Download USER MANUAL

Transcript
HGM9580 BUS TIE BUS PARALLEL UNIT
No.
Items
4
5
Active Actions
Active Delay
6
Description
Parameters
Defaults
Description
(0~2)
(0~20.0)s
2
2.0
0: Warn; 1:Trip 2: Indication
Time from detecting active to confirm
LCD display detailed contents when the
input is active.
Flexible Input Port 3
1
Contents Setting
(0~50)
0
2
Active Type
(0~1)
0
3
4
5
Arming
Active Actions
Active Delay
(0~2)
(0~2)
(0~20.0)s
2
2
2.0
6
Description
User defined. See form 3
0: Closed to active
1: Open to active
0: From paralleling 1: Always 2:Never
0: Warn; 1:Trip 2: Indication
Time from detecting active to confirm
LCD display detailed contents when the
input is active.
Flexible Input Port 4
1
Contents Setting
(0~50)
13
2
Active Type
(0~1)
0
Flexible Input Port 5
1
Contents Setting
(0~50)
0
2
Active Type
(0~1)
0
3
4
5
Arming
Active Actions
Active Delay
(0~2)
(0~2)
(0~20.0)s
2
2
2.0
6
Description
Flexible Input Port 6
1
Contents Setting
(0~50)
0
2
Active Type
(0~1)
0
3
4
5
Arming
Active Actions
Active Delay
(0~2)
(0~2)
(0~20.0)s
2
2
2.0
6
Description
Flexible Input Port 7
1
Contents Setting
(0~50)
0
2
Active Type
(0~1)
0
3
Arming
(0~2)
2
4
5
Active Actions
Active Delay
(0~2)
(0~20.0)s
2
2.0
6
Description
HGM9580 Bus Tie Bus Parallel Unit
ISSUE 2014-02-16
Bus Closed. See form 3
0: Closed to active
1: Open to active
User defined. See form 3
0: Closed to active
1: Open to active
0: From paralleling 1: Always 2:Never
0: Warn; 1:Trip 2: Indication
Time from detecting active to confirm
LCD display detailed contents when the
input is active.
User defined. See form 3
0: Closed to active
1: Open to active
0: From paralleling 1: Always 2:Never
0: Warn; 1:Trip 2: Indication
Time from detecting active to confirm
LCD display detailed contents when the
input is active.
User defined. See form 3
0: Closed to active
1: Open to active
0: From paralleling
1: Always 2: Never
0: Warn; 1:Trip 2: Indication
Time from detecting active to confirm
LCD display detailed contents when the
input is active.
Version 1.0
Page 21 of 33