Download ACC - anti-sweat controller - User manual

Transcript
ACC
Anti-sweat controller
User manual
LEGGI E CONSERVA
QUESTE ISTRUZIONI
READ AND SAVE
THESE INSTRUCTIONS
IMPORTANT WARNINGS
CAREL bases the development of its products on decades of experience in HVAC, on the continuous investments in technological innovations to products, procedures and strict quality
processes with in-circuit and functional testing on 100% of its products, and on the most innovative production technology available on the market. CAREL and its subsidiaries nonetheless
cannot guarantee that all the aspects of the product and the software included with the product respond to the requirements of the final application, despite the product being developed
according to start-of-the-art techniques. The customer (manufacturer, developer or installer of the final equipment) accepts all liability and risk relating to the configuration of the product in
order to reach the expected results in relation to the specific final installation and/or equipment. CAREL may, based on specific agreements, acts as a consultant for the positive
commissioning of the final unit/application, however in no case does it accept liability for the correct operation of the final equipment/system.
The CAREL product is a state-of-the-art product, whose operation is specified in the technical documentation supplied with the product or can be downloaded, even prior to purchase, from
the website www.carel.com.
Each CAREL product, in relation to its advanced level of technology, requires setup / configuration / programming / commissioning to be able to operate in the best possible way for the
specific application. The failure to complete such operations, which are required/indicated in the user manual, may cause the final product to malfunction; CAREL accepts no liability in such
cases.
Only qualified personnel may install or carry out technical service on the product.
The customer must only use the product in the manner described in the documentation relating to the product.
In addition to observing any further warnings described in this manual, the following warnings must be heeded for all CAREL products:
• Prevent the electronic circuits from getting wet. Rain, humidity and all types of liquids or condensate contain corrosive minerals that may damage the electronic circuits. In any case, the
product should be used or stored in environments that comply with the temperature and humidity limits specified in the manual.
• Do not install the device in particularly hot environments. Too high temperatures may reduce the life of electronic devices, damage them and deform or melt the plastic parts. In any
case, the product should be used or stored in environments that comply with the temperature and humidity limits specified in the manual.
• Do not attempt to open the device in any way other than described in the manual.
• Do not drop, hit or shake the device, as the internal circuits and mechanisms may be irreparably damaged.
• Do not use corrosive chemicals, solvents or aggressive detergents to clean the device.
• Do not use the product for applications other than those specified in the technical manual.
All of the above suggestions likewise apply to the controllers, serial boards, programming keys or any other accessory in the CAREL product portfolio.
CAREL adopts a policy of continual development. Consequently, CAREL reserves the right to make changes and improvements to any product described in this document without prior
warning.
The technical specifications shown in the manual may be changed without prior warning.
The liability of CAREL in relation to its products is specified in the CAREL general contract conditions, available on the website www.carel.com and/or by specific agreements with customers;
specifically, to the extent where allowed by applicable legislation, in no case will CAREL, its employees or subsidiaries be liable for any lost earnings or sales, losses of data and information,
costs of replacement goods or services, damage to things or people, downtime or any direct, indirect, incidental, actual, punitive, exemplary, special or consequential damage of any kind
whatsoever, whether contractual, extra-contractual or due to negligence, or any other liabilities deriving from the installation, use or impossibility to use the product, even if CAREL or its
subsidiaries are warned of the possibility of such damage.
Disposal of the parts of the controller:
INFORMATION FOR USERS ON THE CORRECT HANDLING OF WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT (WEEE)
In reference to European Union directive 2002/96/EC issued on 27 January 2003 and the related national legislation, please note that:
1. WEEE cannot be disposed of as municipal waste and such waste must be collected and disposed of separately;
2. The public or private waste collection systems defined by local legislation must be used. In addition, the equipment can be returned to the distributor at the end of
its working life when buying new equipment.
3. The equipment may contain hazardous substances: the improper use or incorrect disposal of such may have negative effects on human health and on the
environment;
4. The symbol (crossed-out wheeled bin) shown on the product or on the packaging and on the instruction sheet indicates that the equipment has been introduced
onto the market after 13 August 2005 and that it must be disposed of separately;
5. In the event of illegal disposal of electrical and electronic waste, the penalties are specified by local waste disposal legislation
Contents:
1.
Introduction........................................................................................................................................................................................................ 7
1.1
1.2
Models available.................................................................................................................................................................................................................................................7
Main features........................................................................................................................................................................................................................................................7
2.
User interface.................................................................................................................................................................................................... 8
3.
Installation .......................................................................................................................................................................................................... 8
4.
Programming the instruments .............................................................................................................................................................. 10
4.1
5.
Default settings................................................................................................................................................................................................................................................. 10
Accessories ..................................................................................................................................................................................................... 11
5.1
5.2
6.
Parameter copying key............................................................................................................................................................................................................................... 11
RS485 serial interface board.................................................................................................................................................................................................................. 11
Description of the functions ................................................................................................................................................................... 12
6.1
6.2
6.3
6.4
6.5
6.6
6.7
6.8
6.9
7.
Dewpoint calculation .................................................................................................................................................................................................................................... 12
Anti-sweat control........................................................................................................................................................................................................................................... 12
Master management .................................................................................................................................................................................................................................... 13
Slave management ....................................................................................................................................................................................................................................... 13
PI control (proportional and integral)................................................................................................................................................................................................ 13
Overriding the output ................................................................................................................................................................................................................................... 14
Phase control modes ................................................................................................................................................................................................................................... 14
Automatic adaptation to the mains frequency ........................................................................................................................................................................... 14
Alarm situations and alarm management ..................................................................................................................................................................................... 14
Description of the operating parameters......................................................................................................................................... 16
7.1
8.
Summary table of operating parameters ....................................................................................................................................................................................... 23
Tables of alarms and signals ................................................................................................................................................................. 25
8.1
8.2
9.
Alarms..................................................................................................................................................................................................................................................................... 25
Signals.................................................................................................................................................................................................................................................................... 25
Supervision ...................................................................................................................................................................................................... 26
10.
10.1
10.2
10.3
Specifications and connections ...................................................................................................................................................... 27
Electrical specifications .............................................................................................................................................................................................................................. 27
Connections........................................................................................................................................................................................................................................................ 28
Dimensions and assembly....................................................................................................................................................................................................................... 28
ACC –Anti-sweat controller
1. Introduction
The ACC device is a microprocessor controller that prevents the formation of condensate on cold surfaces by measuring the ambient dewpoint and
heating the cold surface so as to keep it at a higher temperature than the dewpoint. The heating is performed by controlling the voltage applied to
special heaters, using the phase control output on the device.
1.1
Models available
Two models are available.
The first is a controller complete with RS485 serial interface.
The second features a socket for an optional RS485 serial interface board.
ACC0082100
Anti-sweat controller with RS485;
ACC0082000
Anti-sweat controller with fitting for RS485 option.
1.2
Main features
Power supply
The supply is 230 Vac mains, 50/60 Hz. Operation is adapted automatically to the mains frequency.
Appearance and ergonomics
The device has been designed so as to also allow outdoor installation, with specific protection against water and dust guaranteed by the case.
Dewpoint measurement
The dewpoint is automatically calculated according to the ambient humidity and temperature, measured by special probe/probes.
