Download Outdoor Unit
Transcript
SiE39-404
Service
Manual
R-410A Heat Pump 50Hz
http://splitoff.ru/tehn-doc.html
,
,
,
.
SiE39-404
R410A Heat Pump
50Hz
1. Introduction ............................................................................................ vi
1.1 Safety Cautions ....................................................................................... vi
1.2 PREFACE ................................................................................................x
Part 1 General Information ........................................................... 1
1. Model Names of Indoor/Outdoor Units....................................................2
2. External Appearance...............................................................................3
2.1 Indoor Units ..............................................................................................3
2.2 Outdoor Units ...........................................................................................4
3. Combination of Outdoor Units.................................................................5
4. Model Selection......................................................................................6
Part 2 Specifications .................................................................... 9
1. Specifications ........................................................................................10
1.1 Outdoor Units .........................................................................................10
1.2 Indoor Units ............................................................................................21
Part 3 Refrigerant Circuit ........................................................... 49
1. Refrigerant Circuit .................................................................................50
1.1 RXYQ5M (*Products after January, 2004)...........................................50
1.2 RXYQ8, 10, 12M (*Products after January, 2004)...............................52
1.3 RXYQ14, 16M (*Products after January, 2004) ..................................54
1.4 Outdoor air processing unit FXMQ125~250MFV1 .................................56
2. Functional Parts Layout ........................................................................57
2.1 RXYQ5M ................................................................................................57
2.2 RXYQ8, 10, 12M ....................................................................................58
2.3 RXYQ14, 16M ........................................................................................59
3. Refrigerant Flow for Each Operation Mode...........................................60
Part 4 Function............................................................................ 73
1. Function general ...................................................................................74
1.1 Symbol ...................................................................................................74
1.2 Operation Mode......................................................................................75
2. Basic Control.........................................................................................76
2.1
2.2
2.3
2.4
Table of Contents
Normal Operation ...................................................................................76
Compressor PI Control...........................................................................77
Electronic Expansion Valve PI Control...................................................83
Cooling Operation Fan Control...............................................................84
: http://splitoff.ru/tehn-doc.html
i
SiE39-404
3. Special Control......................................................................................85
3.1
3.2
3.3
3.4
3.5
3.6
3.7
Startup Control .......................................................................................85
Oil Return Operation ..............................................................................86
Defrosting Operation ..............................................................................88
Pump-down Residual Operation ............................................................89
Restart Standby......................................................................................90
Stopping Operation ................................................................................91
Pressure Equalization prior to Startup....................................................93
4. Protection Control .................................................................................94
4.1
4.2
4.3
4.4
4.5
High Pressure Protection Control...........................................................94
Low Pressure Protection Control............................................................95
Discharge Pipe Protection Control .........................................................96
Inverter Protection Control .....................................................................97
STD Compressor Overload Protection...................................................98
5. Other Control.........................................................................................99
5.1
5.2
5.3
5.4
Outdoor Unit Rotation.............................................................................99
Emergency Operation ..........................................................................100
Demand Operation ...............................................................................102
Heating operation prohibition ...............................................................102
6. Outline of Control (Indoor Unit) ...........................................................103
6.1
6.2
6.3
6.4
6.5
Drain Pump Control..............................................................................103
Louver Control for Preventing Ceiling Dirt............................................105
Thermostat Sensor in Remote Controller.............................................106
Freeze Prevention ................................................................................108
Control of outdoor air Processing unit (Unique Control for
Outdoor Air Processing Unit)................................................................109
Part 5 Test Operation ............................................................... 113
1. Test Operation ....................................................................................114
1.1 Procedure and Outline .........................................................................114
1.2 Operation When Power is Turned On ..................................................117
2. Outdoor Unit PC Board Layout ...........................................................118
3. Field Setting ........................................................................................119
3.1 Field Setting from Remote Controller ...................................................119
3.2 Field Setting from Outdoor Unit............................................................132
Part 6 Troubleshooting ............................................................. 157
1. Troubleshooting by Remote Controller ...............................................160
1.1
1.2
1.3
1.4
The INSPECTION / TEST Button.........................................................160
Self-diagnosis by Wired Remote Controller .........................................161
Self-diagnosis by Wireless Remote Controller .....................................162
Operation of The Remote Controller’s Inspection /
Test Operation Button ..........................................................................165
1.5 Remote Controller Service Mode .........................................................166
1.6 Remote Controller Self-Diagnosis Function .........................................168
2. Troubleshooting by Indication on the Remote Controller ....................173
2.1
2.2
2.3
2.4
ii
“A0” Indoor Unit: Error of External Protection Device ...........................173
“A1” Indoor Unit: PC Board Defect.........................................................174
“A3” Indoor Unit: Malfunction of Drain Level Control System (S1L) ......175
“A6” Indoor Unit: Fan Motor (M1F) Lock, Overload...............................177
: http://splitoff.ru/tehn-doc.html
Table of Contents
SiE39-404
2.5 “A7” Indoor Unit: Malfunction of Swing Flap Motor (MA) .......................178
2.6 “A9” Indoor Unit: Malfunction of Moving Part of
Electronic Expansion Valve (20E) ........................................................180
2.7 “AF” Indoor Unit: Drain Level above Limit..............................................182
2.8 “AJ” Indoor Unit: Malfunction of Capacity Determination Device ..........183
2.9 “C4” Indoor Unit: Malfunction of Thermistor (R2T) for Heat Exchanger 184
2.10 “C5” Indoor Unit: Malfunction of Thermistor (R3T) for Gas Pipes..........185
2.11 “C9” Indoor Unit: Malfunction of Thermistor (R1T) for Suction Air.........186
2.12 “CJ” Indoor Unit: Malfunction of Thermostat Sensor
in Remote Controller ............................................................................187
2.13 “E1” Outdoor Unit: PC Board Defect ......................................................188
2.14 “E3” Outdoor Unit: Actuation of High Pressure Switch ..........................189
2.15 “E4” Outdoor Unit: Actuation of Low Pressure Sensor ..........................190
2.16 “E5” Compressor Motor Lock ................................................................191
2.17 “E6” Compressor Motor Overcurrent/Lock ............................................192
2.18 “E7” Malfunction of Outdoor Unit Fan Motor..........................................193
2.19 “E9” Outdoor Unit: Malfunction of Moving Part of
Electronic Expansion Valve (Y1E, Y2E)...............................................195
2.20 “F3” Outdoor Unit: Abnormal Discharge Pipe Temperature ..................197
2.21 “F6” Refrigerant Overcharged ...............................................................198
2.22 “H7” Abnormal Outdoor Fan Motor Signal .............................................199
2.23 “H9” Outdoor Unit: Malfunction of Thermistor for Outdoor Air (R1T).....200
2.24 “J2” Current Sensor Malfunction...........................................................201
2.25 “J3” Outdoor Unit: Malfunction of Discharge Pipe Thermistor
(R3, R31~33T) .....................................................................................202
2.26 “J5” Outdoor Unit: Malfunction of Thermistor (R2T) for Suction Pipe ...203
2.27 “J6” Outdoor Unit: Malfunction of Thermistor (R4T) for
Outdoor Unit Heat Exchanger ..............................................................204
2.28 “J8” Malfunction of Oil Equalizing Pipe Thermistor (R7T).....................205
2.29 “J9” Malfunction of Receiver Gas Pipe Thermistor (R5T).....................206
2.30 “JA” Outdoor Unit: Malfunction of Discharge Pipe Pressure Sensor.....207
2.31 “JC” Outdoor Unit: Malfunction of Suction Pipe Pressure Sensor .........208
2.32 “L4” Outdoor Unit: Malfunction of Inverter Radiating
Fin Temperature Rise...........................................................................209
2.33 “L5” Outdoor Unit: Inverter Compressor Abnormal ...............................210
2.34 “L8” Outdoor Unit: Inverter Current Abnormal.......................................211
2.35 “L9” Outdoor Unit: Inverter Start up Error..............................................212
2.36 “LC” Outdoor Unit: Malfunction of Transmission Between Inverter
and Control PC Board ..........................................................................213
2.37 “P1” Outdoor Unit: Inverter Over-Ripple Protection ...............................215
2.38 “P4” Outdoor Unit: Malfunction of Inverter Radiating Fin
Temperature Rise Sensor ....................................................................216
2.39 “UO” Low Pressure Drop Due to Refrigerant Shortage or
Electronic Expansion Valve Failure......................................................217
2.40 “U1” Reverse Phase, Open Phase.........................................................218
2.41 “U2” Power Supply Insufficient or Instantaneous Failure ......................219
2.42 “U3” Check Operation not executed ......................................................221
2.43 “U4” Malfunction of Transmission Between Indoor Units ......................222
2.44 “U5” Malfunction of Transmission Between Remote Controller
and Indoor Unit.....................................................................................224
2.45 “U7” Malfunction of Transmission Between Outdoor Units ....................225
2.46 “U8” Malfunction of Transmission Between Master and
Slave Remote Controllers ....................................................................227
Table of Contents
: http://splitoff.ru/tehn-doc.html
iii
SiE39-404
2.47 “U9” Malfunction of Transmission Between Indoor and
Outdoor Units in the Same System ......................................................228
2.48 “UA” Excessive Number of Indoor Units ................................................230
2.49 “UC” Address Duplication of Central Remote Controller ........................231
2.50 “UE” Malfunction of Transmission Between Central Remote
Controller and Indoor Unit ....................................................................232
2.51 “UF” Refrigerant System not Set, Incompatible Wiring/Piping ...............234
2.52 “UH” Malfunction of System, Refrigerant System Address Undefined...235
3. Troubleshooting (OP: Central Remote Controller) ..............................236
3.1 “UE” Malfunction of Transmission Between Central Remote
Controller and Indoor Unit ....................................................................236
3.2 “M1” PC Board Defect ............................................................................237
3.3 “M8” Malfunction of Transmission Between Optional Controllers
for Centralized Control .........................................................................238
3.4 “MA” Improper Combination of Optional Controllers for
Centralized Control...............................................................................239
3.5 “MC” Address Duplication, Improper Setting ..........................................241
4. Troubleshooting (OP: Schedule Timer)...............................................242
4.1 “UE” Malfunction of Transmission Between Central Remote
Controller and Indoor Unit ....................................................................242
4.2 “M1” PC Board Defect ............................................................................244
4.3 “M8” Malfunction of Transmission Between Optional Controllers for
Centralized Control...............................................................................245
4.4 “MA” Improper Combination of Optional Controllers for
Centralized Control...............................................................................246
4.5 “MC” Address Duplication, Improper Setting ..........................................248
5. Troubleshooting (OP: Unified ON/OFF Controller) .............................249
5.1 Operation Lamp Blinks .........................................................................249
5.2 Display “Under Host Computer Integrate Control” Blinks
(Repeats Single Blink)..........................................................................251
5.3 Display “Under Host Computer Integrate Control” Blinks
(Repeats Double Blink) ........................................................................254
Part 7 Replacement procedure for INV compressor,
VRV II (RXYQ5M to 48M)................................................ 257
1. Replacement procedure for INV compressor,
VRV II (RXYQ5M-48M) .......................................................................258
1.1 Replacement procedure .......................................................................258
Part 8 Appendix......................................................................... 259
1. Piping Diagrams..................................................................................260
1.1 Outdoor Unit .........................................................................................260
1.2 Indoor Unit............................................................................................263
2. Wiring Diagrams for Reference...........................................................269
2.1 Outdoor Unit .........................................................................................269
2.2 Field Wiring ..........................................................................................272
2.3 Indoor Unit............................................................................................275
3. List of Electrical and Functional Parts .................................................293
3.1 Outdoor Unit .........................................................................................293
3.2 Indoor Side ...........................................................................................295
iv
: http://splitoff.ru/tehn-doc.html
Table of Contents
SiE39-404
4. Option List ...........................................................................................301
4.1 Option List of Controllers......................................................................301
4.2 Option Lists (Outdoor Unit)...................................................................303
5. Piping Installation Point.......................................................................304
5.1 Piping Installation Point ........................................................................304
5.2 The Example of A Wrong Pattern.........................................................305
6. Selection of Pipe Size, Joints and Header ..........................................306
6.1 RXYQ5MY1B, RXYQ8MY1B, RXYQ10MY1B, RXYQ12MY1B,
RXYQ14MY1B,
RXYQ16MY1B .....................................................................................306
6.2 RXYQ18MY1B, RXYQ20MY1B, RXYQ22MY1B, RXYQ24MY1B,
RXYQ26MY1B, RXYQ28MY1B, RXYQ30MY1B, RXYQ32MY1B,
RXYQ34MY1B, RXYQ36MY1B, RXYQ38MY1B, RXYQ40MY1B,
RXYQ42MY1B, RXYQ44MY1B, RXYQ46MY1B, RXYQ48MY1B .......308
7. Thermistor Resistance / Temperature Characteristics........................311
8. Pressure Sensor .................................................................................313
9. Method of Replacing The Inverter’s Power Transistors
and Diode Modules .............................................................................314
Part 9 Precautions for New Refrigerant (R410) ....................... 317
1. Precautions for New Refrigerant (R410) .............................................318
1.1 Outline ..................................................................................................318
1.2 Refrigerant Cylinders............................................................................320
1.3 Service Tools........................................................................................321
Index
............................................................................................. i
Drawings & Flow Charts ................................................................ v
Table of Contents
: http://splitoff.ru/tehn-doc.html
v
Introduction
SiE39-404
1. Introduction
1.1
Safety Cautions
Cautions and
Warnings
! Be sure to read the following safety cautions before conducting repair work.
! The caution items are classified into “
Warning” and “
Caution”. The “
Warning”
items are especially important since they can lead to death or serious injury if they are not
followed closely. The “
Caution” items can also lead to serious accidents under some
conditions if they are not followed. Therefore, be sure to observe all the safety caution items
described below.
! About the pictograms
This symbol indicates an item for which caution must be exercised.
The pictogram shows the item to which attention must be paid.
This symbol indicates a prohibited action.
The prohibited item or action is shown inside or near the symbol.
This symbol indicates an action that must be taken, or an instruction.
The instruction is shown inside or near the symbol.
! After the repair work is complete, be sure to conduct a test operation to ensure that the
equipment operates normally, and explain the cautions for operating the product to the
customer
1.1.1 Caution in Repair
Warning
Be sure to disconnect the power cable plug from the plug socket before
disassembling the equipment for a repair.
Working on the equipment that is connected to a power supply can cause an
electrical shook.
