PowerFlex Digital DC Drive
Power Wiring
AC Input Voltages
PowerFlex DC drives are rated for the following AC input voltages @ 50/60 Hz ±5%:
Mains Circuit (Terminals U, V, W)
•
•
•
•
•
•
•
230V ±10%, 3Ph
400V ±10%, 3Ph
440V ±10%, 3Ph
460V ±10%, 3Ph
480V ±10%, 3Ph
575V ±10%, 3Ph
690V ±10%, 3Ph
Field Circuit (Terminals U1, V1)
• 230V ±10%, 1Ph
• 400V ±10%, 1Ph
• 460V ±10%, 1Ph
Control Circuit (Terminals U2, V2)
• 115V ±15% or 230V ±15%, 1Ph
Note: For frame B and C drives only, a jumper must be placed between terminals SA-SB on the Switching Power Supply
circuit board for the control circuits to work with 115V AC input. Refer to Frame B drives SA-SB Terminal Block
Location on page 37 and Frame C Drives SA-SB Terminal Block Location on page 38 for terminal block locations.
DC Output Voltages
The output voltages below take into account an AC input undervoltage within the stated tolerance limits and a voltage
drop of 4% due to an AC input line reactor. It is the same as the rated armature voltage suggested for the connected motor.
Armature Circuit
AC Input Voltage
(Terminals U, V, W)
230V ±10 %, 3Ph
400V ±10 %, 3Ph
440V ±10 %, 3Ph
460V ±10 %, 3Ph
480V ±10 %, 3Ph
575V ±10 %, 3Ph
690V ±10 %, 3Ph
DC Output Armature Voltage (Terminals C & D)
Two Quadrant Drive
Four Quadrant Drive
260V
240V
470V
420V
530V
460V
560V
480V
580V
500V
680V
600V
810V
720V
Field Circuit
AC Input Voltage
(Terminals U1 & V1)
230V ±10 %, 1Ph
400V ±10 %, 1Ph
460V ±10%, 1Ph
DC Output Field Voltage(1) (Terminals C1 & D1)
Fixed Field
Adjustable Field
200V
200V
310V
310V
360V
360V
(1) The max field voltage is equal to 0.85 x AC input line voltage
Rockwell Automation Publication 20P-TD001F-EN-P - February 2013