Download PSI Certified Stationary Engine Fuel System

Transcript
Step
Action
Value(s)
v
6
Using a high impedance DVOM check for
continuity between EGO 1 connector signal
ground pin C and EGO 1 signal pin A
Do you have continuity?
v
7
8
9
Using a high impedance DVOM check for
continuity between EGO 1 heater ground pin
D and ECM pin 49
Do you have continuity?
v Replace EGO 1 sensor
Is the replacement complete?
v Remove all test equipment except the DST.
v Connect any disconnected components, fuses, etc.
v Using the DST clear DTC information from the
ECM.
v Turn the ignition OFF and wait 30 seconds.
v Start the engine and operate the vehicle to full
operating temperature
v Observe the MIL
v Observe engine performance and driveability
v After operating the engine within the test parameters of DTC-1151 check for any stored
codes.
Does the engine operate normally with no stored
codes?
203
Yes
No
Repair the
shorted circuit
as necessary.
Refer to Wiring Repairs in
Engine Electrical.
Go to step (8)
Go to Step
(7)
Repair the
open EGO
heater ground
Go to Step
(9)
-
System OK
Go to OBD
System
Check