the RPI.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Data is sent to the backplane at the RPI and at
the end of every task.
139
Chapter 8
I/O Modules
Notes:
140
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Chapter
9
Develop Motion Applications
Motion Control Options
Topic
Page
Motion Control Options
141
Motion Overview
142
Obtain Axis Information
142
Program Motion Control
143
Additional Resources
144
ControlLogix controllers support digital, analog, and Integrated Motion
interfaces:
• Digital drive interfaces include EtherNet/IP connected drives and
SERCOS interface connected drives.
• Analog drives support ±10V analog output and can interface with a variety
of feedback device types including quadrature encoder, SSI, and LVDT
feedback.
• Integrated Motion supports Kinetix 350, Kinetix 5500, Kinetix 6500, and
PowerFlex 755 drives.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
141
Chapter 9
Develop Motion Applications
The configuration process varies, depending on your application and your drive
selection. The following are general steps to configure a motion application.
Motion Overview
1. Create a controller project.
2. Select the type of drive.
Drive Type
Requirements
CIP Sync
• EtherNet/IP communication module
• Digital drive with an EtherNet/IP connection
SERCOS interface
Select a SERCOS interface module:
• 1756-M03SE
• 1756-M08SE
• 1756-M16SE
Analog interface
Select an analog interface module:
• 1756-HYD02
• 1756-M02AE
• 1756-M02AS
3. Create axis tags as needed.
4. Configure the drive.
5. Create axes as needed.
You can obtain axis information by using these methods:
• Double-click the axis to open the Axis Properties dialog box.
• Use a Get System Value (GSV) or Set System Value (SSV) instruction to
read or change the configuration at run-time.
• View the Quick View pane to see the state and faults of an axis.
• Use an axis tag for status and faults.
Obtain Axis Information
Figure 25 - Obtain Axis Information
Axis Properties Dialog Box
SSV (or GSV) Instruction
Axis Tag
Quick View Pane
142
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Develop Motion Applications
Program Motion Control
Chapter 9
The controller provides a set of motion control instructions for your axes:
• The controller uses these instructions just like the rest of the Logix5000
instructions.
• Each motion instruction works on one or more axes.
• Each motion instruction needs a motion control tag. The tag uses a
MOTION_INSTRUCTION data type and stores the instruction’s
information status.
• You can program using motion control instructions in these programming
languages:
– Ladder Diagram (LD)
– Structured Text (ST)
– Sequential Function Chart (SFC)
Figure 26 - Motion Control Instruction
Motion Control Tag
ATTENTION: Use the tag for the motion control operand of motion
instruction only once. Unintended operation of the control variables
may happen if you reuse of the same motion control tag in other
instructions.
Example
In this example, a simple ladder diagram that homes, jogs, and moves an axis.
If Initialize_Pushbutton = on and the axis = off (My_Axis_X.ServoActionStatus = off) then
the MSO instruction turns on the axis.
If Home_Pushbutton = on and the axis hasn’t been homed (My_Axis_X.AxisHomedStatus = off) then
the MAH instruction homes the axis.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
143
Chapter 9
Develop Motion Applications
If Jog_Pushbutton = on and the axis = on (My_Axis_X.ServoActionStatus = on) then
the MAJ instruction jogs the axis forward at 8 units/second.
If Jog_Pushbutton = off then
the MAS instruction stops the axis at 100 units/.second2.
Make sure that Change Decel is Yes. Otherwise, the axis decelerates at its maximum speed.
If Move_Command = on and the axis = on (My_Axis_X.ServoActionStatus = on) then
the MAM instruction moves the axis. The axis moves to the position of 10 units at 1 unit/second.
Additional Resources
144
Refer to these publications for additional information about motion control.
Resource
Description
SERCOS Motion Configuration and Startup User Manual,
publication MOTION-UM001
Details how to configure a SERCOS motion application
system.
Motion Coordinated Systems User Manual, publication
MOTION-UM002
Details how to create and configure a coordinated motion
application system.
CIP Motion Configuration and Startup User Manual,
publication MOTION-UM003
Details how to configure a CIP motion application system.
Logix5000 Controllers Motion Instructions Reference
Manual, publication MOTION-RM002
Provides programmers with details about the motion
instructions that are available for a Logix5000 controller.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Chapter
10
Develop Applications
Elements of a
Control Application
Topic
Page
Elements of a Control Application
145
Tasks
146
Programs
149
Routines
152
Tags
153
Programming Languages
156
Add-On Instructions
157
Monitoring Controller Status
158
Monitoring I/O Connections
159
System Overhead Time Slice
162
A control application is comprised of several elements that require planning for
efficient application execution. Application elements include the following:
• Tasks
• Programs
• Routines
• Tags
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
145
Chapter 10
Develop Applications
Figure 27 - Elements of a Control Program
Controller Fault Handler
Task 32
Task 1
Configuration
Status
Watchdog
Program 100
Program 1
Program
(local) Tags
Main Routine
Fault Routine
Other
Routines
Controller (global) Tags
Tasks
146
I/O Data
System-shared Data
A Logix5000 controller lets you use multiple tasks to schedule and prioritize the
execution of your programs based on specific criteria. This multitasking allocates
the controller’s processing time among the different operations in your
application:
• The controller executes only one task at a time.
• One task can interrupt another’s execution and take control.
• In any given task, multiple programs may be used. However, only one
program executes at a time.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Develop Applications
Chapter 10
Figure 28 - Task within a Control Application
Controller Fault Handler
Task 32
Task 1
Configuration
Status
Watchdog
Program 100
Program 1
Program
(local) Tags
Main Routine
Fault Routine
Other
Routines
Controller (global) Tags
I/O Data
System-shared Data
Figure 29 - Tasks
Main Task
(continuous)
Task 2
(periodic)
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
147
Chapter 10
Develop Applications
A task provides scheduling and priority information for a set of one or more
programs. Configure tasks as continuous, periodic, or event using the Task
Properties dialog box.
Figure 30 - Configuring the Task Type
This table explains the types of tasks you can configure.
Table 36 - Task Types and Execution Frequency
Task Type
Task Execution
Description
Continuous
All of the time
The continuous task runs in the background. Any CPU time not allocated to other operations (such as motion,
communication, and other tasks) is used to execute the programs in the continuous task.
• The continuous task runs constantly. When the continuous task completes a full scan, it restarts immediately.
• A project does not require a continuous task. If used, there can be only one continuous task.
Periodic
• At a set interval, such as every
100 ms
• Multiple times within the scan
of your other logic
A periodic task performs a function at a specific interval.
• Whenever the time for the periodic task expires, the task interrupts any lower priority tasks, executes once, and then
returns control to where the previous task left off.
• You can configure the time period from 0.1...2,000,000.00 ms. The default is 10 ms. It is also controller and configuration
dependent.
• The performance of a periodic task depends on the type of Logix5000 controller and on the logic in the task.
Event
Immediately when an event occurs
An event task performs a function only when a specific event (trigger) occurs. The trigger for the event task can be the
following:
• Module input data change of state
• A consumed tag trigger
• An EVENT instruction
• An axis trigger
• A motion event trigger
The ControlLogix controller supports up to 32 tasks, only one of which can be
continuous.
A task can have up to 100 separate programs, each with its own executable
routines and program-scoped tags. Once a task is triggered (activated), all the
programs assigned to the task execute in the order in which they are grouped.
Programs can appear only once in the Controller Organizer and cannot be shared
by multiple tasks.
148
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Develop Applications
Chapter 10
Task Priority
Each task in the controller has a priority level. The operating system uses the
priority level to determine which task to execute when multiple tasks are
triggered. A higher priority task will interrupt any lower priority task. The
continuous task has the lowest priority and is always interrupted by a periodic or
event task.
You can configure periodic and event tasks to execute from the lowest priority of
15 up to the highest priority of 1. Configure the task priority using the Task
Properties dialog box.
Figure 31 - Configure Task Priority
Programs
The controller operating system is a preemptive multitasking system that is IEC
1131-3 compliant. This system provides the following:
• Programs to group data and logic
• Routines to encapsulate executable code written in a single programming
language
Each program contains the following:
• Program tags
• A main executable routine
• Other routines
• An optional fault routine
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
149
Chapter 10
Develop Applications
Figure 32 - Program within a Control Application
Controller Fault Handler
Task 32
Task 1
Configuration
Status
Watchdog
Program 100
Program 1
Main Routine
Program (local)
Tags
Fault Routine
Other Routines
Controller (global) Tags
I/O Data
Figure 33 - Programs
150
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
System-shared Data
Develop Applications
Chapter 10
Scheduled and Unscheduled Programs
The scheduled programs within a task execute to completion from first to last.
Programs that aren’t attached to any task show up as unscheduled programs.
Unscheduled programs within a task are downloaded to the controller with the
entire project. The controller verifies unscheduled programs but does not execute
them.
You must schedule a program within a task before the controller can scan the
program. To schedule an unscheduled program, use the Program/Phase Schedule
tab of the Task Properties dialog box.
Figure 34 - Scheduling an Unscheduled Program
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
151
Chapter 10
Develop Applications
Routines
A routine is a set of logic instructions in a single programming language, such as
Ladder Diagram (ladder logic). Routines provide the executable code for the
project in a controller. A routine is similar to a program file or subroutine in a
PLC or SLC processor.
Each program has a main routine. This is the first routine to execute when the
controller triggers the associated task and calls the associated program. Use logic,
such as the Jump to Subroutine ( JSR) instruction, to call other routines.
You can also specify an optional program fault routine. The controller executes
this routine if it encounters an instruction-execution fault within any of the
routines in the associated program.
Figure 35 - Routines in a Control Application
Controller Fault Handler
Task 32
Task 1
Configuration
Status
Watchdog
Program 100
Program 1
Program (local)
Tags
Main Routine
Fault Routine
Other Routines
Controller (global) Tags
I/O Data
Figure 36 - Routines
Routine
Routine
152
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
System-shared Data
Develop Applications
Chapter 10
With a Logix5000 controller, you use a tag (alphanumeric name) to address data
(variables). In Logix5000 controllers, there is no fixed, numeric format. The tag
name identifies the data and lets you do the following:
• Organize your data to mirror your machinery.
• Document your application as you develop it.
Tags
This example shows data tags created within the scope of the Main Program of
the controller.
Figure 37 - Tags Example
Controller Organizer —Main Program Tags
Program Tags Window—Main Program Tags
Analog I/O Device
Integer Value
Storage Bit
Counter
Timer
Digital I/O Device
There are several guidelines for creating and configuring program tags for
optimal task and program execution. For more information, see the Logix5000
Controllers and I/O Tag Data Programming Manual, publication 1756-PM004.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
153
Chapter 10
Develop Applications
Extended Properties
The Extended Properties feature lets you define additional information, such as
limits, engineering units, or state identifiers, for various components within your
controller project.
Component
Extended Properties
Tag
In the tag editor, add extended properties to a tag.
User-defined data type
In the data type editor, add extended properties to data types.
Add-On Instructions
In the properties associated with the Add-On Instruction definition, add
extended properties to Add-On Instructions.
Pass-through behavior is the ability to assign extended properties at a higher level
of a structure or Add-On Instruction and have that extended property
automatically available for all members. Pass-through behavior is available for
descriptions, state identifiers, and engineering units and is user configurable.
Configure pass-through behavior on the Project tab of the Controller Properties
dialog box. If you choose not to show pass-through properties, then only
extended properties that have been configured for a given component are
displayed.
Pass-through behavior is not available for limits.When an instance of a tag is
created, if limits are associated with the data type, the instance is copied.
You need to know which tags have limits associated with them as there is no
indication in the tag browser that extended properties are defined for a tag. If,
however, you try to use extended properties that have not been defined for a tag,
the editors show a visual indication and the routine does not verify.
