INSTALLATION QUICK GUIDE
System accessories
WBAN
WSHN-EE
WSAN-XPR
WSAN-EE
31-05-2010
GR09D006GB-02
1
PEE20016 / 18
300 or 500 - litres domestic hot water kit
KBQRE3X / KBQER5X
2
PEE20019
Domestic hot water kit control
CACSX
3
PEE20014
Boiler management kit
KVICX
4
PEE20020
Boiler management kit (only for WBAN)
KVICX
5
PEE20015
100 - litres hydraulic circuit-breaker
KSAX
6
PEE20017
Wall electronic ambient thermostat
KITERAX
7
PEE20012 / 13
Kit for management of radiant panels with connections of 1” – 1” ¼
KVMSP1X / KVMSP2X
8
PEE20010 / 11
Water connection hoses with 1” – 1” ¼ connections
KTFL1X / KTFL2X
SCOPE / RECEIVERS
The RECEIVERS of this guide are the qualified plumbers and electricians, trained to operate in security according to the local rules and
informed on the risks resulted from the hydraulic and electric operations.
The SCOPE of the guide is to give the base information about the installation and configuration of the ELFOSystem HOME components.
DEEPENINGS on the functioning and configuration are quoted in the documents:
Clivet_Talk_Compact control system manual– ElfoEnergySmall Application (heat pump electronic)
Clivet_Talk_Compact control system accessory manual – DHW Application (electronic of DHW module)
KITERAX digital timer thermostat user's manual (wall mounted room thermostat)
STRUCTURE of the guide follows the arrangements of operations chronology
System Electrical and hydraulic connections
Setting and configurations of electronic modules
start-up
OPERATIONS SEQUENCE
1
Electrical and hydraulic connections: type - system
1. WBAN o WSHN-EE + DOMESTIC HOT WATER + RADIATORS
2. WBAN o WSHN-EE + DOMESTIC HOT WATER + RADIATORS + RADIANT PANELS
3. WBAN o WSAN-XPR o WSHN-EE + DOMESTIC HOT WATER + RADIATORS + BOILER + RADIANT PANELS
4. WSAN-XPR o WSHN-EE + DOMESTIC HOT WATER + RADIANT PANELS
5. WSAN-XPR o WSHN-EE + DOMESTIC HOT WATER + FAN COILS
6. WSAN-XPR o WSHN-EE + DOMESTIC HOT WATER + FAN COILS + RADIANT PANELS
7. WBAN o WSAN-XPR o WSHN-EE o WSAN-EE + BOILER + FAN COILS + RADIANT PANELS
2
Configuration - settings
United mounted communication parameters
Communication parameters on DHW module (PAR menu)
Managed system type (type sistem = 7 set on machine, type sistem = 1…….6  set on DHW ( CNF menu)
DHW and ANTILEGIONELLA scheduling (DHW, SCH menu)
3
Start-up – settings
date / hour (DHW menu TIME)
System STATE (DHW menu USER)
System SEASON (DHW menu USER)
DHW Setpoint (DHW menu USER)
MAINTENANCE Delta (DHW menu USER)
HYDRAULIC DIAGRAM
WBAN o WSHN-EE + DOMESTIC HOT WATER + RADIATORS
System type 1
UR %
Pag. 23
Indicative plumbing diagram
Only the components supplied or managed by CLIVET are indicated
The system components defined by Designer and Installer are not indicated (ex. expansion tanks, vents, cocks , calibration/safety valves etc.)
100 - LITRES HYDRAULIC CIRCUITBREAKER
300 OR 500 - LITRES DOMESTIC HOT WATER KIT
PEE20016 o 18
Page. 1
1x
1x
1x
1x
1x
AP5
RS 485
GND
+-
PEE20015
1x
WATER CONNECTION HOSES WITH 1”
– 1” ¼ CONNECTIONS
PEE20010 o 11
2x
WALL ELECTRONIC AMBIENT THERMOSTAT
PEE20017
1x
Wiring diagram
WIRING DIAGRAM
UR %
+ -
XC
GND
87 88 90 91 92
AP5
RS 485
+GND
+61
1
3
2
6
87
25 21
L1
XC
L2
XC
81
84
83
400/3/50+N
L3
N
GND
ACS
N
86
XC
XC
GND
+ -
XC
T3
T2
Pag. 23
T1
ACS
61
RS485
86
ACS
230/1/50
Page. 2
Hydraulic diagram
HYDRAULIC DIAGRAM
WBAN o WSHN-EE + DOMESTIC HOT WATER + RADIATORS
System type 2
UR %
Pag. 23
Indicative plumbing diagram
Only the components supplied or managed by CLIVET are indicated
