Download Service Manual

Transcript
Error Codes: Outdoor Units
1
3.8
“F3” Malfunctioning in Discharge Pipe Temperature
Remote controller
display
33
ESIE08-01
F3
Method of
malfunction
detection
Abnormality is detected according to the temperature detected by the discharge pipe temperature
sensor.
Malfunction
decision conditions
■
When the discharge pipe temperature rises to an abnormally high level
■
When the discharge pipe temperature rises suddenly
Supposed causes
■
Faulty discharge pipe thermistor
■
Faulty connection of discharge pipe thermistor
■
Insufficient refrigerant amount
■
Faulty compressor
■
Disconnection of discharge pipe thermistor
4
5
3–68