Access Extended Properties in Logic
You can access limits defined on tags by using the .@Min and .@Max syntax:
• You cannot write to extended properties values in logic.
• To use extended tag properties in an Add-On Instruction, you must pass
them in as input operands to the Add-On Instruction.
• Aliases to tags that have extended properties cannot access the extended
properties in logic.
• Limits can be configured for input and output parameters in Add-On
Instructions. However, limits cannot be defined on an InOut parameter of
an Add-On Instruction.
• Limits cannot be accessed inside Add-On Instruction logic. Limits are for
use by HMI applications only.
154
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Develop Applications
Chapter 10
If an array tag is using indirect addressing to access limits in logic, the following
conditions apply:
• If the array tag has limits configured, the extended properties are applied to
any array element that does not explicitly have that particular extended
property configured. For example, if the array tag MyArray has Max
configured to 100, then any element of the array that does not have Max
configured inherits the value of 100 when being used in logic. However, it
will not be visible to you that the value inherited from MyArray is
configured in the tag properties.
• At least one array element must a limit configured for indirectly referenced
array logic to verify. For example, if MyArray[x].@Max is being used in
logic, at least one array element of MyArray[] must have Max extended
property configured if Max is not configured by MyArray.
• Under the following circumstances a data type default value is used:
– Array is accessed programmatically with indirect reference.
– Array tag does not have the extended property configured.
– A member of an array does not have the extended property configured.
For example, for an array of SINT type, when max limit is called in logic
for a member, the value 127 will be used.
If an array element is directly accessed, the element has to have the extended
property defined. If not verification will fail.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
155
Chapter 10
Develop Applications
Programming Languages
The ControlLogix controller supports these programming languages, both
online and offline.
Table 37 - ControlLogix Controller Programming Languages
Language
Is best used in programs with
Relay ladder
Continuous or parallel execution of multiple operations (not sequenced)
Boolean or bit-based operations
Complex logical operations
Message and communication processing
Machine interlocking
Operations that service or maintenance personnel may have to interpret in
order to troubleshoot the machine or process
Function block diagram
Continuous process and drive control
Loop control
Calculations in circuit flow
Sequential function chart (SFC)
High-level management of multiple operations
Repetitive sequence of operations
Batch process
Motion control using structured text
State machine operations
Structured text
Complex mathematical operations
Specialized array or table loop processing
ASCII string handling or protocol processing
For information about programming in these languages, see the Logix5000
Controllers Common Procedures Programming Manual, publication
1756-PM001.
156
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Develop Applications
Chapter 10
With RSLogix 5000 software, version 16.03.00 or later, and Logix Designer
application, version 21.00.00 or later, you can design and configure sets of
commonly used instructions to increase project consistency. Similar to the
built-in instructions contained in Logix5000 controllers, these instructions you
create are called Add-On Instructions. Add-On Instructions reuse common
control algorithms. With them, you can do the following:
• Ease maintenance by animating logic for a single instance.
• Protect intellectual property with locking instructions.
• Reduce documentation development time.
Add-On Instructions
You can use Add-On Instructions across multiple projects. You can define your
instructions, obtain them from somebody else, or copy them from another
project.
This table explains some of the capabilities and advantages of use Add-On
Instructions.
Table 38 - Add-On Instruction Capabilities
Capability
Description
Save Time
With Add-On Instructions, you can combine your most commonly used logic into sets of reusable instructions. You save time when you
create instructions for your projects and then share them with others. Add-On Instructions increase project consistency because
commonly used algorithms all work in the same manner, regardless of who implements the project.
Use Standard Editors
You create Add-On Instructions by using one of three programming editors:
• Relay Ladder
• Function Block Diagram
• Structured Text
Export Add-On Instructions
You can export Add-On Instructions to other projects as well as copy and paste them from one project to another. Give each instruction
a unique name so that you don’t accidentally overwrite another instruction of the same name.
Use Context Views
Context views let you visualize an instruction’s logic for a specific instant, simplifying online troubleshooting of your Add-On
Instructions. Each instruction contains a revision, a change history, and an auto-generated help page.
Create Custom Help
When you create an instruction, you enter information for the description fields. This information then becomes custom Help.
Apply Source Protection
As the creator of Add-On Instructions, you can limit users of your instructions to read-only access, or you can bar access to the internal
logic or local parameters used by the instructions. This source protection lets you prevent unwanted changes to your instructions and
protects your intellectual property.
Once defined in a project, Add-On Instructions behave similarly to the built-in
instructions in Logix5000 controllers. They appear on the instruction tool bar
for easy access along with internal instructions.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
157
Chapter 10
Develop Applications
Figure 38 - Add-On Instructions
Controller Organizer
Instruction Toolbar
For more information about using Add-On Instructions, see the
Add-On Instructions Programming Manual, publication 1756-PM010.
Monitoring Controller Status
The ControlLogix controller uses Get System Value (GSV) and Set System Value
(SSV) instructions to get and set (change) controller data. The controller stores
system data in objects. There is no status file, as in the PLC-5 processor.
The GSV instruction retrieves the specified information and places it in the
destination. The SSV instruction sets the specified attribute with data from the
source. Both instructions are available from the Input/Output tab of the
Instruction toolbar.
Figure 39 - GSV and SSV Instructions for Monitoring and Setting Attributes
158
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Develop Applications
Chapter 10
When you add a GSV/SSV instruction to the program, the valid object classes,
object names, and attribute names for the instruction are shown. For the GSV
instruction, you can get values for all the available attributes. For the SSV
instruction, only the attributes you can set are shown.
Some object types appear repeatedly, so you may have to specify the object name.
For example, there can be several tasks in your application. Each task has its own
Task object that you access by the task name.
There are several objects and attributes that you can use the GSV and SSV
instructions to monitor and set the system. For more information about GSV
instructions, SSV instructions, objects, and attributes see the Logix5000
Controllers General Instructions Reference Manual, publication 1756-RM003.
Monitoring I/O Connections
If communication with a device in the controller’s I/O configuration does not
occur in an application-specific period of time, the communication times out and
the controller produces warnings.
The minimum timeout period that, once expired without communication, causes
a timeout is 100 ms. The timeout period may be greater, depending on the
application’s RPI. For example, if your application uses the default RPI = 20 ms,
the timeout period is 160 ms.
For more information on how to determine the time for your application, search
the Rockwell Automation Knowledgebase for answer ID 38535. The document
is available at http://www.rockwellautomation.com/knowledgebase.
When a timeout does occur, the controller produces these warnings;
• An I/O fault status code is indicated on the status display of the 1756-L7x
controller.
• The I/O status indicator on the front of the 1756-L6x controller flashes
green.
• A ! shows over the I/O configuration folder and over the devices that
have timed out.
• A module fault code is produced, which you can access via the following:
– The Module Properties dialog box
– A GSV instruction
For more information about I/O faults, see the Major, Minor, and I/O Faults
Programming Manual, publication 1756-PM014.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
159
Chapter 10
Develop Applications
Determine if I/O Communication has Timed Out
This example can be used with either the 1756-L7x or 1756-L6x controllers:
• The GSV instruction gets the status of the I/O status indicator (via the
LEDStatus attribute of the Module object) and stores it in the
IO_LED tag.
• IO_LED is a DINT tag that stores the status of the I/O status indicator or
status display on the front of the controller.
• If IO_LED equals 2, than at least one I/O connection has been lost and
the Fault_Alert is set.
Figure 40 - GSV Used to Identify I/O Timeout
For more information about attributes available with the Module object, see the
Logix5000 Controllers General Instructions Reference Manual, publication
1756-RM003.
Determine if I/O Communication to a Specific I/O Module has
Timed Out
If communication times out with a device (module) in the I/O configuration of
the controller, the controller produces a fault code and fault information for the
module. You can use GSV instructions to get fault code and information via the
FaultCode and FaultInfo attributes of the Module object.
For more information about attributes available with the Module object, see the
Logix5000 Controllers General Instructions Reference Manual, publication
1756-RM003.
160
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Develop Applications
Chapter 10
Interrupt the Execution of Logic and Execute the Fault Handler
Depending on your application, you might want an I/O connection error to
cause the Controller Fault Handler to execute. To do so, set the module property
that causes a major fault to result from an I/O connection error. The major fault
then causes the execution of the Controller Fault Handler.
First, develop a routine in the Controller Fault Handler that can respond to I/O
connection faults. Then, in the Module Properties dialog box of the I/O module
or parent communication module, check Major Fault On Controller If
Connection Fails While in Run Mode.
Figure 41 - I/O Connection Fault Causes Major Fault
I/O Module Properties
Parent Communication Module Properties
For more information about programming the Controller Fault Handler, see the
Major, Minor, and I/O Faults Programming Manual, publication 1756-PM014.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
161
Chapter 10
Develop Applications
System Overhead Time Slice
The controller communicates with other devices at either a specified rate
(scheduled) or when there is processing time available to service the
communication.
The system overhead time slice specifies the percentage of time a controller
devotes to service communication. If you have a continuous task, the system
overhead time slice entered on the Advanced tab of the Controller Properties
dialog box specifies the continuous task/service communication ratio. However,
if there is no continuous task, the overhead time slice has no effect.
The table shows the ratio between the continuous task and service
communication at various system overhead time slices for RSLogix 5000, version
16.03.00 or later, and Logix Designer version 21.00.00 or later.
Ratio between Continuous Task and Service Communication
Time Slice
Continuous Task Duration
Service Communication Duration
10%
9 ms
1 ms
20%
4 ms
1 ms
25%
3 ms
1 ms
33%
2 ms
1 ms
50%
1 ms
1 ms
66%
1 ms
2 ms
75%
1 ms
3 ms
80%
1 ms
4 ms
90%
1 ms
9 ms
As shown in the table, if the system overhead time slice is less than or equal to
50%, the duration will stay fixed at 1 ms. The same applies for 66% and higher,
except there are multiple 1 ms intervals. For example, at 66% there are two 1 ms
intervals of consecutive time and at 90% there are nine 1 ms intervals of
consecutive time.
162
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Develop Applications
Chapter 10
Configure the System Overhead Time Slice
To configure the system overhead time slice, perform this procedure.
1. In the Controller Organizer, right-click the controller and choose
Properties.
The Controller Properties dialog box appears.
2. Click the Advanced tab.
3. Enter a numeric value in the System Overhead Time Slice box.
4. Use either Run Continuous Task (default) or Reserve for System Tasks.
• The Run Continue Task radio button is used when there is no
communication or background tasks to process; controller immediately
returns to the continuous task.
• The Reserve for System Task radio button allocates the entire 1 ms of
the system overhead time slice whether the controller has
communication or background tasks to perform before returning back
to the continuous task. This lets you simulate a communication load on
the controller during design and programming before HMIs, controller
to controller messaging, and so forth, are set up.
5. Click OK.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
163
Chapter 10
Develop Applications
Sample Controller Projects
Logix Designer application includes sample projects that you can copy and
modify to fit your application. To access the sample projects, either choose Open
Sample Project in the Quick Start menu or navigate to File > Open > Projects >
Samples.
Figure 42 - Opening Sample Projects
164
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Chapter
11
Using the PhaseManager Tool
PhaseManager Overview
Topic
Page
PhaseManager Overview
165
Minimum System Requirements
167
State Model Overview
167
PhaseManager Tool versus Other State Models
170
Equipment Phase Instructions
170
The PhaseManager™ tool lets you add equipment phases to your controller. An
equipment phase helps you lay out your code in sections that are easier to write,
find, follow, and change.
Table 39 - PhaseManager Terminology
Term
Description
Equipment phase
• As with a program, an equipment phase is run in a task and is given a set of routines and
tags.