The system components defined by Designer and Installer are not indicated (ex. expansion tanks, vents, cocks , calibration/safety valves etc.)
WATER CONNECTION HOSES WITH 1” – 1” ¼ CONNECTIONS
300 OR 500 - LITRES DOMESTIC HOT WATER KIT
PEE20016 o 18
AP5
1x
1x
1x
1x
1x
KIT FOR MANAGEMENT OF RADIANT PANELS WITH CONNECTIONS OF 1” – 1” ¼
PEE20012 o 13
Page.3
1x
1x
SMR
1x
TS
KA1
1x KA1
RS 485
GND
+-
PEE20010 o 11
2x
100 - LITRES HYDRAULIC CIRCUIT-BREAKER
PEE20015
1x
WALL ELECTRONIC AMBIENT THERMOSTAT
PEE20017
2x
Wiring diagram
WIRING DIAGRAM
UR %
+ -
XC
GND
87 88 90 91 92
AP5
RS 485
+-
GND
+-
*
1
3
61
11 9
7 5 3
1
CN3
12 10 8
6
4 2
2
XC2
XT3
55
29 61
87
6
25 21 26
84
85
6
2
3
1
L2
ACS
SMR
86
XC
Pag. 23
N
83
*
400/3/50+N
XC L3
81
TS
L1
XC
N
23 24 25
GND
XC
GND
XC
+ -
ACS
T3
61
T2
86
T1
ACS
RS485
RS485
230/1/50
*
Page. 4
KA1
See details at page 25
Hydraulic diagram
HYDRAULIC DIAGRAM
WBAN o WSAN-XPR o WSHN-EE + DOMESTIC HOT WATER + RADIATORS + BOILER + RADIANT PANELS
System type 3
UR %
Pag. 23
ON / OFF
Indicative plumbing diagram
Only the components supplied or managed by CLIVET are indicated
The system components defined by Designer and Installer are not indicated (ex. expansion tanks, vents, cocks , calibration/safety valves etc.)
WATER CONNECTION HOSES WITH 1” –
1” ¼ CONNECTIONS
300 OR 500 - LITRES DOMESTIC HOT WATER KIT
PEE20016 o 18
AP5
1x
1x
1x
1x
1x
RS 485
GND
+-
PEE20010 o 11
27 28 29 30
22 23 24 25 26
11 9
7
5 3
6
4
1
2
1x
12 10 8
2x
CN3
Page.5
2x
PEE20015
2x
1x
WALL ELECTRONIC AMBIENT THERMOSTAT
PEE20017
2x
KIT FOR MANAGEMENT OF RADIANT PANELS WITH CONNECTIONS OF 1” – 1” ¼
BOILER MANAGEMENT KIT
PEE20014
100 - LITRES HYDRAULIC CIRCUITBREAKER
1x
SDCV
1x BT5 PEE20012 o 13
1x
1x
SMR
1x
TS
KA1
1x KA1
Wiring diagram
WIRING DIAGRAM
UR %
+ -
XC
GND
87 88 90 91 92
XT3
RS 485
GND
34
29
+-
22 23 24 25 26
27 28 29 30
+61
87
*
1
9 7 53 1
1
CN3
1 1
8 6 42
2 0
GND
25
23
XT3
1
61
3
XC2
2
55
30 28 27
XT3
XT3
81 PE 61
29
6
61
7
4 5 81
81 PE 61
XC3
SDCV
XC3
SDCV
L1
XC
L2
XC
81
84
83
BT5
TS
3
*
SMR
400/3/50+N
L3
N
86
XC
81
3
ACS
85
1
2
25 21 26
N
AP5
XC
XC
GND
+ -
T3
T2
Pag. 23
T1
ACS
2
61
86
1
6
ACS
81
2
61
1
3
RS485
230/1/50
6
ON / OFF
9
8
6 61 PE 7 4 5 81
XC3
SDCV
*
Page. 6
KA1
See details page. 25
Hydraulic diagram
HYDRAULIC DIAGRAM
WSAN-XPR o WSHN-EE + DOMESTIC HOT WATER + RADIANT PANELS
System type 4
UR %
Pag. 23
Indicative plumbing diagram
Only the components supplied or managed by CLIVET are indicated
The system components defined by Designer and Installer are not indicated (ex. expansion tanks, vents, cocks , calibration/safety valves etc.)
WATER CONNECTION HOSES WITH 1” – 1” ¼
CONNECTIONS
300 OR 500 - LITRES DOMESTIC HOT WATER KIT
PEE20016 o 18
Page. 7
AP5
1x
1x
1x
1x
1x
RS 485
GND
+-
PEE20010 o 11
2x
WALL ELECTRONIC AMBIENT THERMOSTAT
PEE20017
1x
Wiring diagram
WIRING DIAGRAM
UR %
+ -
XC
GND
87 88 90 91 92
AP5
RS 485
+-
GND
+61
87
1
26 21
L1
XC
L2
XC
81
3
83
2
86
6
400/3/50+N
L3
N
GND
ACS
N
XC
XC
GND
+ -
XC
T3
T2
Pag. 23
T1
ACS
61
86
ACS
RS485
230/1/50
Page.8
Hydraulic diagram
HYDRAULIC DIAGRAM
WSAN-XPR o WSHN-EE + DOMESTIC HOT WATER + FAN COILS
System type 5
UR %
Pag. 23
Indicative plumbing diagram
Only the components supplied or managed by CLIVET are indicated
The system components defined by Designer and Installer are not indicated (ex. expansion tanks, vents, cocks , calibration/safety valves etc.)
WATER CONNECTION HOSES WITH 1” – 1” ¼
CONNECTIONS
300 OR 500 - LITRES DOMESTIC HOT WATER KIT
PEE20016 o 18
Page. 9
AP5
1x
1x
1x
1x
1x
RS 485
GND
+-