Manual setting or configuration by parameter
The operation of the ACC controller can be set as follows:
ƒ manually, using the trimmers and dipswitches (restricted to the main functions);
ƒ using the internal parameters (via programming key or serial line).
In the first case, the main functions are available for the simple use of the controller and setting by non-specialist personnel.
In the second case, the available functions are increased considerably, allowing maximum operating flexibility.
External alarm management/on-off signal
This is used to force the output to a preset value or to enable/disable operation when a protector is activated or upon receiving an external control
signal.
PI control (proportional and integral)
This function combines normal proportional control with an integral action that, if correctly set based on the specific operating conditions, allows more
accurate temperature control.
Master/Slave mode
This function is used to create small networks of anti-sweat controllers, configuring one controller as the Master, which calculates the dewpoint and then
sends this value to the others controllers connected in the network and configured as Slaves. This means that just one humidity and room temperature
probe can be used for the entire network.
Serial connection
An RS485 serial output is available for connection via two wires plus shield to the supervisor or telemaintenance network that support the Carel
supervisor protocol or for the construction of Master/Slave networks.
Phase control function
The control of the power section can be modified to adapt it to the type of load.
Index of protection
The gasket inside and the materials used to make the case guarantee the controller IP43 index of protection, which can be increased to IP54 when using
suitable cable glands and cables.
Fastening
The device is fastened using 4 screws.
CE mark/Electromagnetic compatibility
The ACC controller is compliant with the EU standards on electromagnetic compatibility, while quality and safety are ensured by the CAREL ISO 9001
certified design and production system and by the CE mark on the product.
Code +030220751 – Rel. 1.2 – 09/10/07
7
ACC –Anti-sweat controller
2. User interface
The status of the controller is displayed using LEDs that are only visible with the cover open.
The LEDs indicate:
ƒ power on;
ƒ serial connection status;
ƒ alarm status.
To set the operation of the controller, 1 trimmer and 4 dipswitches are available for the main functions, while internal parameters are used to set all the
other functions. The parameters can be set using the programming key, while access to the parameters for display and setting, as well as access to the
variables that represent the status of the controller, is available via serial line.
3. Installation
To install the controller, proceed as follows, with reference to the connection diagrams shown at the end of the manual.
IMPORTANT: 230 Vac mains voltage present on the board.
1. Connect the power supply:
Fit a 10A T (or lower rating) fuse in the power supply line (live L), based on the maximum current expected.
2. Connect the probes and control signals: the probes can be installed at a maximum distance of 10 m from the controller, as long as cables
with a minimum cross-section of 1 mm2 are used. To improve immunity to disturbance, use shielded cables (connect just one end of the
shield to the earth).
3. Program the instrument: for a more detailed description see the chapter “Programming the instruments”.
4. Connect the actuators: the actuators should only be connected after having programmed the controller. In this regard, the maximum current
indicated in the “technical specifications” must be considered.
If the controller is used in residential environments (IEC-EN55014-1) a shielded cable must be used.
5. Connect to the serial network: the controller is fitted with a connector for housing a serial interface board, FCSER00000, for connection to the
supervisor network. Use a shielded cable with the shield connected to GNX.
WARNINGS:
The controller must be installed so as to ensure normal cooling, according to the flow of air. Normally, if there are no cooling fans, it is installed
vertically, with the cable outlets downwards.
The temperature of the surface the control is mounted on must not exceed 70° C.
The index of protection is guaranteed only if the following precautions are heeded:
• only use one cable in each cable gland
• perforate the membrane of the cable gland based on the diameter of the cable used; to ensure tightness, the hole must be significantly
smaller than the diameter of the cable used. Use the pre-cut sections on the membrane where possible
• pass the cable through the cable gland, ensuring tightness
• if the installation requires more than one cable in the same cable gland or cables with a smaller diameter than the hole made, it is the
installer’s responsibility to guarantee the appropriate index of protection; for example, using a sheath to increase the thickness or to hold the
cables together, making sure there are not gaps.
The maximum length of the connection cables is 10 m except where specified otherwise.
Size the cross-section of the power wires based on the current input of the load and the length of the cables.
If a shielded cable is used to connect the load, both ends of the shield should be earthed. On the controller side, the shield should be earthed using a
metal cable clamp screwed to the earth bar before the terminals (Fig.3.a).
Fig. 3.a
To ensure compliance with the safety standards, the electrical system must be fitted with a suitable switch or disconnector (compliant with standards IEC
60947-1 and IEC 60947-3), located near the appliance.
Code +030220751 – Rel. 1.2 – 09/10/07
8
ACC –Anti-sweat controller
If the appliance is used in a manner that is not specified by the manufacturer, the protection featured for the appliance may be compromised and the
appliance may be seriously damaged.
Avoid assembling the controllers in environments with the following characteristics:
ƒ relative humidity greater than 90% non-condensing;
ƒ strong vibrations or knocks;
ƒ exposure to continuous water sprays;
ƒ exposure to aggressive or pollutant atmospheres (e.g. sulphur or ammonia fumes, saline mist, smoke) so as to avoid corrosion and oxidisation;
ƒ strong magnetic and/or radio interference (for example, near transmitting antennae);
ƒ exposure of the controllers to direct sunlight or the elements in general.
Observe the following warnings when connecting the controllers:
ƒ The incorrect connection of the power supply may seriously damage the system.
ƒ Use cable ends suitable for the corresponding terminals.
Loosen each screw and insert the cable ends, then tighten the screws and slightly tug the cables to check that they are sufficiently tight; to tighten
the screws, do not use automatic screwdriver, or alternatively adjust to a torque of less than 50 Ncm. If spring terminals are used, compress the
spring using a screwdriver, insert the stripped wire then release the spring and slightly tug the cables to check that they are sufficiently tight.
ƒ Separate as much as possible (at least 3 cm) the signal cables from the cables carrying inductive loads and power cables to avoid possible
electromagnetic disturbance.
Never lay power cables (including the electrical cables) and probe signal cables in the same conduits.
Do not install the probe cables in the immediate vicinity of power devices (contactors, circuit breakers or similar). Reduce the path of the probe
cables as much as possible, and avoid spiral paths that enclose power devices.
Remember that the NTC temperature probes do not have polarity, and therefore the order the ends are connected is indifferent.
CLEANING THE INSTRUMENT.
When cleaning the instrument do not use ethyl alcohol, hydrocarbons (petrol), ammonia and derivatives. Use neutral detergents and water.
Code +030220751 – Rel. 1.2 – 09/10/07
9
ACC –Anti-sweat controller
4. Programming the instruments
The instruments are programmed by dipswitches and trimmer, and by setting the internal parameters accessible via programming key or via serial line.
The functions that can be set manually are shown in the tables below:
Dipswitch
Dip1
Select Master/Slave mode
Dip2
Select serial connection mode, Supervisor/LAN
Dip3
Select Trimmer mode
(Master only)
Dip4
Select digital input ID1 mode
Trimmer
SET
OFF:
ON:
OFF:
ON:
OFF:
ON:
OFF:
ON:
Function
Manual offset
Configuration
ID1=External alarm (Dip4 OFF)
ID1=External enabling signal (Dip4 ON)
Master
Slave
Supervisor
LAN
local manual offset
LAN manual offset
external alarm
external enabling signal
range
0.0 – “OFST par.” °C
Status of input ID1
Open
Closed
Open
Closed
Description
Alarm not active
alarm active
Controller enabled
Controller disabled, output 0%
Digital input ID1 is normally open by default. A parameter can be set to change the operating logic and manage it as a normally closed contact, in
which case the meaning of “Open” and “Closed” must be reversed.
