Download 1 specifications
Transcript
AISIN Aisin gas heat pump (3) Diagnosing for current leakage If the ground leakage circuit breaker trips, measure insulation resistance values using a megohmmeter and diagnose for current leakage. Leakage diagnosing procedure [1] Checking the 200-V units If the resistance value can be recovered by disconnecting the CN1, CN2, and CN4 connectors from the outdoor unit circuit board, current is leaking from either of these connections. Check each unit independently. Example of DIP switch setting Indoor unit address Refrigerant piping Communication cable Outdoor unit Outdoor unit address Indoor unit No.1 Remote control unit SW1 SW2 [2] Checking the indoor units If the resistance value can be recovered by disconnecting the power terminals from the terminal blocks of each indoor unit, current is leaking from either indoor unit. Note: Do not connect the megohmmeter communications circuits. to the Indoor unit No.2 Remote control unit (4) Checking the remote control circuit Check the terminals of the indoor units and remote control unit for incomplete electrical contact and for wire disconnections. (5) Checking the DIP switches Check the DIP switches of the indoor and outdoor units and remote control unit for incorrect settings. Indoor unit No. Indoor unit No.10 Remote control unit Outdoor unit No. Setting of the slide switch of the remote control unit Sub SW4 Outdoor unit No. setting Indoor unit No. setting Main 3-33