Download technical manu technical manual
Transcript
WIRING DIAGRAMS GMH8 WARNING:DISCONNECT POWER BEFORE SERVICING.WIRING TO UNIT MUST BE PROPERLY POLARIZED AND GROUNDED. INTEGRATED CONTROL MODULE HUMIDIFIER XFMR (6) GND GND (8) 24 VAC HUMIDIFIER C2 MVC (9) HI MVH (12) G R W Y 5 MIN 2 STG MODE BR 7 8 4 5 6 1 2 3 24V THERMOSTAT CONNECTIONS C BL AUXILIARY LIMITS BR INTEGRATED CONTROL MODULE M1 MVL (2) C ID BLOWER PRESSURE SWITCH G PS (10) NO C PSO (4) TO MICRO HLI (7) Y W HLO (1) R RO2 (11) RO1 (5) XFMR (3) 24 VAC RD RD 40 VA TRANSFORMER BR BL GAS VALVE RD PU XFMR-H 115 VAC XFMR-N FLAME SENSOR OR 2 YL YL 1 FP BK BK 24V BL IND-N CIRCULATOR BLWR BK 15 PIN PLUG ON SOME MODELS GR ID BLWR IND EAC-H BLOWER COMPARTMENT ELECTRONIC AIR CLEANER LINE-N JUNCTION BOX BK WH DOOR SWITCH 24 VAC HUMIDIFIER DOOR SWITCH SWITCH LOCATED IN BLOWER COMPARTMENT ON SOME MODELS NO EAC-N LINE-H BURNER COMPARTMENT C OR RD CIR-N CAP BR WH BR BR CICULATOR BLOWER BR 115V XFMR IGN-N INTEGRATED CONTROL MODULE PARK INTEGRATED CONTROL MODULE BK (HI) BL (MED) OR(MED LOW) RD (LOW) WH (N) WH PU RD YL WH WH HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. HOT SURFACE IGNITER IGN PRIMARY LIMIT PRESSURE SWITCH DISCONNECT YL RD YL YL WH BK L GND N TO 115VAC/ 1 Ø /60 HZ POWER SUPPLY WITH OVERCURRENT PROTECTION DEVICE BR BL BR PM C 1 2 HOT SURFACE IGNITER BK HI 3 JUNCTION BOX WH 2 STAGE GAS VALVE LINE-N GND LINE H PU INDUCED DRAFT BLOWER PU PU FLAME SENSOR ROLLOUT LIMITS (SINGLE CONTROL ON SOME MODELS) 0 TO 115 VAC/ 1/60HZ POWER SUPPLY WITH OVERCURRENT PROTECTION DEVICE STEADY ON = NORMAL OPERATION OFF LOW VOLTAGE (24V) = CONTROL FAILURE 1 1 FLASH = 2 2 FLASHES = PRESSURE SWITCH STUCK CLOSED 3 3 FLASHES = PRESSURE SWITCH STUCK OPEN 4 4 FLASHES = OPEN HIGH LIMIT 5 5 FLASHES = FLAME SENSE WITHOUT GAS VALVE 6 6 FLASHES = OPEN ROLLOUT OR OPEN FUSE SYSTEM LOCKOUT (RETRIES/RECYCLES EXCEEDED) 7 FLASHES = LOW FLAME SIGNAL 8 8 FLASHES = CHECK IGNITER OR IMPROPER GROUND C RAPID FLASHES = REVERSED 115 VAC POLARITY/VERIFY GND PK PINK BR BROWN WH WHITE BL BLUE GY GRAY RD RED HI VOLTAGE (115V) EQUIPMENT GND FIELD GND FIELD SPLICE HI VOLTAGE FIELD SWITCH (TEMP.) 7 COLOR CODES: YL YELLOW OR ORANGE PU PURPLE GR GREEN BK BLACK LOW VOLTAGE FIELD JUNCTION TERMINAL INTERNAL TO INTEGRATED CONTROL PLUG CONNECTION IGNITER SWITCH (PRESS.) OVERCURRENT PROT. DEVICE NOTES: 1. SET HEAT ANTICIPATOR ON ROOM THERMOSTAT AT 0.7 AMPS. 2. MANUFACTURER'S SPECIFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING. 3. IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105 °C. USE COPPER CONDUCTORS ONLY. 4. BLOWER SPEEDS SHOULD BE ADJUSTED BY INSTALLER TO MATCH THE INSTALLATION REQUIREMENTS SO AS TO PROVIDE THE CORRECT HEATING TEMPERATURE RISE AND THE CORRECT COOLING CFM. (SEE SPEC SHEET FOR AIR FLOW CHART) 5. UNIT MUST BE PERMANENTLY GROUNDED A ND CONFORM TO N.E.C. AND LOCAL CODES. 6. TO RECALL THE LAST 5 FAULTS, MOST RECENT TO LEAST RECENT, DEPRESS SWITCH FOR MORE THAN 2 SECONDS WHILE IN STANDBY(NO THERMOSTAT INPUTS). Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. 15