Download continued - Lochinvar
Transcript
Service Manual 2 Maintenance Maintenance and annual startup Table 2A_Service and Maintenance Schedules Owner maintenance Service technician (see the following pages for instructions) (see the Power-fin User’s Information Manual for instructions) General: • Check appliance area • Address reported problems • Inspect interior; clean and vacuum if necessary; • Check pressure/temperature gauge Daily • Inspect condensate system and flush with fresh water • Check for leaks (water, gas, flue, condensate) ANNUAL START-UP • Examine venting system • Check system water pressure/system piping/expansion tank • Check vent piping • Check control settings Monthly • Check igniter • Check wiring and connections • Check air piping • Check relief valve • Check flue gas passageways • Check condensate drain system • Flame inspection (stable, uniform) • Inspect and clean the burner • Check manifold gas pressure • Clean the heat exchanger if flue temperature is more than 54°F (30°C) above return water temperature. • Perform start-up checkout and performance verification per Section 7 in the Power-fin Installation and Operation Manual. Periodically • Test low water cutoff (if used) • Reset button (low water cutoff) Every 6 months • Check appliance piping (gas and water) for leaks • Operate relief valve If combustion indicate need: or performance • Clean heat exchanger • Remove and clean compressed air only • Clean the blower wheel 22 burner using End of season months • Shut appliance down (unless boiler used for domestic hot water)