Download VDC Series Manual
Transcript
Installation & Service Manual Voltage-Dip Compensators For VDC L4T/L6T & S4T/S6T series Models 120V / 208V / 220V / 230V 50/60Hz DIP-PROOFING TECHNOLOGIES INC. LEADERS IN VOLTAGE-DIP PROOFING Installation & Service Manual Contents Introduction .............................................................................. 3 Theory of operation ................................................................. 3 Specifications .......................................................................... 5 VDC support for the SEMI F47 standard ................................. 7 Installation Guide ..................................................................... 9 Power Wiring............................................................................ 9 Indicator error codes .............................................................. 11 Adjustments ........................................................................... 11 Compensator Run Time......................................................... 11 I2t controlled run time curves ................................................ 12 Fault Diagnosis Chart ............................................................ 13 Mechanical Construction ....................................................... 16 Dimension Table .................................................................... 16 Mechanical Outline ................................................................ 17 Accessories ........................................................................... 18 Voltage Sag Simulator ........................................................... 19 Notice IMPORTANT SAFETY INSTRUCTIONS. SAVE THESE INSTRUCTIONS! This manual contains important instructions that should be followed during installation and adjustment of VDC series Voltage Dip Compensators. Page 2 VDC L4T/L6T & VDC S4T/S6T Series - Firmware ver 1.4 & up Installation & Service Manual Introduction The reliability of electrical power to industry is in general very high, nevertheless, voltage sags or dips do occur. These instabilities are caused by short circuits, lightning strikes on overhead power lines and heavy load switching. The duration of such faults is generally shorter than one second. Power Quality data shows that voltage sags with a maximum depth of around 50% constitute 92% of all events. Most plant can ride through such voltage dips by virtue of their mechanical and electrical inertia. However, this is not the case with electrically held-in contactors and relays that control the machinery. Contactors typically drop out from 5ms to 20ms after power is removed. Each short voltage dip now becomes a power failure and the plant must be restarted. This can be complicated, time-consuming and costly. DIP-PROOFING TECHNOLOGIES’ Voltage Dip Compensators are designed to maintain the switchgear control voltage during voltage sags, effectively keeping the plant connected. The stored electrical and magnetic energy is allowed to flow, supporting the mechanical inertia of the machinery. When the power is restored after a short voltage dip, the plant is still running at near synchronous speed, the inrush currents will be small and the stress to the system minimal. The VDC provides an economic solution for users who need their equipment to comply with the Semi F47 standard for voltage sag immunity. Historically, this problem has been addressed by using DC contactors, latched contactors and intelligent controls such as PLC’s. These systems are complex and expensive and do not provide a solution for equipment already in existence. The current approach to this problem has been to employ intelligent control systems which provide a curative solution. In contrast, the Voltage Dip Compensator, provides a preventative solution. Theory of operation The VOLTAGE-DIP COMPENSATOR is designed to be maintenance free and highly reliable. It consists of 5/7 static switches , a sag compensation transformer and the controls. The Voltage Dip Compensator block diagram is shown in Fig 1 below. 