Download Specs_Vol 3_Div13thr.. - Precon Industries File Access

Transcript
UPH Barracks
Fort Hunter Liggett, CA
***Safety Pays***
Certified Final Submittal
W912QR-13-R-0038
TABLE III
STANDARD RATING CONDITIONS AND MINIMUM PERFORMANCE RATINGS FOR WATER HEATING
EQUIPMENT
STORAGE
CAPACITY
GALLONS
FUEL
A.
120 max.
Elect.
120 min.
Gas
100 max.
Gas
100 min.
Oil
50 max.
Oil
51 min.
OR
REQUIRED PERFORMANCE
12 kW max.
10 CFR 430
EF = 0.95-0.00132V
minimum
12 kW min.
ASHRAE 90.1
SL = 1.9 W/sq. ft.
(Addenda B)
maximum
75,000 Btu/h
max.
10 CFR 430
75,000 Btu/h
ANSI Z21.10.3
ET = 80 percent;
SL = 1.3+38/V max.
105,000 Btu/h
10 CFR 430
EF = 0.80-0.0019V
minimum
OR 105,000 Btu/h
10 CFR 430
EC = 83 percent;
SL = 1.3+38/V
maximum
OR
EF = 0.80-0.0019V
minimum
Unfired Hot Water Storage, instantaneous water heater, and pool heater.
Volumes and inputs:
C.
TEST PROCEDURE
STORAGE WATER HEATERS
Elect.
B.
INPUT
RATING
maximum HL shall be 6.5 Btu/h/sq. ft.
Instantaneous Water Heater
Gas
All
All
ANSI Z21.10.3
ET = 80 percent
Oil
All
All
ANSI Z21.10.3
EC = 83 percent
D.
Pool Heater
All
ANSI Z21.56
ET = 78 percent
Gas or
Oil
All
TERMS:
EF = Energy factor, overall efficiency.
ET = Thermal efficiency with 70 degrees F delta T.
EC = Combustion efficiency, 100 percent - flue loss when smoke = 0
(trace is permitted).
SL = Standby loss in W/sq. ft. based on 80 degrees F delta T, or in
percent per hour based on nominal 90 degrees F delta T.
HL = Heat loss of tank surface area
V = Storage volume in gallons
-- End of Section --
SECTION 22 00 00.00 48
Page 48