4.1
Default settings
The functions that are available by setting the parameters are mostly disabled by default, as they need to be set based on the specific application.
Offset setting by trimmer
Differential setting
Digital input ID1
Digital input ID1
Output in the event of alarms
Master/Slave mode
Supervisor/LAN mode
Trimmer mode
PI control
Phase control function
Output ramp
Output linearisation
Code +030220751 – Rel. 1.2 – 09/10/07
from 0 to 5°C
2°C
external alarm (modifiable by dipswitch)
Normally open
100%
Master (modifiable by dipswitch)
Supervisor (modifiable by dipswitch)
Local offset (modifiable by dipswitch)
inactive
short impulse
5 seconds
active
10
ACC –Anti-sweat controller
5. Accessories
5.1
Parameter copying key
Programming key PSOPZKEY00/A0
The programming keys PSOPZKEY00 (Figure 5.1.a) and PSOPZKEYA0 (Figure 5.1.b) are used to copy the complete set of parameters relating to the
CAREL ACC controller parameters. The keys must be connected to the PROG KEY connector (4 pin AMP) fitted on the controllers, and work even
without switching the controller on (see the summary diagram in Figure 5.1.c.).
Fig. 5.a
Fig. 5.b
Fig. 5.c
Two functions are available, and are selected by using the two supplied dipswitches; these can be accessed by removing the
battery cover:
- load the parameters for a controller onto the key (UPLOAD - Fig. 5.1.d);
- copy from the key to a controller (DOWNLOAD - Fig. 5.1.e);
Warning: the parameters can only be copied between instruments with the same code and compatible software release. The
UPLOAD operation can, however, always be performed.
The following operations are used for the UPLOAD and/or DOWNLOAD functions, simply by changing the settings of the dipswitches on the key:
- open the rear cover on the key and position the 2 dipswitches according to the desired operation;
- close the rear cover on the key and insert the key in the connector on the controller;
- press the button and check the LED: red for a few seconds, then green, indicates that the operation was completed correctly.
Other signals or the flashing of the LED indicates that problems have occurred: refer to the table below;
- at the end of the operation, release the button, after a few seconds the LED goes OFF;
- remove the key from the controller.
LED signal
Red LED flashing
Green LED flashing
Red/green LED flashing
(orange signal)
Red and green LEDs on
Red LED on steady
LEDs off
Cause
Batteries discharged at start copy
Batteries discharged during copy
or at end of copy
Instrument not compatible
Error in data being copied
Data transfer error
Batteries disconnected
Meaning and solution
The batteries are discharged, the copy operation cannot be performed. Replace the batteries.
During the copy operation or at the end of the operation the battery level is low. Replace the
batteries and repeat the operation.
The parameter set-up cannot be copied as the connected controller model is not compatible. This
error only occurs for the DOWNLOAD function; check the code of the controller and run the copy
only for compatible codes.
Error in the data being copied. The instrument's EEPROM is corrupted, and therefore the key
cannot be copied.
The copy operation was not completed due to a serious error when transferring or copying the
data. Repeat the operation, if the problem persists check the key connections.
Check the batteries.
Table 5.a
5.2
RS485 serial interface board
The RS485 serial interface option (FCSER00000) shown in Figure 5.2.a is used to connect the instrument to the RS 485 serial network for supervision.
Figures 5.2.b and 5.2.c show the assembly of the interface in the instrument. Observe the correct polarity of the connector, making sure the protrusion
on the serial board matches the notch on the controller, without forcing the board.
Fig. 5.2..a
Code +030220751 – Rel. 1.2 – 09/10/07
Fig. 5.2.b
11
Fig. 5.2.c
ACC –Anti-sweat controller
6. Description of the functions
6.1
Dewpoint calculation
The dewpoint is only calculated in Master mode, based on values measured by the humidity and room temperature probes B1 and B2.
In Slave mode, the dewpoint is updated via serial by the Master or by the external supervisor and probes B1 and B2 are ignored (the inputs can be
disconnected).
Associated parameters
name
range
def.
ADG1
ADG2
FILT
Carel spv
var
I8
I9
I11
90 to 110
90 to 110
0 to 13
ADO1
ADO2
DEWP
PB1H
PB2T
PB1A
PB2A
A5
A6
A8
A21
A22
D23
D24
-20.0 to 20.0
-10.0 to 10.0
-50.0 to +99.9
0.0 to 100.0
-50.0 to +90.0
0/1
0/1
6.2
100
100
6
res.
UOM.
1%
1%
1
description
Probe B1 gain
Probe B2 gain
Probe filter
0.0
0.0
R/W
R
R
R
R
0.1%
0.1°C
0.1°C
0.1rH
0.1°C
1
1
Probe B1 offset
Probe B2 offset
Dewpoint
Humidity probe B1 reading
Temperature probe B2 reading
Probe B1 fault alarm
Probe B2 fault alarm
0= minimum filter
13= maximum filter
0=inactive
0=inactive
1=active
1=active
Anti-sweat control
The output is controlled according to the temperature measured by probe B3, as shown in the figure.
The set point is calculated automatically, adding an offset to the dewpoint that is equal to the value set by parameter plus the value set by trimmer( if
any), plus the differential.
The end scale of the trimmer is settable by parameter.
The output can be disabled if the temperature measured by probe B3 exceeds a limit value, set by parameter.
The maximum value of the output can be reduced by parameter.
OUT
100%
max
diff
offs
Dew-point
Trimmer
SET
Function
Manual offset
setpoint
t(B3) °C
Range
0.0 – “OFST par.” °C
Associated parameters
name
range
def.
MAX
ADG3
FILT
Carel spv
var
I4
I10
I11
10 to 100
90 to 110
0 to 13
OFFS
DIFF
OFST
TMAX
ADO3
PB3T
TRIM
SETP
PB3A
A1
A2
A3
A4
A7
A23
A24
A25
D25
-20.0 to 20.0
0.0 to 20.0
0.0 to 20.0
0.0 to 50.0
-10.0 to 10.0
-50.0 to +90.0
0.0 to 20.0
-50.0 to +90.0
0/1
Code +030220751 – Rel. 1.2 – 09/10/07
100
100
6
res.
UOM
1%
1%
1
description
Maximum output
Probe B3 gain
Probe filter
0.0
2.0
5.0
30.0
0.0
R
R
R
R
0.1°C
0.1°C
0.1°C
0.1°C
0.1°C
0.1°C
0.1°C
0.1°C
1
Dewpoint offset
Differential
End scale offset set by trimmer (0.0 = trimmer disabled)
Temperature limit
Probe B3 offset
Temperature probe B3 reading
Reading offset by trimmer
Set point calculated\
Probe B3 fault alarm
0=inactive
0= minimum filter
13= maximum filter
12
1=active
ACC –Anti-sweat controller
6.3
Master management
In Master configuration, all three probes are required (B1, B2 and B3). The dewpoint is calculated according to the values measured by probes B1 and
B2. The output is controlled according to the value read by probe B3. In the event of alarms on probes B1 or B2, the dewpoint value is forced to 99.9.