1 3 Static Switch - 1 Static Switch - 2 Compensation Transformer Static Switch - 3 Supply in Controls Static Switch - 4 To Load Static Switch - 5 Static Switch - 6 Static Switch - 7 6 Tap models only. 2 Fig 1 Compensator Block Diagram VDC L4T/L6T & VDC S4T/S6T Series - Firmware ver 1.4 & up Page 3 Installation & Service Manual Volts The STATIC SWITCHES are robust and can withstand large current surges. They are ideally suited for contactor operation where high peak currents of short duration occur during energizing. V in (Sag duration 42ms) V out Supply sags 300 Supply recovers 200 100 0 -100 -200 -300 Compensator Running 0 10 20 30 40 50 60 70 80 90 100 Time ms Fig 2 Compensator output waveform. During stand-by operation, static switch1 supplies power directly to the load,static switches 2 to 5 are switched off and the compensation transformer carries no load. The supply voltage is constantly monitored for deviations; should there be a deviation from Vnom which is greater than ±10%, static switch 1 is switched off and static switch 2 is activated. Depending on the sag depth the controls will operate static switches 2 to 5/7 to maintain the compensator output voltage within ±10% of the nominal supply voltage.The switch-over is accomplished in 350µs. A 3.15 second timer, adjustable in increments of 50ms , starts timing the compensator out. Should the input voltage recover within the set time, static switches 2 to 5/7 will be deactivated and static switch 1 will be switched on and the load is reconnected to the supply. If the input voltage does not recover within the set time the load is switched back to the supply regardless of the voltage level. If I2t control is enabled then the run time will be dynamically optimized to the longest time that load conditions will allow. The VDC employs tap switch fuses to prevent catastrophic damage to the unit in the event of a tap switch failure. If a tap switch should fail the fuse will open. A VDC with a failed tap switch will continue to function normally and will attempt to serve any sags that occur. However if sag conditions require activation of the failed tap then the load will be dropped because there is no output from that tap. Page 4 VDC L4T/L6T & VDC S4T/S6T Series - Firmware ver 1.4 & up Installation & Service Manual Specifications VDC L4T/L6T & S4T/S6T series 120V models VDC L6T3K120 VDC L4T3K120 VDC S6T1K120 VDC S4T1K120 120V MODELS AC INPUT SUPPLY 120V Single phase supply voltage 50/60Hz: +10% Maximum input voltage: Minimum input voltage: -50% -64% -50% -64% 8.5A Full load current (A RMS): 8.5A 24A 24A 550A Maximum surge current for 3 seconds duration: AC OUTPUT 120V Nominal output voltage: ± 10% Voltage fluctuations over full operating range: 8.5A 24A 24A Nominal load current (A): 8.5A cos ⌽ from 1 to 0 Power factor range: Sinusoidal Wave shape: Nominal load (VA): 1000 1000 3000 3000 Maximum up-time (sec): 3.15s Timer control: See Figs 9 & 10 p12 I2t control: 12A Overload current limit (A RMS): 12A 35A 35A 30A Short circut curremt limit (A RMS): 30A 75A 75A TIMER 0.05 to 3.15s Range: 0.05s steps Setting: INDICATORS green LED System OK: red LED Compensator running: TEMPERATURE 45°C (113°F) Maximum ambient working temperature: CUBICLE