If it is necessary to supply power to the equipment to conduct the repair or
inspecting the circuits, do not touch any electrically charged sections of the
equipment.
If the refrigerant gas discharges during the repair work, do not touch the
discharging refrigerant gas.
The refrigerant gas can cause frostbite.
When disconnecting the suction or discharge pipe of the compressor at the
welded section, release the refrigerant gas completely at a well-ventilated
place first.
If there is a gas remaining inside the compressor, the refrigerant gas or
refrigerating machine oil discharges when the pipe is disconnected, and it can
cause injury.
If the refrigerant gas leaks during the repair work, ventilate the area. The
refrigerant gas can generate toxic gases when it contacts flames.
The step-up capacitor supplies high-voltage electricity to the electrical
components of the outdoor unit.
Be sure to discharge the capacitor completely before conducting repair work.
A charged capacitor can cause an electrical shock.
Do not start or stop the air conditioner operation by plugging or unplugging the
power cable plug.
Plugging or unplugging the power cable plug to operate the equipment can
cause an electrical shock or fire.
vi
: http://splitoff.ru/tehn-doc.html
SiE39-404
Introduction
Caution
Do not repair the electrical components with wet hands.
Working on the equipment with wet hands can cause an electrical shock.
Do not clean the air conditioner by splashing water.
Washing the unit with water can cause an electrical shock.
Be sure to provide the grounding when repairing the equipment in a humid or
wet place, to avoid electrical shocks.
Be sure to turn off the power switch and unplug the power cable when cleaning
the equipment.
The internal fan rotates at a high speed, and cause injury.
Do not tilt the unit when removing it.
The water inside the unit can spill and wet the furniture and floor.
Be sure to check that the refrigerating cycle section has cooled down
sufficiently before conducting repair work.
Working on the unit when the refrigerating cycle section is hot can cause burns.
Use the welder in a well-ventilated place.
Using the welder in an enclosed room can cause oxygen deficiency.
1.1.2 Cautions Regarding Products after Repair
Warning
Be sure to use parts listed in the service parts list of the applicable model and
appropriate tools to conduct repair work. Never attempt to modify the
equipment.
The use of inappropriate parts or tools can cause an electrical shock,
excessive heat generation or fire.
When relocating the equipment, make sure that the new installation site has
sufficient strength to withstand the weight of the equipment.
If the installation site does not have sufficient strength and if the installation
work is not conducted securely, the equipment can fall and cause injury.
Be sure to install the product correctly by using the provided standard
For integral units
installation frame.
only
Incorrect use of the installation frame and improper installation can cause the
equipment to fall, resulting in injury.
Be sure to install the product securely in the installation frame mounted on a
window frame.
If the unit is not securely mounted, it can fall and cause injury.
Be sure to use an exclusive power circuit for the equipment, and follow the
technical standards related to the electrical equipment, the internal wiring
regulations and the instruction manual for installation when conducting
electrical work.
Insufficient power circuit capacity and improper electrical work can cause an
electrical shock or fire.
: http://splitoff.ru/tehn-doc.html
For integral units
only
vii
Introduction
SiE39-404
Warning
Be sure to use the specified cable to connect between the indoor and outdoor
units. Make the connections securely and route the cable properly so that there
is no force pulling the cable at the connection terminals.
Improper connections can cause excessive heat generation or fire.
When connecting the cable between the indoor and outdoor units, make sure
that the terminal cover does not lift off or dismount because of the cable.
If the cover is not mounted properly, the terminal connection section can cause
an electrical shock, excessive heat generation or fire.
Do not damage or modify the power cable.
Damaged or modified power cable can cause an electrical shock or fire.
Placing heavy items on the power cable, and heating or pulling the power cable
can damage the cable.
Do not mix air or gas other than the specified refrigerant (R410A) in the
refrigerant system.
If air enters the refrigerating system, an excessively high pressure results,
causing equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leak and repair it before
charging the refrigerant. After charging refrigerant, make sure that there is no
refrigerant leak.
If the leak cannot be located and the repair work must be stopped, be sure to
perform pump-down and close the service valve, to prevent the refrigerant gas
from leaking into the room. The refrigerant gas itself is harmless, but it can
generate toxic gases when it contacts flames, such as fan and other heaters,
stoves and ranges.
When replacing the coin battery in the remote controller, be sure to disposed
of the old battery to prevent children from swallowing it.
If a child swallows the coin battery, see a doctor immediately.
Caution
Installation of a leakage breaker is necessary in some cases depending on the
conditions of the installation site, to prevent electrical shocks.
Do not install the equipment in a place where there is a possibility of
combustible gas leaks.
If a combustible gas leaks and remains around the unit, it can cause a fire.
Be sure to install the packing and seal on the installation frame properly.
For integral units
If the packing and seal are not installed properly, water can enter the room and only
wet the furniture and floor.
1.1.3 Inspection after Repair
Warning
Check to make sure that the power cable plug is not dirty or loose, then insert
the plug into a power outlet all the way.
If the plug has dust or loose connection, it can cause an electrical shock or fire.
If the power cable and lead wires have scratches or deteriorated, be sure to
replace them.
Damaged cable and wires can cause an electrical shock, excessive heat
generation or fire.
Do not use a joined power cable or extension cable, or share the same power
outlet with other electrical appliances, since it can cause an electrical shock,
excessive heat generation or fire.
viii
: http://splitoff.ru/tehn-doc.html
SiE39-404
Introduction
Caution
Check to see if the parts and wires are mounted and connected properly, and
if the connections at the soldered or crimped terminals are secure.
Improper installation and connections can cause excessive heat generation,
fire or an electrical shock.
If the installation platform or frame has corroded, replace it.
Corroded installation platform or frame can cause the unit to fall, resulting in
injury.
Check the grounding, and repair it if the equipment is not properly grounded.
Improper grounding can cause an electrical shock.
Be sure to measure the insulation resistance after the repair, and make sure
that the resistance is 1 Mohm or higher.
Faulty insulation can cause an electrical shock.
Be sure to check the drainage of the indoor unit after the repair.
Faulty drainage can cause the water to enter the room and wet the furniture
and floor.
1.1.4 Using Icons
Icons are used to attract the attention of the reader to specific information. The meaning of each
icon is described in the table below:
1.1.5 Using Icons List
Icon
Type of
Information
Note
Description
A “note” provides information that is not indispensable, but may
nevertheless be valuable to the reader, such as tips and tricks.
Note:
Caution
A “caution” is used when there is danger that the reader, through
incorrect manipulation, may damage equipment, loose data, get
an unexpected result or has to restart (part of) a procedure.
Warning
A “warning” is used when there is danger of personal injury.
Reference
A “reference” guides the reader to other places in this binder or
in this manual, where he/she will find additional information on a
specific topic.
Caution
Warning
: http://splitoff.ru/tehn-doc.html
ix
Introduction
1.2
SiE39-404
PREFACE
Thank you for your continued patronage of Daikin products.
This is the new service manual for Daikin's Year 2004 VRVII series Heat Pump System.
Daikin offers a wide range of models to respond to building and office air conditioning needs.
We are confident that customers will be able to find the models that best suit their needs.
This service manual contains information regarding the servicing of VRVII series Heat Pump
System.
There are some changes in piping and control system for products before December 2003.
Please refer the service information for product before December, 2003 to the service manual
Si39-302.
October, 2004
After Sales Service Division
x
: http://splitoff.ru/tehn-doc.html
SiE39-404
Part 1
General Information
1. Model Names of Indoor/Outdoor Units....................................................2
2. External Appearance...............................................................................3
2.1 Indoor Units ..............................................................................................3
2.2 Outdoor Units ...........................................................................................4
3. Combination of Outdoor Units.................................................................5
4. Model Selection......................................................................................6
General Information
: http://splitoff.ru/tehn-doc.html
1
Model Names of Indoor/Outdoor Units
SiE39-404
1. Model Names of Indoor/Outdoor Units
Indoor Units
Type
Model Name
Power Supply
Ceiling Mounted
Cassette Type
(Double Flow)
FXCQ
20M
25M
32M
40M
50M
63M
80M
—
125M
—
—
Ceiling Mounted
Cassette Type
(Multi Flow) 600×600
FXZQ
20M
25M
32M
40M
50M
—
—
—
—
—
—
Ceiling Mounted
Cassette Type
(Multi Flow)
FXFQ
—
25M
32M
40M
50M
63M
80M
100M
125M
—
—
Ceiling Mounted
Cassette Corner Type
FXKQ
—
25M
32M
40M
—
63M
—
—
—
—
—
Slim Ceiling Mounted
Duct Type
FXDQ
20N
25N
32N
40N
50N
63N
—
—
—
—
—
Ceiling Mounted
Built-In Type
FXSQ
20M
25M
32M
40M
50M
63M
80M
100M
125M
—
—
Ceiling Mounted
Duct Type
FXMQ
—
—
—
40M
50M
63M
80M
100M
125M
200M
250M
Ceiling Suspended
Type
FXHQ
—
—
32M
—
—
63M
—
100M
—
—
—
Wall Mounted Type
FXAQ
20M
25M
32M
40M
50M
63M
—
—
—
—
—
Floor Standing Type
FXLQ
20M
25M
32M
40M
50M
63M
—
—
—
—
—
Concealed Floor
Standing Type
FXNQ
20M
25M
32M
40M
50M
63M
—
—
—
—
—
Outdoor Air Processing
Unit
FXMQMF
—
—
—
—
—
—
—
—
125MF 200MF 250MF
VE
V1
Indoor Units (Connection Unit Series)
Type
Model Name
Ceiling Suspended
Cassette Type
FXUQ
Wall Mounted Type
Power Supply
—
—
—
—
—
—
71M
100M
125M
—
—
FXAQ-MH
20MH
25MH
32MH
40MH
50MH
—
—
—
—
—
—
Floor Standing Type FXLQ-MH
20MH
25MH
32MH
40MH
50MH
—
—
—
—
—
—
Connection Unit
50M
50M
50M
50M
50M
—
71M
100M
125M
—
—
BEVQ-M
V1
VE
Note: BEV unit is required for each indoor unit.
Outdoor Units
Series
Heat Pump
Model Name
RXYQ
5M
8M
10M
12M
14M
RXYQ
28M
30M
32M
34M
36M
Series
Heat Pump
18M
20M
22M
24M
26M
42M
44M
46M
48M
Model Name
VE:
V1:
Y1B:
2
16M
Power Supply
38M
40M
Y1B
Power Supply
Y1B
1φ, 220~240V, 50Hz, 1φ, 220V, 60Hz
1φ, 220~240V, 50Hz
3φ, 380~415V, 50Hz
: http://splitoff.ru/tehn-doc.html General Information
SiE39-404
External Appearance
2. External Appearance
2.1
Indoor Units
Ceiling Mounted Cassette Type (Double Flow)
FXCQ20M
FXCQ25M
FXCQ32M
FXCQ40M
FXCQ50M
FXCQ63M
FXCQ80M
FXCQ125M
Wall Mounted Type
FXAQ20M
FXAQ25M
FXAQ32M
FXAQ40M
FXAQ50M
FXAQ63M
Ceiling Mounted Cassette
Type (Multi Flow) 600×600
Floor Standing Type
FXLQ20M(H)
FXLQ25M(H)
FXLQ32M(H)
FXLQ40M(H)
FXLQ50M(H)
FXLQ63M(H)
FXZQ20M
FXZQ25M
FXZQ32M
FXZQ40M
FXZQ50M
Ceiling Mounted Cassette Type (Multi Flow)
FXFQ25M
FXFQ32M
FXFQ40M
FXFQ50M
FXFQ63M
FXFQ80M
FXFQ100M
FXFQ125M
Concealed Floor Standing Type
FXNQ20M
FXNQ25M
FXNQ32M
FXNQ40M
FXNQ50M
FXNQ63M
Ceiling Mounted Cassette Corner Type
FXKQ25M
FXKQ32M
FXKQ40M
FXKQ63M
New Ceiling Suspended Cassette Type
FXUQ71M
FXUQ100M
FXUQ125M
+
+
+
BEVQ71M
BEVQ100M
BEVQ125M
Connection Unit
Slim Ceiling Mounted Duct Type
Wall Mounted Type (Connection Unit Series)
FXDQ20N
FXDQ25N
FXDQ32N
FXDQ40N
FXDQ50N
FXDQ63N
FXAQ20MH
FXAQ25MH
FXAQ32MH
FXAQ40MH
FXAQ50MH
Ceiling Mounted Built-In Type
Floor Standing Type (Connection Unit Series)
FXSQ20M
FXSQ25M
FXSQ32M
FXSQ40M
FXSQ50M
FXSQ63M
FXSQ80M
FXSQ100M
FXSQ125M
FXLQ20MH
FXLQ25MH
FXLQ32MH
FXLQ40MH
FXLQ50MH
Ceiling Mounted Duct Type
FXMQ40M
FXMQ50M
FXMQ63M
FXMQ80M
FXMQ100M
FXMQ125M
FXMQ200M
FXMQ250M
+BEVQ50M
+BEVQ50M
Outdoor Air Processing Unit
FXMQ40~125M
FXMQ200 · 250M
Ceiling Suspended Type
FXHQ32M
FXHQ63M
FXHQ100M
General Information
: http://splitoff.ru/tehn-doc.html
3
External Appearance
2.2
4
SiE39-404
Outdoor Units
RXYQ5M
RXYQ8M, 10M
RXYQ12M, 14M, 16M
5HP
8,10HP
12,14,16HP
RXYQ18M, 20M
RXYQ22M, 24M, 26M
18, 20HP
22, 24, 26HP
RXYQ28M, 30M , 32M
RXYQ34M, 36M
28, 30, 32HP
34, 36HP
RXYQ38M, 40M , 42M
RXYQ44M, 46M, 48M
38, 40, 42HP
44, 46, 48HP
: http://splitoff.ru/tehn-doc.html General Information
SiE39-404
Combination of Outdoor Units
3. Combination of Outdoor Units
System Number
Capacity of units
5HP
1
8HP
1
10HP
1
12HP
1
14HP
1
16HP
1
18HP
2
20HP
2
22HP
2
24HP
2
26HP
2
28HP
2
30HP
2
32HP
2
34HP
3
36HP
3
38HP
3
40HP
3
42HP
3
44HP
3
46HP
3
48HP
3
Note:
General Information
5
l
8
Module
10
12
Outdoor Unit Multi Connection Piping Kit+Pipe
Size Reducer (Option)
14
16
l
l
—
l
l
l
l
l
ll
l
l
l
Heat Pump: BHFP22M90+BHFP22M90P
l
l
l
l
ll
ll
l
l
l
l
l
l
ll
l
l
l
l
l
Heat Pump: BHFP22M135+BHFP22M135P
l
l
l
ll
ll
ll
lll
For multiple connection of 18HP systems or more, an optional Daikin outdoor unit multi
connection piping kit is required.