If the serial connection is configured as LAN, the Master also becomes the network master and sends the value of the dewpoint calculated to any Slaves
connected.
The value is set at regular intervals in broadcasting mode, thus without needing to define how many Slaves are connected and their addresses. The
dewpoint value sent, when suitably configured by dipswitch, can be increased by the value of an offset set by trimmer, thus allowing simultaneous
control of all the Slaves connected.
If the serial connection is configured as Supervisor, the Master becomes a network slave and responds to the queries from the Supervisor.
Dipswitch
Dip1
Select Master/Slave mode
Dip2
Select serial connection mode, Supervisor/LAN
Dip3
Select Trimmer mode
(Master only)
6.4
OFF:
ON:
OFF:
ON:
OFF:
ON:
Master
Slave
Supervisor
LAN
local manual offset
LAN manual offset
Slave management
In Slave configuration, the value of the dewpoint is received via network (from a controller configured as the LAN master or from the supervisor, which
in turn reads the value from a controller configured as the Supervisor master), and consequently probes B1 and B2 do not need to be connected. The
output is controlled according to value read by probe B3.
If the dewpoint value is not received via the network or the value received is 99.9, an alarm is activated.
•
If the serial connection is configured as LAN, the Slave does not respond when broadcasting mode is used. The timeout for no data reception
is 10 s.
o If the serial connection is configured as Supervisor, the Slave responds even when broadcasting mode is used, however generating a conflict
with any other Slaves connected to the LAN. The timeout for no data reception is 20 minutes. For Slaves controlled by Master, Dip2 must be
in the ON position.
6.5
PI control (proportional and integral)
In addition to the normal contribution of proportional control, the output is also controlled using the integral time on the error (deviation between the
value measured and set point). This is used to reduce the error to zero.
out = Kp*err + Ki*Integral(err)
where err=error, Kp=proportional gain, Ki=integral gain, Ti=integral time, given by:
err = (set point – measurement)
Kp = max. output/diff
Ki = Kp/Ti
By definition the integral time is the time required, when the error if constant, for the integral part to have the same contribution as the proportional
part. The integral time can be set by parameter (default 10 minutes). The contribution of the integral part can be reduced so as to avoid the
phenomenon of “wind-up” (default 50%), however in this case the error will not be removed in steady operation. Special care is required when setting
the Ti, as excessively short times (see the inertia of the system) may lead to instability. For a more detailed explanation of integral control, see the
documents available on control theory.
Associated parameters
name
INTT
AWUP
EPIR
Carel spv
var
I6
I7
D1
range
def.
1 to 30
0 to 100
0/1
10
50
0
res.
UOM
1min
1%
1
description
Integral time for PI control
Limitation of the integral action (antiwind-up)
Enable PI control (Integral)
0=disabled
1=enabled
To simplify the fine-tuning of the parameters, some variables that are available that describe the control status in terms of the various components:
OUTP
OUTI
OUTR
ERRR
I31
I32
I33
A26
-255 to 255
-255 to 255
0 to 255
-200.0 to 200.0
R
R
R
R
1
1
1
0.1°C
proportional component (255 = 100%)
integral component (255 = 100%)
controller output (255 = 100%)
control error (set point – b3)
The values are expressed with the maximum resolution possible (8 bits plus sign), therefore the value 255 corresponds to 100%.
Code +030220751 – Rel. 1.2 – 09/10/07
13
ACC –Anti-sweat controller
6.6
Overriding the output
The output can forced to the desired value required at any time via serial line, irrespective of the value calculated by the controller. This function is
temporary and is not saved; it is disabled automatically when the data reception timeout elapses: 10 s if DIP2 ON, 20 min if DIP2 OFF.
Associated parameters
name Carel spv
var
range
def.
res.
UOM
OUTV
I14
0 to 100
R/W
1%
EOVR
D15
0/1
0
1
6.7
description
Read/override output
Enable override output
0=disabled
1=enabled
Phase control modes
By default control is based on short impulses. Alternatively, control can be enabled for long impulses (control is maintained until the end of the half
period).
The displacement of the phase control function can also be changed with reference to the zero-crossing of the mains voltage, so as to adapt it to the
cosϕ of the load. The linearisation of the output RMS voltage can also be enabled, rather than use the traditional sinusoidal relationship between phase
control and voltage. Finally, the instant variation in the output can be limited so as to optimise operation, and limit peak current.
Voltage(RMS) output
100%
ELIN on
ELIN off
Phase delay @ 100% output
100%
0%
OUTV
Associated parameters
name
Carel
spv var
range
def.
STEP
DLPL
ELIN
ELPL
I12
I13
D2
D3
0 to 10
0 to 100
0/1
0/1
5
0
1
0
6.8
res.
UO
M
1sec
1%
1
1
description
Output ramp (minimum time for variation from 0% to 100%)
Phase displacement: 100% corresponds to 90°
Enable output linearisation
0=disabled
Enable long impulse phase control
0=disabled
1=enabled
1=enabled
Automatic adaptation to the mains frequency
At power-on the mains frequency is measured so as to adapt operation to 50Hz or 60Hz
The status of the mains frequency reading is accessible via serial line.
name
OKHZ
STHZ
6.9
Carel spv
var
D26
D27
range
def.
0/1
0/1
R
R
res.
UOM
1
1
description
mains frequency reading status
mains frequency
0=no ok
0=50Hz
1=ok
1=60Hz
Alarm situations and alarm management
Alarm status is activated in the event of:
ƒ external alarm (or in any case, closing of the contact connected to the digital input configured as the alarm input)
ƒ fault on probes B1, B2 or B3 in master configuration
ƒ fault on probe B3 in slave configuration
ƒ interruption to the serial connection in slave configuration
ƒ error reading/writing the parameters saved in non-volatile memory (EEPROM)
The alarm status is signalled by the red LED, depending on the causes, in order of priority:
ƒ on steady
parameter alarm
ƒ 1 impulse
probe alarm or serial connection interruption
ƒ 2 impulses
digital alarm input closed
In the event of more than one alarm at the same time, the signal with the highest priority is shown.
Warning: if digital input ID1 is set as normally closed, the alarm is active when ID1 is open
Code +030220751 – Rel. 1.2 – 09/10/07
14
ACC –Anti-sweat controller
The probe fault alarm is generated if the probe is disconnected or short-circuited. In alarm status, the controller output provides one of three possible
voltage values, which can be set by parameter:
ƒ 0%;
ƒ 50% of the maximum output set by parameter;
ƒ 100% of the maximum output set by parameter (default).
Normal operation is restored automatically as soon as the alarm situation is resolved.
In the event of alarms due to errors when reading/writing the parameters, the parameters take the default values. The alarm is reset only when a correct
parameter copy operation is performed using the key or the parameters are written from the supervisor. If the alarm persists, the EEPROM is faulty.
Dipswitch
Dip4
Select digital input ID1 mode
OFF:
ON:
external alarm
external enabling signal
Associated parameters
name
range
def.
ALMO
Carel spv
var
I5
0 to 2
2
res.