Extruded Aluminum Construction: Height (mm) (Dim. L3 on p17): 280 305 273 273 Height (in) (Dim. L3 on p17): 11.02 12.07 10.75 10.75 150 (5.90) 311 (12.24) Width mm (in): 110 (4.33) 162 (6.38) Depth mm (in): Mass (kg): 5.0 5.0 9.0 9.0 Mass (lbs): 11.0 11.0 19.8 19.8 CONNECTION 2mm 2 5mm 2 Cable, Copper panel wire; size mm 2: 14 AWG 10 AWG Cable, Copper panel wire; size AWG: 1.76Nm (15.6lb-n) Screw terminal torque Nm (lb-in): LISTINGS Listing pending. Underwriters Laboratories Inc: STANDARDS SUPPORTED Semiconductor processing equipment voltage sag immunity. SEMI F47: The VDC family is designed for applications that must meet the SEMI F47 Voltage Sag Immunity Standard for Semiconductor Processing Equipment and where size and cost are critical factors. VDC L4T/L6T & VDC S4T/S6T Series - Firmware ver 1.4 & up Page 5 Installation & Service Manual Specifications VDC L4T/L6T & S4T/S6T series 208V / 220V / 230V models AC INPUT SUPPLY Single phase supply voltage 50/60Hz: Maximum input voltage: Minimum input voltage: Full load current (A RMS): Maximum surge current for 3 cycles duration: AC OUTPUT Nominal output voltage (V): Voltage fluctuations over full operating range: Nominal load current (A): Power factor range: Wave shape: Nominal load (VA): Maximum up-time (sec): Timer control: I2t control: Overload current limit (A RMS): Short circut curremt limit (A RMS): TIMER Range: Setting: INDICATORS System OK: Compensator running: TEMPERATURE Maximum ambient working temperature: CUBICLE Construction: Height (mm) (Dim. L3 on p17): Height (in) (Dim. L3 on p17): Width mm (in): Depth mm (in): Mass (kg): Mass (lbs): CONNECTION Cable, Copper panel wire; size mm 2: Cable, Copper panel wire; size AWG: Screw terminal torque Nm (lb-in): LISTINGS Underwriters Laboratories Inc: STANDARDS SUPPORTED SEMI F47: 208V 220V 208V 220V VDC L6T5K230 VDC L4T5K230 VDC S6T1K230 VDC S4T1K230 VDC L6T5K220 VDC L4T5K220 VDC S6T1K220 VDC S4T1K220 VDC L6T5K208 VDC L4T5K208 VDC S6T1K208 VDC S4T1K208 208 / 220 /230V MODELS 230V +10% -50% -64% -50% -64% -50% -64% -50% -64% -50% -64% -50% -64% 4.8A 24A 4.6A 22.7A 4.3A 21.7A 550A 4.8A 24A 4.6A 1000 5000 1000 28A 75A 3.15s See Figs 9 & 10 p12 12A 28A 12A 35A 75A 35A 12A 35A 230V ± 10% 22.7A 4.3A cos ⌽ from 1 to 0 Sinusoidal 5000 1000 21.7A 5000 28A 75A 0.05 to 3.15s 0.05s steps green LED red LED 45°C (113°F) 293 280 304 11.02 11.97 11.54 150 (5.90) 311 (12.24) 110 (4.33) 162 (6.38) 9.0 5.0 11.0 19.8 2mm 2 14AWG 5mm 2 10AWG Extruded Aluminum 293 293 280 304 280 304 11.02 11.97 11.54 11.02 11.97 11.54 150 (5.90) 311 (12.24) 150 (5.90) 311 (12.24) 110 (4.33) 162 (6.38) 110 (4.33) 162 (6.38) 5.0 9.0 5.0 9.0 11.0 19.8 11.0 19.8 2mm 2 5mm 2 2mm 2 14AWG 10AWG 14AWG 1.76Nm (15.6lb-in) 5mm 2 10AWG Listing pending. Semiconductor processing equipment voltage sag immunity. The VDC S6T & L6T series should be used for critical applications where support down to 37% of nominal supply voltage is needed. Page 6 VDC L4T/L6T & VDC S4T/S6T Series - Firmware ver 1.4 & up Installation & Service Manual VDC support for the SEMI F47 standard 100 0 90 10 80 20 70 Required equipment voltage sag ride through capability. This is the equipment "no fault" operation area. 60 50 40 30 30 40 50 60 F47 Specification 0.05 to 1 sec 70 20 80 10 90 0 0.01 0.02 0.1 Sag depth % Vsupply Vsupply % This standard was drafted by the Semiconductor Industry to specify Voltage Sag Immunity requirements for semiconductor processing equipment. The profile for the F47 standard is shown in Fig 3. 