MCAC-HTSM-2008-04 Troubleshooting 3. E3 malfunction LED indicates E3 Communication malfunction in outdoor PCB Check whether the indicator lights LED1 or LED2 on the main control board are flashing Yes Replace PCB No Yes Install the IC-U3 chip of the PCB over again, check whether the system can run normally Trouble is solved No Yes Check whether the output of the transformer to CN4 socket is well Replace PCB No Replace the transformer Outdoor Units 259