UOM
1
MOID
STID
ALRM
EEPA
ELAN
D4
D17
D22
D28
D29
0/1
0/1
0/1
0/1
0/1
1
R
R
R
R
1
1
1
1
1
Code +030220751 – Rel. 1.2 – 09/10/07
description
output in alarm status
operating logic of digital input ID1
status of digital input ID1
alarm status
parameter error alarm
serial connection alarm
15
0=0%
1=50% MAX
2=100% MAX
0=normally closed
0=open
0=inactive
0=inactive
0=inactive
1=normally open
1=closed
1=active
1=active
1=active
ACC –Anti-sweat controller
7. Description of the operating parameters
MAC
type of unit
type and Carel supervisor address
integer var. 1 (read only)
resolution and unit of measure
1
range
143
default
143
Non-modifiable parameter used to identify the type of controller in supervision network connections or when connected to the programming key.
REL
software release
type and Carel supervisor address
integer var. 2 (read only)
resolution and unit of measure
1
range
0 to 255
default
-Non-modifiable parameter used to identify the software version installed on the controller. The least significant digit is used to identify functional
variations that do not imply changes to the parameter structure. The parameters can only be copied using the programming key between two
controllers if the REL parameter has the same value or differs only as regards the least significant digit (for example: the parameters can be copied
between controllers with REL 12 and 14, while they cannot be copied between controllers with REL 12 and 20).
SADR
serial address
type and Carel supervisor address
integer var. 3
resolution and unit of measure
1
range
1 to 255
default
1
Parameter used to identify the individual controller, so as to make it accessible within the supervision network.
MAX
maximum output
type and Carel supervisor address
integer var. 4
resolution and unit of measure
1%
range
10 to 100
default
100
Parameter used to set the maximum output value of the controller.
Expressed as a % of the mains voltage.
ALMO
output in alarm status
type and Carel supervisor address
integer var. 5
resolution and unit of measure
1
range
0 to 2
default
2
Parameter used to set the value of the output in the event of alarms.
ALMO=0 output at 0%
ALMO=1 output at 50%
ALMO=2 output at 100%
INTT
integral time
type and Carel supervisor address
integer var. 6
resolution and unit of measure
1min
range
1 to 30
default
10
Parameter used to set the intensity of the integral action in PI control.
Only used if PI control is enabled.
AWUP integral action limit
type and Carel supervisor address
integer var. 7
resolution and unit of measure
1%
range
0 to 100
default
50
Parameter used to limit the contribution of the integral action in PI control, with the purpose of avoiding excessive overshoot and delays in the controlled value, in
systems whose inertia cannot be accurately defined in advance and therefore when the control function is hard to calibrate (DIFF and INTT).
Only used if PI control is enabled.
Code +030220751 – Rel. 1.2 – 09/10/07
16
ACC –Anti-sweat controller
ADG1
probe B1 gain
type and Carel supervisor address
integer var. 8
resolution and unit of measure
1%
range
90 to 100
default
100
Parameter used to adjust the value of the probe connected to input B1 using the gain of the measurement amplifier. Effective measurement =
(measurement x ADG1)/100. The value calculated can also added to an offset defined by parameter ADO1.
ADG2
probe B2 gain
type and Carel supervisor address
integer var. 9
resolution and unit of measure
1%
range
90 to 100
default
100
Parameter used to adjust the value of the probe connected to input B2 using the gain of the measurement amplifier. Effective measurement =
(measurement x ADG2)/100. The value calculated can also added to an offset defined by parameter ADO2.
ADG3
probe B3 gain
type and Carel supervisor address
integer var. 10
resolution and unit of measure
1%
range
90 to 100
default
100
Parameter used to adjust the value of the probe connected to input B3 using the gain of the measurement amplifier.
Effective measurement = (measurement x ADG3)/100. The value calculated can also added to an offset defined by parameter ADO3.
FILT
probe measurement filter
type and Carel supervisor address
integer var. 11
resolution and unit of measure
1
range
0 to 13
default
6
Parameter used to set the way the values measured by the probes are filtered.
The values shown are typical and may change according to the mode set (CPU workload).
FILT=0
FILT=1
FILT=2
FILT=3
FILT=4
FILT=5
FILT=6
FILT=7
FILT=8
FILT=9
FILT=10
FILT=11
FILT=12
FILT=13
time const. (s)
0
0
0.15
0
0.3
0
0.6
0.6
1.2
1.2
2.4
2.4
5
10
meas. update (s)
0.08
0.15
0.08
0.3
0.15
0.6
0.3
0.15
0.6
0.3
0.6
0.3
0.6
0.6
meas./average
8
16
8
32
16
64
32
16
64
32
64
32
64
64
STEP
output ramp
type and Carel supervisor address
integer var. 12
resolution and unit of measure
1s
range
0 to 10
default
5
Parameter used to set the minimum time for the variation of the output from 0% to 100% and vice-versa.
DLPL
phase displacement
type and Carel supervisor address
integer var. 13
resolution and unit of measure
1
range
0 to 100
default
0
Parameter used to set the displacement in the phase control function with reference to the zero crossing of the mains voltage. Used to optimise the
voltage to the load, adapting the displacement to the cosϕ of the load. The maximum value of 100 corresponds to a displacement of around 90°. The
output should be forced to 100% and parameter DLPL set accordingly to reach the maximum voltage output. For resistive loads (cosϕ=1), the
displacement should be set to zero.
Code +030220751 – Rel. 1.2 – 09/10/07
17
ACC –Anti-sweat controller
OUTV
read/override output
type and Carel supervisor address
integer var. 14
resolution and unit of measure
1%
range
0 to 100
default
Variable used to read the output value and, if the Override function is enabled, to override it.
This variable can only be written if parameter EOVR=1.
OUTP
proportional component reading
type and Carel supervisor address
integer var. (read only) 31
resolution and unit of measure
1
range
-255 to 255
default
-Variable used to read the value of the proportional component calculated by the control algorithm.
OUTP=ERRR*Kp
where Kp is the proportional gain defined by
Kp=(maxOUT)/Differential
The value read is the actual value used in the algorithm, expressed in 8 bits plus sign, therefore 255 corresponds to 100% of the maximum output voltage.
OUTI
integral component reading
type and Carel supervisor address
integer var. (read only) 32
resolution and unit of measure
1
range
-255 to 255
default
-Variable used to read the value of the integral component calculated by the control algorithm.
OUTI=Ki*Integral(ERRR)=Integral(Ki*ERRR)
where Ki is the integral gain defined by
Ki=Kp/Ti
where Ti is the integral time (parameter INTT)
The value calculated is in any case limited, as an absolute value, by the AWUP parameter..
The value read is the actual value used in the algorithm, expressed in 8 bits plus sign, therefore 255 corresponds to 100% of the maximum output voltage.
OUTR
output reading
type and Carel supervisor address
integer var. (read only) 33
resolution and unit of measure
1
range
0 to 255
default
-Variable used to read the overall value of the output calculated by the control algorithm.
During control, this value is the sum of the components OUTP and OUTI, limited between 0 and 255.
In the event of active alarms or other conditions that force the output to a preset value, OUTR is not calculated as shown previously, but rather reflects
the preset value. If the Override function is enabled, OUTR maintains its normal value, even if the output is set by the OUTV parameter. The value read
is the actual value used in the algorithm, expressed in 8 bits plus sign, therefore 255 corresponds to 100% of the maximum output voltage.