1 10 100 Sag duration sec 100 Fig 3 SEMI F47 Standard. The blue zone represents the operation area where no equipment faults must occur due to voltage sags on the supply. The “no fault” window is from 50ms to 1 second with variable depth sag to a maximum of 50% of the nominal supply voltage. The VDC family is designed for applications that must meet the SEMI F47 Voltage Sag Immunity Standard for Semiconductor Processing Equipment and where size and cost are critical factors. Vsupply % 0 90% 90 78% % 80 70 67% 58% 60 40 30 20 10 0 0.01 0.02 0.1 60 5.9s 8.6s12.5s 11s 15s 22s 32s 46s 67s VDC support provides voltage sag immunity and extends the "no fault" equipment operation area. 1 30 50 For 120V models - 9.6A 2.1s 3.0s 4.1s For 230V models - 4.3A F47 Specification 0.05 to 1 sec 20 40 50% 6 tap models o only 43% 6 tap models only 36% 50 10 Sag depth % Vsupply 100 10 100 Sag duration sec 70 80 90 100 Fig 4 VDC extended support for the SEMI F47 Standard. Times shown are for the VDC S4T/S6T series with Iload = 9.6A for 120V models, Iload = 4.3A for 230V models & duty cycle 1 maximum length event every 20 minutes. The green area in Fig 4 shows the extended support provided by the VDC S4T/ 6T series. Support times are shown in green for 120V models at a load current of 9.6 amps and in red for 230 models at a load current of 4.3 amps.The “no fault” window is extended VDC L4T/L6T & VDC S4T/S6T Series - Firmware ver 1.4 & up Page 7 Installation & Service Manual from 50ms to 4.1 &12.5 seconds respectively with a maximum continuous sag depth of 50%. VDC L4T3K/5K & VDC L6T3K/5K support times are shown in Fig 5. 90 78% 80 70 30 58% 60 40 50% 20 VDC support provides voltage sag immunity and extends the "no fault" equipment operation area. 10 0 0.01 0.02 41.7s F47 Specification 0.05 to 1 sec 23.8s 30 36% 7.7s 40 50 43% 2.1s 6 tap models only 6 tap models only 4.2s 50 0.1 1 10 20 67% 13.5s Vsupply % 0 90% 10 100 Sag duration sec Sag depth % Vsupply 100 60 70 80 90 100 Fig 5 VDC extended support for the SEMI F47 Standard. Times shown are for the VDC L4T/6T 3K/5K series with Iload = 24A & duty cycle 1 maximum length event every 7 minutes. 100 0 90 10 80 20 70 30 DPI support provides voltage sag and supply interruption immunity. The "no fault" equipment operation area is extended to protect against momentary interruptions. 60 50 40 30 F47 Specification 0.05 to 1 sec 20 10 0 0.01 0.02 40 50 Sag depth % Vsupply Vsupply % The VDC S6T & L6T series should be used for critical applications where support down to 37% of nominal supply voltage is needed. The Fig 5 shows the extended support area. The “no fault” window is extended from 50ms to 2.1 seconds with a maximum continuous sag depth of 63%. 60 70 80 90 0.1 1 10 100 Sag duration sec 100 Fig 6 DPI support for the SEMI F47 Standard. For applications that require protection against momentary interruptions and sags refer to our Voltage Dip Proofing Inverter (DPI) product line for a simple cost effective solution that is easy to intergate into OEM products or retrofit to existing equipment. The DPI support profile is shown together with the F47 curve in Fig 6. It can be seen that the DPI provides complete protection for all sag depths and interruptions from 0 to 3 seconds. Page 8 VDC L4T/L6T & VDC S4T/S6T Series - Firmware ver 1.4 & up Installation & Service Manual Installation Guide 1. Remove the unit from its packing 2. Place the unit horizontally on a bench and visually check for any mechanical damage. Ensure that all the casing screws are tight then shake the unit to check that there is nothing loose internally. Note : Please inform your shipping agent if any damage has occurred during transit : the damaged unit(s) and all packing material should be kept in case the insurers wish to inspect the damage. 