Download Hardware Service Manual, PowerFlex Digital DC Drive, Frame C
Transcript
Access Procedures Chapter 3 Total Resistance Values Table 14 - 230V AC Input Drives Drive Current Rating Code 521 DC Amps 521 AC Line Amps 426 HP Set RTA Value Using TA Potentiometer (Ohms) 4.699 150 Table 15 - 460V AC Input Drives Drive Current Rating Code 495 667 DC Amps 495 667 AC Line Amps 404.4 544.9 HP Set RTA Value Using TA Potentiometer (Ohms) 4.945 3.67 300 400 3. Seal the TA potentiometer in place using RV (silicon). 4. Continue with Install the Pulse Transformer Circuit Board on page 70. Configuring a Pulse Transformer Board FIR3-xx Rev. “M” and Higher Set DIP switches S3 and S4 (shown in the illustration below) on the pulse transformer board to the correct settings based on the appropriate AC input voltage, armature output current, and HP rating shown in Table 16 or Table 17 on page 70. S4 S3 1 1 XTM X4 XR X5 XCD_IO XSW XCT XUVW XCD XP2 TR2 X3 XP1 XI2CA S4 S3 XY TR1 1 TR3 1 XTA TO1 T1 KGO1 KG1 T4 KG4 TO4 KGO4 TO2 KGO2 T2 KG2 Rockwell Automation Publication 20P-TG003A-EN-P - February 2012 T5 KG5 TO5 KGO5 TO3 KGO3 T3 KG3 T6 KG6 TO6 KGO6 69