Download SERVICE MANUAL - GoDuctless.com
Transcript
9. 18-class unit in single operation (OUTDOOR UNIT : MXZ-3B24NA MXZ-3B30NA MXZ-4B36NA) (1) COOL operation Data is based on the condition of indoor humidity 50% Air flow speed : High Inverter output frequency : 24 Hz <How to work fixed-frequency operation> 1. Set emergency switch to COOL or HEAT. The switch is located on indoor unit. 2. Press emergency run ON/OFF button. 3. Compressor starts running at 24 Hz (COOL) or 32 Hz (HEAT). 4. Indoor fan runs at High speed and continues for 30 minutes. 5. To cancel this operation, press emergency run ON/OFF button or any button on remote controller. 160 6.0 F ure (˚ perat m e t -bulb r Dry Indoo ) 86 5.0 Outdoor unit current (A) Outdoor low pressure (PSIG) 170 4.0 150 80 F re (˚ ratu e p tem -bulb y r D or Indo 75 86 80 75 70 24 Hz 3.0 140 ) 2.0 130 70 1.0 24 Hz 120 0.0 65 70 75 80 85 90 95 100 105 110 115 (˚F) 65 70 75 80 85 90 95 100 105 110 115 (˚F) Ambient temperature (˚F) Ambient temperature (˚F) (2) HEAT operation Data is based on the condition of outdoor humidity 75%. Set air flow to High speed. Inverter output frequency is 32 Hz. Outdoor unit current (A) 7.0 6.0 5.0 oor Ind e( tur a r pe tem b l -bu Dry ˚F ) 75 70 65 4.0 32 Hz 3.0 2.0 15 20 25 30 35 40 45 50 55 60 65 70 75 (˚F) Ambient temperature (˚F) OBH560G 46