PEE20010 o 11
2x
WALL ELECTRONIC AMBIENT THERMOSTAT
PEE20017
1x
Wiring diagram
WIRING DIAGRAM
UR %
+ -
XC
GND
87 88 90 91 92
AP5
RS 485
+-
GND
+1
61
3
87
25 21
L1
XC
L2
XC
81
2
83
6
86
400/3/50+N
L3
N
GND
ACS
N
XC
RS485
XC
GND
+ -
XC
Pag. 23
T3
T2
ACS
T1
61
86
ACS
230/1/50
Page.10
Hydraulic diagram
HYDRAULIC DIAGRAM
WBAN o WSAN-XPR o WSHN-EE o WSAN-EE + BOILER + RADIANT PANELS + FAN COIL
System type 6
UR %
Pag. 23
Indicative plumbing diagram
Only the components supplied or managed by CLIVET are indicated
The system components defined by Designer and Installer are not indicated (ex. expansion tanks, vents, cocks , calibration/safety valves etc.)
WATER CONNECTION HOSES WITH 1” – 1” ¼
CONNECTIONS
300 OR 500 - LITRES DOMESTIC HOT WATER KIT
PEE20016 o 18
AP5
1x
1x
1x
1x
1x
RS 485
GND
+-
PEE20010 o 11
2x
WALL ELECTRONIC AMBIENT THERMOSTAT
PEE20017
1x
KIT FOR MANAGEMENT OF RADIANT PANELS WITH CONNECTIONS OF 1” – 1” ¼
PEE20012 o 13
Page.11
1x
1x
SMR
1x
TS
KA1
1x KA1
Wiring diagram
WIRING DIAGRAM
UR %
+ -
XC
GND
87 88 90 91 92
AP5
RS 485
GND
+61
1
*
23 24 25
+-
3
11
8 6 42
CN 2 0
3 1
9 753 1
1
2
XC2
XT3
55
29 61
*
6
6
87
3
81
85
2
1
TS
83
25 21
L1
XC
L2
ACS
N
86
SMR
400/3/50+N
XC L3
N
GND
T3
XC
XC
GND
Pag. 23
T2
+ -
T1
ACS
61
86
ACS
RS485
230/1/50
*
Page.12
KA1
See details at page 25
Hydraulic diagram
HYDRAULIC DIAGRAM
WBAN o WSAN-XPR o WSHN-EE o WSAN-EE + BOILER + RADIANT PANELS + FAN COILS
System type 7
UR %
ON / OFF
Indicative plumbing diagram
Only the components supplied or managed by CLIVET are indicated
The system components defined by Designer and Installer are not indicated (ex. expansion tanks, vents, cocks , calibration/safety valves etc.)
WATER CONNECTION HOSES WITH 1” – 1” ¼
CONNECTIONS
22 23 24 25 26
7
5 3
6
4
1
2
1x
12 10 8
2x
11 9
2x
CN3
PEE20014
27 28 29 30
BOILER MANAGEMENT KIT
1x
SDCV
1x BT5
KIT FOR MANAGEMENT OF RADIANT PANELS WITH CONNECTIONS OF 1” – 1” ¼
PEE20012 o 13
Page.13
1x
1x
SMR
1x
TS
KA1
1x KA1
PEE20010 o 11
2x
100 - LITRES HYDRAULIC CIRCUIT-BREAKER
PEE20015
1x
WALL ELECTRONIC AMBIENT THERMOSTAT
PEE20017
2x
Wiring diagram
WIRING DIAGRAM
UR %
+ -
XC
GND
87 88 90 91 92
XT3
1
9 7 53 1
1
XT3
61
29
CN3
1 1
8 6 42
2 0
25
23
22 23 24 25 26
*
34
29
27 28 29 30
XC2
55
XC
30 28 27
XT3
57
81 PE 61
XT3
BT5
61
1
25
2
7
4 5 81
81 PE 61
XC3
SDCV
XC3
SDCV
3
81
3
*
SMR
TS
2
1
6
61
1
2
3
81
6
ON / OFF
9
8
6 61 PE 7 4 5 81
XC3
SDCV
Page.14
Unit mounted communications parameters
UNITED MOUNTED COMMUNICATION PARAMETERS
1. Unit mounted communications parameters
2. Communication parameters on DHW module (PAR menu)
3. (System type = 7  setting on machine, System type = 1…….6  setting on DHW,menu CNF)
4.
DHW and ANTILEGIONELLA scheduling (DHW , SCH menu)
Parameter
1
machine communication
Mnemonic
name
Description
Default
Min
Max
163
RemMode
Remote input setting 0=H/C from ID
1=H/C from keypad or supervisor
1
0
1
164
Address
ModBus serial address
1
0
127
165
Baud Rate
Baud Rate (0=4800 / 1=9600)
1
0
1
166
Parity
Parity 0=NO / 1=YES
0
0
1
213
CommandH2O
Set up the priority of who determines the request of sanitary water
0
0
1
50
EnH20sanitaria
Sanitary water valve control enabling
2
0
2
CommandH2O=1 :the request of production of domestic hot water is taken only by the
supervisor (activation and deactivation), or the machine digital input status is always ignored.
164,165,166 parameters must be the same as 33,34,35 parameters of DHW module
Page.15
Communication parameters on DHW module
COMMUNICATION PARAMETERS ON DHW MODULE
2
DHW communication