: http://splitoff.ru/tehn-doc.html
5
Model Selection
SiE39-404
4. Model Selection
VRV II Heat Pump Series
Connectable indoor units number and capacity
5HP
8HP
10HP
12HP
14HP
16HP
System name
HP
RXYQ5M
RXYQ8M
RXYQ10M
RXYQ12M
RXYQ14M
RXYQ16M
Outdoor unit 1
RXYQ5M
RXYQ8M
RXYQ10M
RXYQ12M
RXYQ14M
RXYQ16M
Outdoor unit 2
–
–
–
–
–
–
Outdoor unit 3
–
–
–
–
–
–
Total number of connectable indoor units
8
13
16
19
20
20
Total capacity of connectable indoor units (kW)
7.0~18.2
11.2~29.1
14.0~36.4
16.8~43.6
20.0~52.0
22.5~58.5
HP
18HP
20HP
22HP
24HP
26HP
28HP
RXYQ18M
RXYQ20M
RXYQ22M
RXYQ24M
RXYQ26M
RXYQ28M
Outdoor unit 1
RXYQ8M
RXYQ10M
RXYQ10M
RXYQ10M
RXYQ10M
RXYQ12M
Outdoor unit 2
RXYQ10M
RXYQ10M
RXYQ12M
RXYQ14M
RXYQ16M
RXYQ16M
Outdoor unit 3
–
–
–
–
–
–
Total number of connectable indoor units
20
20
22
32
32
32
Total capacity of connectable indoor units (kW)
25.2~65.5
28.0~72.8
30.8~80.0
34.0~88.4
36.5~94.9
39.3~102.1
System name
30HP
32HP
34HP
36HP
38HP
40HP
System name
HP
RXYQ30M
RXYQ32M
RXYQ34M
RXYQ36M
RXYQ38M
RXYQ40M
Outdoor unit 1
RXYQ14M
RXYQ16M
RXYQ10M
RXYQ10M
RXYQ10M
RXYQ10M
Outdoor unit 2
RXYQ16M
RXYQ16M
RXYQ10M
RXYQ10M
RXYQ12M
RXYQ14M
Outdoor unit 3
–
–
RXYQ14M
RXYQ16M
RXYQ16M
RXYQ16M
Total number of connectable indoor units
32
32
34
36
38
40
Total capacity of connectable indoor units (kW)
42.5~110.5
45.0~117.0
48.0~124.8
50.5~131.3
53.3~138.5
56.5~146.9
42HP
44HP
46HP
48HP
System name
HP
RXYQ42M
RXYQ44M
RXYQ46M
RXYQ48M
Outdoor unit 1
RXYQ10M
RXYQ12M
RXYQ14M
RXYQ16M
Outdoor unit 2
RXYQ16M
RXYQ16M
RXYQ16M
RXYQ16M
Outdoor unit 3
RXYQ16M
RXYQ16M
RXYQ16M
RXYQ16M
Total number of connectable indoor units
40
40
40
40
Total capacity of connectable indoor units (kW)
59.0~153.4
61.8~160.6
65.0~169.0
67.5~175.5
6
: http://splitoff.ru/tehn-doc.html General Information
SiE39-404
Model Selection
Connectable Indoor Unit
Type
Model Name
Power Supply
Ceiling Mounted
Cassette Type
(Double Flow)
FXCQ
20M
25M
32M
40M
50M
63M
80M
—
125M
—
—
Ceiling Mounted
Cassette Type
(Multi Flow) 600×600
FXZQ
20M
25M
32M
40M
50M
—
—
—
—
—
—
Ceiling Mounted
Cassette Type
(Multi Flow)
FXFQ
—
25M
32M
40M
50M
63M
80M
100M
125M
—
—
Ceiling Mounted
Cassette Corner Type
FXKQ
—
25M
32M
40M
—
63M
—
—
—
—
—
Slim Ceiling Mounted
Duct Type
FXDQ
20N
25N
32N
40N
50N
63N
—
—
—
—
—
Ceiling Mounted
Built-In Type
FXSQ
20M
25M
32M
40M
50M
63M
80M
100M
125M
—
—
Ceiling Mounted
Duct Type
FXMQ
—
—
—
40M
50M
63M
80M
100M
125M
200M
250M
Ceiling Suspended
Type
FXHQ
—
—
32M
—
—
63M
—
100M
—
—
—
Wall Mounted Type
FXAQ
20M
25M
32M
40M
50M
63M
—
—
—
—
—
Floor Standing Type
FXLQ
20M
25M
32M
40M
50M
63M
—
—
—
—
—
Concealed Floor
Standing Type
FXNQ
20M
25M
32M
40M
50M
63M
—
—
—
—
—
Outdoor Air Processing
Unit
FXMQMF
—
—
—
—
—
—
—
—
VE
125MF 200MF 250MF
V1
Connectable Indoor Unit (Connection Unit Series)
Type
Model Name
Ceiling Suspended
Cassette Type
FXUQ
Wall Mounted Type
Power Supply
—
—
—
—
—
—
71M
100M
125M
—
—
FXAQ-MH
20MH
25MH
32MH
40MH
50MH
—
—
—
—
—
—
Floor Standing Type FXLQ-MH
20MH
25MH
32MH
40MH
50MH
—
—
—
—
—
—
Connection Unit
50M
50M
50M
50M
50M
—
71M
100M
125M
—
—
BEVQ-M
V1
VE
Note: BEV unit is required for each indoor unit.
Indoor unit capacity
New refrigerant model code
Selecting model capacity
Equivalent output
P20
type
2.2
kW
0.8HP
P25
type
2.8
kW
1HP
P32
type
3.5
kW
1.25HP
P40
type
4.5
kW
1.6HP
P50
type
5.6
kW
2.0HP
P63
type
7.0
kW
2.5HP
P80
type
9.0
kW
3.2HP
P100
type
11.2
kW
4HP
P125
type
14.0
kW
5HP
P200
type
22.4
kW
8HP
P250
type
28.0
kW
10HP
Use the above tables to determine the capacities of indoor units to be connected. Make sure the
total capacity of indoor units connected to each outdoor unit is within the specified value (kW).
! The total capacity of connected indoor units must be within a range of 50 to 130% of the
rated capacity of the outdoor unit.
! In some models, it is not possible to connect the maximum number of connectable indoor
units. Select models so the total capacity of connected indoor units conforms to the
specification.
General Information
: http://splitoff.ru/tehn-doc.html
7
Model Selection
8
SiE39-404
: http://splitoff.ru/tehn-doc.html General Information
SiE39-404
Part 2
Specifications
1. Specifications ........................................................................................10
1.1 Outdoor Units .........................................................................................10
1.2 Indoor Units ............................................................................................21
Specifications
: http://splitoff.ru/tehn-doc.html
9
Specifications
SiE39-404
1. Specifications
1.1
Outdoor Units
Model Name
H1 Cooling Capacity (19.5°CWB)
RXYQ5MY1B
RXYQ8MY1B
kcal / h
12,500
20,000
Btu / h
49,500
78,900
kW
14.5
23.1
kW
14.0
22.4
kcal / h
13,800
21,500
Btu / h
54,600
85,400
kW
16.0
25.0
Ivory White (5Y7.5/1)
Ivory White (5Y7.5/1)
1600×635×765
1600×930×765
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing Color
Dimensions: (H×W×D)
mm
Heat Exchanger
Type
Comp.
13.72
6480
6480, 2900
Motor Output×Number
of Units
kW
3.2×1
(1.2+4.5)×1
Soft start
Soft start
Propeller Fan
Propeller Fan
0.75×1
Motor Output
kW
0.35×1
Air Flow Rate
m³/min
75
175
Direct Drive
Direct Drive
Liquid Pipe
mm
φ9.5 (Flare Connection)
φ9.5 (Flare Connection)
Gas Pipe
mm
φ15.9 (Flare Connection)
φ19.1 (Brazing Connection)
Oil Equalizing Pipe
mm
—
—
kg
160
230
Machine Weight (Mass)
High Pressure Switch, Fan Driver Overload Protector,
Inverter Overload Protector, Fusible Plugs
Safety Devices
Defrost Method
Capacity Control
%
Refrigerant Name
Charge
kg
Control
Refrigerator
Oil
13.72+10.47
m³/h
r.p.m
Drive
Refrigerant
Hermetically Sealed Scroll Type
Number of Revolutions
Type
Connecting
Pipes
Cross Fin Coil
Hermetically Sealed Scroll Type
Piston Displacement
Starting Method
Fan
Cross Fin Coil
Charge Volume
L
Deicer
Deicer
24~100
14~100
R410A
R410A
5.6
8.6
Electronic Expansion Valve
Electronic Expansion Valve
Synthetic (ether) oil
Synthetic (ether) oil
1.2
1.9+1.6
Installation Manual, Operation Manual, Connection Pipes,
Clamps
Standard Accessories
Drawing No.
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector,
Fusible Plugs
4D038964B
Installation Manual, Operation Manual, Connection Pipes,
Clamps
4D038965B
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
H3 Indoor temp. : 20°CDB / outdoor temp. : 7°CDB, 6°CWB / Equivalent piping length : 7.5m, level difference
: 0m.
10
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications
SiE39-404
Specifications
Model Name
RXYQ10MY1B
H1 Cooling Capacity (19.5°CWB)
25,000
30,000
Btu / h
98,700
118,000
kW
28.9
34.6
kW
28.0
33.5
kcal / h
27,000
32,300
Btu / h
108,000
128,000
kW
31.5
37.5
Ivory White (5Y7.5/1)
Ivory White (5Y7.5/1)
1600×930×765
1600×1240×765
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing Color
Dimensions: (H×W×D)
mm
Heat Exchanger
Type
Comp.
13.72+10.47
m³/h
13.72+10.47
6480, 2900
6480, 2900
Motor Output×Number
of Units
kW
(2.7+4.5)×1
(4.2+4.5)×1
Soft start
Soft start
Propeller Fan
Propeller Fan
0.75×1
Motor Output
kW
0.75×1
Air Flow Rate
m³/min
180
210
Direct Drive
Direct Drive
Liquid Pipe
mm
φ9.5 (Flare Connection)
φ12.7 (Flare Connection)
Gas Pipe
mm
φ22.2 (Brazing Connection)
φ28.6 (Brazing Connection)
Oil Equalizing Pipe
mm
—
—
kg
230
281
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector,
Fusible Plugs
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector,
Fusible Plugs
Machine Weight (Mass)
Safety Devices
Defrost Method
Capacity Control
%
Refrigerant Name
Charge
kg
Control
Refrigerator
Oil
Hermetically Sealed Scroll Type
r.p.m
Drive
Refrigerant
Cross Fin Coil
Hermetically Sealed Scroll Type
Number of Revolutions
Type
Connecting
Pipes
Cross Fin Coil
Piston Displacement
Starting Method
Fan
RXYQ12MY1B
kcal / h
Charge Volume
L
Deicer
Deicer
14~100
14~100
R410A
R410A
9.6
11.4
Electronic Expansion Valve
Electronic Expansion Valve
Synthetic (ether) oil
Synthetic (ether) oil
1.9+1.6
1.9+1.6
Installation Manual, Operation Manual, Connection Pipes,
Clamps
Standard Accessories
Drawing No.
4D038966B
Installation Manual, Operation Manual, Connection Pipes,
Clamps
4D038967C
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
H3 Indoor temp. : 20°CDB / outdoor temp. : 7°CDB, 6°CWB / Equivalent piping length : 7.5m, level difference
: 0m.
Specifications
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
11
Specifications
SiE39-404
Model Name
RXYQ14MY1B
H1 Cooling Capacity (19.5°CWB)
35,500
40,000
Btu / h
141,000
157,000
kW
41.3
45.9
kW
40.0
44.5
kcal / h
38,700
43,000
Btu / h
154,000
171,000
kW
45.0
50.0
Ivory White (5Y7.5/1)
Ivory White (5Y7.5/1)
1600×1240×765
1600×1240×765
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing Color
Dimensions: (H×W×D)
mm
Heat Exchanger
Type
Comp.
13.72+10.47+10.47
m³/h
13.72+10.47+10.47
6480, 2900×2
6480, 2900×2
Motor Output×Number
of Units
kW
(2.0+4.5+4.5)×1
(3.0+4.5+4.5)×1
Soft start
Soft start
Propeller Fan
Propeller Fan
0.75×1
Motor Output
kW
0.75×1
Air Flow Rate
m³/min
210
210
Direct Drive
Direct Drive
Liquid Pipe
mm
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
Gas Pipe
mm
φ28.6 (Brazing Connection)
φ28.6 (Brazing Connection)
Oil Equalizing Pipe
mm
—
—
kg
323
325
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector,
Fusible Plugs
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector,
Fusible Plugs
Machine Weight (Mass)
Safety Devices
Defrost Method
Capacity Control
%
Refrigerant Name
Charge
kg
Control
Refrigerator
Oil
Hermetically Sealed Scroll Type
r.p.m
Drive
Refrigerant
Cross Fin Coil
Hermetically Sealed Scroll Type
Number of Revolutions
Type
Connecting
Pipes
Cross Fin Coil
Piston Displacement
Starting Method
Fan
RXYQ16MY1B
kcal / h
Charge Volume
L
Deicer
Deicer
10~100
10~100
R410A
R410A
12.9
14.4
Electronic Expansion Valve
Electronic Expansion Valve
Synthetic (ether) oil
Synthetic (ether) oil
1.9+1.6+1.6
1.9+1.6+1.6
Installation Manual, Operation Manual, Connection Pipes,
Clamps
Standard Accessories
Drawing No.
4D038968C
Installation Manual, Operation Manual, Connection Pipes,
Clamps
4D038969C
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
H3 Indoor temp. : 20°CDB / outdoor temp. : 7°CDB, 6°CWB / Equivalent piping length : 7.5m, level difference
: 0m.