• Unlike a program, an equipment phase runs by a state model and lets you do one activity.
State model
• A state model divides the operating cycle of your equipment into a series of states. Each
state is an instance in the operation of the equipment, the actions, or conditions of the
equipment at a given time.
• The state model of an equipment phase resembles that of the S88 and PackML state
models.
State machine
An equipment phase includes an embedded state machine that does the following:
• Calls the routine associated with an active state
• Manages the transitions between states with minimal coding
• Makes sure that the equipment goes from state to state along an allowable path
PHASE tag
When you add an equipment phase, the application creates a tag for the equipment phase.
The tag uses the PHASE data type.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
165
Chapter 11
Using the PhaseManager Tool
Figure 43 - PhaseManager Overview
A PHASE tag gives you the status of an equipment phase.
Controller
Controller Tags
Tasks
MainTask
An equipment phase directs one activity of your equipment.
A state model divides the activity into a series of states.
Add Water Phase
Mix Phase
Running State Routine
How to add water
Drain Phase
Space Parts Phase
MainProgram
Equipment phase instructions control the transitions between states and handle faults.
PSC
POVR
PCLF
PRNP
PATT
PCMD
PFL
PXRQ
PPD
PDET
My Equipment Program
Other code controls the specific actions of your equipment.
Water Feed
166
Conveyor
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Enable Axes
Using the PhaseManager Tool
Chapter 11
To develop PhaseManager programs, you need the following:
• A ControlLogix controller at firmware revision 16 or later
• A communication path to the controller
• RSLogix 5000 software, version 16.03.00 or later or Logix Designer
application, version 21.00.00 or later
Minimum System
Requirements
To enable PhaseManager support, you need either the Full or Professional edition
of the software, or the software with PhaseManager software (catalog number
9324-RLDPMENE).
A state model defines what your equipment does under different conditions, and
how the states relate to each other. Each state can be described as either an Acting
state or Waiting state.
State Model Overview
Table 40 - States in PhaseManager Software
State
Description
Acting
Does something or several things for a certain time or until certain conditions are met. An acting
state runs once or repeatedly.
Waiting
Shows that certain conditions are met and the equipment is waiting for the signal to go to the
next state.
Figure 44 - PhaseManager State Transitions
Start
Idle
Your equipment can go from any state in the box
to the stopping or aborting state.
Hold
Running
Holding
Held
Hold
Restart
Resetting
Acting
Restarting
Stop
Abort
Acting states represent the things
your equipment does at a given time.
Abort
Reset
Complete
Stopping
Aborting
Waiting
Reset
Stopped
Aborted
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Waiting states represent the
condition of your equipment
when it is between acting states.
167
Chapter 11
Using the PhaseManager Tool
With a state model, you define the behavior of your equipment during Acting
states.
Table 41 - Acting States in the PhaseManager State Model
State
Question to Ask
Resetting
How does the equipment get ready to run?
Running
What does the equipment do to make product?
Holding
How does the equipment temporarily stop making product without making scrap?
Restarting
How does the equipment resume production after holding?
Stopping
What happens during a normal shutdown?
Aborting
How does the equipment shut down if a fault or failure occurs?
How Equipment Changes States
The state model’s arrows show the states through which your equipment
progresses:
• Each arrow is called a transition.
• A state model lets the equipment make only certain transitions. This
restriction standardizes the equipment’s behavior so that other equipment
using the same model will behave the same way.
Figure 45 - PhaseManager Transition Commands
= Transition
Command
Done — No command. Use PSC instruction instead.
Start
Idle
Your equipment can go from any state in the box
when it receives a stop or abort commend.
Hold
Running
Holding
Held
Hold
Restart
Resetting
Restarting
Stop
Abort
Reset
Complete
Reset
168
Abort
Stopping
Aborting
Stopped
Aborted
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Using the PhaseManager Tool
Chapter 11
Table 42 - PhaseManager Transitions
Type of Transition
Description
Command
A command tells the equipment to do something. For example, the operator pushes the start
button to begin production and the stop button to halt production.
The PhaseManager tool uses these commands:
Reset
Stop
Restart
Start
Hold
Abort
Done
Equipment goes to a waiting state when it is finished with what it is doing. You do not give the
equipment a command. Instead, you set up your code to signal when the phase state is
finished.
Fault
A fault tells you that something out of the ordinary has happened. You set up your code to look
for faults and take action if it finds any. If you want to shut down your equipment as quickly as
possible when it detects a fault, set up your code to look for that fault and give the abort
command if it finds it.
Manually Change States
You can manually change an equipment phase. To manually change a
PhaseManager state, perform this procedure.
1. Open the Equipment Phase Monitor.
2. Take ownership of the equipment phase by clicking Owners and clicking
Yes.
3. Click the command that initiates the state you need (for example, Start or
Reset).
4. After you have finished manually changing the state, click Owners to
release your ownership.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
169
Chapter 11
Using the PhaseManager Tool
PhaseManager Tool versus
Other State Models
This table compares PhaseManager state models to other state models.
Table 43 - PhaseManager Tool and Other State Models
PhaseManager Tool
Equipment Phase
Instructions
S88
PackML
Resetting…Idle
Idle
Starting…Ready
Running…Complete
Running…Complete
Producing
Subroutines or breakpoints
Pausing…Paused
Standby
Holding…Held
Holding…Held
Holding…Held
Restarting
Restarting
None
Stopping…Stopped
Stopping…Stopped
Stopping…Stopped
Aborting…Aborted
Aborting…Aborted
Aborting…Aborted
The controller supports several equipment-phase relay ladder and structured text
instructions.
Table 44 - Instructions for Use with PhaseManager Tool
Instruction
Instruction Function
PSC
Signal a phase that the state routine is complete and to proceed to the next state.
PCMD
Change the state or substate of a phase.
PFL
Signal a failure for a phase.
PCLF
Clear the failure code of a phase.
PXRQ
Initiate communication with RSBizWare™ Batch software.
PRNP
Clear the NewInputParameters bit of a phase.
PPD
Set up breakpoints within the logic of a phase.
PATT
Take ownership of a phase to either of the following:
• Prevent another program or RSBizWare Batch software from commanding a phase.
• Make sure another program or RSBizWare Batch software does not already own a phase.
PDET
Relinquish ownership of a phase.
POVR
Override a command.
For more information about instructions for use with equipment phases, see the
PhaseManager User Manual, publication LOGIX-UM001.
170
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Chapter
12
Redundant Systems
ControlLogix Redundancy
Overview
Topic
Page
ControlLogix Redundancy Overview
171
System Requirements
173
System Considerations
174
Build a Redundant System
175
ControlNet Considerations in Redundant Systems
176
EtherNet/IP Considerations in Redundant Systems
176
Redundancy and Scan Time
177
Redundancy provides more system availability by switching control to a
secondary controller chassis if a fault occurs in the primary controller chassis.
The redundant system switches control from the primary to the secondary when
these faults occur:
• Power loss to primary chassis
• Hardware or firmware failure of any module in the primary chassis
• A major fault in the user program on the primary controller
• Loss of communication between the primary chassis and remote
ControlNet or EtherNet/IP modules
• Disconnection of an Ethernet patch cable from an EtherNet/IP
communication module in the primary chassis
• Removal or insertion of any module in the primary chassis
• A user command that causes a switchover
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
171
Chapter 12
Redundant Systems
Figure 46 - ControlLogix Enhanced Redundancy System
Workstation
HMI
Ethernet
Ethernet
Switch
Switch
Primary
Secondary
EtherNet/IP
Diagnostic
Analog Input
ST
AT
ST
AT
Diagnostic
Analog Output
ST
AT
ST
AT
Relay Module
ControlNet
Diagnostic
Analog Output
DC OUTPUT
ST
AT
ST
AT
Digital Ouput
ControlNet Scanner
Diagnostic
Digital Input
ST
AT
ST
AT
Analog Input
DC INPUT
ControlNet
I/O Connected via ControlNet Network
1756-CN2R
1756-RM
1756-L6x
1756-CN2R
1756-EN2T
1756-RM
ControlNet
PRI COM OK
PRI COM OK
1756-L6x
EtherNet/IP
Redundancy Module
Logix5563
ControlNet
1756-EN2T
Redundancy Module
ControlNet Scanner
Logix5563
Relay Ouput
Redundant Chassis
I/O can be connected via an EtherNet/IP network beginning with Enhanced Redundancy System revision 19.50.
Redundancy requires no additional programming and is transparent to any
devices connected over an EtherNet/IP or ControlNet network.
Redundancy modules placed in each redundant chassis maintain the
communication between the redundant chassis.
Depending on how you organize your project, outputs may or may not
experience a change in state (bump) during a switchover:
• During the switchover, outputs that are controlled by the highest priority
task will experience a bumpless switchover. For example, outputs will not
revert to a previous state.
• Outputs in lower priority tasks may experience a change of state.
For detailed information about ControlLogix redundancy systems, see the
ControlLogix Enhanced Redundancy User Manual, publication 1756-UM535.
172
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Redundant Systems
System Requirements
Chapter 12
Most redundant systems must use at least these system components. For some
applications, the ControlNet and EtherNet/IP modules are optional.
Table 45 - System Requirements
Quantity
Item
Notes
2
ControlLogix chassis
Both chassis must be the same size.
2
ControlLogix power supply
Must be the same in each chassis.
2
ControlLogix controller
• Use either 1756-L6x or 1756-L7x controllers.
• Use the same catalog number, series, firmware revision, and
memory size controllers in each chassis.
• Same slot placement.
2
ControlLogix ControlNet
communication module
• Use 1756-CN2/B, 1756-CN2R/B, or 1756-CN2RXT modules.
• ControlNet modules in both chassis must be identical in firmware
revision, in series, slot placement, and module type.
2
ControlLogix EtherNet/IP
communication modules
• Use the 1756-EN2T, 1756-EN2TXT, or 1756-EN2TR modules.
• Must be identical in firmware revision, slot placement and module
type.
2
Redundancy module
• Use 1756-RM or 1756-RMXT modules.
• Redundancy modules in both chassis must be identical in firmware
revision and slot placement.
• For L7x high performance systems, RM modules must be RM/B and
must have the same series and firmware revision in both chassis.
1
Redundancy module cable
(fiber-optic)
• Use the 1756-RMCx cable.
• Standard lengths are available.
2
Additional ControlNet nodes
• Place all I/O in remote chassis or DIN rails.
• Add at least two nodes to each ControlNet network in addition to
the redundant chassis pair.
• For enhanced redundancy, you must have at least one
keeper-capable ControlNet device at a node address lower than the
node addresses of the ControlNet modules in the redundant chassis.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
173
Chapter 12
Redundant Systems
System Considerations
When you are configuring a redundant ControlLogix system, these
considerations specific to modules in the redundant chassis must be made.
Items in Primary and
Secondary Chassis
Consideration
ControlLogix controller
• When configured for redundancy, the secondary controller automatically receives
and buffers data.
• A redundant controller uses twice as much data memory and I/O memory space as
a nonredundant controller.
• A redundant controller has a significantly longer scan time than a nonredundant
controller.
• The ControlLogix Enhanced Redundancy User Manual, publication 1756-UM535,
provides detailed information about minimizing the scan time impact.
• You do not need a redundancy-specific version of Logix Designer software, but it
must match your Enhanced Redundancy System revision level.
Communication modules
• In an enhanced redundancy system, as many as seven communication modules can
reside in a controller chassis in any combination of EtherNet/IP modules and
ControlNet modules.
• To connect to other networks, bridge through another ControlLogix chassis outside
the redundant system.
• For best results, use a separate networks for HMI and I/O communication.