Parameter
 1 min.  OK
As soon as it is powered, on the display
will appear
LOAD it is
necessary to wait 1 minute for the
software loading
Mnemonic
name
Description
Default
Min
Max
P33
Index
Index: switich address
1
0
127
P34
Baud Rate
BaudRate 0=4800 1 :9600 2:19200
1
0
1
P35
Parita
Parity (0=no, 1=ODD, 2=Even)
0
0
1
P49
EnableBT2
EnableBT2
0 = absent probe 1= present probe
1
0
1
P69
TimeOutRete
TimeOutRete: Timeout time for serial communication (Modbus)
60
1
600
I09
Interazione
Interaction 0 = electromech., 1 = via bus
1
0
1
I27
EnSolare
0= managing DHW 3-ways valve 1=enabled solar
0
0
1
Resistance forcing 0 = disabled N = the set value idicates the temperature in °C
under which the resistances are forced in On.
I36
How to modify the parameters in the PARAMETER LIST menu
1 First screenshot
2 Select Log User
3 Confirm
4 Insert password
5 Confirm password
6 Select menu
How to modify the parameters
6 Confirm
7 Select parameter
8 Confirm
9 Modify parameter
10 Confirm
11 Main menu (press X twice)
Slide PASSWORD menu and set MDS parameter = 0 (Master)
Page.16
System type managed
SYSTEM TYPE MANAGED
System 1
WBAN o WSHN-EE + DOMESTIC HOT WATER + RADIATORS (pag. 1)
System 2
WBAN o WSHN-EE + DOMESTIC HOT WATER + RADIATORS + RADIANT PANELS (pag.3)
System 3
WBAN o WSAN-XPR o WSHN-EE + DOMESTIC HOT WATER + RADIATORS + BOILER + RADIANT
PANELS (pag.5)
System 4
WSAN-XPR o WSHN-EE + DOMESTIC HOT WATER + RADIANT PANELS (pag.7)
System 5
WSAN-XPR o WSHN-EE + DOMESTIC HOT WATER + FAN COILS (pag.9)
System 6
WSAN-XPR o WSHN-EE + DOMESTIC HOT WATER + FAN COILS + RADIANT PANELS (pag .11)
System 7
WBAN o WSAN-XPR o WSHN-EE o WSAN-EE + BOILER + FAN COILS + RADIANT PANELS (pag.13)
How to have access at the menu (CNF system parameters
1 First screenshot
2 Select Log User
list –
PAR DHW parameters
3 Confirm
Access at CNF menu
Set C0….C02 parameters as shown in the table on page
list –
SCH scheduler
System type 7 see on page 19
parameters list
– PAS password change)
4 Insert password
5 Confirm password
9 Modify parameter
10 Confirm
6 Select menu
How to modify the parameters in the SYSTEM CONFIGURATION menu
6 Confirm
Page.17
7 Select parameter
8 Confirm
11 Main menu (press X twiùce)
DHW parameters
DHW PARAMETERS
Parameters
Mnemonic
Description
Sys. 1
Sys. 2
Sys. 3
Sys. 4
Sys. 5
Sys. 6
C00
Config Impianto
Type of managed system
1
2
3
4
5
6
C01
EnTermAmb
C02
EnTermRad
Radiant panel thermostat is present
CLIMATIC COMPENSATIONS
Ambient thermostat is present
1
1
1
1
1
1
1
1
C03
CompExt
Outside temp. compensation enabling
0
0
0
0
C04
CextMaxH
Outside temp. of winter max. correction
15
0
0
15
15
15
C05
CextMinH
Outside temp. of winter min. correction
0
0
0
0
C06
MaxCExtH
Winter correction max. value
10
10
10
10
C07
EnCompExtR
C08
SetMinC
C09
Radiant compensation enabling of the outside temp.
0
0
Min. Setpoint in cooling
18
18
SetMaxC
Max. Setpoint in cooling
23
23
C10
TMinExtC
Min. outside temp. on cooling
20
20
C11
TMaxExtC
Max. outside temp. on cooling
35
35
C12
SetMinH
Min. Setpoint in heating
30
30
C13
SetMaxH
Max. Setpoint in heating
35
35
C14
TMinExtH
Min. outside temp. on heating
5
5
C15
TMaxExtH
Max. outside temp. on heating
HEAT PUMP OPTION
20
20
C16
0
0
0
0
0
C17
URProbeExt
Enables ext. RH% probe
HEAT PUMP SETPOINT
SetCool
Summer Setpoint
5.7
5.7
5.7
5.7
5.7
C18
SetHeat
Winter Setpoint
41.2
41.2
41.2
41.2
41.2
C19
SetMantCool
Summer Maintenance Setpoint
20
20
20
20
20
C20
SetMantHeat
Winter Maintenance Setpoint
30
30
30
30
30
30
C21
SaltoH2O
Differential between heat pump Setpoint and SetAccumulo
3.0
6.0
6.0
6.0
6.0
6.0
C22
SetPointR
25
25
25
C23
DeltaMantACS
DHW production maintenance Delta
10.0
10.0
10.0
C24
BandaSanitaria
DHW production band
2.0
2.0
2.0
2.0
2.0
2.0
C25
SetAccumACS
DHW production storage set
45.0
45.0
45.0
45.0
45.0
45.0
C26
SetLegioACS
DHW production Legio set
65.0
65.0
65.0
65.0
65.0
65.0
C27
SetHotH2OACS
DHW production Set Hot H2O
60.0
60.0
60.0
60.0
60.0
60.0
41.2
Radiant Setpoint
DHW OPTION
The parameters in common with the heat pump must be modified
and the one memorized on the module.
Page.18
0
10.0
25
10.0
10.0
only by the DHW module, on the contrary it is produced conflict between the datum memorized on the heat pump
heat pump parameters
HEAT PUMP PARAMETERS
This system is directly managed by heat pump because is without DHW (domestic hot water)part .
Control on PDC the following parameters
Parameters
Mnemonic
Description
Sys. 7
CLIMATIC COMPENSATIONS
9
CompExt
External temperature compensation enabling
0
12
CextMaxH
Ext. temp. for max. winter correction
15
13
CextMinH
Ext. temp. for min. winter correction
0
15
MaxCExtH
Max. value of winter correction
10
190
EnCompExtR
External temperature radiating
compensation enabling
0
194
SetMinC
Min. set-point in cooling
18
195
SetMaxC
Max. set-point in cooling
23
196
TMinExtC
Min. external temperature in cooling
20
197
TMaxExtC
Max. external temperature in cooling
35
198
SetMinH
Min. set-point in heating
30
199
SetMaxH
Max. set-point in heating
35
200
TMinExtH
Min. external temperature in heating
5
201
TMaxExtH
Max. external temperature in heating
20
156
URProbeExt
HEAT PUMP OPTION
Enables external RH% probe
0
HEAT PUMP SETPOINT
32
SetCool
Summer Set Point
5.7
33
SetHeat
Winter Set Point
41.2
42
SetMantCool
Summer maintenance Set Point
20
43
SetMantHeat
Winter maintenance Set Point
30
192
SetPointR
Radiating set-point
25
Page.19
Symbols visualization
SYMBOLS VISUALIZATION
LED
Page.20
NAME
MEANING
SUMMER
On: it indicates summer
WINTER
On: it indicates winter
3-WAY VALVE
Off: it indicates the valve commutated on the system
On: it indicates the valve commutated on DHW
Flashing: it indicates the DHW production with heat pump in progress
3
ROOM PUMP
Off: it indicates the room pump off
On: it indicates the room pump on by request of the ambient thermostat
Flashing: it indicates the room pump on without ambient thermostat
4
RADIANT PUMP
Off: it indicates the radiant pump off
On: it indicates the radiant pump on by request of the radiant thermostat
Flashing: it indicates the radiant pump on without radiant thermostat
RESISTANCES
Off: it indicates resistances off
On: it indicates resistances on
STORAGE
On: it indicates the active storage function
ANTILEGIO
On: it indicates the active antilegionella function
CIRCULATION PUMP
Off: it indicates the circulation pump off
On: it indicates the circulation pump on
ALARM
Off: it indicates no alarm
On: it indicates at least one alarm
Flashing: it indicates at least one warning
OFFLINE
Off: it indicates Modbus communication
On: it indicates no Modbus communication with the heat pump
DHW keyboard : only for user
DHW KEYBOARD : ONLY FOR USER
START-UP OPERATIONS SEQUENCE:
1.
Set date / hour
2.
choose SYSTEM STATE
3.
choose SYSTEM SEASON
4.
set DHW setpoint
5.
set MAINTENANCE DELTA
Back to main menu
Scrolling up
Scrolling down
Confirm
To come back to the main menu press
or automatically after 60 sec.
YR
TIME