12
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications
SiE39-404
Specifications
Model Name (Combination Unit)
RXYQ18MY1B
RXYQ20MY1B
Model Name (Independent Unit)
RXYQ8MY1B+RXYQ10MY1B
RXYQ10MY1B+RXYQ10MY1B
H1 Cooling Capacity (19.5°CWB)
kcal / h
45,000
50,000
Btu / h
178,000
197,000
kW
52.0
57.8
kW
50.4
56.0
kcal / h
48,500
54,000
Btu / h
193,000
216,000
kW
56.5
63.0
Ivory White (5Y7.5/1)
Ivory White (5Y7.5/1)
(1600×930×765)+(1600×930×765)
(1600×930×765)+(1600×930×765)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing Color
Dimensions: (H×W×D)
mm
Heat Exchanger
Type
Comp.
m³/h
(13.72+10.47)×2
(13.72+10.47)×2
r.p.m
(6480, 2900)×2
(6480, 2900)×2
Motor Output×Number
of Units
kW
(1.2+4.5)+(2.7+4.5)
(2.7+4.5)×2
Soft start
Propeller Fan
kW
0.75×2
0.75×2
Air Flow Rate
m³/min
175+180
180+180
Direct Drive
Direct Drive
Liquid Pipe
mm
φ15.9 (Brazing Connection)
φ15.9 (Brazing Connection)
Gas Pipe
mm
φ28.6 (Brazing Connection)
φ28.6 (Brazing Connection)
Oil Equalizing Pipe
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
kg
230+230
230+230
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector,
Fusible Plugs
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector,
Fusible Plugs
Deicer
Deicer
Machine Weight (Mass)
Safety Devices
Defrost Method
Capacity Control
%
Refrigerant Name
Charge
kg
Control
Refrigerator
Oil
Soft start
Propeller Fan
Motor Output
Drive
Refrigerant
Hermetically Sealed Scroll Type
Number of Revolutions
Type
Connecting
Pipes
Cross Fin Coil
Hermetically Sealed Scroll Type
Piston Displacement
Starting Method
Fan
Cross Fin Coil
Charge Volume
L
7~100
7~100
R410A
R410A
8.6+9.6
9.6+9.6
Electronic Expansion Valve
Electronic Expansion Valve
Synthetic (ether) oil
Synthetic (ether) oil
(1.9+1.6)+(1.9+1.6)
(1.9+1.6)+(1.9+1.6)
Installation Manual, Operation Manual, Connection Pipes,
Clamps
Standard Accessories
Drawing No.
4D038965B, 4D038966B
Installation Manual, Operation Manual, Connection Pipes,
Clamps
4D038966B
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
H3 Indoor temp. : 20°CDB / outdoor temp. : 7°CDB, 6°CWB / Equivalent piping length : 7.5m, level difference
: 0m.
Specifications
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
13
Specifications
SiE39-404
Model Name (Combination Unit)
RXYQ22MY1B
RXYQ24MY1B
Model Name (Independent Unit)
RXYQ10MY1B+RXYQ12MY1B
RXYQ10MY1B+RXYQ14MY1B
H1 Cooling Capacity (19.5°CWB)
kcal / h
55,000
60,500
Btu / h
217,000
240,000
kW
63.5
70.2
kW
61.5
68.0
kcal / h
59,300
65,700
Btu / h
236,000
262,000
kW
69.0
76.5
Ivory White (5Y7.5/1)
Ivory White (5Y7.5/1)
(1600×930×765)+(1600×1240×765)
(1600×930×765)+(1600×1240×765)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing Color
Dimensions: (H×W×D)
mm
Heat Exchanger
Type
Comp.
m³/h
(13.72+10.47)×2
(13.72+10.47)+(13.72+10.47+10.47)
r.p.m
(6480, 2900)×2
(6480, 2900)+(6480, 2900×2)
Motor Output×Number
of Units
kW
(2.7+4.5)+(4.2+4.5)
(2.7+4.5)+(2.0+4.5+4.5)
Soft start
Propeller Fan
kW
0.75×2
0.75×2
Air Flow Rate
m³/min
180+210
180+210
Direct Drive
Direct Drive
Liquid Pipe
mm
φ15.9 (Brazing Connection)
φ15.9 (Brazing Connection)
Gas Pipe
mm
φ28.6 (Brazing Connection)
φ34.9 (Brazing Connection)
Oil Equalizing Pipe
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
kg
230+281
230+323
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector,
Fusible Plugs
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector,
Fusible Plugs
Deicer
Deicer
Machine Weight (Mass)
Safety Devices
Defrost Method
Capacity Control
%
Refrigerant Name
Charge
kg
Control
Refrigerator
Oil
Soft start
Propeller Fan
Motor Output
Drive
Refrigerant
Hermetically Sealed Scroll Type
Number of Revolutions
Type
Connecting
Pipes
Cross Fin Coil
Hermetically Sealed Scroll Type
Piston Displacement
Starting Method
Fan
Cross Fin Coil
Charge Volume
L
7~100
6~100
R410A
R410A
9.6+11.4
9.6+12.9
Electronic Expansion Valve
Electronic Expansion Valve
Synthetic (ether) oil
Synthetic (ether) oil
(1.9+1.6)+(1.9+1.6)
(1.9+1.6)+(1.9+1.6+1.6)
Installation Manual, Operation Manual, Connection Pipes,
Clamps
Standard Accessories
Drawing No.
4D038966B, 4D038967C
Installation Manual, Operation Manual, Connection Pipes,
Clamps
4D038966B, 4D038968C
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20°CDB / outdoor temp. : 7°CDB, 6°CWB / Equivalent piping length : 7.5m, level difference
: 0m.
14
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications
SiE39-404
Specifications
Model Name (Combination Unit)
RXYQ26MY1B
RXYQ28MY1B
Model Name (Independent Unit)
RXYQ10MY1B+RXYQ16MY1B
RXYQ12MY1B+RXYQ16MY1B
H1 Cooling Capacity (19.5°CWB)
kcal / h
65,000
70,000
Btu / h
256,000
275,000
kW
74.9
80.5
kW
72.5
78.0
kcal / h
70,000
75,300
Btu / h
279,000
299,000
kW
81.5
87.5
Ivory White (5Y7.5/1)
Ivory White (5Y7.5/1)
(1600×930×765)+(1600×1240×765)
(1600×1240×765)+(1600×1240×765)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing Color
Dimensions: (H×W×D)
mm
Heat Exchanger
Type
Comp.
m³/h
(13.72+10.47)+(13.72+10.47+10.47)
(13.72+10.47)+(13.72+10.47+10.47)
r.p.m
(6480, 2900)+(6480, 2900×2)
(6480, 2900)+(6480, 2900×2)
Motor Output×Number
of Units
kW
(2.7+4.5)+(3.0+4.5+4.5)
(4.2+4.5)+(3.0+4.5+4.5)
Soft start
Propeller Fan
kW
0.75×2
0.75×2
Air Flow Rate
m³/min
180+210
210+210
Direct Drive
Direct Drive
Liquid Pipe
mm
φ19.1 (Brazing Connection)
φ19.1 (Brazing Connection)
Gas Pipe
mm
φ34.9 (Brazing Connection)
φ34.9 (Brazing Connection)
Oil Equalizing Pipe
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
kg
230+325
281+325
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector,
Fusible Plugs
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector,
Fusible Plugs
Deicer
Deicer
Machine Weight (Mass)
Safety Devices
Defrost Method
Capacity Control
%
Refrigerant Name
Charge
kg
Control
Refrigerator
Oil
Soft start
Propeller Fan
Motor Output
Drive
Refrigerant
Hermetically Sealed Scroll Type
Number of Revolutions
Type
Connecting
Pipes
Cross Fin Coil
Hermetically Sealed Scroll Type
Piston Displacement
Starting Method
Fan
Cross Fin Coil
Charge Volume
L
6~100
6~100
R410A
R410A
9.6+14.4
11.4+14.4
Electronic Expansion Valve
Electronic Expansion Valve
Synthetic (ether) oil
Synthetic (ether) oil
(1.9+1.6)+(1.9+1.6+1.6)
(1.9+1.6)+(1.9+1.6+1.6)
Installation Manual, Operation Manual, Connection Pipes,
Clamps
Standard Accessories
Drawing No.
4D038966B, 4D038969C
Installation Manual, Operation Manual, Connection Pipes,
Clamps
4D038967C, 4D038969C
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
H3 Indoor temp. : 20°CDB / outdoor temp. : 7°CDB, 6°CWB / Equivalent piping length : 7.5m, level difference
: 0m.
Specifications
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
15
Specifications
SiE39-404
Model Name (Combination Unit)
RXYQ30MY1B
RXYQ32MY1B
Model Name (Independent Unit)
RXYQ14MY1B+RXYQ16MY1B
RXYQ16MY1B+RXYQ16MY1B
H1 Cooling Capacity (19.5°CWB)
kcal / h
75,500
80,000
Btu / h
298,000
314,000
kW
87.2
91.9
kW
84.5
89.0
kcal / h
81,700
86,000
Btu / h
325,000
342,000
kW
95.0
100
Ivory White (5Y7.5/1)
Ivory White (5Y7.5/1)
(1600×1240×765)+(1600×1240×765)
(1600×1240×765)+(1600×1240×765)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing Color
Dimensions: (H×W×D)
mm
Heat Exchanger
Type
Comp.
(13.72+10.47+10.47)×2
(6480, 2900×2)×2
(6480, 2900×2)×2
Motor Output×Number
of Units
kW
(2.0+4.5+4.5)+(3.0+4.5+4.5)
(3.0+4.5+4.5)+(3.0+4.5+4.5)
Soft start
Soft start
Propeller Fan
Propeller Fan
0.75×2
Motor Output
kW
0.75×2
Air Flow Rate
m³/min
210×2
210×2
Direct Drive
Direct Drive
Liquid Pipe
mm
φ19.1 (Brazing Connection)
φ19.1 (Brazing Connection)
Gas Pipe
mm
φ34.9 (Brazing Connection)
φ34.9 (Brazing Connection)
Oil Equalizing Pipe
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
kg
323+325
325+325
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector,
Fusible Plugs
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector,
Fusible Plugs
Deicer
Deicer
Machine Weight (Mass)
Safety Devices
Defrost Method
Capacity Control
%
Refrigerant Name
Charge
kg
Control
Refrigerator
Oil
(13.72+10.47+10.47)×2
m³/h
r.p.m
Drive
Refrigerant
Hermetically Sealed Scroll Type
Number of Revolutions
Type
Connecting
Pipes
Cross Fin Coil
Hermetically Sealed Scroll Type
Piston Displacement
Starting Method
Fan
Cross Fin Coil
Charge Volume
L
5~100
5~100
R410A
R410A
12.9+14.4
14.4+14.4
Electronic Expansion Valve
Electronic Expansion Valve
Synthetic (ether) oil
Synthetic (ether) oil
(1.9+1.6+1.6)+(1.9+1.6+1.6)
(1.9+1.6+1.6)+(1.9+1.6+1.6)
Installation Manual, Operation Manual, Connection Pipes,
Clamps
Standard Accessories
Drawing No.
4D038968C, 4D038969C
Installation Manual, Operation Manual, Connection Pipes,
Clamps
4D038969C
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
H3 Indoor temp. : 20°CDB / outdoor temp. : 7°CDB, 6°CWB / Equivalent piping length : 7.5m, level difference
: 0m.
16
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications
SiE39-404
Specifications
Model Name (Combination Unit)
RXYQ34MY1B
RXYQ36MY1B
Model Name (Independent Unit)
RXYQ10MY1B+RXYQ10MY1B+RXYQ14MY1B
RXYQ10MY1B+RXYQ10MY1B+RXYQ16MY1B
H1 Cooling Capacity (19.5°CWB)
kcal / h
85,500
90,000
Btu / h
338,000
354,000
kW
99.1
104
kW
96.0
101
kcal / h
92,700
97,000
Btu / h
370,000
387,000
kW
108
113
Ivory White (5Y7.5/1)
Ivory White (5Y7.5/1)
(1600×930×765)+(1600×930×765)+(1600×1240×765)
(1600×930×765)+(1600×930×765)+(1600×1240×765)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing Color
Dimensions: (H×W×D)
mm
Heat Exchanger
Type
Comp.
(13.72+10.47)×2+(13.72+10.47+10.47)
(6480, 2900)×2+(6480, 2900×2)
(6480, 2900)×2+(6480, 2900×2)
Motor Output×Number
of Units
kW
(2.7+4.5)+(2.7+4.5)+(2.0+4.5+4.5)
(2.7+4.5)+(2.7+4.5)+(3.0+4.5+4.5)
Soft start
Soft start
Propeller Fan
Propeller Fan
Motor Output
kW
0.75×3
0.75×3
Air Flow Rate
m³/min
180+180+210
180+180+210
Direct Drive
Direct Drive
Liquid Pipe
mm
φ19.1 (Brazing Connection)
φ19.1 (Brazing Connection)
Gas Pipe
mm
φ34.9 (Brazing Connection)
φ41.3 (Brazing Connection)
Oil Equalizing Pipe
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
kg
230+230+323
230+230+325
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector,
Fusible Plugs
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector,
Fusible Plugs
Deicer
Deicer
Machine Weight (Mass)
Safety Devices
Defrost Method
Capacity Control
%
Refrigerant Name
Charge
kg
Control
Refrigerator
Oil
(13.72+10.47)×2+(13.72+10.47+10.47)
m³/h
r.p.m
Drive
Refrigerant
Hermetically Sealed Scroll Type
Number of Revolutions
Type
Connecting
Pipes
Cross Fin Coil
Hermetically Sealed Scroll Type
Piston Displacement
Starting Method
Fan
Cross Fin Coil
Charge Volume
L
4~100
4~100
R410A
R410A
9.6+9.6+12.9
9.6+9.6+14.4
Electronic Expansion Valve
Electronic Expansion Valve
Synthetic (ether) oil
Synthetic (ether) oil
(1.9+1.6)+(1.9+1.6)+(1.9+1.6+1.6)
(1.9+1.6)+(1.9+1.6)+(1.9+1.6+1.6)
Installation Manual, Operation Manual, Connection Pipes,
Clamps
Standard Accessories
Drawing No.
4D038966B, 4D038968C
Installation Manual, Operation Manual, Connection Pipes,
Clamps
4D038966B, 4D038969C
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
H3 Indoor temp. : 20°CDB / outdoor temp. : 7°CDB, 6°CWB / Equivalent piping length : 7.5m, level difference
: 0m.
