Table 3.2 Configurable Parameters Display Function (In order of Display) SP1 Set Point 1 Range Function -19999 to +19999 Sets first output trip or control (Chapter 5 refers) SP2 Set Point 2 -19999 to +19999 Sets second output trip or control (Chapter 5 refers) HYS Hysteresis 0 to +19999 in real display units Sets hysteresis applied to SP1 and SP2 when used for ON/OFF control units (Chapter 5 refers) OL Output Latch Latch set by code in range0-3 as shown in Table 5.1 Allows SP1 and/or SP2 to be latched until reset externally, from the keypad or via communications port. OA Output Action (Inversion) of SP1 & SP2 Action set by code in range0-15 as shown in Table 5.2 Pb Proportional Band 0 to 1024 Sets output relay action. Can be set to ‘normal’ or ‘inverted’ operation for either or both set points. Gives fail safe operation of any alarm combination, High-High, High-Low, LowHigh & Low-Low. (Chapter 5 refers) Also selects whether analogue outputs controlled by display module or PID element in CPU Inversion of the analogue output 'O' Selects 'Ont'.'Offt' or 'da' function 1-1023 Selects PID mode and value of proportional band, in displayed units. 1024 Selects Integral 'It' only control Ont Output on delay 0 to 255 When PID is not used, (PB=0) the mnemonic (Ont) sets a delay on time for SP1 & SP2. Set in seconds. Or (It) Integral 0 to 6000 Selects integral value for PID control in seconds/repeat. 0= Proportional only control. OFFt Output off delay 0 to 255 When PID is not used,(PB=0) the mnemonic (Offt) sets a delay off time for SP1 & SP2 set in seconds. Or (dt) Derivative Time 0 to 255 Selects derivative value for PID control. 0 = OFF (no derivative) dA Display Averaging & Peak Hold 0 to 15 When PID is not used,(PB=0) the mnemonic (dA) sets a display averaging update rate. Readings may be averaged over a number of updates and can be set as follows: Mantracourt Electronics Limited ADP User Manual 20