 1 min.  OK
PROBES
scheduler clock
(DHW production and antilegionella
cycles)
Temperature probe reading
As soon as it is powered, on the display will appear
LOAD it is necessary to wait 1 minute for the software
loading
ALARM
USER
Page.21
It displays the ACTIVE alarms
(visible only if active alarms are
present)
Year
MON
Month
DAY
Day
HR
Hours
MIN
Minutes
SEC
Sec
Acc1
BT1 probe
Acc2
BT2 probe
IN
Return H2O (read on heat pump)
OUT
BT1
BT2
Supply H2O (read on heat pump)
BT1 in alarm
BT2 in alarm
H2O
storage temp. no available
RES
Resistance alarm
FLO
Flow switch alarm of charged installation
PDC
Heat pump in alarm or offline
LTR
Resistance alarm on for low temperature of the storage
SYSTEM STATUS
SYSTEM SEASON
OFF – DHW only – system only - DHW + system
DHW SETPOINT
Dhw temperature
MAINTENANCE DELTA
MNITENANCE SET = min DHW temperature = DHWsetpoint –
maintenance delta
Summer / Winter
DHW production and antilegionella cycle
DHW PRODUCTION
ANTILEGIONELLA CYCLE
Request by scheduler
Heat pump activation
LegioSetPoint
Storage SetPoint
ELECTRIC RESISTANCE zone
Sanitary Band
Sanitary Band
Storage SetPoint
Maintenance SetPoint
ELECTRIC RESISTANCE/ heat
pump
Sanitary Band
I 15
STORAGE phase