Specifications
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
17
Specifications
SiE39-404
Model Name (Combination Unit)
RXYQ38MY1B
RXYQ40MY1B
Model Name (Independent Unit)
RXYQ10MY1B+RXYQ12MY1B+RXYQ16MY1B
RXYQ10MY1B+RXYQ14MY1B+RXYQ16MY1B
kcal / h
95,000
101,000
Btu / h
374,000
397,000
kW
109
117
kW
106
113
kcal / h
102,000
109,000
Btu / h
407,000
433,000
kW
119
127
Ivory White (5Y7.5/1)
Ivory White (5Y7.5/1)
(1600×930×765)+(1600×1240×765)+(1600×1240×765)
(1600×930×765)+(1600×1240×765)+(1600×1240×765)
H1 Cooling Capacity (19.5°CWB)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing Color
Dimensions: (H×W×D)
mm
Heat Exchanger
Type
Comp.
(13.72+10.47)×2+(13.72+10.47+10.47)
(6480, 2900)×2+(6480, 2900×2)
(6480, 2900), (6480, 2900×2)×2
Motor Output×Number
of Units
kW
(2.7+4.5)+(4.2+4.5)+(3.0+4.5+4.5)
(2.7+4.5)+(2.0+4.5+4.5)+(3.0+4.5+4.5)
Soft start
Soft start
Propeller Fan
Propeller Fan
Motor Output
kW
0.75×3
0.75×3
Air Flow Rate
m³/min
180+210+210
180+210+210
Direct Drive
Direct Drive
Liquid Pipe
mm
φ19.1 (Brazing Connection)
φ19.1 (Brazing Connection)
Gas Pipe
mm
φ41.3 (Brazing Connection)
φ41.3 (Brazing Connection)
Oil Equalizing Pipe
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
kg
230+281+325
230+323+325
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector,
Fusible Plugs
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector,
Fusible Plugs
Deicer
Deicer
Machine Weight (Mass)
Safety Devices
Defrost Method
Capacity Control
%
Refrigerant Name
Charge
kg
Control
Refrigerator
Oil
(13.72+10.47)+(13.72+10.47+10.47)×2
m³/h
r.p.m
Drive
Refrigerant
Hermetically Sealed Scroll Type
Number of Revolutions
Type
Connecting
Pipes
Cross Fin Coil
Hermetically Sealed Scroll Type
Piston Displacement
Starting Method
Fan
Cross Fin Coil
Charge Volume
L
4~100
4~100
R410A
R410A
9.6+11.4+14.4
9.6+12.9+14.4
Electronic Expansion Valve
Electronic Expansion Valve
Synthetic (ether) oil
Synthetic (ether) oil
(1.9+1.6)+(1.9+1.6)+(1.9+1.6+1.6)
(1.9+1.6)+(1.9+1.6+1.6)+(1.9+1.6+1.6)
Installation Manual, Operation Manual, Connection Pipes,
Clamps
Standard Accessories
Drawing No.
4D038966B, 4D038967C, 4D038969C
Installation Manual, Operation Manual, Connection Pipes,
Clamps
4D038966B, 4D038968C, 4D038969C
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
H3 Indoor temp. : 20°CDB / outdoor temp. : 7°CDB, 6°CWB / Equivalent piping length : 7.5m, level difference
: 0m.
18
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications
SiE39-404
Specifications
Model Name (Combination Unit)
RXYQ42MY1B
RXYQ44MY1B
Model Name (Independent Unit)
RXYQ10MY1B+RXYQ16MY1B+RXYQ16MY1B
RXYQ12MY1B+RXYQ16MY1B+RXYQ16MY1B
kcal / h
105,000
110,000
Btu / h
413,000
432,000
kW
121
127
kW
117
123
kcal / h
113,000
118,000
Btu / h
450,000
470,000
kW
132
138
Ivory White (5Y7.5/1)
Ivory White (5Y7.5/1)
(1600×930×765)+(1600×1240×765)+(1600×1240×765)
(1600×1240×765)+(1600×1240×765)+(1600×1240×765)
H1 Cooling Capacity (19.5°CWB)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing Color
Dimensions: (H×W×D)
mm
Heat Exchanger
Type
Comp.
m³/h
(13.72+10.47)+(13.72+10.47+10.47)×2
(13.72+10.47)+(13.72+10.47+10.47)×2
r.p.m
(6480, 2900), (6480, 2900×2)×2
(6480, 2900), (6480, 2900×2)×2
Motor Output×Number
of Units
kW
(2.7+4.5)+(3.0+4.5+4.5)×2
(4.2+4.5)+(3.0+4.5+4.5)×2
Soft start
Propeller Fan
kW
0.75×3
0.75×3
Air Flow Rate
m³/min
180+210+210
210+210+210
Direct Drive
Direct Drive
Liquid Pipe
mm
φ19.1 (Brazing Connection)
φ19.1 (Brazing Connection)
Gas Pipe
mm
φ41.3 (Brazing Connection)
φ41.3 (Brazing Connection)
Oil Equalizing Pipe
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
kg
230+325+325
281+325+325
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector,
Fusible Plugs
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector,
Fusible Plugs
Deicer
Deicer
Machine Weight (Mass)
Safety Devices
Defrost Method
Capacity Control
%
Refrigerant Name
Charge
kg
Control
Refrigerator
Oil
Soft start
Propeller Fan
Motor Output
Drive
Refrigerant
Hermetically Sealed Scroll Type
Number of Revolutions
Type
Connecting
Pipes
Cross Fin Coil
Hermetically Sealed Scroll Type
Piston Displacement
Starting Method
Fan
Cross Fin Coil
Charge Volume
L
4~100
4~100
R410A
R410A
9.6+14.4+14.4
11.4+14.4+14.4
Electronic Expansion Valve
Electronic Expansion Valve
Synthetic (ether) oil
Synthetic (ether) oil
(1.9+1.6)+(1.9+1.6+1.6)+(1.9+1.6+1.6)
(1.9+1.6)+(1.9+1.6+1.6)+(1.9+1.6+1.6)
Installation Manual, Operation Manual, Connection Pipes,
Clamps
Standard Accessories
Drawing No.
4D038966B, 4D038969C
Installation Manual, Operation Manual, Connection Pipes,
Clamps
4D038967C, 4D038969C
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
H3 Indoor temp. : 20°CDB / outdoor temp. : 7°CDB, 6°CWB / Equivalent piping length : 7.5m, level difference
: 0m.
Specifications
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
19
Specifications
SiE39-404
Model Name (Combination Unit)
RXYQ46MY1B
RXYQ48MY1B
Model Name (Independent Unit)
RXYQ14MY1B+RXYQ16MY1B+RXYQ16MY1B
RXYQ16MY1B+RXYQ16MY1B+RXYQ16MY1B
kcal / h
116,000
120,000
Btu / h
455,000
471,000
kW
133
138
kW
129
134
kcal / h
125,000
129,000
Btu / h
496,000
513,000
kW
145
150
Ivory White (5Y7.5/1)
Ivory White (5Y7.5/1)
(1600×1240×765)+(1600×1240×765)+(1600×1240×765)
(1600×1240×765)+(1600×1240×765)+(1600×1240×765)
H1 Cooling Capacity (19.5°CWB)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing Color
Dimensions: (H×W×D)
mm
Heat Exchanger
Type
Comp.
m³/h
(13.72+10.47+10.47)×3
(13.72+10.47+10.47)×3
r.p.m
(6480, 2900×2)×3
(6480, 2900×2)×3
Motor Output×Number
of Units
kW
(2.0+4.5+4.5)+(3.0+4.5+4.5)×2
(3.0+4.5+4.5)×3
Soft start
Propeller Fan
kW
0.75×3
0.75×3
Air Flow Rate
m³/min
210+210+210
210+210+210
Direct Drive
Direct Drive
Liquid Pipe
mm
φ19.1 (Brazing Connection)
φ19.1 (Brazing Connection)
Gas Pipe
mm
φ41.3 (Brazing Connection)
φ41.3 (Brazing Connection)
Oil Equalizing Pipe
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
kg
323+325+325
325+325+325
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector,
Fusible Plugs
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector,
Fusible Plugs
Deicer
Deicer
Machine Weight (Mass)
Safety Devices
Defrost Method
Capacity Control
%
Refrigerant Name
Charge
kg
Control
Refrigerator
Oil
Soft start
Propeller Fan
Motor Output
Drive
Refrigerant
Hermetically Sealed Scroll Type
Number of Revolutions
Type
Connecting
Pipes
Cross Fin Coil
Hermetically Sealed Scroll Type
Piston Displacement
Starting Method
Fan
Cross Fin Coil
Charge Volume
L
3~100
3~100
R410A
R410A
12.9+14.4+14.4
14.4+14.4+14.4
Electronic Expansion Valve
Electronic Expansion Valve
Synthetic (ether) oil
Synthetic (ether) oil
(1.9+1.6+1.6)+(1.9+1.6+1.6)+(1.9+1.6+1.6)
(1.9+1.6+1.6)+(1.9+1.6+1.6)+(1.9+1.6+1.6)
Installation Manual, Operation Manual, Connection Pipes,
Clamps
Standard Accessories
Drawing No.
4D038968C, 4D038969C
Installation Manual, Operation Manual, Connection Pipes,
Clamps
4D038969C
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
H3 Indoor temp. : 20°CDB / outdoor temp. : 7°CDB, 6°CWB / Equivalent piping length : 7.5m, level difference
: 0m.
20
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications
SiE39-404
1.2
Specifications
Indoor Units
Ceiling Mounted Cassette Type (Double Flow)
Model
H1 Cooling Capacity (19.5°CWB)
FXCQ20MVE
FXCQ25MVE
FXCQ32MVE
kcal/h
2,000
2,500
3,150
4,000
Btu/h
7,900
9,900
12,500
15,900
kW
2.3
2.9
3.7
4.7
kW
2.2
2.8
3.6
4.5
kcal/h
2,200
2,800
3,400
4,300
Btu/h
8,500
10,900
13,600
17,000
kW
2.5
3.2
4.0
5.0
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
mm
305×775×600
305×775×600
305×775×600
305×990×600
Rows×Stages×Fin Pitch
mm
2×10×1.5
2×10×1.5
2×10×1.5
2×10×1.5
Face Area
m²
2×0.100
2×0.100
2×0.100
2×0.145
D17K2AA1
D17K2AB1
D17K2AB1
2D17K1AA1
Model
Type
Fan
Sirocco Fan
Sirocco Fan
Sirocco Fan
Sirocco Fan
W
10×1
15×1
15×1
20×1
m³/min
7/5
9/6.5
9/6.5
12/9
cfm
247/177
318/230
318/230
424/318
Motor Output × Number
of Units
Air Flow Rate (H/L)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Piping
Connections
FXCQ40MVE
Direct Drive
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Glass Wool/Urethane Foam
Glass Wool/Urethane Foam
Glass Wool/Urethane Foam
Glass Wool/Urethane Foam
Liquid Pipes
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
Gas Pipes
mm
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
VP25
VP25
VP25
VP25
Drain Pipe
mm
Dia. 32
( External
Internal Dia. 25 )
Dia. 32
( External
Internal Dia. 25 )
Dia. 32
( External
Internal Dia. 25 )
Dia. 32
( External
Internal Dia. 25 )
Machine Weight (Mass)
kg
26
26
26
31
dBA
32/27
34/28
34/28
34/29
Safety Devices
Fuse, Thermal Protector for
Fan Motor
Fuse, Thermal Protector for
Fan Motor
Fuse, Thermal Protector for
Fan Motor
Fuse, Thermal Protector for
Fan Motor
Refrigerant Control
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
R410A M Series
R410A M Series
R410A M Series
R410A M Series
Model
BYBC32G-W1
BYBC32G-W1
BYBC32G-W1
BYBC50G-W1
Panel Color
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
53×1,030×680
53×1,030×680
53×1,030×680
53×1,245×680
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
H5 Sound Level (H/L) (220V)
Connectable outdoor unit
Decoration
Panels
(Option)
Dimensions: (H×W×D)
mm
Air Filter
Weight
kg
8
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Washer for Hanging
Brackets, Clamp Metal,
Drain Hose, Insulation for
Fitting, Washer Fixing
Plates, Sealing Pads,
Clamps, Screws, Washers.
Standard Accessories
Drawing No.
8
8
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Washer for Hanging
Brackets, Clamp Metal,
Drain Hose, Insulation for
Fitting, Washer Fixing
Plates, Sealing Pads,
Clamps, Screws, Washers.
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Washer for Hanging
Brackets, Clamp Metal,
Drain Hose, Insulation for
Fitting, Washer Fixing
Plates, Sealing Pads,
Clamps, Screws, Washers.
3D039413
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
Specifications
8.5
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Washer for Hanging
Brackets, Clamp Metal,
Drain Hose, Insulation for
Fitting, Washer Fixing
Plates, Sealing Pads,
Clamps, Screws, Washers.