I/O modules
• All I/O is remote from the redundant controller chassis.
• Beginning with Enhanced Redundancy System revision 19.50, EtherNet/IP
networks in redundant systems can be used for remote I/O or produced/consumed
data.
Redundant power supplies
The 1756-PA75R and 1756-PB75R redundant power supplies provide reliable chassis
power.
Redundant ControlNet media
Redundant media provide more reliable ControlNet communication.
For complete information about designing and planning modules for use in your
redundant ControlLogix chassis, see the ControlLogix Enhanced Redundancy
User Manual, publication 1756-UM535.
174
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Redundant Systems
Chapter 12
Enhanced versus Standard Redundancy
While the enhanced and standard redundancy systems operate in a similar
manner, there are some key differences between the two platforms. This table
compares the enhanced and standard redundancy system features.
Table 46 - Comparison of Enhanced Redundancy to Standard Redundancy
Feature
Enhanced
System(1)
Supports enhanced ControlLogix ControlNet and EtherNet/IP communication
modules, for example, the 1756-CN2/B or 1756-EN2T modules
Standard
System
Supports standard ControlLogix ControlNet and EtherNet/IP communication
modules, for example, the 1756-CNB/D or 1756-ENBT modules
Compatible with the single-slot 1756-RM redundancy modules
Compatible with the double-slot 1757-SRM redundancy modules
Support for all 1756-L6x and 1756-L7x ControlLogix controllers
Use of ControlLogix- system components, for example, the 1756-L63XT controller
and the 1756-CN2XT module
Availability of I/O over an EtherNet/IP network, including Redundant I/O systems
(1) Availability of some features supported in enhanced redundancy are dependent on the system revision used. For more information,
see ControlLogix Enhanced Redundancy System User Manual, publication 1756-UM535.
Build a Redundant System
To build a typical redundant system, perform this procedure.
1. Install a ControlLogix chassis and power supply.
2. To the primary chassis, add 1756-L6x or 1756-L7x controllers.
Note that you cannot mix 1756-L6x and 1756-L7x controllers in the same
chassis.
3. Add one or more ControlNet or EtherNet/IP communication modules.
4. Add one redundancy module.
5. Set up a secondary chassis that is identical to the primary chassis.
IMPORTANT
Components in the redundant chassis pair must be identical in
module configuration.
6. Connect the redundancy modules in both chassis.
7. Add I/O modules to ControlNet or EtherNet/IP networks.
8. Add operator interfaces to ControlNet or EtherNet/IP networks.
For detailed information on designing and building an enhanced redundant
system, refer to the ControlLogix Enhanced Redundancy System User Manual,
publication 1756-UM535.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
175
Chapter 12
Redundant Systems
ControlNet Considerations
in Redundant Systems
You can have as many as seven ControlNet communication modules in a
redundant chassis.
IMPORTANT
With each ControlNet network, you must have at least two nodes external
to the redundant controller chassis to avoid timeouts on switchover.
The lowest node of each ControlNet network must be outside the
redundant controller chassis.
For information on ControlNet considerations for enhanced redundant systems,
refer to the ControlLogix Enhanced Redundancy System User Manual,
publication 1756-UM535.
EtherNet/IP Considerations
in Redundant Systems
You can have as many as seven EtherNet/IP modules in the redundant chassis.
In a redundant system, you can use EtherNet/IP for HMI communication or
inter-controller messaging. HMI can communicate directly to with the primary
controller. You no longer need RSLinx Alias Topics.
ControlLogix redundancy supports EtherNet/IP for I/O control or producing
and consuming data beginning with Enhanced Redundancy System revision
19.50, and can be used for the following:
• 1715 Redundant I/O
• Remote I/O modules
• HMI connections to the primary controller
• Producing and consuming data
For information on EtherNet/IP considerations for enhanced redundant systems,
refer to the ControlLogix Enhanced Redundancy System User Manual,
publication 1756-UM535.
IP Address Swapping
Firmware revision 13, and later, supports IP address swapping in redundant
systems. With IP address swapping, you configure the primary and secondary
EtherNet/IP modules with the same IP address. The primary EtherNet/IP
module takes the IP address; the secondary module takes that address plus one in
the last address segment.
On a switchover, the EtherNet/IP modules swap IP addresses. HMI devices
automatically continue to communicate with the new primary controller because
the IP addresses were swapped. Because of the way EtherNet/IP modules work,
during a switchover, communication between the controller and an HMI device
halts for several seconds, typically less than a minute.
176
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Redundant Systems
Redundancy and Scan Time
Chapter 12
At the end of every program, the primary controller synchronizes and crossloads
fresh data to the secondary controller. This keeps the secondary controller up-todate and ready to take over. It also increases the scan time when compared to a
nonredundant system.
The amount of time a crossload consumes depends on how much data the
primary controller has to crossload:
• The primary controller synchronizes and crossloads any tag to which an
instruction wrote a value, even the same value, since the last crossload.
• Crossloading also requires a small amount of overhead time (1 ms per
crossload) to tell the secondary controller which program the primary
controller is executing.
Redundancy firmware revision 16.53, or later, provides the ability to limit which
programs are followed by synchronization and data crossloading. In many
applications, changing this can reduce the overall impact to the task scan time by
reducing the number of times a data area is synchronized. Removing a
synchronization point results in 1 ms of overhead time saved, in addition to any
time that was used to crossload the data.
For complete details about the scan time of a redundant system, see the
ControlLogix Enhanced Redundancy System User Manual, publication
1756-UM535.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
177
Chapter 12
Redundant Systems
Notes:
178
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Chapter
13
SIL 2 Certification
Introduction to SIL
Topic
Page
Introduction to SIL
179
Programming and Debugging Tool (PADT)
179
Typical SIL2 Configurations
180
Certain catalog numbers of the ControlLogix system are type-approved and
certified for use in SIL2 applications according to these standards:
• IEC 61508
• IEC 61511
Approval requirements are based on the standards current at the time of
certification.
These requirements consist of mean time between failures (MTBF), probability
of failure, failure rates, diagnostic coverage and safe failure fractions that fulfill
SIL2 criteria. The results make the ControlLogix system suitable up to, and
including, SIL2. When the ControlLogix system is in the Maintenance or
Programming mode, the user is responsible for maintaining a safe state.
The TÜV Rheinland Group has approved the ControlLogix system for use in up
to, and including, SIL 2 safety related applications in which the de-energized
state is typically considered to be the safe state.
In addition, specific configuration and programming considerations described in
the Using ControlLogix in SIL2 Applications Safety Reference Manual,
publication 1756-RM001, must be made.
Programming and Debugging Tool (PADT)
For support in creation of programs, the Programming and Debugging Tool
(PADT) is required. The PADT for the ControlLogix system is the Logix
Designer application, per IEC 61131-3, and the Using ControlLogix in SIL2
Applications Safety Reference Manual, publication 1756-RM001.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
179
Chapter 13
SIL 2 Certification
Typical SIL2 Configurations
SIL2-certified ControlLogix systems can be used in non-redundancy or
redundancy configurations. For the purposes of documentation, the various
levels of availability that can be achieved by using various ControlLogix system
configurations are referred to as fail-safe, high-availability, or fault-tolerant.
This table lists each system configuration and the hardware that is part of the
system’s safety loop.
Table 47 - SIL2 Configurations and Hardware Summary
System Configuration
Safety Loop Hardware
Fail-safe Configuration on page 181
• Nonredundant controller
• Nonredundant communication modules
• Nonredundant remote I/O
High-availability Configuration on page 182
• Redundant controllers
• Redundant communication modules
• Nonredundant remote I/O
Fault-tolerant Configuration on page 183
•
•
•
•
IMPORTANT
180
Redundant controllers
Redundant communication modules
Redundant remote I/O
I/O termination boards
Note that the system user is responsible the tasks listed here when any of
the ControlLogix SIL2 system configurations are used:
• The setup, SIL rating, and validation of any sensors or actuators
connected to the ControlLogix control system.
• Project management and functional testing.
• Programming the application and the module configuration according
to the descriptions in the following chapters.
The SIL2 portion of the certified system excludes the development tools
and display/human machine interface (HMI) devices; these tools and
devices are not part of the safety loop.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
SIL 2 Certification
Chapter 13
Fail-safe Configuration
In a fail-safe configuration, the hardware used in the safety loop is not redundant.
Therefore, if a fault occurs anywhere in the SIL2 system, the system is
programmed to fail to safe.
The failure to safe is typically an emergency shutdown where all outputs are deenergized.
Figure 47 - Fail-safe ControlLogix Configuration
Overall Safety Loop
SIL2-certified ControlLogix Safety Loop
Controller Chassis
Sensor
Remote I/O Chassis
EN
BT
CN
BR
I/O
CN
BR
Actuator
ControlNet
I/O
EN
BT
EtherNet/IP
This figure shows a typical SIL loop that does not use redundancy. This figure
shows the following:
• Overall safety loop
• ControlLogix portion of the overall safety loop
TIP
When certain considerations are made, it possible to connect to remote I/O
via an EtherNet/IP network. To connect to remote I/O using an EtherNet/IP
network, you must make considerations similar to those required for a
SIL2-certified ControlNet network.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
181
Chapter 13
SIL 2 Certification
High-availability Configuration
In the high-availability configuration, redundant controller chassis are used to
increase the availability of the control system. The modules in the redundant
controller chassis include the redundancy modules and ControlNet modules for
redundant communication, as well as the ControlLogix controllers.
Figure 48 - Typical SIL Loop with Controller Chassis Redundancy
Studio 5000 Environment
For SIL applications, a programming
terminal is not normally connected.
HMI
For Diagnostics and Visualization
(read-only access to controllers in the safety loop)
Plant-wide Ethernet/Serial
Overall Safety Loop
SIL2-certified ControlLogix components’ portion of the overall safety loop.
Primary Chassis
Sensor
Remote I/O Chassis
EN CN CN
2T 2 2
R
M
I/O
CN
2
Actuator
ControlNet Network
Secondary Chassis
EN CN CN
2T 2 2
R
M
To other
safety-related
ControlLogix and
remote I/O
chassis
To nonsafety related systems outside the ControlLogix portion of the SIL2-certified loop.
ControlNet Network
IMPORTANT
182
The high-availability ControlLogix system is fault-tolerant only for the devices
in the primary/secondary controller chassis. The rest of the high-availability
system is not considered to be fault-tolerant.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
SIL 2 Certification
Chapter 13
Figure 48 on page 182 shows a typical SIL loop that uses redundancy, including
the following:
• The overall safety loop
• The ControlLogix portion of the overall safety loop
• How other devices (for example, HMI) connect to the loop, while
operating outside the loop
Fault-tolerant Configuration
The most recently-certified ControlLogix SIL2 configuration is the
fault-tolerant configuration. The fault-tolerant configuration of the
ControlLogix system uses fully-redundant controllers, communication modules,
and remote I/O.
Figure 49 - Fault-tolerant Configuration
SIL2-certified ControlLogix Safety Loop
Secondary Chassis
Primary Chassis
PRI
PRI
COM
DC OUTPUT
DC INTPUT
ANALOG INTPUT
DC OUTPUT
ANALOG INTPUT
DC INTPUT
DC OUTPUT
CAL
CAL
DIAGNOSTIC
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11121314 15 K
DIAGNOSTIC
OK
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11121314 15 K
OK
DIAGNOSTIC
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11121314 15 K
Digital Input
Termination Board
Field Device
DC INTPUT
ANALOG INTPUT
DC OUTPUT
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11121314 15 K
ANALOG INTPUT
CAL
CAL
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11121314 15 K
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11121314 15 K
OK
OK
DC INTPUT
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11121314 15 K
DIAGNOSTIC
DIAGNOSTIC
Analog Input
Termination
Board
OK
I/O Chassis B
I/O Chassis A
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11121314 15 K
COM
OK
DIAGNOSTIC
DIAGNOSTIC
DIAGNOSTIC
Digital Output
Termination Board
Field Device
Field Device
The fault-tolerant configuration uses safety and programming principles
described in this manual, as well as programming and hardware described in the
application technique manuals.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
183
Chapter 13
SIL 2 Certification
For more information about the ControlLogix SIL2- certified fault-tolerant
system, see the application technique manual that corresponds with your
application.