It is disabled in the time bands set by the scheduler
Par
Description
range
UM
def

During the recharging the heat pump is activated if temp < Storage SetPoint - Sanitary
Band
I14
EnProdLegio
0-1
flag
1

It end when Storage SetPoint is reached
I15
DurataLegio
0-120
min
5

To be re-enabled the scheduler must set at zero and then reactivated the control
I20
EnRES : 0=without resistances, 1=With resistances
0-1
flag
0
I21
NumGradiniRES
0-2
num
0
MAINTENANCE phase

The heat pump is activated if temp < Maintenance SetPoint

The heat pump is de-activated when temp = Storage SetPoint

It ends when the scheduler enables again the STORAGE phase
SCH-scheduling
The function is active only with parameters I14 and I20 =1
The antilegionella cycle:

Is enabled in the time bands set by scheduler

It uses the electric resistances if t > Storage SetPoint

It uses the heat pump in the Storage SetPoint zone….. Sanitary Band if the heat pump was already
active for the DHW production, otherwise it uses the resistances

It is always priority on the ambient thermoregulation
Par
Description
Meaning
S01
StartAccumuloLegio
Start hour of storage/antilegionella
DHW production
S02
StopAccumuloLegio
Stop hour of storage/antilegionella

Antilegionella cycles
S03
PeriodoLegio
0=weekly, 1=monthly

Activation of the circulation pump on DHW storage
S04
GiornoSettLegio
0=mon,….,6=sun
S05
GiornoMeseLegio
It is possible until the 28th month’s day
S06
StartPompa
Start hour of the daily circulation
S07
StopPompa
Stop hour of the daily circulation
Setting of the time bands :

By S01 and S02 the DHW production is enabled ; the antilegionella cycles use the same hours but
only during days defined by parameters S03/4/5
Page.22
300 or 500 - litres domestic hot water kit
300 OR 500 - LITRES DOMESTIC HOT WATER KIT
+-
Ø 1" 1/4 GAS F
ACS
87
AP5
81
RS 485
GND
+-
3
2
1
6
L3
XC
L1
61
N
XC
+
BT2
-
ACS
Ø 1" 1/4 GAS F
2
T1
T2
GND
400/3/50+N
ST2
XC L2
86
83
1
*
N
GND
PEE20016 / 18 KBQRE3X / KBQRE5X
400/3/50+N
BT1
T3
R1
2
Ø 1" 1/4 GAS F
1
Ø 1" GAS F
RS485
set-up for solar
*
Recirculation on domestic hot water facility
The magnesium sacrificial anodes assure the boiler anti-corrosive protection .
The wear status of the magnesium bar can be checked without emptying the boiler .
The anode can be replaced if screwing the valve on the plug the water comes out.
1x
Wiring diagram with module for the
management of the domestic hot water
production
1x
1” ¼ 3-way switching valve
1x
PEE20016 300 - litres storage with a 2KW resistance; Dimensions 600 x 1680mm .
1x
Page.23
PEE20018 500 - litres storage with a 4KW resistance; Dimensions 760 x 1690mm.
1x
1” ¼ non-return valve
AP5
RS 485
GND
+-
Serial communication board + twisted
cable from 15 m.
Domestic hot water kit control
DOMESTIC HOT WATER KIT CONTROL
+-
ST2
81 90
87
AP5
81
L
XC L3
86
N
L2
L1
RS 485
GND
+-
Ø 1" 1/4 GAS F
N
GND
PEE20019 CACSX
400/3/50+N
N
61
1
ACS
XC
GND
2
BT2
ACS
83
L
L
N
ST2
+
-
XC
COM
AI2
Ø 1" 1/4 GAS F
2
T1
T2
T3
COM
400/3/50+N
BT1
AI1
R1
Ø 1" 1/4 GAS F
Ø 1" GAS F
RS485
Recirculation on domestic hot water facility
Module is made up of:

