Download Process Control - FOUNDATION Fieldbus™ Device - Lab-Volt
Transcript
Ex. 2-1 – Differential-Pressure Transmitter Configuration Procedure Figure 2-16.Position Adjust screen. 25. Select Block Mode in the parameters tree. Return the DP_FLOW and Pressure blocks Target mode to Auto. Also, change the Analog Input 1 Target mode to OOS. Click Apply to confirm your choices. 26. Go to Function Blocks Ź Analog Input 1 and make the changes illustrated in Figure 2-17 and Figure 2-18: 28 x Set Transducer Scale.Units Index to the same unit as PRESS. ENG. UNIT above (e.g., kPa). x Enter the value corresponding to maximum pressure in the selected unit next to Set Transducer Scale.EU at 100%. x Select Indirect for Linearization Type. © Festo Didactic 86002-10