OFFS
dewpoint offset
type and Carel supervisor address
analogue var. 1
resolution and unit of measure
0.1°C
range
-20.0 to 20.0
default
0.0
Parameter used to set an offset for the dewpoint measured and consequently increase or decrease the working set point.
The effective offset also depends on the value set using the SET trimmer and the settings of the dipswitches.
DIFF
differential
type and Carel supervisor address
resolution and unit of measure
range
default
Parameter used to set the value of the control differential.
Code +030220751 – Rel. 1.2 – 09/10/07
analogue var. 2
0.1°C
0.0 to 20.0
2.0
18
ACC –Anti-sweat controller
OFST
SET trimmer end scale
type and Carel supervisor address
analogue var. 3
resolution and unit of measure
0.1°C
range
0.0 to 20.0
default
5.0
Parameter used to set the end scale of the SET trimmer and as a consequence the maximum field of variation for the manually settable offset.
The effective offset also depends on the value set using the OFFS parameter and the settings of the dipswitches.
TMAX
maximum temperature limit
type and Carel supervisor address
analogue var. 4
resolution and unit of measure
0.1°C
range
0.0 to 90.0
default
30.0
Parameter used to set the maximum temperature value measured by probe B3 beyond which the output is disabled.
ADO1
probe B1 offset
type and Carel supervisor address
analogue var. 5
resolution and unit of measure
0.1% rH
range
-10.0 to 10.0
default
0.0
Parameter used to adjust the value read by the probe connected to input B1 using the offset of the measurement amplifier.
Effective measurement = (measurement x ADG1)/100 + ADO1).
ADO2
probe B2 offset
type and Carel supervisor address
analogue var. 6
resolution and unit of measure
0.1°C
range
-10.0 to 10.0
default
0.0
Parameter used to adjust the value read by the probe connected to input B2 using the offset of the measurement amplifier.
Effective measurement = (measurement x ADG2)/100 + ADO2).
ADO3
probe B3 offset
type and Carel supervisor address
analogue var. 7
resolution and unit of measure
0.1°C
range
-10.0 to 10.0
default
0.0
Parameter used to adjust the value read by the probe connected to input B3 using the offset of the measurement amplifier.
Effective measurement = (measurement x ADG3)/100 + ADO3).
DEWP
dewpoint
type and Carel supervisor address
analogue var. 8
resolution and unit of measure
0.1°C
range
-50.0 to 99.9
default
-Variable that depending on the operating mode set represents the dewpoint calculated or used.
Master mode:
ƒ read only variable that represents the value calculated based on the values read by probes B1 and B2 and used for control
ƒ the value is forced to 99.9 in the event of alarms on probes B1 or B2
ƒ the value is sent in broadcasting mode via serial line if LAN mode is selected
Slave mode:
ƒ read/write variable sent via serial line used for control
ƒ the failed update of the dewpoint or reception of the value 99.9 causes an alarm
PB1H
probe B1 reading
type and Carel supervisor address
analogue var. (read only) 21
resolution and unit of measure
0.1% rH
range
0.0 to 100.0
default
-Variable used to read the humidity value in rH measured by probe B1.
Code +030220751 – Rel. 1.2 – 09/10/07
19
ACC –Anti-sweat controller
PB2T
probe B2 reading
type and Carel supervisor address
analogue var. (read only) 22
resolution and unit of measure
0.1°C
range
-50.0 to 90.0
default
-Variable used to read the temperature value in °C measured by probe B2.
PB3T
probe B3 reading
type and Carel supervisor address
analogue var. (read only) 23
resolution and unit of measure
0.1°C
range
-50.0 to 90.0
default
-Variable used to read the temperature value in °C measured by probe B3.
TRIM
SET trimmer reading
type and Carel supervisor address
analogue var. (read only) 24
resolution and unit of measure
0.1°C
range
0 to ”OFST” par.
default
-Variable used to read the offset value set manually by trimmer.
The effective offset also depends on the value set using the OFFS parameter and the settings of the dipswitches.
SETP
set point calculated reading
type and Carel supervisor address
resolution and unit of measure
range
default
Variable used to read the value of the set point calculated.
analogue var. (read only) 25
0.1°C
-50.0 to 90.0
--
ERRR
error reading
type and Carel supervisor address
analogue var. (read only) 26
resolution and unit of measure
0.1°C
range
-200.0 to 200.0
default
-Variable used to read the value of the error (difference between the set point and the measurement of the controlled value B3) calculated by the
control algorithm and based on which the proportional and integral components are calculated. The error is equal to: error= B3 reading-set point
EPIR
enable PI control
type and Carel supervisor address
digital var. 1
resolution and unit of measure
1
range
0 /1
default
0
Parameter used to enable PI control (proportional + integral).
EPIR=0
disabled
EPIR=1
enabled
ELIN
enable output linearisation
type and Carel supervisor address
digital var. 2
resolution and unit of measure
1
range
0 /1
default
1
Parameter used to enable the linearisation of the output voltage, compensating the sinusoidal relationship between phase and voltage.
ELIN=0
disabled
ELIN=1
enabled
ELPL
select phase control function
type and Carel supervisor address
digital var. 3
resolution and unit of measure
1
range
0 /1
default
0
Parameter used to select the type of phase control..
ELPL=0 short impulse (around 3 ms)
ELPL=1 impulse long (from the moment of switching until the end of the mains half period)
Code +030220751 – Rel. 1.2 – 09/10/07
20
ACC –Anti-sweat controller
MOID
operating logic of ID1
type and Carel supervisor address
digital var. 4
resolution and unit of measure
1
range
0 /1
default
1
Parameter used to select the operating logic of digital input ID1.
MOID=0 normally closed
MOID=1 normally open
EOVR
enable Override function
type and Carel supervisor address
digital var. 15
resolution and unit of measure
1
range
0 /1
default
0
Variable used to enable the Override function and consequently force the output to the value defined by the OUTV parameter, irrespective of the value
calculated by the control algorithm:
EOVR=0 disabled
EOVR=1
enabled
The variable is forced to zero (Override disabled) on power-up and in any case when the serial line data reception timeout elapses: 10 s if DIP2 ON, 20
min if DIP2 OFF.
FDEF
reset parameter default values
type and Carel supervisor address
resolution and unit of measure
range
default
Variable used to reset the default values of the parameters.
digital var. 16
1
0 /1
0
FDEF=0
FDEF=1
no action
reset default
The value is automatically set back to 0 when the function is activated. It is not saved in the EEPROM.
STID
input ID1 status
type and Carel supervisor address
resolution and unit of measure
range
default
Variable used to read the status of digital input ID1.
STID=0
STID=1
digital var. (read only) 17
1
0 /1
--
open
closed
STD1
dipswitch 1 status
type and Carel supervisor address
resolution and unit of measure
range
default
Variable used to read the position of dipswitch 1.
STD1=0
STD1=1
digital var. (read only) 18
1
0 /1
--
Off
On
STD2
dipswitch 2 status
type and Carel supervisor address
resolution and unit of measure
range
default
Variable used to read the position of dipswitch 2.
STD2=0
STD2=1
digital var. (read only) 19
1
0 /1
--
Off
On
STD3
dipswitch 3 status
type and Carel supervisor address
resolution and unit of measure
range
default
Variable used to read the position of dipswitch 3.