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
21
Specifications
SiE39-404
Ceiling Mounted Cassette Type (Double Flow)
Model
H1 Cooling Capacity (19.5°CWB)
FXCQ50MVE
FXCQ63MVE
FXCQ80MVE
FXCQ125MVE
kcal/h
5,000
6,300
8,000
12,500
Btu/h
19,900
25,000
31,800
49,600
kW
5.8
7.3
9.3
14.5
kW
5.6
7.1
9.0
14.0
kcal/h
5,400
6,900
8,600
13,800
Btu/h
21,500
27,300
34,100
54,600
kW
6.3
8.0
10.0
16.0
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
mm
305×990×600
305×1,175×600
305×1,665×600
305×1,665×600
Rows×Stages×Fin Pitch
mm
2×10×1.5
2×10×1.5
2×10×1.5
2×10×1.5
Face Area
m²
2×0.145
2×0.184
2×0.287
2×0.287
2D17K1AA1
2D17K2AA1VE
3D17K2AA1
3D17K2AB1
Sirocco Fan
Model
Type
Fan
Sirocco Fan
Sirocco Fan
Sirocco Fan
W
20×1
30×1
50×1
85×1
m³/min
12/9
16.5/13
26/21
33/25
Motor Output × Number
of Units
Air Flow Rate (H/L)
cfm
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Piping
Connections
424/318
582/459
918/741
1,165/883
Direct Drive
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Glass Wool/Urethane Foam
Glass Wool/Urethane Foam
Glass Wool/Urethane Foam
Glass Wool/Urethane Foam
Liquid Pipes
mm
φ6.4 (Flare Connection)
φ9.5 (Flare Connection)
φ9.5 (Flare Connection)
φ9.5 (Flare Connection)
Gas Pipes
mm
φ12.7 (Flare Connection)
φ15.9 (Flare Connection)
φ15.9 (Flare Connection)
φ15.9 (Flare Connection)
VP25
VP25
VP25
VP25
Drain Pipe
mm
Dia. 32
( External
Internal Dia. 25 )
Dia. 32
( External
Internal Dia. 25 )
Dia. 32
( External
Internal Dia. 25 )
Dia. 32
( External
Internal Dia. 25 )
Machine Weight (Mass)
kg
32
35
47
48
dBA
34/29
37/32
39/34
44/38
Safety Devices
Fuse, Thermal Protector for
Fan Motor
Fuse, Thermal Protector for
Fan Motor
Fuse, Thermal Protector for
Fan Motor
Fuse, Thermal Protector for
Fan Motor
Refrigerant Control
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
R410A M Series
R410A M Series
R410A M Series
R410A M Series
BYBC50G-W1
BYBC63G-W1
BYBC125G-W1
BYBC125G-W1
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
53×1,245×680
53×1,430×680
53×1,920×680
53×1,920×680
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
H5 Sound Level (H/L)
Connectable outdoor unit
Model
Panel Color
Decoration
Panels
(Option)
Dimensions: (H×W×D)
mm
Air Filter
Weight
kg
8.5
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Washer for Hanging
Brackets, Clamp Metal,
Drain Hose, Insulation for
Fitting, Washer Fixing
Plates, Sealing Pads,
Clamps, Screws, Washers.
Standard Accessories
Drawing No.
9.5
12
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Washer for Hanging
Brackets, Clamp Metal,
Drain Hose, Insulation for
Fitting, Washer Fixing
Plates, Sealing Pads,
Clamps, Screws, Washers.
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Washer for Hanging
Brackets, Clamp Metal,
Drain Hose, Insulation for
Fitting, Washer Fixing
Plates, Sealing Pads,
Clamps, Screws, Washers.
3D039413
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
22
12
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Washer for Hanging
Brackets, Clamp Metal,
Drain Hose, Insulation for
Fitting, Washer Fixing
Plates, Sealing Pads,
Clamps, Screws, Washers.
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications
SiE39-404
Specifications
Ceiling Mounted Cassette Type (Multi Flow) 600×600
Model
H1 Cooling Capacity (19.5°CWB)
FXZQ20MVE
FXZQ25MVE
kcal/h
2,000
2,500
3,150
Btu/h
7,900
9,900
12,500
kW
2.3
2.9
3.7
kW
2.2
2.8
3.6
kcal/h
2,200
2,800
3,400
Btu/h
8,500
10,900
13,600
kW
2.5
3.2
4.0
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
mm
260×575×575
260×575×575
260×575×575
Rows×Stages×Fin Pitch
mm
2×10×1.5
2×10×1.5
2×10×1.5
Face Area
m²
0.269
0.269
0.269
QTS32C15M
QTS32C15M
QTS32C15M
Turbo Fan
Model
Type
Fan
Turbo Fan
Turbo Fan
W
55×1
55×1
55×1
m³/min
9/7
9/7
9.5/7.5
Motor Output × Number
of Units
Air Flow Rate (H/L)
cfm
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Piping
Connections
318/247
318/247
335/265
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene/
Foamed Polyethylene
Foamed Polystyrene/
Foamed Polyethylene
Foamed Polystyrene/
Foamed Polyethylene
Liquid Pipes
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
Gas Pipes
mm
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
VP20
VP20
VP20
Drain Pipe
mm
Dia. 26
( External
Internal Dia. 20 )
Dia. 26
( External
Internal Dia. 20 )
Dia. 26
( External
Internal Dia. 20 )
Machine Weight (Mass)
H5 Sound Level (H/L) (230V)
kg
18
18
18
dBA
30/25
30/25
32/26
Safety Devices
Refrigerant Control
Connectable outdoor unit
Model
Panel Color
Decoration
Panels
(Option)
FXZQ32MVE
Dimensions: (H×W×D)
mm
Air Filter
Weight
kg
Standard Accessories
Drawing No.
Fuse
Fuse
Fuse
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
R410A M Series
R410A M Series
R410A M Series
BYFQ60BW1
BYFQ60BW1
BYFQ60BW1
White (Ral 9010)
White (Ral 9010)
White (Ral 9010)
55×700×700
55×700×700
55×700×700
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
2.7
2.7
2.7
Operation Manual, Installation Manual,
Paper Pattern for Installation, Drain
Hose, Clamp Metal, Washer Fixing
Plate, Sealing Pads, Clamps, Screws,
Washer for Hanging Bracket,
Insulation for Fitting.
Operation Manual, Installation Manual,
Paper Pattern for Installation, Drain
Hose, Clamp Metal, Washer Fixing
Plate, Sealing Pads, Clamps, Screws,
Washer for Hanging Bracket,
Insulation for Fitting.
Operation Manual, Installation Manual,
Paper Pattern for Installation, Drain
Hose, Clamp Metal, Washer Fixing
Plate, Sealing Pads, Clamps, Screws,
Washer for Hanging Bracket,
Insulation for Fitting.
3D038929A
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
Specifications
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
23
Specifications
SiE39-404
Ceiling Mounted Cassette Type (Multi Flow) 600×600
Model
FXZQ40MVE
H1 Cooling Capacity (19.5°CWB)
4,000
5,000
Btu/h
15,900
19,900
kW
4.7
5.8
kW
4.5
5.6
kcal/h
4,300
5,400
Btu/h
17,000
21,500
kW
5.0
6.3
Galvanized Steel Plate
Galvanized Steel Plate
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
mm
260×575×575
260×575×575
Rows×Stages×Fin Pitch
mm
2×10×1.5
2×10×1.5
Face Area
m²
0.269
0.269
QTS32C15M
QTS32C15M
Turbo Fan
Turbo Fan
Model
Type
Fan
FXZQ50MVE
kcal/h
Motor Output × Number
of Units
Air Flow Rate (H/L)
W
55×1
55×1
m³/min
11/8
14/10
cfm
388/282
494/353
Direct Drive
Direct Drive
Temperature Control
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Sound Absorbing Thermal Insulation Material
Foamed Polystyrene/Foamed
Polyethylene
Foamed Polystyrene/Foamed
Polyethylene
Drive
Piping
Connections
Liquid Pipes
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
Gas Pipes
mm
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
VP20
VP20
Drain Pipe
mm
Dia. 26
( External
Internal Dia. 20 )
Dia. 26
( External
Internal Dia. 20 )
Machine Weight (Mass)
H5 Sound Level (H/L) (230V)
kg
18
18
dBA
36/28
41/33
Safety Devices
Refrigerant Control
Connectable outdoor unit
Model
Panel Color
Decoration
Panels
(Option)
Dimensions: (H×W×D)
mm
Air Filter
Weight
kg
Standard Accessories
Drawing No.
Fuse
Fuse,
Electronic Expansion Valve
Electronic Expansion Valve
R410A M Series
R410A M Series
BYFQ60BW1
BYFQ60BW1
White (Ral 9010)
White (Ral 9010)
55×700×700
55×700×700
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
2.7
2.7
Operation Manual, Installation Manual,
Paper Pattern for Installation, Drain
Hose, Clamp Metal, Washer Fixing
Plate, Sealing Pads, Clamps, Screws,
Washer for Hanging Bracket,
Insulation for Fitting.
Operation Manual, Installation Manual,
Paper Pattern for Installation, Drain
Hose, Clamp Metal, Washer Fixing
Plate, Sealing Pads, Clamps, Screws,
Washer for Hanging Bracket,
Insulation for Fitting.
3D038929A
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
24
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications
SiE39-404
Specifications
Ceiling Mounted Cassette Type (Multi-flow)
Model
H1 Cooling Capacity (19.5°CWB)
FXFQ25MVE
FXFQ32MVE
FXFQ40MVE
kcal/h
2,500
3,150
4,000
5,000
Btu/h
9,900
12,500
15,900
19,900
kW
2.9
3.7
4.7
5.8
kW
2.8
3.6
4.5
5.6
kcal/h
2,800
3,400
4,300
5,400
Btu/h
10,900
13,600
17,000
21,500
kW
3.2
4.0
5.0
6.3
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
mm
246×840×840
246×840×840
246×840×840
246×840×840
Rows×Stages×Fin Pitch
mm
2×8×1.2
2×8×1.2
2×8×1.2
2×8×1.2
Face Area
m²
0.363
0.363
0.363
0.363
QTS46D14M
QTS46D14M
QTS46D14M
QTS46D14M
Turbo Fan
Model
Type
Fan
Turbo Fan
Turbo Fan
Turbo Fan
W
30×1
30×1
30×1
30×1
m³/min
13/10
13/10
15/11
16/11
Motor Output × Number
of Units
Air Flow Rate (H/L)
cfm
459/353
459/353
530/388
565/388
Direct Drive
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Liquid Pipes
Gas Pipes
Piping
Connections
Drain Pipe
Machine Weight (Mass)
H5 Sound Level (H/L) (220V)
Polyurethane Form
Polyurethane Form
Polyurethane Form
Polyurethane Form
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
mm
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
mm
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25
Dia. 32
( External
Internal Dia. 25 )
(
)
(
)
(
VP25
)
kg
24
24
24
24
dBA
30/27
30/27
31/27
32/27
Safety Devices
Refrigerant Control
Connectable outdoor unit
Model
Panel Color
Decoration
Panels
(Option)
FXFQ50MVE
Dimensions: (H×W×D)
mm
Air Filter
Weight
kg
Standard Accessories
Drawing No.
Fuse
Fuse
Fuse
Fuse
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
R410A M Series
R410A M Series
R410A M Series
R410A M Series
BYCP125D-W1
BYCP125D-W1
BYCP125D-W1
BYCP125D-W1
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
45×950×950
45×950×950
45×950×950
45×950×950
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
5.5
5.5
5.5
5.5
Operation manual,
Installation manual, Paper
pattern for installation, Drain
hose, Clamp metal, Washer
fixing plate, Sealing pads,
Clamps, Screws, Washer for
hanging bracket, Insulation
for fitting.
Operation manual,
Installation manual, Paper
pattern for installation, Drain
hose, Clamp metal, Washer
fixing plate, Sealing pads,
Clamps, Screws, Washer for
hanging bracket, Insulation
for fitting.
Operation manual,
Installation manual, Paper
pattern for installation, Drain
hose, Clamp metal, Washer
fixing plate, Sealing pads,
Clamps, Screws, Washer for
hanging bracket, Insulation
for fitting.
Operation manual,
Installation manual, Paper
pattern for installation, Drain
hose, Clamp metal, Washer
fixing plate, Sealing pads,
Clamps, Screws, Washer for
hanging bracket, Insulation
for fitting.
3D038812
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
Specifications
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
25
Specifications
SiE39-404
Ceiling Mounted Cassette Type (Multi-flow)
Model
H1 Cooling Capacity (19.5°CWB)
FXFQ63MVE
FXFQ80MVE
FXFQ100MVE
FXFQ125MVE
kcal/h
6,300
8,000
10,000
12,500
Btu/h
25,000
31,800
39,700
49,600
kW
7.3
9.3
11.6
14.5
kW
7.1
9.0
11.2
14.0
kcal/h
6,900
8,600
10,800
13,800
Btu/h
27,300
34,100
42,700
54,600
kW
8.0
10.0
12.5
16.0
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
mm
246×840×840
246×840×840
288×840×840
288×840×840
Rows×Stages×Fin Pitch
mm
2×10×1.2
2×10×1.2
2×12×1.2
2×12×1.2
Face Area
m²
0.454
0.454
0.544
0.544
QTS46D14M
QTS46D14M
QTS46C17M
QTS46C17M
Model
Type
Fan
Turbo Fan
Turbo Fan
Turbo Fan
Turbo Fan
W
30×1
30×1
120×1
120×1
m³/min
18.5/14
20/15
26/21
30/24
cfm
653/494
706/530
918/741
1,059/847
Motor Output × Number
of Units
Air Flow Rate (H/L)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Piping
Connections
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Polyurethane Form
Polyurethane Form
Polyurethane Form
Polyurethane Form
Liquid Pipes
mm
φ9.5 (Flare Connection)
φ9.5 (Flare Connection)
φ9.5 (Flare Connection)
φ9.5 (Flare Connection)
Gas Pipes
mm
φ15.9 (Flare Connection)
φ15.9 (Flare Connection)
φ15.9 (Flare Connection)
φ15.9 (Flare Connection)
mm
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25
Dia. 32
( External
Internal Dia. 25 )
Drain Pipe
Machine Weight (Mass)
H5 Sound Level (H/L)
(
VP25
)
25
29
29
36/31
39/33
42/36
Panel Color
mm
Air Filter
kg
Drawing No.
)
25
Model
Standard Accessories
(
33/28
Connectable outdoor unit
Weight
)
kg
Refrigerant Control
Dimensions: (H×W×D)
(
dBA
Safety Devices
Decoration
Panels
(Option)
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Fuse
Fuse
Fuse
Fuse
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
R410A M Series
R410A M Series
R410A M Series
R410A M Series
BYCP125D-W1
BYCP125D-W1
BYCP125D-W1
BYCP125D-W1
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
45×950×950
45×950×950
45×950×950
45×950×950
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
5.5
5.5
5.5
5.5
Operation manual,
Installation manual, Paper
pattern for installation, Drain
hose, Clamp metal, Washer
fixing plate, Sealing pads,
Clamps, Screws, Washer for
hanging bracket, Insulation
for fitting.
Operation manual,
Installation manual, Paper
pattern for installation, Drain
hose, Clamp metal, Washer
fixing plate, Sealing pads,
Clamps, Screws, Washer for
hanging bracket, Insulation
for fitting.
Operation manual,
Installation manual, Paper
pattern for installation, Drain
hose, Clamp metal, Washer
fixing plate, Sealing pads,
Clamps, Screws, Washer for
hanging bracket, Insulation
for fitting.
Operation manual,
Installation manual, Paper
pattern for installation, Drain
hose, Clamp metal, Washer
fixing plate, Sealing pads,
Clamps, Screws, Washer for
hanging bracket, Insulation
for fitting.