3. Check that compensator voltage is the same as the system control voltage. Refer to the rating label on the unit end plate. WARNING: Never connect a 120V unit to a 208V or 230V supply! 4. Decide on the location where the unit is to be installed, this will probably be inside a switch gear panel. 5. Mount the unit vertically using M6 bolts. 6. Connect unit as shown in Fig 7 using 2mm2 (14AWG), VDC S series & 5mm2 (10AWG), VDC L series copper panel wire. 7. Apply terminal screw tightening torque of 0.6 - 0.8Nm (5.2 - 7 lb-in), VDC S series & 1.5 - 1.8Nm (13 - 16 lb-in) VDC L series. 8. This device does not have a disconnect switch. If such a switch is required it must be provided by others. Power Wiring Connect Line In (Supply) to Terminal 1 Connect Common Line in to Terminal 2 Connect Common Line out to Terminal 3 Connect Line Out (Load) to Terminal 4 Connect the ground screw(s) to the panel ground point. 1 2* 3* 4 Ground in Ground out Line in Line out (Load) (Supply) Common line in *Note: 2 & 3 linked internally. Common line out Fig 7 Power Wiring Diagram VDC L4T/L6T & VDC S4T/S6T Series - Firmware ver 1.4 & up Page 9 Installation & Service Manual 9. Once the unit has been mounted and the external wiring completed, power can be applied.Turn on the power to the unit. The green LED indicator "System OK" will come on after approximately one second and the unit is fully operational. 10. In applications which require no break maintenance, a bypass switch must be installed. Order the appropriate Bypass Switch (see p17) which should be connected as shown in Fig 8. DIP-PROOFING TECHNOLOGIES System OK INC. Compensator Running Voltage Dip Compensator VDC 1 2 3 4 Ground Ground To DPI or VDC 1 2 3 4 out in Common Line Line in Line out DPI Bypass Housed Bypass Switch Common Line out in Line in To Supply 1 2 3 Line out 4 Line In Line Out (Supply Vnom) (Load) Common line in Common line out Fig 8 Housed Bypass Switch Connection Diagram Functional Description of the Indicators System OK : Green LED indicator When the green LED is ON the system is fully functional; the unit self test & initialization routine has been run successfully. Compensator Running : Red LED indicator The red LED is on when the compensator is running during a voltage dip. Page 10 VDC L4T/L6T & VDC S4T/S6T Series - Firmware ver 1.4 & up Installation & Service Manual Indicator error codes Flashes Indicator Condition 1 2 Profile ✓ System OK Green ✓ Star t up Test . System OK Green Compensator running Red Event not fully suppor ted. Resets after 24 hours. Supply check, AC input low. ✓ Load current check, overload. Test and Maintenance There are no user serviceable parts inside the unit, if faulty return to factory or local agent for repairs. Adjustments Adjustment points are marked on the control card and can be reached by removing the front cover of the VDC; see Mechanical Construction on page 15. Compensator Run Time Timer controlled Run Time - SW1 (see Fig.11 page 13) This switch sets the running time of the compensator and can be set in 50ms steps to a maximum of 3.15 seconds. To determine the run time which is currently set, add the figures printed next to each switch that is in the ON position. For example, a running time setting of 3.15 seconds requires these switch combinations: 1-on, 2-on, 3-on, 4-on, 5-on, 6-on. I2t controlled Run Time. Run Time is dynamically optimized to the longest that load conditions will allow. The I2t optimized Run Time can be determined using the curves on page 12. To enable this option set all SW1 switches to OFF. Factory Setting : I2t control (SW1 1-6- off) VDC L4T/L6T & VDC S4T/S6T Series - Firmware ver 1.4 & up Page 