Download USER MANUAL
Transcript
HGM9580 BUS TIE BUS PARALLEL UNIT 4.5 MANUAL OPERATION Manual mode is selected by pressing the button; a LED besides the button will illuminate to confirm the operation. 1. Press button: If either of the two buses is deactivate, then bus close signal will be initiated and the bus will be paralleled with the other bus. If both of Bus 1 and Bus 2 are active, the controller will adjust frequency and voltage to synchronize bus with bus; when synchronism requirements has been achieved, bus close signal will be initiated and the bus will be paralleled with the other bus. 2. Press button, then bus open relay activates and the bus split from the other bus. HGM9580 Bus Tie Bus Parallel Unit ISSUE 2014-02-16 Version 1.0 Page 14 of 33