3D038812
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
26
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications
SiE39-404
Specifications
Ceiling Mounted Cassette Corner Type
Model
H1 Cooling Capacity (19.5°CWB)
FXKQ25MVE
FXKQ32MVE
FXKQ40MVE
kcal/h
2,500
3,150
4,000
6,300
Btu/h
9,900
12,500
15,900
25,000
kW
2.9
3.7
4.7
7.3
kW
2.8
3.6
4.5
7.1
kcal/h
2,800
3,400
4,300
6,900
Btu/h
10,900
13,600
17,000
27,300
kW
3.2
4.0
5.0
8.0
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
mm
215×1,110×710
215×1,110×710
215×1,110×710
215×1,310×710
Rows×Stages×Fin Pitch
mm
2×11×1.75
2×11×1.75
2×11×1.75
3×11×1.75
Face Area
m²
0.180
0.180
0.180
0.226
3D12H1AN1V1
3D12H1AN1V1
3D12H1AP1V1
4D12H1AJ1V1
Sirocco Fan
Model
Type
Fan
FXKQ63MVE
Sirocco Fan
Sirocco Fan
Sirocco Fan
W
15×1
15×1
20×1
45×1
m³/min
11/9
11/9
13/10
18/15
Motor Output × Number
of Units
Air Flow Rate (H/L)
cfm
388/318
388/318
459/353
635/530
Direct Drive
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Liquid Pipes
Gas Pipes
Piping
Connections
Drain Pipe
Machine Weight (Mass)
Polyethylene Foam
Polyethylene Foam
Polyethylene Foam
Polyethylene Foam
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
φ9.5 (Flare Connection)
mm
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
φ15.9 (Flare Connection)
mm
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25
Dia. 32
( External
Internal Dia. 25 )
(
)
(
)
(
VP25
)
kg
31
31
31
34
dBA
38/33
38/33
40/34
42/37
Safety Devices
Fuse,
Thermal Fuse for Fan Motor
Fuse,
Thermal Fuse for Fan Motor
Fuse,
Thermal Fuse for Fan Motor
Fuse,
Thermal Fuse for Fan Motor
Refrigerant Control
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
R410A M Series
R410A M Series
R410A M Series
R410A M Series
BYK45FJW1
BYK45FJW1
BYK45FJW1
BYK71FJW1
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
70×1,240×800
70×1,240×800
70×1,240×800
70×1,440×800
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
H5 Sound Level (H/L) (220V)
Connectable Outdoor Units
Model
Panel Color
Decoration
Panels
(Option)
Dimensions: (H×W×D)
mm
Air Filter
Weight
kg
Standard Accessories
Drawing No.
8.5
8.5
8.5
9.5
Operation Manual,
Installation Manual, Paper
Pattern for Installation, Drain
Hose, Clamp Metal,
Insulation for Fitting, Sealing
Pads, Clamps, Screws,
Washers, Positioning Jig for
Installation, Insulation for
Hanger Bracket, Air Outlet
Blocking Pad.
Operation Manual,
Installation Manual, Paper
Pattern for Installation, Drain
Hose, Clamp Metal,
Insulation for Fitting, Sealing
Pads, Clamps, Screws,
Washers, Positioning Jig for
Installation, Insulation for
Hanger Bracket, Air Outlet
Blocking Pad.
Operation Manual,
Installation Manual, Paper
Pattern for Installation, Drain
Hose, Clamp Metal,
Insulation for Fitting, Sealing
Pads, Clamps, Screws,
Washers, Positioning Jig for
Installation, Insulation for
Hanger Bracket, Air Outlet
Blocking Pad.
Operation Manual,
Installation Manual, Paper
Pattern for Installation, Drain
Hose, Clamp Metal,
Insulation for Fitting, Sealing
Pads, Clamps, Screws,
Washers, Positioning Jig for
Installation, Insulation for
Hanger Bracket, Air Outlet
Blocking Pad.
3D038813
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured at a point 1m in front of the unit and 1m downward.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Specifications
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
27
Specifications
SiE39-404
Slim Ceiling Mounted Duct Type
Model
H1 Cooling Capacity (19.5°CWB)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
FXDQ20NVE
FXDQ25NVE
kcal/h
2,000
2,500
3,150
Btu/h
7,900
9,900
12,500
kW
2.3
2.9
3.7
kW
2.2
2.8
3.6
kcal/h
2,200
2,800
3,400
Btu/h
8,500
10,900
13,600
kW
2.5
3.2
4.0
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
Casing
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
Fan
mm
200×900×620
200×900×620
200×900×620
Rows×Stages×Fin Pitch
mm
2×12×1.5
2×12×1.5
2×12×1.5
Face Area
m²
0.176
0.176
0.176
Model
—
—
—
Type
Sirocco Fan
Sirocco Fan
Sirocco Fan
Motor Output × Number
of Units
Air Flow Rate (H/L)
W
62×1
62×1
62×1
m³/min
9.5/7.5
9.5/7.5
10.5/8.5
External Static Pressure
Pa
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections
FXDQ32NVE
44-15 H5
44-15 H5
44-15 H5
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Foamed Polyethylene
Foamed Polyethylene
Removal / Washable / Mildew Proof
Removal / Washable / Mildew Proof
Removal / Washable / Mildew Proof
Liquid Pipes
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
Gas Pipes
mm
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
Drain Pipe
mm
VP20
(External Dia. 26 Internal Dia. 20)
VP20
(External Dia. 26 Internal Dia. 20)
VP20
(External Dia. 26 Internal Dia. 20)
Machine Weight (Mass)
H6 Sound Level (H/L)
Safety Devices
kg
26
26
26
dBA
33/29
33/29
33/29
Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor
Refrigerant Control
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
Standard Accessories
Drawing No.
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
3D045744
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
H4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 External static pressure is changeable to set by the remote controller this pressure means “High static
pressure - Standard static pressure”.
H6 The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to
be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx.
5dBA.
28
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications
SiE39-404
Specifications
Slim Ceiling Mounted Duct Type
Model
H1 Cooling Capacity (19.5°CWB)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
FXDQ40NVE
FXDQ50NVE
kcal/h
4,000
5,000
6,300
Btu/h
15,900
19,900
25,000
kW
4.7
5.8
7.3
kW
4.5
5.6
7.1
kcal/h
4,300
5,400
6,900
Btu/h
17,000
21,500
27,300
kW
5.0
6.3
8.0
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
Casing Color
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
Fan
mm
200×900×620
200×900×620
200×1100×620
Rows×Stages×Fin Pitch
mm
3×12×1.5
3×12×1.5
3×12×1.5
Face Area
m²
0.176
0.176
0.227
Model
—
—
—
Type
Sirocco Fan
Sirocco Fan
Sirocco Fan
Motor Output × Number
of Units
Air Flow Rate (H/L)
W
62×1
130×1
130×1
m³/min
10.5/8.5
12.5/10.0
16.5/13.0
External Static Pressure
Pa
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections
FXDQ63NVE
44-15 H5
44-15 H5
44-15 H5
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Foamed Polyethylene
Foamed Polyethylene
Removal / Washable / Mildew Proof
Removal / Washable / Mildew Proof
Removal / Washable / Mildew Proof
Liquid Pipes
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
φ9.5 (Flare Connection)
Gas Pipes
mm
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
φ15.9 (Flare Connection)
Drain Pipe
mm
VP20
(External Dia. 26 Internal Dia. 20)
VP20
(External Dia. 26 Internal Dia. 20)
VP20
(External Dia. 26 Internal Dia. 20)
Machine Weight (Mass)
H6 Sound Level (H/L)
Safety Devices
kg
27
28
31
dBA
34/30
35/31
36/32
Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor
Refrigerant Control
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
Standard Accessories
Drawing No.
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
3D045744
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
H4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 External static pressure is changeable to set by the remote controller this pressure means “High static
pressure - Standard static pressure”.
H6 The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to
be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx.
5dBA.
Specifications
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
29
Specifications
SiE39-404
Ceiling Mounted Built-in Type
Model
H1 Cooling Capacity (19.5°CWB)
FXSQ20MVE
FXSQ25MVE
kcal/h
2,000
2,500
3,150
Btu/h
7,900
9,900
12,500
kW
2.3
2.9
3.7
kW
2.2
2.8
3.6
kcal/h
2,200
2,800
3,400
Btu/h
8,500
10,900
13,600
kW
2.5
3.2
4.0
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
mm
300×550×800
300×550×800
300×550×800
Rows×Stages×Fin Pitch
mm
3×14×1.75
3×14×1.75
3×14×1.75
Face Area
m²
0.088
0.088
0.088
D18H3A
D18H3A
D18H3A
Model
Type
Fan
Sirocco Fan
Sirocco Fan
Sirocco Fan
W
50×1
50×1
50×1
Air Flow Rate (H/L)
m³/min
9/6.5
9/6.5
9.5/7
H4 Static external
pressure
Pa
Motor Output × Number of
Units
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight (Mass)
88-39-20
88-39-20
64-39-15
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Glass Fiber
Glass Fiber
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
mm
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
mm
VP25
(External Dia. 32 Internal Dia. 25)
VP25
(External Dia. 32 Internal Dia. 25)
VP25
(External Dia. 32 Internal Dia. 25)
kg
30
30
30
dBA
37/32
37/32
38/32
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
R410A M Series
R410A M Series
R410A M Series
Model
BYBS32DJW1
BYBS32DJW1
BYBS32DJW1
Panel Color
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
mm
55×650×500
55×650×500
55×650×500
kg
3
3
3
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
H7 Sound Level (H/L) (220V)
Safety Devices
Refrigerant Control
Connectable outdoor unit
Decoration
Panel
(Option)
FXSQ32MVE
Dimensions: (H×W×D)
Weight
Standard Accessories
Drawing No.
3D039431
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
H4 Static external pressure is changeable to change over the connectors inside electrical box, this pressure
means
“High static pressure-Standard -Low static pressure”.
H5 Static external pressure is changeable to change over the connectors inside electrical box, this pressure
means
“High static pressure-Standard”.
6 Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.
H7 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
values are normally somewhat higher during actual operation as a result of ambient conditions.
30
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications
SiE39-404
Specifications
Ceiling Mounted Built-in Type
Model
H1 Cooling Capacity (19.5°CWB)
FXSQ40MVE
FXSQ50MVE
kcal/h
4,000
5,000
6,300
Btu/h
15,900
19,900
25,000
kW
4.7
5.8
7.3
kW
4.5
5.6
7.1
kcal/h
4,300
5,400
6,900
Btu/h
17,000
21,500
27,300
kW
5.0
6.3
8.0
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
mm
300×700×800
300×700×800
300×1,000×800
Rows×Stages×Fin Pitch
mm
3×14×1.75
3×14×1.75
3×14×1.75
Face Area
m²
0.132
0.132
0.221
D18H2A
D18H2A
2D18H2A
Sirocco Fan
Model
Type
Fan
Sirocco Fan
Sirocco Fan
W
65×1
85×1
125×1
Air Flow Rate (H/L)
m³/min
11.5/9
15/11
21/15.5
H4 Static external
pressure
Pa
Motor Output × Number of
Units
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight (Mass)
88-49-20
88-59-29
88-49-20
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Glass Fiber
Glass Fiber
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
φ9.5 (Flare Connection)
mm
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
φ15.9 (Flare Connection)
mm
VP25
(External Dia. 32 Internal Dia. 25)
VP25
(External Dia. 32 Internal Dia. 25)
VP25
(External Dia. 32 Internal Dia. 25)
kg
30
31
41
dBA
38/32
41/36
42/35
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
R410A M Series
R410A M Series
R410A M Series
Model
BYBS45DJW1
BYBS45DJW1
BYBS71DJW1
Panel Color
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
mm
55×800×500
55×800×500
55×1,100×500
kg
3.5
3.5
4.5
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
H7 Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable outdoor unit
Decoration
Panel
(Option)
FXSQ63MVE
Dimensions: (H×W×D)
Weight
Standard Accessories
Drawing No.
3D039431
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
H4 Static external pressure is changeable to change over the connectors inside electrical box, this pressure
means
“High static pressure-Standard -Low static pressure”.
H5 Static external pressure is changeable to change over the connectors inside electrical box, this pressure
means
“High static pressure-Standard”.
6 Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.
H7 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
values are normally somewhat higher during actual operation as a result of ambient conditions.
Specifications
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
31
Specifications
SiE39-404
Ceiling Mounted Built-in Type
Model
H1 Cooling Capacity (19.5°CWB)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
FXSQ80MVE
FXSQ100MVE
FXSQ125MVE
kcal/h
8,000
10,000
12,500
Btu/h
31,800
39,700
49,600
kW
9.3
11.6
14.5
kW
9.0
11.2
14.0
kcal/h
8,600
10,800
13,800
Btu/h
34,100
42,700
54,600
kW
10.0
12.5
16.0
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
Casing
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
mm
300×1,400×800
300×1,400×800
300×1,400×800
Rows×Stages×Fin Pitch
mm
3×14×1.75
3×14×1.75
3×14×1.75
Face Area
m²
0.338
0.338
0.338
3D18H2A
3D18H2A
3D18H2A
Model
Type
Fan
Sirocco Fan
Sirocco Fan
Sirocco Fan
W
225×1
225×1
225×1
Air Flow Rate (H/L)
m³/min
27/21.5
28/22
38/28
H5 Static external
pressure
Pa
Motor Output × Number of
Units
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight (Mass)
H7 Sound Level (H/L)
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Glass Fiber
Glass Fiber
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
φ9.5 (Flare Connection)
φ9.5 (Flare Connection)
φ15.9 (Flare Connection)
φ15.9 (Flare Connection)
mm
VP25
(External Dia. 32 Internal Dia. 25)
VP25
(External Dia. 32 Internal Dia. 25)
VP25
(External Dia. 32 Internal Dia. 25)
kg
51
51
52
dBA
43/37
43/37
46/41
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
R410A M Series
R410A M Series
R410A M Series
BYBS125DJW1
BYBS125DJW1
BYBS125DJW1
Panel Color
Drawing No.
Microprocessor Thermostat for
Cooling and Heating
φ9.5 (Flare Connection)
Model
Standard Accessories
Microprocessor Thermostat for
Cooling and Heating
φ15.9 (Flare Connection)
Connectable outdoor unit
Weight
78-39
Direct Drive
mm
Refrigerant Control
Dimensions: (H×W×D)
107-75
Direct Drive
mm
Safety Devices
Decoration
Panel
(Option)
113-82
Direct Drive
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
mm
55×1,500×500
55×1,500×500
55×1,500×500
kg
6.5
6.5
6.5
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
3D039431
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
H4 Static external pressure is changeable to change over the connectors inside electrical box, this pressure
means
“High static pressure-Standard -Low static pressure”.