Table 48 - ControlLogix SIL2 System Configuration Manuals
184
If using
Then reference this manual
SIL2 Fault-tolerant I/O subroutines
ControlLogix SIL2 System Configuration Using RSLogix 5000
Subroutines, publication 1756-AT010
SIL2 Fault-tolerant I/O Add-On Instructions
ControlLogix SIL2 System Configuration Using RSLogix 5000
Subroutines, publication 1756-AT012
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Appendix
A
Status Indicators
1756-L7x Controller Status
Display and Indicators
Topic
Page
1756-L7x Controller Status Display and Indicators
185
1756-L7x Controller Status Display
185
1756-L7x Controller Status Indicators
193
1756-L6x Status Indicators
194
The 1756-L7x controllers have four status indicators and one four-character
scrolling status display.
Figure 50 - 1756-L7x Status Display and Indicators
Logix557x
Scrolling Status Display, see page 186
Status Indicators, see page 193
RUN FORCE SD
OK
REM PR
OG
RUN
32009-MC
1756-L7x Controller
Status Display
The 1756-L7x controller status display scrolls messages that provide information
about the controller’s firmware revision, ESM status, project status, and major
faults.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
185
Appendix A
Status Indicators
General Status Messages
The messages described in this table are typically indicated upon powerup,
powerdown, and while the controller is running to show the status of the
controller and the ESM.
Table 49 - General Status Messages
Message
Interpretation
No message is indicated
The controller is Off.
Check the OK indicator to determine if the controller is powered and determine the state of the controller.
TEST
Power-up tests are being conducted by the controller.
PASS
Power-up tests have been successfully completed.
SAVE
A project is being saved to the SD card. You can also view the SD Indicator (see page 193) for additional status information.
Allow the save to complete before:
• removing the SD card.
• disconnecting power.
LOAD
A project is being loaded from the SD card at controller powerup. You can also view the SD Indicator (see page 193) for additional status information.
Allow the load to complete before doing the following:
• Removing the SD card
• Disconnecting power
• Removing the ESM module
UPDT
A firmware upgrade is being conducted from the SD card upon powerup. You can also view the SD Indicator (see page 193) for additional status
information.
If you do not want the firmware to update upon powerup, change the controller’s Load Image property.
CHRG
The capacitor-based ESM is being charged.
1756-L7x/X
The controller catalog number and series.
Rev XX.xxx
The major and minor revision of the controller’s firmware.
No Project
No project is loaded on the controller.
To load a project, do one of the following:
• Use Logix Designer application to download the project to the controller
• Use a SD card to load a project to the controller
Project Name
The name of the project that is currently loaded on the controller.
BUSY
The I/O modules associated with the controller are not yet fully-powered.
Allow time for powerup and I/O module self-testing.
Corrupt Certificate
Received
The security certificate associated with the firmware is corrupted.
Go to http://www.rockwellautomation.com/support/ and download the firmware revision you are trying to upgrade to. Replace the firmware revision you
have previously installed with that posted on the Technical Support website.
Corrupt Image Received
The firmware file is corrupted.
Go to http://www.rockwellautomation.com/support/ and download the firmware revision you are trying to upgrade to. Replace the firmware revision you
have previously installed with that posted on the Technical Support website.
ESM Not Present
An ESM is not present and the controller cannot save the application at powerdown.
Insert a compatible ESM, and, if using a capacitor-based ESM, do not remove power until the ESM is charged.
ESM Incompatible
The ESM is incompatible with the memory size of the controller.
Replace the incompatible ESM with a compatible ESM.
ESM Hardware Failure
A failure with the ESM has occurred and the controller is incapable of saving of the program in the event of a powerdown.
Replace the ESM before removing power to the controller so the controller program is saved.
ESM Energy Low
The capacitor-based ESM does not have sufficient energy to enable the controller to save the program in the event of a powerdown.
Replace the ESM.
ESM Charging
The capacitor-based ESM is charging.
Do not remove power until charging is complete.
186
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Status Indicators
Appendix A
Table 49 - General Status Messages (continued)
Message
Interpretation
Flash in Progress
A firmware upgrade initiated via ControlFLASH or AutoFlash utilities is in progress.
Allow the firmware upgrade to complete without interruption.
Firmware Installation
Required
The controller is using boot firmware (that is revision 1.xxx) and requires a firmware upgrade.
Upgrade controller firmware.
SD Card Locked
An SD card that is locked is installed.
Fault Messages
If the controller is faulted, these messages may be indicated on the status display.
Table 50 - Fault Messages
Message
Interpretation
Major Fault TXX:CXX message
A major fault of Type XX and Code XX has been detected.
For example, if the status display indicates Major Fault T04:C42 Invalid JMP Target, then a JMP instruction is programmed to jump to an
invalid LBL instruction.
For details about major recoverable faults, see the Logix5000 Major, Minor, and I/O Fault Codes Programming Manual, publication
1756-PM014.
I/O Fault Local:X #XXXX message
An I/O fault has occurred on a module in the local chassis. The slot number and fault code are indicated along with a brief description.
For example, I/O Fault Local:3 #0107 Connection Not Found indicates that a connection to the local I/O module in slot three is not open.
Take corrective action specific to the type of fault indicated.
For details about each I/O fault code, see the Logix5000 Major, Minor, and I/O Fault Codes Programming Manual, publication 1756-PM014.
I/O Fault ModuleName #XXXX message
An I/O fault has occurred on a module in a remote chassis. The name of the faulted module is indicated with the fault code and brief
description of the fault.
For example, I/O Fault My_Module #0107 Connection Not Found indicates that a connection to the module named My_Module is not
open.
Take corrective action specific to the type of fault indicated.
For details about each I/O fault code, see the Logix5000 Major, Minor, and I/O Fault Codes Programming Manual, publication 1756-PM014.
I/O Fault ModuleParent:X #XXXX message An I/O fault has occurred on a module in a remote chassis. The module’s parent name is indicated because no module name is configured in
the I/O Configuration tree of Logix Designer application. In addition, the fault code is indicated with a brief description of the fault.
For example, I/O Fault My_CNet:3 #0107 Connection Not Found indicates that a connection to a module in slot 3 of the chassis with the
communication module named My_CNet is not open.
Take corrective action specific to the type of fault indicated.
For details about each I/O fault code, see the Logix5000 Major, Minor, and I/O Fault Codes Programming Manual, publication 1756-PM014.
X I/O Faults
I/O faults are present and X = the number of I/O faults present.
In the event of multiple I/O faults, the controller indicates the first fault reported. As each I/O fault is resolved, the number of faults
indicated decreases and the next fault reported is indicated by the I/O Fault message.
Take corrective action specific to the type of fault indicated.
For details about each I/O fault code, see the Logix5000 Major, Minor, and I/O Fault Codes Programming Manual, publication 1756-PM014.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
187
Appendix A
Status Indicators
Major Fault Messages
Major faults are indicated by Major Fault TXX:CXX message on the controller
status display. This table lists specific fault types, codes, and the associated
messages as they are shown on the status display.
For detailed descriptions and suggested recovery methods for major faults, see the
Logix5000 Major, Minor, and I/O Fault Codes Programming Manual,
publication 1756-PM014.
Table 51 - Major Fault Status Messages
188
Type
Code
Message
1
1
Run Mode Powerup
1
60
Non-recoverable
1
61
Non-recoverable – Diagnostics Saved on CF Card
1
62
Non-recoverable – Diagnostics and Program Saved on SD Card
3
16
I/O Connection Failure
3
20
Chassis Failure
3
21
3
23
Connection Failure
4
16
Unknown Instruction
4
20
Invalid Array Subscript
4
21
Control Structure LEN or POS < 0
4
31
Invalid JSR Parameter
4
34
Timer Failure
4
42
Invalid JMP Target
4
82
SFC Jump Back Failure
4
83
Value Out of Range
4
84
Stack Overflow
4
89
Invalid Target Step
4
90
Invalid Instruction
4
91
Invalid Context
4
92
Invalid Action
4
990
User-defined
4
991
4
992
4
993
4
994
4
995
4
996
4
997
4
998
4
999
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Status Indicators
Appendix A
Table 51 - Major Fault Status Messages (continued)
Type
Code
Message
6
1
Task Watchdog Expired
7
40
Save Failure
7
41
Bad Restore Type
7
42
Bad Restore Revision
7
43
Bad Restore Checksum
8
1
Keyswitch Change Ignored
11
1
Positive Overtravel Limit Exceeded
11
2
Negative Overtravel Limit Exceeded
11
3
Position Error Tolerance Exceeded
11
4
Encoder Channel Connection Fault
11
5
Encoder Noise Event Detected
11
6
SERCOS Drive Fault
11
7
Synchronous Connection Fault
11
8
Servo Module Fault
11
9
Asynchronous Connection Fault
11
10
Motor Fault
11
11
Motor Thermal Fault
11
12
Drive Thermal Fault
11
13
SERCOS Communications Fault
11
14
Inactive Drive Enable Input Detected
11
15
Drive Phase Loss Detected
11
16
Drive Guard Fault
11
32
Motion Task Overlap Fault
11
33
CST Reference Loss Detected
18
1
CIP Motion Initialization Fault
18
2
CIP Motion Initialization Fault Mfg
18
3
CIP Motion Axis Fault
18
4
CIP Motion Axis Fault Mfg
18
5
CIP Motion Fault
18
6
CIP Module Fault
18
7
Motion Group Fault
18
8
CIP Motion Configuration Fault
18
9
CIP Motion APR Fault
18
10
CIP Motion APR Fault Mfg
18
128
CIP Motion Guard Fault
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
189
Appendix A
Status Indicators
I/O Fault Codes
I/O faults indicated by the controller are indicated on the status display in one of
these formats:
• I/O Fault Local:X #XXXX message
• I/O Fault ModuleName #XXXX message
• I/O Fault ModuleParent:X #XXXX message
The first part of the format is used to indicate the location of the faulted module.
How the location is indicated depends on your I/O configuration and the
module’s properties specified in Logix Designer application.
The latter part of the format, #XXXX message, can be used to diagnose the type
of I/O fault and potential corrective actions. For details about each I/O fault
code, see the Logix5000 Major, Minor, and I/O Fault Codes Programming
Manual, publication 1756-PM014.