STD3=0 Off
STD3=1 On
Code +030220751 – Rel. 1.2 – 09/10/07
digital var. (read only) 20
1
0 /1
--
21
ACC –Anti-sweat controller
STD4
dipswitch 4 status
type and Carel supervisor address
resolution and unit of measure
range
default
Variable used to read the position of dipswitch 4.
STD4=0 Off
STD4=1 On
digital var. (read only) 21
1
0 /1
--
ALRM
alarm status
type and Carel supervisor address
digital var. (read only) 22
resolution and unit of measure
1
range
0 /1
default
-Variable used to read the status of the alarm.
ALRM=0 inactive
ALRM=1 active
The alarm may be signalled externally, associated with the digital input, or due to a fault on probes B1 or B2.
PB1A
probe B1 alarm status
type and Carel supervisor address
digital var. (read only) 23
resolution and unit of measure
1
range
0 /1
default
-Variable used to read the status of the probe B1 fault alarm.
PB1A=0 inactive
PB1A =1 active
The alarm is activated automatically if the value read by probe B1 is outside of the range of possible values, typically due to disconnection or shortcircuit. The alarm is not detected if slave mode is selected.
PB2A
probe B2 alarm status
type and Carel supervisor address
digital var. (read only) 24
resolution and unit of measure
1
range
0 /1
default
-Variable used to read the status of the probe B2 fault alarm.
PB2A=0 inactive
PB2A =1 active
The alarm is activated automatically if the value read by probe B2 is outside of the range of possible values, typically due to disconnection or shortcircuit. The alarm is not detected if slave mode is selected.
PB3A
probe B3 alarm status
type and Carel supervisor address
digital var. (read only) 25
resolution and unit of measure
1
range
0 /1
default
-Variable used to read the status of the probe B3 fault alarm.
PB3A=0 inactive
PB3A =1 active
The alarm is activated automatically if the value read by probe B3 is outside of the range of possible values, typically due to disconnection or short-circuit.
OKHZ
mains frequency reading status
type and Carel supervisor address
digital var. (read only) 26
resolution and unit of measure
1
range
0 /1
default
-Variable used to read the status relating to the reading of the mains frequency.
OKHZ=0 reading in progress
OKHZ =1 reading completed
At the end of the reading, the variable STHZ signals the frequency, 50 or 60Hz.
Code +030220751 – Rel. 1.2 – 09/10/07
22
ACC –Anti-sweat controller
STHZ
mains frequency
type and Carel supervisor address
digital var. (read only) 27
resolution and unit of measure
1
range
0 /1
default
-Variable used to read the mains frequency detected by the controller.
STHZ=0 50Hz
STHZ=1 60Hz
The value of the variable is only meaningful after the mains frequency has been read by the controller (see parameter OKHZ).
EEPA
invalid parameter alarm status
type and Carel supervisor address
digital var. (read only) 28
resolution and unit of measure
1
range
0 /1
default
-Variable used to read the status of the parameter read/write error alarm.
EEPA=0 inactive
EEPA =1 active
ELAN
LAN connection alarm status
type and Carel supervisor address
digital var. (read only) 29
resolution and unit of measure
1
range
0 /1
default
-Variable used to read the status of the alarm relating to the interruption of the serial connection.
ELAN=0 inactive
ELAN =1 active
The alarm is disabled in master mode.
7.1
Summary table of operating parameters
name
MAC
REL
SADR
MAX
ALMO
add.
I1
I2
I3
I4
I5
range
143
0 to 255
1 to 255
10 to 100
0 to 2
def.
R
R
1
100
2
User value
-
res. UOM
1
1
1
1%
1
description
Type of unit
FW release
Serial address (note 1)
Maximum output
Output in alarm status
INTT
AWUP
ADG1
ADG2
ADG3
FILT
I6
I7
I8
I9
I10
I11
1 to 30
0 to 100
90 to 110
90 to 110
90 to 110
0 to 13
10
50
100
100
100
6
1min
1%
1%
1%
1%
1
Integral time in PI control
Limitation of the integral action (antiwind-up)
Probe B1 gain
Probe B2 gain
Probe B3 gain
0= minimum filter
Probe filter
5
0
R/W
R
R
R
R
R
1sec
1%
1%
Output ramp (minimum time for variation from 0% to 100%)
Phase displacement: 100% corresponds to 90°
Read/Override output (NOTE 2)
not used
proportional component (255 = 100%)
integral component (255 = 100%)
controller output (255 = 100%)
not used
0=0%
1=50% MAX
2=100% MAX
13= maximum filter
STEP
DLPL
OUTV
OUTP
OUTI
OUTR
OFFS
DIFF
OFST
TMAX
ADO1
ADO2
ADO3
I12
0 to 10
I13
0 to 100
I14
0 to 100
I15 to I30
0
I31
-255 to 255
I32
-255 to 255
I33
0 to 255
I34 to I50
0
A1
A2
A3
A4
A5
A6
A7
-20.0 to 20.0
0.0 to 20.0
0.0 to 20.0
0.0 to 50.0
-20.0 to 20.0
-10.0 to 10.0
-10.0 to 10.0
Code +030220751 – Rel. 1.2 – 09/10/07
0.0
2.0
5.0
30.0
0.0
0.0
0.0
-
1
1
1
0.1°C
0.1°C
0.1°C
0.1°C
0.1%
0.1°C
0.1°C
Dewpoint offset
Differential
End scale for offset set by trimmer (0.0 = trimmer disabled)
Temperature limit
Probe B1 offset
Probe B2 offset
Probe B3 offset
23
ACC –Anti-sweat controller
name
DEWP
PB1H
PB2T
PB3T
TRIM
SETP
ERRR
EPIR
ELIN
ELPL
MOID
EOVR
FDEF
STID
STD1
STD2
STD3
STD4
ALRM
PB1A
PB2A
PB3A
OKHZ
STHZ
EEPA
ELAN
add.
range
A8
-50.0 to +99.9
A9 to
0
A20
A21
0.0 to 100.0
A22
-50.0 to +90.0
A23
-50.0 to +90.0
A24
0.0 to “OFST”
A25
-50.0 to +90.0
A26 -200.0 to 200.0
A14 to
0
A40
D1
D2
D3
D4
D5 to
D14
D15
D16
D17
D18
D19
D20
D21
D22
D23
D24
D25
D26
D27
D28
D29
D30 to
D32
def.