1x

DIMENSIONS

2 water temperature probes 5 m. length. (BT1, BT2)
1 safety thermostat 5 m. lenght (ST2)
Power circuit and and resistance control comprehensive of short circuit protection (resistance not provided by Clivet)
(L x H x P) 290x410x140mm.
Page.24
Kit for management of radiant panels with connections of 1” – 1” ¼
1
KIT FOR MANAGEMENT OF RADIANT PANELS WITH CONNECTIONS OF 1” – 1” ¼
PEE20012 / 13 KVMSP1X / KVMSP2X
UNDERFLOOR
HEATING
RETURN
HEAT
PUMP
UNDERFLOOR
HEATING OUTLET
3
*
23 24 25
6
*
2
1
11
8 6 42
CN 2 0
3 1
9 753 1
1
SMR
Page.25
XT3
XC2
XT3
61
55
29
TS
Kit for management of radiant panels with connections of 1” – 1” ¼
KIT FOR MANAGEMENT OF RADIANT PANELS WITH CONNECTIONS OF 1” – 1” ¼
PEE20012 / 13 KVMSP1X / KVMSP2X
*
11 9
7
5
3
1x
Connection diagram
23 24 25
1” 3-way valve with ON-OFF actuator (PEE20012) for
PDC (heat pump) from 4 to 18kW
1
CN3
XT3
61
12 10 8
6
4
2
23
25
1 1/4” 3-way valve with ON-OFF actuator (PEE20013)
for PDC (heat pump) from 19 to 30kW
1x
KA1
1x
SMR
53
Supply temperature probe of radiant panels (13 metres)
KA1
1x
54
Temperature safety thermostat (TS)
2
3
2 3
1x
KA1
1
1
Relay
Radiant valve
Page.26
Boiler management kit
BOILER MANAGEMENT KIT
PEE20014 KVICX
The unit is disabled and the boiler is activated if :
 the outside temperature measured by the probe on the unit is lower than the
limit defined by parameter 88.
 The system temperature measured by BT5 is higher than the limit defined by
parameter 86.
30
28
27
29
YV 3
12 10 8
6
4
2
11 9
5 3
1
2
CN3
7
3
12 10 8
6
4 2
CN3
11 9
7 5 3
1
2
1
3
81
61
PE
YV 5
2
1
3
YV 1
PEE20015
1
2
3
4
5
6
7
11 9
12 10 8
CN3
1
27 28 29 30
XT3
1
3
22 23 24 25 26
27 28 29 30
BT 5
27 28 29 30
22 23 24 25 26
2
22 23 24 25 26
XT3
YV 6
34
29
Assemble the PLUG-IN expansion module above the main electronic module using
the fitting SPACERS.
Check that all pins under the board are correctly inserted in the connector.
Connect as indicated in the diagram.
Before powering up the unit check the parameter configuration : 140 = 1 (PLUG-IN
module enabling).
PAR
85
2
DEFAULT*
MEANING
Enables Boiler+Heat pump function
0
86
Water temperature value: over it the heat pump is disabled
and the YV 5 / 6 output is still excited
55 °C
87
Hysteresis for heat pump enabling and YV 5 / 6 deactivation
2 °C
88
Outside temperature threshold: below it the boiler is enabled
-5 °C
89
Hysteresis for outside temperature for heat pump activation
3 °C
1
3
ON / OFF
PEE20015
8 9 PE 81 4 5 61 7 6
XC3
SDCV
Motorized 2-way valve for
boiler interception for 1”
2x
27 28 29 30
Page.27
22 23 24 25 26
1x
12 10 8
6
4
2
11 9
5 3
1
CN3
7
2x
100 - litres
hydraulic circuitbreaker supplied by
request
Motorized 2-way valve for
heat pump for 1”
KDT3VX valve control board to connect to the heat pump
* The values are indicative and can be updated ; in case of doubt contact an
authorized service Centre.
1x
1x
Connector box of valve control
BT5
Temperature probe 12 metres
Boiler management kit (only for WBAN)
BOILER MANAGEMENT KIT (only for WBAN)
PEE20020 KVICX
The unit is disabled and the boiler is activated if :
 the outside temperature measured by the probe on the unit is lower than the
limit defined by parameter 88.
 The system temperature measured by BT5 is higher than the limit defined by
parameter 86.
22 23 24 25 26
27 28 29 30
XT3
34
29
2
BT 5
1
3
30
28
27
29
YV 3
2
1
3
81
61
PE
YV 5
2
1
3
YV 1
PEE20015
3
CN3
11 9
12 10 8
7
6
5
4
2
1
XT3
YV 6
PAR
1
ON / OFF
PEE20015
8 9 PE 81 4 5 61 7 6
XC3
SDCV
2x
1x
Page.28
Motorized 2-way valve for
boiler interception for 1”
BT5
2x
85
Enables Boiler+Heat pump function
86
Water temperature value: over it the heat pump is disabled
and the YV 5 / 6 output is still excited
2
3
100 - litres
hydraulic circuitbreaker supplied by
request
Motorized 2-way valve for
heat pump for 1”
DEFAULT*
MEANING
0
55 °C
87
Hysteresis for heat pump enabling and YV 5 / 6 deactivation
2 °C
88
Outside temperature threshold: below it the boiler is enabled
-5 °C
89
Hysteresis for outside temperature for heat pump activation
3 °C
* The values are indicative and can be updated ; in case of doubt contact an
authorized service Centre.
1x
Connector box of valve control
Temperature probe 12 metres
100 - litres hydraulic circuit-breaker
100 - LITRES HYDRAULIC CIRCUIT-BREAKER
PEE20015 KSAX
120
220
50
BLEED 1/2" GAS F
500 Ø
4 x IN/OUT
1"1/4 GAS F
120
4 x IN/OUT
1"1/4 GAS F
220
900
2 x 1/2" GAS F
DISCHARGE 1/2" GAS F
100 - litres hydraulic circuit-breaker
1x
Page.29
Max. operating pressure 6 bar
Diameter 500mm, Height 900mm, 8 connections 1” ¼ e 4 connections ½”
Wall electronic ambient thermostat
WALL ELECTRONIC AMBIENT THERMOSTAT
PEE20017
KITERAX
For use see details on PEE20017 manual
BATTERY REPLACEMENT
CONNECTIONS
Page.30
DIMENSIONS
ASSEMBLE
Water connection hoses with 1” – 1” ¼ connections
WATER CONNECTION HOSES WITH 1” – 1” ¼ CONNECTIONS
2x
Connection of 1” (PEE20010) between
the unit and the system. Lenght 300 for
heat pump from 4 to 18kW
2x
Connection of 1 ¼” (PEE20011) between
the unit and the system. Lenght 300 for
heat pump from 19 to 30kW
Page.31
PEE20010 / 11 KTFL1X/ KTFL2X
Index
INDEX
ELECTRICAL AND HYDRAULIC SYSTEMS
WBAN o WSHN-EE + DOMESTIC HOT WATER + RADIATORS .......................................................................................................... page 1
WBAN o WSHN-EE + DOMESTIC HOT WATER + RADIATORS + RADIANT PANELS ....................................................................... page 3