11 Installation & Service Manual I2t controlled run time curves Use the curves below (Fig 9 for “S” series & Fig 10 for “L” series) to determine the I t controlled run times for a specific load current and sag depth. Note that the two left most curves are for six tap models only. 2 10.00 Time - 78% Time - 67% Time - 58% Time - 50% Time - 43% Time - 36% 9.00 Load Current (amps) 8.00 7.00 6.00 5.00 4.00 6 Tap only 6 Tap only 3.00 2.00 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 45.0 50.0 55.0 60.0 2 I t Up-time (seconds) Fig 9 Maximum I t controlled Up-times for VDC S4T/S6T1K series. Duty cycle 1 maximum length event every 20 minutes. 2 26.00 Time-78% sag Time-58% sag Time-43% sag 24.00 Time-67% sag Time-50% sag Time-36% sag Load current (amps) 22.00 20.00 18.00 16.00 14.00 6 Tap only 12.00 0.00 5.00 6 Tap only 10.00 15.00 20.00 25.00 30.00 35.00 40.00 45.00 50.00 55.00 60.00 2 I t Up-time (sec) Fig 10 Maximum I2t controlled Up-times for VDC L4T/S6T3K & VDC L4T/S6T5K series. Duty cycle 1 maximum length event every 7 minutes. Page 12 VDC L4T/L6T & VDC S4T/S6T Series - Firmware ver 1.4 & up Installation & Service Manual LED1 LED2 Green Red System OK Running Note 2 : VDC setting. DSW2 is set by factory. Do not change settings. Note 1 : VDC setting. To activate "I2t controlled runtime" set all DSW1 switches to the OFF position. DSW2 ON DSW1 Default I2t control 1600msec 800msec 400msec 200msec 100msec 50msec O 6 5 4 SW1 3 Off 6T HC On 4T LC AV - NV - 6T - 6 tap VDC 4T - 4 tap VDC HC - 3K/5K VDC LC - 1K VDC AV - Auto supply sensing on NV - Auto supply sensing off ~ #4 Not used 2 1 Set run time Push & release to calibrate. Fig 11 Control Card Indicator & Adjustment Locations Fault Diagnosis Chart Symptom Probable Cause Remedy System OK LED (green) is off, no voltage on output terminals. No supply voltage on input terminals 1 & 2. Check supply. System OK LED (green) is off. Compensator Running LED (red) flashes onc e every second. There is no voltage on output terminals 3 & 4. Overload condition, load current exceeds unit overload rating. Check load current, if it exceeds the Overload rating eliminate any devices that do not need to be suppor ted or use a larger unit. System OK LED (green) is off, voltage on terminals 3 & 4 no voltage on 1 & 2. Supply and load wires are reversed. Terminals 1 & 4. Powered up for > 3 seconds. System OK LED (green) is off. Compensator Running LED (red) is off. There may / may not be voltage on terminals 3 & 4. Unit failure. Return to local agent or manufacturer for repair. System OK LED (green) flashes twice every second. voltage present on output terminals. Low supply voltage. A 208/220/230V unit is being used with a 120V supply. Change unit to 120V model. Unit failure when supply switched on. A 120V unit is being used on a 208V or 220V supply. Change unit to correct voltage model. Note: The 120V unit will be damaged! VDC L4T/L6T & VDC S4T/S6T Series - Firmware ver 1.4 & up Swap supply & load wires. Supply terminal 1 and load terminal 4. Page 13 Page 14 4 Line out (Load) 3 2 Common line CN3 1 Line in (Supply) Out In Ground CN4 G2 Switch Static G1 A2 C2 TH2 R10 JP4 R8 JP3 R7 CT1 JP2 120V JP1 220V AC1 AC2 AC1 AC2 E1 G1 E2 G2 A1 C1 TH1 R11 R9 TX1 Z4 Z2 Z1 Z5 Z3 CN1:11 CN1:14 CN1:16 CN1:17 CN1:10 CN1:12 CN1:8 CN1:6 CN1:4 Control Card CN1:1 CN1:7 CN1:13 CN1:3 CN1:5 CN1:9 CN1:15 G2 VSS2 E2 CTRL2 PS2 G1 VSS1 E1 CTRL1 PS1 G2 VSS2 E2 CTRL2 PS2 CN6 CN5 Tap Switch 6 Tap Switch 5 Tap Switch 4 Tap Switch 3 Tap Switch 2 G2 VSS2 E2 CTRL2 PS2 G1 VSS1 E1 CTRL1 PS1 Tap Switch 1 G1 VSS1 E1 CTRL1 PS1 Tap Switch Drivers VDR5 Static Switch drivers TAP6 CN2: TAP5 CN2: TAP4 CN2:2 5 TAP3 