R/W
R
User value
-
res. UOM
0.1°C
R
R
R
R
R
R
R
-
0.1rH
0.1°C
0.1°C
0.1°C
0.1°C
0.1°C
0/1
0/1
0/1
0/1
0
0
1
0
1
R
-
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0
0
0
R
R
R
R
R
R
R
R
R
R
R
R
R
R
-
description
Dewpoint (NOTE 3)
not used
Humidity probe B1 reading
Temperature probe B2 reading
Temperature probe B3 reading
Offset by trimmer reading
Set point calculated
Control error (set point – B3)
not used
1
1
1
1
Enable PI control (Integral)
Enable output linearisation
Enable long impulse phase control
Operating logic of digital input ID1
not used
0=disabled
0=disabled
0=disabled
0=normally closed
1=enabled
1=enabled
1=enabled
1=normally open
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Enable override output (NOTE 2)
Reset default values (NOTE 4)
digital input ID1 status
dipswitch 1 status
dipswitch 2 status
dipswitch 3 status
dipswitch 4 status
alarm status
probe B1 fault alarm
probe B2 fault alarm
probe B3 fault alarm
mains freq. reading status
mains frequency
parameter error alarm
serial connection alarm
not used
0=disabled
0=no action
0=open
0=Off
0=Off
0=Off
0=Off
0=inactive
0=inactive
0=inactive
0=inactive
0=no ok
0=50Hz
0=inactive
0=inactive
1=enabled
1=enabled
1=closed
1=On
1=On
1=On
1=On
1=active
1=active
1=active
1=active
1=ok
1=60Hz
1=active
1=active
A indicates analogue variables
I indicates integer variables
D indicates digital variables
R indicates read only variables (no default values, as these are initialised/updated automatically at power-on)
NOTE 1: The parameter should be modified via serial
connection with care, as this implies the dynamic management of the address by the Supervisor.
NOTE 2: The override control is disabled at power-on and when serial communication is interrupted for more than 10 seconds.
NOTE 3: The value 99.9 is used by the Master to signal to the Slaves
that the correct of the dewpoint cannot be calculated due to humidity alarm or room temperature
probes.
NOTE 4: The value is automatically set back to 0 when a command is received.
Code +030220751 – Rel. 1.2 – 09/10/07
24
ACC –Anti-sweat controller
8. Tables of alarms and signals
8.1
Alarms
The alarm status is indicated by the red LED
status of the red LED
off
on
flashing 1 impulse
flashing 2 impulses
description
no alarm
parameter error alarm
probe alarm (Master)
probe or LAN connection alarm (Slave)
external alarm
possible causes of alarm
non-volatile memory error (EEPROM)
probes disconnected or short-circuited
probes disconnected or short-circuited, or failed update of the dewpoint via LAN
closing of the contact connected to the digital input
The status of the digital input that activates the external alarm depends on the operating logic set (by default normally open)
If there are multiple alarms activated at the same time, the first in order shown in the table is signalled.
The active alarm status forces the output to the value defined by the ALMO parameter.
The alarm status is available via serial line.
8.2
Signals
Power is signalled by the green LED.
The status of the serial connection is signalled by the yellow LED.
status of the yellow LED
off
description
connection deactivated
flashing
on
data reception
connection active
possible causes
cable disconnected
supervisor off-line
protocol not supported
await data reception from Master or Supervisor
data reception in progress
the connection is active, but no data has been received for less than 10 s
The serial connection is automatically deactivated 10 seconds after the last valid data is received.
If the Master is in LAN serial mode (Dip 1 and Dip 2 = ON), the yellow LED has the following meaning:
on
flashing
connection active
data transmission
Code +030220751 – Rel. 1.2 – 09/10/07
the connection is active, but no data is being sent
the Master is sending data to the slaves connected to the LAN
25
ACC –Anti-sweat controller
9. Supervision
Carel supervisor protocol ver 3.0s is supported (19200 baud).
To set the addresses of the individual variables, see the column “Carel spv var” in the table of parameters.
The variables are grouped into blocks: if a variable in a certain block is modified, the entire block is sent down.
Integer variables relating to parameters
I1 – I14
Integer status variables
I31 – I33
Analogue variables relating to parameters
A1 – A8
Analogue status variables
A21 – A26
Digital variables relating to parameters
D1 – D4
Digital status variables/commands
D15 – D29
If an external supervisor is used with a network of Master and Slave controllers, the supervisor is responsible for reading the value of the dewpoint
calculated by the Master and sending it to the various Slaves connected.
The supervisor can manage the network in standard mode, that is, assigning each Slave the specific network address, or alternatively in broadcasting
mode, in which case the address of the Slave does not need to be assigned, however this does not allow the possibility to read the status of the Slave.
Code +030220751 – Rel. 1.2 – 09/10/07
26
ACC –Anti-sweat controller
10. Specifications and connections
10.1 Electrical specifications
Power supply
Analogue outputs
Analogue inputs
230 Vac single-phase, -15% +10% 50/60 Hz
1 phase control 0 to 230 Vac single-phase, 8 A (min 500 mA)
1 input for 0 to 10 V humidity probes (Rin: 20 k )
precision 5% (typical 2%), excluding the probes
2 inputs for std Carel NTC temp. probes (10 k @25 °C)
range of measurement: –50T90 °C
precision 1°C [-10T50]; 2°C [-40T-10 and 50T90], excluding the probes
Digital inputs
1 input for voltage-free contact
typical voltage 12 V with the contact open, typical current 6 mA with the contact closed.
Serial ports
1 standard two wire RS485 connector (only on some models)
CAREL supervisor protocol; baud rate 19200; max length 1 km with shielded cable
Light signals
Green power LED
Red alarm LED
Yellow serial connection LED (flashing during valid data reception)
Controller setting
1 trimmer for manually setting the offset
4 dipswitches
Terminals and connectors
Power supply and analogue outputs:
Screw terminals for cable cross-section min. 2.5 mm2 max 4 mm2.
Signals:
Spring terminals for cable cross-section min. 1.5 mm2 max 2.5 mm2.
4 pin JST connector for the programming key
Operating conditions
-10T50 °C, <90% RH non-condensing
Storage conditions
-20T70 °C, <90% RH non-condensing
Index of protection
IP43 (can reach IP54)
Environmental pollution
Normal
Protection against electric shock
Class I
PTI of the insulating materials
250 V
Period of stress across the insulating parts
Long
Type of action -disconnection
1C
Category of resistance to heat and fire
Category D (UL94 – V0)
Immunity against voltage surges
Category 1
Ageing characteristics
60,000 operating hours
No. of automatic operating cycles
100,000
Software class and structure
Class A
Case
Metallic (Al) with plastic cover (75°C ball pressure test)
Dimensions
140x135x90 mm
Assembly
Metallic case fastened to the panel or wall using 4 screws dia. 3.5/4 mm
Certification
EMC: EN 61326-1, EN 55014-1, EN 55014-2
Safety: EN 60730-1
Code +030220751 – Rel. 1.2 – 09/10/07
27
ACC –Anti-sweat controller
10.2 Connections
Offset
Trimmer
LEDs
PROG.
KEY
230 V~
Fig. 10.a
L, N
L1, N
ID1, GND
B1, GND, +V
B2, GND
B3, GND
GNX, RXTX+, RXTX-
230 Vac power supply input
230 Vac power supply output to load
Programmable digital input. Alarm or external enabling signal, see dipswitch configuration.
0 to 10 V analogue input for ambient humidity probe reading.
NTC analogue input 10 k•@25 °C for room temperature probe reading.
NTC analogue input 10 k•@25°C for control temperature probe reading.
RS485 serial (FCSER0000 option required).
10.3 Dimensions and assembly
Fig. 10.b
Code +030220751 – Rel. 1.2 – 09/10/07
28
NOTES:
__________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
NOTES:
__________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
_________________________________________________________________________________________________________
“ACC” +030220751 - rel. 1.2 – 09/10/07
CAREL S.p.A.
Via dell’Industria, 11 - 35020 Brugine - Padova (Italy)
Tel. (+39) 049.9716611 Fax (+39) 049.9716600
http://www.carel.com - e-mail: [email protected]