WBAN o WSAN-XPR o WSHN-EE + DOMESTIC HOT WATER + RADIATORS + BOILER + RADIANT PANELS .............................. page 5
WSAN-XPR o WSHN-EE + DOMESTIC HOT WATER + RADIANT PANELS ....................................................................................... page 7
WSAN-XPR o WSHN-EE + DOMESTIC HOT WATER + FAN COILS .................................................................................................... page 9
WSAN-XPR o WSHN-EE + DOMESTIC HOT WATER + FAN COILS + RADIANT PANELS ................................................................ page 11
WBAN o WSAN-XPR o WSHN-EE o WSAN-EE + BOILER + FAN COILS + RADIANT PANELS ....................................................... page 13
ACCESSORY KIT
Unit mounted communication parameters .......................................................................................................................................... pag. 15
Communication parameters on DHW module ..................................................................................................................................... pag. 16
System type managed .......................................................................................................................................................................... pag. 17
DHW parameters ................................................................................................................................................................................... pag. 18
Heat pump parameters ......................................................................................................................................................................... pag. 19
Symbol display ...................................................................................................................................................................................... pag. 20
DHW keyboard : only for user .............................................................................................................................................................. pag. 21
DHW production and antilegionella cycle ........................................................................................................................................... pag. 22
PEE20016 / 18 300 or 500 - litres domestic hot water kit KBQRE3X / KBQRE5X ............................................................................ pag. 23
PEE20019 Domestic hot water kit control CACSX ............................................................................................................................. pag. 24
PEE20012 /13 Kit for management of radiant panels with connections of 1” – 1” ¼ KVMSP1X / KVMSP2X............................... pag. 25
PEE20014 Boiler management kit KVICX ............................................................................................................................................ pag. 27
PEE20020 Boiler management kit (only for WBAN) KVICX .............................................................................................................. pag. 28
PEE20015 100 - litres hydraulic circuit-breaker KSAX ...................................................................................................................... pag. 29
PEE20017 Wall electronic ambient thermostat KITERAX .................................................................................................................. pag. 30
PEE20010 / 11 Water connection hoses with 1” – 1” ¼ connections KTFL1X / KTFL2X ................................................................ pag. 31
Page.32
31-05-10 MODIFICATIONS RISPECT REV.01
Valve wirings pages 6, 14, 27
MODIFICATIONS RISPECT REV.0
Revision images
On the beginning pages: insert text about destination and purpose of the guide
From page 15 to 22 revision: heat pump and DHW parameters and operations
Page 24 entered PEE20019
Page 25 - 26 up-to-date electrical connections, inserted image
Page 28 entered PEE20020
Page 31 up-to-date idex
New type of codification used
MODIFICATIONS RISPECT REV.00
Page 16 added parameter I36
Page 21 added active LTR or FLO alarm
Page 22 replaced DHW graphic
Page 23 and 24 image correction
Page 26 correction of the valve description
Page 27 and 28 correction of data tables
Page.33
Page.34
CLIVET SPA
Feltre (BL) ITALY
Tel. + 39 0439 3131
Fax + 39 0439 313300
[email protected]
CLIVET UK LTD
Fareham (Hampshire) U.K.
Tel. + 44 (0) 1489 572238
Fax + 44 (0) 1489 573033
[email protected]
CLIVET SAS
Verrierès le Buisson - FRANCE
Tel. + 33 (0)1 69 20 25 75
Fax + 33 (0)1 69 20 60 76
[email protected]
CLIVET ESPAÑA S.A.
Madrid - SPAIN
Tel. + 34 91 6658280
Fax + 34 91 6657806
[email protected]
CLIVET GmbH
Norderstedt - GERMANY
Tel. +49 (0) 40 32 59 57-0
Fax +49 (0) 40 32 59 57-194
[email protected]
CLIVET NEDERLAND B.V.
Amersfoort - Netherlands
Tel. + 31 (0) 33 7503420
Fax + 31 (0) 33 7503424
[email protected]
CLIVET RUSSIA
Moscow - RUSSIA
Tel. +74956462009
Fax +74956462009
[email protected]
CLIVET MIDEAST FZC
Dubai - UAE
Tel. +97 14 3518501
Fax +97 14 3518502
[email protected]
The data contained in this bulletin is not binding and may be changed by the manufacturer without prior notice.
All reproduction, even partial, is PROHIBITED.
© Copyright - CLIVET S.p.A. - Feltre (BL) - Italia
CLIVET TF AIR SYSTEMS (P) LTD.
Malur - INDIA
Tel. +91 8151 232683/5
Fax +91-8151-232684
[email protected]