Table 52 - I/O Fault Messages
190
Code
Message
#0001
Connection Failure
#0002
Insufficient Resource
#0003
Invalid Value
#0004
IOI Syntax
#0005
Destination Unknown
#0006
Partial Data Transferred
#0007
Connection Lost
#0008
Service Unsupported
#0009
Invalid Attribute Value
#000A
Attribute List Error
#000B
State Already Exists
#000C
Object Mode Conflict
#000D
Object Already Exists
#000E
Attribute Not Settable
#000F
Permission Denied
#0010
Device State Conflict
#0011
Reply Too Large
#0012
Fragment Primitive
#0013
Insufficient Command Data
#0014
Attribute Not Supported
#0015
Data Too Large
#0100
Connection In Use
#0103
Transport Not Supported
#0106
Ownership Conflict
#0107
Connection Not Found
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Status Indicators
Appendix A
Table 52 - I/O Fault Messages (continued)
Code
Message
#0108
Invalid Connection Type
#0109
Invalid Connection Size
#0110
Module Not Configured
#0111
RPI Out of Range
#0113
Out of Connections
#0114
Wrong Module
#0115
Wrong Device Type
#0116
Wrong Revision
#0117
Invalid Connection Point
#0118
Invalid Configuration Format
#0119
Module Not Owned
#011A
Out of Connection Resources
#0203
Connection Timeout
#0204
Unconnected Message Timeout
#0205
Invalid Parameter
#0206
Message Too Large
#0301
No Buffer Memory
#0302
Bandwidth Not Available
#0303
No Bridge Available
#0304
ControlNet Schedule Error
#0305
Signature Mismatch
#0306
CCM Not Available
#0311
Invalid Port
#0312
Invalid Link Address
#0315
Invalid Segment Type
#0317
Connection Not Scheduled
#0318
Invalid Link Address
#0319
No Secondary Resources Available
#031E
No Available Resources
#031F
No Available Resources
#0800
Network Link Offline
#0801
Incompatible Multicast RPI
#0814
Data Type Mismatch
#FD01
Bad Backplane EEPROM
#FD02
No Error Code
#FD03
Missing Required Connection
#FD04
No CST Master
#FD05
Axis or GRP Not Assigned
#FD06
SERCOS Transition Fault
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
191
Appendix A
Status Indicators
Table 52 - I/O Fault Messages (continued)
192
Code
Message
#FD07
SERCOS Init Ring Fault
#FD08
SERCOS Comm Fault
#FD09
SERCOS Init Node Fault
#FD0A
Axis Attribute Reject
#FD1F
Safety I/O
#FD20
No Safety Task
#FE01
Invalid Connection Type
#FE02
Invalid Update Rate
#FE03
Invalid Input Connection
#FE04
Invalid Input Data Pointer
#FE05
Invalid Input Data Size
#FE06
Invalid Input Force Pointer
#FE07
Invalid Output Connection
#FE08
Invalid Output Data Pointer
#FE09
Invalid Output Data Size
#FE0A
Invalid Output Force Pointer
#FE0B
Invalid Symbol String
#FE0C
Invalid Scheduled P/C Instance
#FE0D
Invalid Symbol Instance
#FE0E
Module Firmware Updating
#FE0F
Invalid Firmware File Revision
#FE10
Firmware File Not Found
#FE11
Firmware File Invalid
#FE12
Automatic Firmware Update Failed
#FE13
Update Failed - Active Connection
#FE14
Searching Firmware File
#FE22
Invalid Connection Type
#FE23
Invalid Unicast Allowed
#FF00
No Connection Instance
#FF01
Path Too Long
#FF04
Invalid State
#FF08
Invalid Path
#FF0B
Invalid Config
#FF0E
No Connection Allowed
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Status Indicators
1756-L7x Controller
Status Indicators
Appendix A
The status indicators are below the status display on the controller. They indicate
the state of the controller as described in these tables.
RUN Indicator
To change the controller mode indicated by the RUN indicator, either use the
mode switch on the front of the controller or use the Controller Status menu in
the Logix Designer application.
Table 53 - RUN Indicator
State
Description
Off
The controller is either in Program or Test mode.
Steady green
The controller is in Run mode.
FORCE Indicator
The Force indicator shows if I/O forces are enabled on the controller.
Table 54 - FORCE Indicator
State
Description
Off
No tags contain I/O force values.
Solid amber
I/O forces are active (enabled) though I/O force values may or may not be configured.
Use caution if you install (add) a force. If you install (add) a force, it immediately takes
effect.
Flashing amber
One or more input or output addresses have been forced to an On or Off state, but the forces have
not been enabled.
Use caution if you enable I/O forces. If you enable I/O forces, all existing I/O forces also
take effect.
SD Indicator
The SD indicator shows if the Secure Digital (SD) card is in use.
Table 55 - SD Indicator
State
Description
Off
No activity is occurring with the SD card.
Flashing green
The controller is reading from or writing to the SD card.
Do not remove the SD card while the controller is reading or writing.
Solid green
Flashing red
The SD card does not have a valid file system.
Solid red
The SD card is not recognized by the controller.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
193
Appendix A
Status Indicators
OK Indicator
The OK indicator shows the state of the controller.
Table 56 - OK Indicator
1756-L6x Status Indicators
State
Description
Off
No power is applied to the controller.
Flashing red
Either of the following is true:
• It is a new controller, just out of the box, and it requires a firmware upgrade. If a firmware
upgrade is required, the status display indicates Firmware Installation Required. To upgrade
firmware, see Upgrade Controller Firmware on page 50.
• It is a previously-used or in-use controller and a major fault has occurred. For details about
major recoverable and nonrecoverable faults, see the Logix5000 Major, Minor, and I/O Fault
Codes Programming Manual, publication 1756-PM014.
Solid red
One of the following is true:
• The controller is completing power-up diagnostics
• The charge of the capacitor in the ESM is being discharged upon powerdown.
• The controller is powered, but is inoperable.
• The controller is loading a project to nonvolatile memory.
Solid green
The controller is operating normally.
The 1756-L6x controllers have status indicators on the front of the controller at
show the state of the controller.
Status Indicators
RUN Indicator
To change the controller mode indicated by the RUN indicator, either use the
mode switch on the front of the controller or use the Controller Status menu in
the Logix Designer application.
Table 57 - RUN Indicator
194
State
Description
Off
The controller is either in Program or Test mode.
Steady green
The controller is in Run mode.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Status Indicators
Appendix A
I/O Indicator
The I/O indicator shows the status of I/O modules in the controller’s project.
Table 58 - I/O Indicator
State
Description
Off
Either of the following is true:
• There are no devices are in the I/O configuration of the controller. If needed, add the required
devices to the I/O configuration of the controller.
• The controller does not contain a project (controller memory is empty). If prepared, download
the project to the controller.
Solid green
The controller is communicating with all of the devices in its I/O configuration.
Flashing green
One or more devices in the I/O configuration of the controller are not responding. For more
information, go online with the Logix Designer application to check the I/O configuration of the
controller.
Flashing red
A chassis fault exists. Troubleshoot the chassis and replace it if necessary.
FORCE Indicator
The FORCE indicator shows if I/O forces are active or enabled.
Table 59 - FORCE Indicator
State
Description
Off
Either of the following is true:
• No tags contain I/O force values.
• I/O forces are inactive (disabled).
Steady amber
I/O forces are active (enabled) though I/O force values may or may not be configured.
Use caution if you install (add) a force. If you install (add) a force, it immediately takes
effect.
Flashing amber
One or more input or output addresses have been forced to an On or Off state, but the forces have not
been enabled.
Use caution if you enable I/O forces. If you enable I/O forces, all existing I/O forces also
take effect.
RS232 Indicator
The RS232 indicator shows if the serial port is in use.
Table 60 - RS232 Status Indicator
State
Description
Off
There is no serial connection activity.
Flashing green
There is serial connection activity.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
195
Appendix A
Status Indicators
BAT Indicator
The BAT indicator shows the charge of the battery and if the program is being
saved.
Table 61 - BAT Indicator
State
Controller
Series
Description
Off
N/A
The controller is able to support memory.
Solid green
A
The series A controllers do not use this state.
B
The series B controller is conducting a save of the program to internal-nonvolatile
memory during a controller power down.
N/A
Either of the following is true:
• A battery is not installed.
• The battery is 95% discharged and should be replaced.
Solid red
Note that if the indicator is solid red before a power down, the indicator remains red
while the controller is completing a program save to internal-nonvolatile memory.
OK Indicator
The OK indicator shows the state of the controller.
Table 62 - OK Indicator
196
State
Description
Off
No power is applied to the controller.
Flashing red
Either of the following is true:
• It is a new controller, just out of the box, and it requires a firmware upgrade.
• It is a previously-used or in-use controller and a major fault has occurred.
• The controller is experiencing a non-recoverable, major fault.
Steady red
• A nonrecoverable major fault occurred and the program was cleared from memory.
• The controller is completely powered up, in diagnostics mode.
• The controller is powered, but inoperable.
Steady green
The controller is operating normally.
Flashing green
The controller is storing or loading a project to or from nonvolatile memory.
If using a CompactFlash card, leave the card in the controller until the OK status indicator
turns solid green.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Appendix
B
Using Electronic Keying
Electronic Keying
Topic
Page
Electronic Keying
197
Exact Match
198
Compatible Keying
199
Disabled Keying
201
The electronic keying feature automatically compares the expected module, as
shown in the RSLogix 5000 I/O Configuration tree, to the physical module
before I/O communication begins. You can use electronic keying to help prevent
communication to a module that does not match the type and revision expected.
For each module in the I/O Configuration tree, the user-selected keying option
determines if, and how, an electronic keying check is performed. Typically, three
keying option are available:
• Exact Match
• Compatible Keying
• Disable Keying
You must carefully consider the benefits and implications of each keying option
when selecting between them. For some specific module types, fewer options are
available.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
197
Appendix B
Using Electronic Keying
Electronic keying is based on a set of attributes unique to each product revision.
When a Logix5000 controller begins communicating with a module, this set of
keying attributes is considered.
Table 63 - Keying Attributes
Attribute
Description
Vendor
The manufacturer of the module, for example, Rockwell Automation/Allen-Bradley.
Product Type
The general type of the module, for example, communication adapter, AC drive, or digital
I/O.
Product Code
The specific type of module, generally represented by its catalog number, for example,
1756-IB16I.
Major Revision
A number that represents the functional capabilities and data exchange formats of the
module. Typically, although not always, a later, that is higher, Major Revision supports at
least all of the data formats supported by an earlier, that is lower, Major Revision of the
same catalog number and, possibly, additional ones.
Minor Revision
A number that indicates the module’s specific firmware revision. Minor Revisions
typically do not impact data compatibility but may indicate performance or behavior
improvement.
You can find revision information on the General tab of a module’s Properties
dialog box.
Figure 51 - General Tab
IMPORTANT
Exact Match
Changing electronic keying selections online may cause the I/O
communication connection to the module to be disrupted and may result in
a loss of data.
Exact Match keying requires all keying attributes, that is, Vendor, Product Type,
Product Code (catalog number), Major Revision, and Minor Revision, of the
physical module and the module created in the software to match precisely to
establish communication. If any attribute does not match precisely, I/O
communication is not permitted with the module or with modules connected
through it, as in the case of a communication module.
Use Exact Match keying when you need the system to verify that the module
revisions in use are exactly as specified in the project, such as for use in highlyregulated industries. Exact Match keying is also necessary to enable Automatic
198
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Using Electronic Keying
Appendix B
Firmware Update for the module via the Firmware Supervisor feature from a
Logix5000 controller.
EXAMPLE
In the following scenario, Exact Match keying prevents I/O communication.
The module configuration is for a 1756-IB16D module with module revision
3.1. The physical module is a 1756-IB16D module with module revision 3.2. In
this case, communication is prevented because the Minor Revision of the
module does not match precisely.
Module Configuration
Vendor = Allen-Bradley
Product Type = Digital Input Module
Catalog Number = 1756-IB16D
Major Revision = 3
Minor Revision = 1
Communication is prevented.
Physical Module
Vendor = Allen-Bradley
Product Type = Digital Input Module
Catalog Number = 1756-IB16D
Major Revision = 3
Minor Revision = 2
IMPORTANT
Compatible Keying
Changing electronic keying selections online may cause the I/O
Communication connection to the module to be disrupted and may result
in a loss of data.
Compatible Keying indicates that the module determines whether to accept or
reject communication. Different module families, communication adapters, and
module types implement the compatibility check differently based on the family
capabilities and on prior knowledge of compatible products.
