3.3 DMT / IDMT (PTOCx, PTRC2)
PTOC2.Health
No.
51
Information
Device is Operational and Protecting (Device OK)
PTOC2.Health.stVal
device annunciation:
0 1
3 1
1 - ON
0 - OFF
IEC Status Health.stVal:
1 - OK
2 - WARNING
3 - ALARM
PTOC2.Str
No.
1837
Information
IEp picked up (IEp picked up)
PTOC2.Str.general
device annunciation:
0 1
0 1
1 - ON
0 - OFF
IEC Status Str.general:
0 - FALSE
1 - TRUE
PTOC2.Op
No.
1839
Information
IEp TRIP (IEp TRIP)
0 1
PTOC2.Op.general
device annunciation:
0 1
1 - ON
0 - OFF
IEC Status Op.general:
0 - FALSE
1 - TRUE
PTOC2.ChgSet
No.
1997
Information
Dynamic settings are ACTIVE (Dyn set. ACTIVE)
PTOC2.ChgSet.stVal
device annunciation:
64
1 - ON
0 - OFF
0 1
0 1
IEC Status ChgSet.stVal:
0 - FALSE
1 - TRUE
SIPROTEC, 7SJ68, PIXIT