CN2:3 4 TAP2 CN2:6 1 TAP1 CN2:4 CN2:1 3 6 6 Tap models only. F6 F5 F4 F3 F2 F1 CN2:5 2 4 tap 1 7 9 8 2 4 6 tap Compensation Transformer Installation & Service Manual Fig 12 VDC Block Wiring Diagram VDC L4T/L6T & VDC S4T/S6T Series - Firmware ver 1.4 & up Installation & Service Manual Notes VDC L4T/L6T & VDC S4T/S6T Series - Firmware ver 1.4 & up Page 15 Installation & Service Manual Mechanical Construction VDC S series - The VDC case is made from extruded aluminium sections. The four parts that make up the case are interlocked and secured by screws. To remove the front cover unscrew four screws : the two top screws from the end plate where the terminal block is located and the two bottom screws from the other end plate. Slide the front cover away from the terminal block to access adjustment area. VDC L series - The VDC case is made from extruded aluminium sections. The six parts that make up the case are interlocked and secured by screws. To remove the front cover unscrew three screws : one from the front cover and one each from the top and bottom end plates. Dimension Table Model VDC S4T1K120 VDC S6T1K120 VDC L4T3K120 VDC L6T3K120 VDC S4T1K208 VDC S6T1K208 VDC L4T5K208 VDC L6T5K208 VDC S4T1K220 VDC S6T1K220 VDC L4T5K220 VDC L6T5K220 VDC S4T1K230 VDC S6T1K230 VDC L4T5K230 VDC L6T5K230 Page 16 L1 177 (6.97) 200 (7.87) L2 237 (9.33) 260 (10.24) VDC Dimensions mm (in) L3 L4 L5 L6 280 (11.02) 110 (4.33) 150 (5.90) 30 (1.18) 303 (11.93) 170 (6.69) 250 (9.84) 293 (11.54) 162 (6.38) 311 (12.24) 40 (1.57) 296 (11.65) 8.0 (0.31) 177 (6.97) 200 (7.87) 237 (9.33) 260 (10.24) 280 (11.02) 110 (4.33) 150 (5.90) 303 (11.93) 170 (6.69) 250 (9.84) 293 (11.54) 162 (6.38) 311 (12.24) 40 (1.57) 296 (11.65) 8.0 (0.31) 177 (6.97) 200 (7.87) 237 (9.33) 260 (10.24) 280 (11.02) 110 (4.33) 150 (5.90) 303 (11.93) 170 (6.69) 250 (9.84) 293 (11.54) 162 (6.38) 311 (12.24) 40 (1.57) 296 (11.65) 8.0 (0.31) 177 (6.97) 200 (7.87) 237 (9.33) 260 (10.24) 280 (11.02) 110 (4.33) 150 (5.90) 303 (11.93) 170 (6.69) 250 (9.84) 293 (11.54) 162 (6.38) 311 (12.24) 40 (1.57) 296 (11.65) 8.0 (0.31) 30 (1.18) 30 (1.18) 30 (1.18) L7 D 140 (5.50) 6.0 (0.24) 140 (5.50) 6.0 (0.24) 140 (5.50) 6.0 (0.24) 140 (5.50) 6.0 (0.24) VDC L4T/L6T & VDC S4T/S6T Series - Firmware ver 1.4 & up Installation & Service Manual Mechanical Outline L7 "L" series case. ØD "S" series case. Model # example DPI52S50-23 or VDC S4T1K230 L6 L1 L2 L3 L1* Model # example DPI52L3K23 or VDC L4T5K120 L1 L2 L3 ØD L6 L6 L7 1 2 3 4 L1* Terminal Cover L4 Ground Screws L6 1 2 34 L5 1 2 3 4 Terminal Cover 1 2 34 VOLTAGE DIP-PROOFING INVERTER MODEL VOLTS SERIAL # POWER DATE MFG HZ L5 L4 Ground Screws Note 1: Terminal cover shown dashed. Note 2: Terminal #1 - Line in (Supply) Terminal #2 - Common line in Terminal #3 - Common line out Terminal #4 - Line out (Load) Fig 13 Dimensions of the VDC series mm (inches) VDC L4T/L6T & VDC S4T/S6T Series - Firmware ver 1.4 & up Page 17 Installation & Service Manual Accessories Housed Bypass Switch Description Where no-break maintenance is required a by pass switch must be installed. It connects the supply directly to the load, "Bypass" position, and disconnects the power terminals of the inverter without interrupting the supply. When in "DPI" position the load is connected to the supply via the inverter. Specifications MODEL ELECTRICAL Maximum current: Maximum input voltage: TEMPERATURE Maximum working temperature: HOUSING Construction: Height: Width: Depth: Mass: BPSW25A 25A 600Vac 45°C (113°F) Extruded Aluminum 202mm (7.95in) 150mm (5.9in) 141mm (5.55in) 1kg (2.2lbs) Mechanical outline Note 1: Dimension units. Without brackets - mm. With brackets - inches. 