Compatible Keying is the default setting. Compatible Keying allows the physical
module to accept the key of the module configured in the software, provided that
the configured module is one the physical module is capable of emulating. The
exact level of emulation required is product and revision specific.
With Compatible Keying, you can replace a module of a certain Major Revision
with one of the same catalog number and the same or later, that is higher, Major
Revision. In some cases, the selection makes it possible to use a replacement that
is a different catalog number than the original. For example, you can replace a
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
199
Appendix B
Using Electronic Keying
1756-CNBR module with a 1756-CN2R module. The release notes for
individual modules indicate the specific compatibility details.
When a module is created, the module developers consider the module’s
development history to implement capabilities that emulate those of the previous
module. However, the developers cannot know future developments. Because of
this, when a system is configured, we recommend that you configure your module
using the earliest, that is, lowest, revision of the physical module that you believe
will be used in the system. By doing this, you can avoid the case of a physical
module rejecting the keying request because it is an earlier revision than the one
configured in the software.
EXAMPLE
In the following scenario, Compatible Keying prevents I/O
communication.
The module configuration is for a 1756-IB16D module with module revision
3.3. The physical module is a 1756-IB16D module with module revision 3.2. In
this case, communication is prevented because the minor revision of the
module is lower than expected and may not be compatible with 3.3.
Module Configuration
Vendor = Allen-Bradley
Product Type = Digital Input Module
Catalog Number = 1756-IB16D
Major Revision = 3
Minor Revision = 3
Communication is prevented.
Physical Module
Vendor = Allen-Bradley
Product Type = Digital Input Module
Catalog Number = 1756-IB16D
Major Revision = 3
Minor Revision = 2
200
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Using Electronic Keying
EXAMPLE
Appendix B
In the following scenario, Compatible Keying allows I/O communication:
The module configuration is for a 1756-IB16D module with module revision
2.1. The physical module is a 1756-IB16D module with module revision 3.2. In
this case, communication is allowed because the major revision of the physical
module is higher than expected and the module determines that it is
compatible with the prior major revision.
Module Configuration
Vendor = Allen-Bradley
Product Type = Digital Input Module
Catalog Number = 1756-IB16D
Major Revision = 2
Minor Revision = 1
Communication is allowed.
Physical Module
Vendor = Allen-Bradley
Product Type = Digital Input Module
Catalog Number = 1756-IB16D
Major Revision = 3
Minor Revision = 2
IMPORTANT
Disabled Keying
Changing electronic keying selections online may cause the I/O
communication connection to the module to be disrupted and may result in
a loss of data.
Disabled Keying indicates the keying attributes are not considered when
attempting to communicate with a module. Other attributes, such as data size
and format, are considered and must be acceptable before I/O communication is
established. With Disabled Keying, I/O communication may occur with a
module other than the type specified in the I/O Configuration tree with
unpredictable results. We generally do not recommend using Disabled Keying.
ATTENTION: Be extremely cautious when using Disabled Keying; if used
incorrectly, this option can lead to personal injury or death, property
damage, or economic loss.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
201
Appendix B
Using Electronic Keying
If you use Disabled Keying, you must take full responsibility for understanding
whether the module being used can fulfill the functional requirements of the
application.
EXAMPLE
In the following scenario, Disable Keying prevents I/O communication.
The module configuration is for a 1756-IA16 digital input module. The physical
module is a 1756-IF16 analog input module. In this case, communication is
prevented because the analog module rejects the data formats that
the digital module configuration requests.
Module Configuration
Vendor = Allen-Bradley
Product Type = Digital Input Module
Catalog Number = 1756-IA16
Major Revision = 3
Minor Revision = 1
Communication is prevented.
Physical Module
Vendor = Allen-Bradley
Product Type = Analog Input Module
Catalog Number = 1756-IF16
Major Revision = 3
Minor Revision = 2
202
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Using Electronic Keying
EXAMPLE
Appendix B
In the following scenario, Disable Keying allows I/O communication.
The module configuration is for a 1756-IA16 digital input module. The physical
module is a 1756-IB16 digital input module. In this case, communication is
allowed because the two digital modules share common data formats.
Module Configuration
Vendor = Allen-Bradley
Product Type = Digital Input Module
Catalog Number = 1756-IA16
Major Revision = 2
Minor Revision = 1
Communication is allowed.
Physical Module
Vendor = Allen-Bradley
Product Type = Digital Input Module
Catalog Number = 1756-IB16
Major Revision = 3
Minor Revision = 2
IMPORTANT
Changing electronic keying selections online may cause the I/O
communication connection to the module to be disrupted and may result in
a loss of data.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
203
Appendix B
Using Electronic Keying
Notes:
204
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Appendix
C
History of Changes
Topic
Page
1756-UM001M-EN-P, February 2012
206
1756-UM001L-EN-P, November 2011
206
1756-UM001K-EN-P, May 2011
206
1756-UM001J-EN-P, July 2010
207
1756-UM001I-EN-P, January 2007
207
1756-UM001H-EN-P, July 2008
207
1756-UM001G-EN-P, January 2007
207
1756-UM001F-EN-P, May 2005
207
1756-UM001E-EN-P, August 2002
208
1756-UM001D-EN-P
208
1756-UM001C-EN-P, June 2001
208
1756-UM001B-EN-P, November 2000
208
This appendix summarizes the revisions to this manual. Reference this appendix
if you need information to determine what changes have been made across
multiple revisions. This may be especially useful if you are deciding to upgrade
your hardware or software based on information added with previous revisions of
this manual.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
205
Appendix C
History of Changes
1756-UM001M-EN-P,
February 2012
Change
Added USB cable text.
Added energy storage module information relating to safety and extreme temperature controllers.
Added parts not included with the 1756-L6x controller.
Added double data rate (DDR) communication reference for 1756-L7x controller.
Added 1756-L71, 1756-L73XT controllers and chassis and changed version information for 1756-L72, 1756-L73,
1756-L74, and 1756-L75 controllers.
Added upgrade restrictions.
Added information about mode switch operation on the controller.
Controller mode can be changed in the Logix Designer application.
Changed 1756-ESMNSE μjoules from 200…40.
Added 1756-L71 information to ControlLogix controller features.
Added 1756-L71 and 1756-L73XT memory options.
Added double data rate (DDR) communication information.
Added 1756-A7XT chassis information.
Added information about the flashing red OK status indicator for nonrecoverable faults.
1756-UM001L-EN-P,
November 2011
Change
Added 1756-ESMNSE stored energy depletion rate.
Added how to uninstall the ESM.
1756-UM001K-EN-P,
May 2011
Change
Added information about new 1756-L72 and 1756-L74 controllers.
Added series A information for the 1756-L72 and 1756-L74 controllers.
Added 1756-L72 and 1756-L74 controller memory size information.
Added 1756-L72 and 1756-L74 to list of controllers that support redundancy.
Added information about redundant systems and the EtherNet/IP network.
206
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
History of Changes
1756-UM001J-EN-P, July 2010
Appendix C
Change
Added 1756-L6x and 1756-L7x installation information.
Added information to identify and describe common start-up tasks completed with ControlLogix controllers.
Updated the ControlLogix example configurations, system design information, controller features descriptions to
include the 1756-L7x controllers, available memory options to include the 1756-L7x information, and ControlLogix
controller CPU resources.
Reformatted information for clarity on communication networks and updated the additional resources.
Placed and reformatted information specific to the use of serial communication.
Reformatted information about controller connections.
Added a list of modules and devices that can be added while online with the Logix Designer application, updated
ControlNet network considerations that must be made when adding modules or devices while online, and updated
EtherNet/IP network considerations that must be made when adding modules or devices while online.
Updated motion information and references with regard to the 1756-L60M03SE combination controller and
reformatted and added graphics.
Made redundancy information corrections and updated information about SIL2 certification and configurations.
Added 1756-L7x status display and status indicator information.
1756-UM001I-EN-P,
January 2007
Change
Added new information about broadcasting over serial ports.
Updated redundancy information.
Updated battery information.
Added new and updated EtherNet/IP motion information.
1756-UM001H-EN-P,
July 2008
Change
Added new information about the 1756-L65 controller .
Added new information about the 1784-CF128 CompactFlash card.
1756-UM001G-EN-P,
January 2007
Change
Added information about the 1756-L64 ControlLogix controller.
Added information about Add-On Instructions.
Updated the Select a System Overhead Percentage section.
Updated the Add Your Axes section.
Updated the Obtain Axis Information section.
1756-UM001F-EN-P,
May 2005
No changes documented.
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
207
Appendix C
History of Changes
1756-UM001E-EN-P,
August 2002
Change
Added information about the battery life of the 1756-BA1 battery when you use it in a ControlLogix5563 controller.
Added information about the 1756-BATM ControlLogix battery module.
1756-UM001D-EN-P
1756-UM001C-EN-P,
June 2001
Revision not published.
Change
Added the Configure an EtherNet/IP Module section.
Added the Download and Go Online over an EtherNet/IP Network section.
Added the Communicate with 1756 I/O over an EtherNet/IP Network section.
Added the Communicate with 1794 I/O over an EtherNet/IP Network section.
Added the Communicate with Another Controller over an EtherNet/IP Network section.
Added the Communicate with a PanelView Terminal over a EtherNet/IP Network section.
Added the Communicate with an RSView™32 Project over an EtherNet/IP Network section.
Added the Add I/O Modules section.
Added the Create Aliases section.
Added the Schedule the ControlNet Network section.
Added the Communicate with Another Controller over a DH+ Network section.
Added the Route PLC-5 or SLC 500 Messages From a DH+ Network section.
Added the Estimate Execution Time section.
Added the Estimate Memory Use section.
Added the Determine When Data Is Updated section.
1756-UM001B-EN-P,
November 2000
Change
Added the Configure a1756-ENET Module section.
Added the Download and Go Online over an Ethernet Network section.
Added the Communicate with 1756 I/O over an Ethernet Network section.
Added the Communicate with Another Controller over an Ethernet Network section.
Added the Communicate with Another Controller over a DH-485 Network section.
Added the Estimate Battery Life section.
Added the Estimate Execution Time (updated numbers) section.
