AISIN Aisin gas heat pump 3.4.14 If Sufficient Heating Cannot Be Obtained Trouble Classification of Likely Causes Sub-Classification Insufficient 1) Electromagnetic [1] Electromagnetic clutch malfunction Trouble with the clutch itself clutch of the heating Incomplete contact compressor is No output Control section not engaged. [2] Indoor temperature sensor malfunction Short-circuiting Sensor fault Check and Remedy - See “(1) Checking the electromagnetic clutch” in 3.3.13. - See “(1) Checking the temperature sensor” in 3.3.12. (Adequate air conditioning cannot be obtained since the indoor temperature is mis-judged to be higher than its actual value.) - Confirm circuit protector 2) Electromagnetic [1] Automatic activation of refrigerant circuit clutch is protector status. disengaged immediately No error is displayed until the refrigerant circuit protector has repeated its after being automatic activation and automatic resetting several times. During this engaged. automatic resetting cycle, therefore, the clutch is repeatedly engaged and disengaged. 3) Improper indoor unit heat exchange 4) Sufficient compressor capabilities cannot be obtained. [1] Insufficient ventilation Indoor unit air filter clogging Heat exchange fin clogging - Clean the indoor unit air filter. [2] Improper indoor fan motor rotation Abnormal output voltage Fan capacitor malfunction Fan motor malfunction - Check the indoor fan motor. See 3.3.9. First, measure the refrigerant pressure and temperature during operation and check the refrigerant cycle. [1] Insufficient heat exchange in evaporator Hot-water heat collection failure Continued flow of coolant into radiator Thermostat malfunction Coolant circuit clogging Failure to collect heat from hot air supply Insufficient ventilation Outdoor fan failure Fin clogging Short-circuiting Too low intake air temperature [2] Insufficient circulation of refrigerant Shortage of refrigerant Underfilling Refrigerant leakage Refrigerant channel clogging Expansion valve sticking Dryer filter clogging [3] Indoor unit electronic expansion valve malfunction [4] Hot-gas bypass valve does not close 3-61 - Check the operational status. - Check the thermo valve. See (4) in 3.3.5 and (1) in 3.3.12. - See “(6) Checking outdoor fan motors” in 3.3.5. - Clean the heat exchanger fins. - See “(1) Checking the amount of refrigerant” in 3.3.10. - See “(3) Checking the indoor electronic expansion valve for clogging” in 3.3.10. - See “(2) Checking the dryer filter for clogging” in 3.3.10.motor. - See “(6) Checking the electronic expansion valves” in 3.3.8. - Check the hot-gas bypass valve.