31 (1.22) 41.0 (1.61) Note 2: Mounting holes 2 x 6 (0.25)Ø. Line in Line in (Supply) 2 3 Line out (Load) 4 41.0 (1.61) To Supply 1 Common Line out in 50 (1.97) 4 110 (4.33) 3 Line out DPI Bypass 2 4 out in Common Line Ground Screws 1 3 2 120 (4.72) 1 50 (1.97) To DPI or VDC 140 (5.51) 150 (5.90) Ordering Stock No: 5003-006 Page 18 Description Housed By-Pass Switch 25Amp VDC L4T/L6T & VDC S4T/S6T Series - Firmware ver 1.4 & up Installation & Service Manual The Sag Simulator is an effective tool to evaluate the effects of momentary voltage sags and interruptions on industrial controls. When used in conjunction with a Voltage Dip-Proofing Inverter or a Voltage Dip Compensator and Bypass switch, it may be used to prove the effectiveness of the DPI or VDC as a solution for these power quality problems. The Sag Simulator is designed for 120/208/ 240Vac operation. The controls consist of a variac to set the sag depth, an LCD display to indicate the sag voltage value and program status, four programming keys to set up and operate the simulator. A variable interrupt timer sets the duration of the voltage sag and the point in the cycle at which it begins. Both variables are set using the programming keys and are indicated on the LCD display. Simulator output is short circuit and overload protected. A 5V synchronization pulse is provided to trigger an oscilloscope. A photograph appears on page 8; the specifications are shown below. CONTROLS & INDICATORS Programming: Menu/parameter indicaton: Four push switches 4 x 20 LCD display SYNC PULSE OUTPUT Amplitude: Polarity: Electrically isolated output: Duration: 5V Positive Yes Equal to sag duration TEMPERATURE Maximum ambient working temperature: 45°C (113°F) HOUSING Construction: Height: Width: Depth: Mass: Extruded aluminium 390mm (15.35in ) 311mm (12.24in) 162mm (6.38in) 15kg (33lb) Simulated Sag Profile Supply V Voltage Sag Simulator Description Positive zero crossing 300 200 Sag Duration 60ms Sag Depth 50% Sag Voltage 110Vrms 100 0 -100 Sag Simulator Specifications Sag Delay 5ms -300 120/208/240Vac 50/60Hz +10% 20A VARIAC CONTROL Variac range: 0-240Vac RMS Maximum power: 1200VA @ 120V / 2400VA @ 240V Maximum continuous current:10A Maximum short term current for 3 seconds: 20A Overload & short circuit protection: Yes Sag Simulator output Supply voltage - 220V 50Hz 0 V Sync AC INPUT SUPPLY Supply voltage: Maximum input voltage: Full load current: -200 10 20 30 40 50 Sync pulse output 60 70 80 90 100 Time ms Terminals 4 & 5 5 0 Duration = 60mS = Sag Duration Amplitude = 5V -5 0 10 20 30 40 50 60 70 80 90 100 Time ms DIRECT VARIAC OUTPUT Variac range: 0-240Vac RMS Maximum power: 1200VA @ 120V / 2400VA @ 240V Maximum continuous current: 10A Overload & short circuit protection: Yes SAG DELAY TIMER Range: 0.00 to 20.00 ms Setting: 0.01 ms steps SAG DURATION TIMER Range: 0.010 to 9.999 seconds Setting: 0.001 second steps VDC L4T/L6T & VDC S4T/S6T Series - Firmware ver 1.4 & up Page 19 Installation & Service Manual Voltage-Dip Compensators For VDC L4T/L6T & S4T/S6T series Models 120V / 208V / 220V / 230V 50/60Hz Motor Control Centre Voltage-Dip Compensator 1 Static Switch - 1 B1 B2 B3 Stop Stop Stop Start Start Start Interlock Interlock Interlock C1 C2 C3 3 Static Switch - 2 Static Switch - 3 Controls Static Switch - 4 Static Switch - 5 Compensation Transformer Main Breaker 2 Bypass Switch Line Voltage Control Voltage A typical VDC connection diagram DIP-PROOFING TECHNOLOGIES INC. LEADERS IN VOLTAGE-DIP PROOFING Doc Ref. 3704-010 Rev 1.2 May 19th 2005 : LPW 1941 Lake Whatcom Blvd. #112 Bellingham WA 98229 USA e-mail: [email protected] Web: www.dipproof.com