208
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Index
Numerics
1747-KY controller key
key 17
1756-BA1
check level 72
controller compatiblity 72
controller parts 31
storage 76
1756-BA2
check level 72
controller compatibility 72
controller parts 31
estimate life 74
life after warning 75
storage 76
1756-BATA
controller compatibility 72
1756-BATM
battery 74
controller compatibility 72
controller parts 31
1756-CN2
uses 89
1756-CN2R
uses 89
1756-CN2RXT
uses 89
1756-CNB
uses 89
1756-CNBR
uses 89
1756-CP3
controller parts 31
1756-DHRIO
communication via 93
uses
remote I/O 94
1756-EN2F
uses 85
1756-EN2T
uses 85
1756-EN2TR
uses 85
1756-EN2TXT
uses 85
1756-EN3TR
uses 85
1756-ENBT
uses 85
1756-ESMCAP
controller parts 17
ESM 26
1756-ESMCAPXT
ESM 26
1756-ESMNRM 26
controller parts 18
ESM 26
1756-ESMNRMXT
ESM 26
1756-ESMNSE
controller parts 18
ESM 26
1756-ESMNSEXT
ESM 26
1756-EWEB
uses 85
1756-IF8H
uses 97
1756-L6x
add
while online 133
BAT indicator 196
CPU 82
FORCE indicator 195
I/O indicator 195
installation
battery, install 36
battery, uninstall 36
CompactFlash card, removal 32
into chassis 39
memory options 82
OK indicator 196
RS232
indicator 195
port 100
RUN indicator 194
serial driver 48
serial port 47
1756-L7x
add
while online 133
CPU 82
double data rate (DDR) 43, 87
FORCE indicator 193
installation
ESM, uninstall 25
into chassis 19
key 20
SD card, install 21
SD card, removal 23
memory options 82
OK indicator 194
parts
included 17
RUN indicator 193
SD indicator 193
status display 185
status indicators 193, 194
USB driver 45
1756-L7xXT
extreme temperature controller 26
1756-N2 122
1756-N2XT 122
1756-OF8H
uses 97
1756-RIO
uses 94
1784-SD1 18
load from 67
SD card 17
store to 64
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
209
Index
1784-SD2
controller parts 18
load from 67
store to 64
A
add
distributed I/O 129
local I/O 123
remote I/O 125
Add-On Instructions
in project 157
application
elements 145
networks and 83
ASCII 107
attributes
keying 198
AutoFlash
upgrade 54
axis
obtain information 142
B
BAT indicator
1756-L6x 196
battery
1756-BA2
estimate 74
life after warning 75
catalog number 31
check if low 72
compatibility 72
install 36
life and use 74
replacement 72
schedule 72
storage 76
uninstall 36
broadcast
messages 109
C
cache
message options 116
messages
about 116
calculate
connection use 117
change
equipment phase 169
chassis
ControlLogix
list 122
insert controller 19, 39
210
communication
Data Highway Plus 92, 93
DH-485 network 105
Foundation Fieldbus 96
HART 97
network options 81
path
set 56
universal remote I/O 94
CompactFlash card
installation 32
load from 67
other tasks 69
removal 32
store to 64
comparision
PhaseManager 170
compatibility
battery 72
compatible keying 199
configurations
fail-safe 181
fault-tolerant 183
high-availability 182
configure
motion 142
serial driver 48
system overhead time slice 163
connect
DH-485 network 105
connection
calculate use 117
DeviceNet
network 92
EtherNet/IP 86
network 86
example 119
local 117
message, required 116
produce/consume
data and 114
required 115
remote 118
scheduled
ControlNet 90
unscheduled
ControlNet 90
considerations
redundancy 174
consume
data 114
continuous task 148
ControlFLASH utility 51
controller
1756-L6x
battery and 72
battery, install 36
battery, uninstall 36
CompactFlash card, installation 32
CompactFlash card, removal 32
insert into chassis 39
serial driver 48
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Index
1756-L7x
battery and 72
communication options 81
ESM, uninstall 25
insert into chassis 19
key, insert 20
SD card, install 21
SD card, removal 23
status display 185
status indicators 193, 194
USB driver 45
battery
check 72
communication path
set 56
connections
calculate 117
CPU resources 82
design system with 80
download 58
estimate
battery life 74
firmware 50
obtain 51
go online 57
memory options 82
monitor
connections 159
parts included 18
program 149
routine 152
tags 153
tasks 146
upload 59
controller parts
1756-BA1 31
1756-BA2 31
1756-BATM 31
1756-CP3 31
1756-ESMCAP 17
1756-ESMNRM 18
1756-ESMNSE 18
1784-SD2 18
battery 31
energy storage module
catalog number 17, 18
catalog number ESM. See energy storage module.
SAMTEC RSP-119350 18
serial cable 31
USB cable 18
ControlLogix
chassis
list 122
controller
add while online 133
design system 80
I/O
remote 124
selection 121
modules
online addition 133
redundancy
about 171
remote I/O
local 122
slot filler 122
ControlLogix-XT
chassis
list 122
ControlNet
module capability 89
module features 89
module list 89
network 87
redundancy system and 176
scheduled connection
scheduled connection 90
unscheduled connection
unscheduled connection 90
CPU
controller 82
D
Data Highway Plus network 92
design
system 80
develop
applications 145
motion applications 141
DeviceNet
connection use 92
module
memory 92
network 90
software for 92
devices
add while online 135
DF1
master 101
point to point 101
radio modem 102
slave 104
DH-485 network
example configuration 105
overview 105
disabled keying 201
display
1756-L7x 185
distributed
I/O 128
add 129
double data rate (DDR)
1756-L7x 43, 87
download
project 58
drive
add while online 134
E
electronic keying
about 197
electrostatic discharge 19, 39
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
211
Index
elements
control application 145
enhanced redundancy. See redundancy.
equipment phase
instructions 170
error
script file 53
ESM 26
1756-ESMCAP 26
1756-ESMCAPXT 26
1756-ESMNRMXT 26
1756-ESMNSE 26
1756-ESMNSEXT 26
uninstall 25
EtherNet/IP
add while online 138
connections 86
module features 84
module list 85
network 84
redundancy system and 176
software for 86
event task 148
exact match keying 198
example configuration
DH-485 network 105
extreme temperature controller
1756-L7xXT 26
F
fail-safe configruation
about 181
fault code
use GSV to get 160
fault handler
execute at I/O fault 161
fault messages 187
I/O 190
Major Recoverable Fault 188
fault-tolerant configruation
about 183
features 81
controller
communication 81
programming 81
filler slot
slot filler 122
firmware
controller 50
determine 50
obtain 51
security certificate, error 53
upgrade
AutoFlash, use 54
FORCE indicator
1756-L6x 195
1756-L7x 193
Foundation Fieldbus 96
212
G
general status messages 186
GSV
fault code 160
monitor
connection 160
H
HART. See Highway Addressable Remote
Transducer.
high-availability configruation
about 182
Highway Addressable Remote Transducer 97
hold-up time
ESM WallClockTime 71
I
I/O
connection error 161
ControlLogix
remote 124
selection 121
determine data update 139
distributed 128
fault codes 190
reconfigure 131
remote 124
I/O configuration
add
distributed I/O 129
local I/O 123
remote I/O 125
while online 132
I/O indicator
1756-L6x 195
indicator 193
BAT
1756-L6x 196
FORCE
1756-L6x 195
1756-L7x 193
I/O
1756-L6x 195
OK
1756-L6x 196
1756-L7x 194
RS232
1756-L6x 195
RUN
1756-L7x 193
SD
1756-L7x 193
install
1756-L6x
battery 36
CompactFlash card 32
insert into chassis 39
1756-L7x
insert into chassis 19
key, insert 20
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Index
SD card 21
battery 36
CompactFlash card 32
SD card 21
instruction
ASCII 107
motion 143
IP address swapping 176
K
module
ControlNet 89
EtherNet/IP 84, 85
motion
about 142
application 141
instructions 143
program 143
MVI56-HART
uses 97
key
1747-KY controller key 17
insert 20
keying
about 197
attributes 198
compatible 199
disabled 201
exact match 198
L
load
from memory card 67
local
connection 117
I/O
add 123
remote I/O 122
Logix Designer application
Add-On Instructions 157
program 149
rebranding of RSLogix 5000 11
routine 152
tags 153
tasks 146
M
Major Recoverable Fault
messages 188
memory
DeviceNet module 92
options 82
memory card
load from 67
other tasks 69
store to 64
message
about 116
broadcast over serial 109
cache 116
determine if 116
fault 187
reconfigure I/O module 131
status display 186
Modbus network 111
mode
serial port 101
N
network
application and 83
controller options 81
ControlNet 87
ControlNet redundancy 176
Data Highway Plus 93
Data Highway Plus DH+. See Data Highway
Plus.
DeviceNet 90
EtherNet/IP 84
EtherNet/IP redundancy 176
Foundation Fieldbus 96
HART 97
universal remote I/O 94
nonvolatile memory 82
O
obtain
axis information 142
firmware 51
OK indicator
1756-L6x 196
1756-L7x 194
online
add
EtherNet/IP 138
to I/O configuration 132
go 57
options
memory 82
P
path
set
communication 56
periodic task 148
PhaseManager
about 165
change states 169
comparison 170
equipment phase instructions 170
state model 167
system requirements 167
terminology 165
transition 168
port
communication 81
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
213
Index
PowerFlex
add while online 134
prevent electrostatic discharge 19, 39
priority
task 149
produce
data 114
produce/consume
connections
required 114
data 114
program
in project 149
scheduled 151
system overhead time slice 162
unscheduled 151
programming languages 156
project
Add-On Instructions 157
download 58
elements 145
go online 57
program 149
routine 152
tags 153
tasks 146
upload 59
protocol
ASCII 107
DF1
master 101
point to point 101
radio modem 102
slave 104
Modbus network 111
serial port 101
R
receive
messages 116
redundancy
about 171
build system 175
considerations 174
ControlNet network 176
EtherNet/IP network 176
scan time 177
system requirements 173
remote
connection 118
I/O 124
remote I/O
add 125
ControlLogix
local 122
universal 94
remove
1756-L6x
CompactFlash card 32
214
1756-L7x
SD card 23
CompactFlash card 32
SD card 23
replace
battery
schedule 72
required
connections
messages 115, 116
requirement
PhaseManager
system 167
redundancy 173
RIO. See universal remote I/O
routine
in project 152
RS232
DF1 device driver 48
indicator
1756-L6x 195
RSWho
set
path 56
RUN indicator
1756-L7x 193
S
safety integration level, see SIL 2 179
SAMTEC RSP-119350
controller parts 18
scan time
redundancy and 177
scheduled
program 151
script file
error 53
SD card
1784-SD1 17
install 21
load from 67
other tasks 69
removal 23
store to 64
SD indicator
1756-L7x 193
security certificate
error 53
selection
I/O 121
send
messages 116
serial
broadcast 109
cable
catalog number 31
DH-485 network configuration 105
driver 48
Modbus network 111
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Index
serial port
1756-L6x 47
ASCII 107
DF1
master 101
point to point 101
radio modem 102
slave 104
mode 101
protocols 101
service communication 162
set up
serial driver 48
USB driver 45
SIL 2 certification
overview 179
software
DeviceNet and 92
EtherNet/IP and 86
required
USB 44
specifications 14
standard redundancy. See redundancy.
state model
overview 167
status
battery 72
display
1756-L7x 185
fault messages 187
indicators
1756-L7x 193, 194
messages
display 186
monitor
connections 159
storage
battery 76
store
to memory card 64
Studio 5000 environment 11
swapping IP address 176
system 81
system overhead time slice 162
configure 163
system requirements
PhaseManager 167
redundancy 173
transistion
PhaseManager 168
type
USB 44
U
uninstall
1756-L6x
battery 36
1756-L7x
ESM 25
battery 36
ESM 25
universal remote I/O 94
communicate via 95
unscheduled
program 151
update
determine frequency 139
upgrade
firmware
AutoFlash, use 54
upload
project 59
USB
cable
catalog number 18
driver 45
software required 44
type 44
T
tag
consume 114
in project 153
produce 114
task
continuous 148
event 148
in project 146
periodic 148
priority 149
time slice 162
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
215
Index
Notes:
216
Rockwell Automation Publication 1756-UM001N-EN-P - November 2012
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products.
At http://www.rockwellautomation.com/support, you can find technical manuals, technical and application notes, sample
code and links to software service packs, and a MySupport feature that you can customize to make the best use of these
tools. You can also visit our Knowledgebase at http://www.rockwellautomation.com/knowledgebase for FAQs, technical
information, support chat and forums, software updates, and to sign up for product notification updates.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer
TechConnectSM support programs. For more information, contact your local distributor or Rockwell Automation
representative, or visit http://www.rockwellautomation.com/support/.
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this
manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada
1.440.646.3434
Outside United States or Canada
Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell
Automation representative.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the
manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States
Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your
distributor to complete the return process.
Outside United States
Please contact your local Rockwell Automation representative for the return procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Publication 1756-UM001N-EN-P - November 2012
Supersedes Publication 1756-UM001M-EN-P - February 2012
Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.