H5 Static external pressure is changeable to change over the connectors inside electrical box, this pressure
means
“High static pressure-Standard”.
6 Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.
H7 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
values are normally somewhat higher during actual operation as a result of ambient conditions.
32
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications
SiE39-404
Specifications
Ceiling Mounted Duct Type
Model
H1 Cooling Capacity (19.5°CWB)
FXMQ40MVE
FXMQ50MVE
FXMQ63MVE
kcal/h
4,000
5,000
6,300
8,000
Btu/h
15,900
19,900
25,000
31,800
kW
4.7
5.8
7.3
9.3
kW
4.5
5.6
7.1
9.0
kcal/h
4,300
5,400
6,900
8,600
Btu/h
17,000
21,500
27,300
34,100
kW
5.0
6.3
8.0
10.0
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
mm
390×720×690
390×720×690
390×720×690
390×720×690
Rows×Stages×Fin Pitch
mm
3×16×2.0
3×16×2.0
3×16×2.0
3×16×2.0
Face Area
m²
0.181
0.181
0.181
0.181
D11/2D3AB1VE
D11/2D3AB1VE
D11/2D3AB1VE
D11/2D3AA1VE
Sirocco Fan
Model
Type
Sirocco Fan
Sirocco Fan
Sirocco Fan
W
100×1
100×1
100×1
160×1
m³/min
14/11.5
14/11.5
14/11.5
19.5/16
cfm
494/406
494/406
494/406
688/565
Pa
157/157-118/108 H4
157/157-118/108 H4
157/157-118/108 H4
157/160-108/98 H4
Direct Drive
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Glass Fiber
Glass Fiber
Glass Fiber
Glass Fiber
H5
H5
H5
H5
Motor Output × Number
of Units
Fan
Air Flow Rate (H/L)
External Static
Pressure 50 / 60Hz
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections
FXMQ80MVE
Liquid Pipes
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
φ9.5 (Flare Connection)
φ9.5 (Flare Connection)
Gas Pipes
mm
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
φ15.9 (Flare Connection)
φ15.9 (Flare Connection)
mm
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25
Dia. 32
( External
Internal Dia. 25 )
Drain Pipe
Machine Weight (Mass)
H7 Sound Level (H/L)
(
)
(
)
(
VP25
)
kg
44
44
44
45
dBA
39/35
39/35
39/35
42/38
Fuse,
Thermal Fuse for Fan Motor
Fuse,
Thermal Fuse for Fan Motor
Fuse,
Thermal Fuse for Fan Motor
Fuse,
Thermal Fuse for Fan Motor
Safety Devices
Refrigerant Control
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Connectable outdoor unit
R410A M Series
R410A M Series
R410A M Series
R410A M Series
Standard Accessories
Operation Manual,
Installation Manual, Drain
Hose, Clamp Metal,
Insulation for Fitting, Sealing
Pads, Clamps, Screws.
Operation Manual,
Installation Manual, Drain
Hose, Clamp Metal,
Insulation for Fitting, Sealing
Pads, Clamps, Screws.
Operation Manual,
Installation Manual, Drain
Hose, Clamp Metal,
Insulation for Fitting, Sealing
Pads, Clamps, Screws.
Operation Manual,
Installation Manual, Drain
Hose, Clamp Metal,
Insulation for Fitting, Sealing
Pads, Clamps, Screws.
Drawing No.
3D038814
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
H4 Static external pressure is changeable to change over the connectors inside electrical box, this pressure
means
"High static pressure-Standard".
H5 Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its
colorimetric method (gravity method) 50% or more.
6 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H7 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
values are normally somewhat higher during actual operation as a result of ambient conditions.
Specifications
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
33
Specifications
SiE39-404
Ceiling Mounted Duct Type
Model
H1 Cooling Capacity (19.5°CWB)
FXMQ100MVE
FXMQ125MVE
FXMQ200MVE
FXMQ250MVE
kcal/h
10,000
12,500
20,000
25,000
Btu/h
39,700
49,600
79,000
99,000
kW
11.6
14.5
23.0
28.8
kW
11.2
14.0
22.4
28.0
kcal/h
10,800
13,800
21,500
27,000
Btu/h
42,700
54,600
85,300
107,500
kW
12.5
16.0
25.0
31.5
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
mm
390×1,110×690
390×1,110×690
470×1,380×1,100
470×1,380×1,100
Rows×Stages×Fin Pitch
mm
3×16×2.0
3×16×2.0
3×26×2.0
3×26×2.0
Face Area
m²
0.319
0.319
0.68
0.68
2D11/2D3AG1VE
2D11/2D3AF1VE
D13/4G2DA1×2
D13/4G2DA1×2
Model
Type
Sirocco Fan
Sirocco Fan
Sirocco Fan
Sirocco Fan
W
270×1
430×1
380×2
380×2
m³/min
29/23
36/29
58/50
72/62
cfm
1,024/812
1,271/1,024
2,047/1,765
2,542/2,189
Pa
157/172-98/98 H4
191/245-152/172 H4
221/270-132 H4
270/191-147 H4
Direct Drive
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Glass Fiber
Glass Fiber
Glass Fiber
Glass Fiber
H5
H5
H5
H5
Motor Output × Number
of Units
Fan
Air Flow Rate (H/L)
External Static
Pressure 50 / 60Hz
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections
Liquid Pipes
mm
φ9.5 (Flare Connection)
φ9.5 (Flare Connection)
φ9.5 (Flare Connection)
φ9.5 (Flare Connection)
Gas Pipes
mm
φ15.9 (Flare Connection)
φ15.9 (Flare Connection)
φ19.1(Brazing Connection)
φ22.2 (Brazing Connection)
mm
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25
PS1B
PS1B
Drain Pipe
Machine Weight (Mass)
H7 Sound Level (H/L)
(
)
(
)
kg
63
65
137
137
dBA
43/39
45/42
48/45
48/45
Fuse,
Thermal Fuse for Fan Motor
Fuse,
Thermal Fuse for Fan Motor
Fuse,
Thermal Protector for Fan
Motor
Fuse,
Thermal Protector for Fan
Motor
Safety Devices
Refrigerant Control
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Connectable outdoor unit
R410A M Series
R410A M Series
R410A M Series
R410A M Series
Standard Accessories
Operation Manual,
Installation Manual, Drain
Hose, Clamp Metal,
Insulation for Fitting, Sealing
Pads, Clamps, Screws.
Operation Manual,
Installation Manual, Drain
Hose, Clamp Metal,
Insulation for Fitting, Sealing
Pads, Clamps, Screws.
Operation Manual,
Installation Manual, Sealing
Pads, Connection Pipes,
Screws, Clamps.
Operation Manual,
Installation Manual, Sealing
Pads, Connection Pipes,
Screws, Clamps.
Drawing No.
3D038814
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
H4 Static external pressure is changeable to change over the connectors inside electrical box, this pressure
means
"High static pressure-Standard".
H5 Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its
colorimetric method (gravity method) 50% or more.
6 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H7 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
values are normally somewhat higher during actual operation as a result of ambient conditions.
34
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications
SiE39-404
Specifications
Ceiling Suspended Type
Model
H1 Cooling Capacity (19.5°CWB)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
FXHQ32MVE
FXHQ63MVE
FXHQ100MVE
kcal/h
3,150
6,300
10,000
Btu/h
12,500
25,000
39,700
kW
3.7
7.3
11.6
kW
3.6
7.1
11.2
kcal/h
3,400
6,900
10,800
Btu/h
13,600
27,300
42,700
kW
4.0
8.0
12.5
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
Casing Color
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
mm
195×960×680
195×1,160×680
195×1,400×680
Rows×Stages×Fin Pitch
mm
2×12×1.75
3×12×1.75
3×12×1.75
Face Area
m²
0.182
0.233
0.293
3D12K1AA1
4D12K1AA1
3D12K2AA1
Sirocco Fan
Model
Type
Fan
Sirocco Fan
Sirocco Fan
W
62×1
62×1
130×1
m³/min
12/10
17.5/14
25/19.5
Motor Output × Number
of Units
Air Flow Rate (H/L)
cfm
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections
424/353
618/494
883/688
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Glass Wool
Glass Wool
Glass Wool
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
Liquid Pipes
mm
φ6.4 (Flare Connection)
φ9.5 (Flare Connection)
φ9.5 (Flare Connection)
Gas Pipes
mm
φ12.7 (Flare Connection)
φ15.9 (Flare Connection)
φ15.9 (Flare Connection)
Drain Pipe
mm
VP20
(External Dia. 26 Internal Dia. 20)
VP20
(External Dia. 26 Internal Dia. 20)
VP20
(External Dia. 26 Internal Dia. 20)
Machine Weight (Mass)
H5 Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable outdoor unit
Standard Accessories
Drawing No.
kg
24
28
33
dBA
36/31
39/34
45/37
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
R410A M Series
R410A M Series
R410A M Series
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Clamps, Washers.
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Clamps, Washers.
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Clamps, Washers.
3D038815
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
Specifications
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
35
Specifications
SiE39-404
Wall Mounted Type
Model
H1 Cooling Capacity (19.5°CWB)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
FXAQ20MVE
FXAQ25MVE
kcal/h
2,000
2,500
3,150
Btu/h
7,900
9,900
12,500
kW
2.3
2.9
3.7
kW
2.2
2.8
3.6
kcal/h
2,200
2,800
3,400
Btu/h
8,500
10,900
13,600
kW
2.5
3.2
4.0
White (3.0Y8.5/10.5)
White (3.0Y8.5/10.5)
White (3.0Y8.5/10.5)
Casing Color
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
mm
290×795×230
290×795×230
290×795×230
Rows×Stages×Fin Pitch
mm
2×14×1.4
2×14×1.4
2×14×1.4
Face Area
m²
0.161
0.161
0.161
QCL9661M
QCL9661M
QCL9661M
Model
Type
Fan
Cross Flow Fan
Cross Flow Fan
Cross Flow Fan
W
40×1
40×1
40×1
m³/min
7.5/4.5
8/5
9/5.5
cfm
265/159
282/177
318/194
Motor Output × Number
of Units
Air Flow Rate (H/L)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections
FXAQ32MVE
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
Foamed Polystyrene /
Foamed Polyethylene
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
Resin Net (Washable)
Resin Net (Washable)
Liquid Pipes
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
Gas Pipes
mm
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
mm
VP13
(External Dia. 18 Internal Dia. 13)
VP13
(External Dia. 18 Internal Dia. 13)
VP13
(External Dia. 18 Internal Dia. 13)
Drain Pipe
Machine Weight (Mass)
H5 Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable outdoor unit
kg
11
11
11
dBA
35/29
36/29
37/29
Fuse
Fuse
Fuse
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
R410A M Series
Operation Manual, Installation
Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.
Standard Accessories
Drawing No.
R410A M Series
Operation Manual, Installation
Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.
R410A M Series
Operation Manual, Installation
Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.
3D039370A
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length:7.5m, level
difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
36
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications
SiE39-404
Specifications
Wall Mounted Type
Model
H1 Cooling Capacity (19.5°CWB)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
FXAQ40MVE
FXAQ50MVE
kcal/h
4,000
5,000
6,300
Btu/h
15,900
19,900
25,000
kW
4.7
5.8
7.3
kW
4.5
5.6
7.1
kcal/h
4,300
5,400
6,900
Btu/h
17,000
21,500
27,300
kW
5.0
6.3
8.0
White (3.0Y8.5/10.5)
White (3.0Y8.5/10.5)
White (3.0Y8.5/10.5)
Casing Color
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
mm
290×1,050×230
290×1,050×230
290×1,050×230
Rows×Stages×Fin Pitch
mm
2×14×1.4
2×14×1.4
2×14×1.4
Face Area
m²
0.213
0.213
0.213
QCL9686M
QCL9686M
QCL9686M
Cross Flow Fan
Model
Type
Fan
Cross Flow Fan
Cross Flow Fan
W
43×1
43×1
43×1
m³/min
12/9
15/12
19/14
Motor Output × Number
of Units
Air Flow Rate (H/L)
cfm
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections
FXAQ63MVE
424/318
530/424
671/494
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
Foamed Polystyrene /
Foamed Polyethylene
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
Resin Net (Washable)
Resin Net (Washable)
Liquid Pipes
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
φ9.5 (Flare Connection)
Gas Pipes
mm
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
φ15.9 (Flare Connection)
mm
VP13
(External Dia. 18 Internal Dia. 13)
VP13
(External Dia. 18 Internal Dia. 13)
VP13
(External Dia. 18 Internal Dia. 13)
Drain Pipe
Machine Weight (Mass)
H5 Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable outdoor unit
kg
14
14
14
dBA
39/34
42/36
46/39
Fuse
Fuse
Fuse
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
R410A M Series
Operation Manual, Installation
Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.
Standard Accessories
Drawing No.
R410A M Series
Operation Manual, Installation
Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.
R410A M Series
Operation Manual, Installation
Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.
3D039370A
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
Specifications
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
37
Specifications
SiE39-404
Floor Standing Type
Model
H1 Cooling Capacity (19.5°CWB)
FXLQ20MVE
FXLQ25MVE
kcal/h
2,000
2,500
3,150
Btu/h
7,900
9,900
12,500
kW
2.3
2.9
3.7
kW
2.2
2.8
3.6
kcal/h
2,200
2,800
3,400
Btu/h
8,500
10,900
13,600
kW
2.5
3.2
4.0
Ivory White (5Y7.5/1)
Ivory White (5Y7.5/1)
Ivory White (5Y7.5/1)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing Color
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
mm
600×1,000×222
600×1,000×222
600×1,140×222
Rows×Stages×Fin Pitch
mm
3×14×1.5
3×14×1.5
3×14×1.5
Face Area
m²
0.159
0.159
0.200
D14B20
D14B20
2D14B13
Model
Type
Fan
FXLQ32MVE
Sirocco Fan
Sirocco Fan
Sirocco Fan
W
15×1
15×1
25×1
m³/min
7/6
7/6
8/6
cfm
247/212
247/212
282/212
Motor Output × Number
of Units
Air Flow Rate (H/L)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Direct Drive
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber/ Urethane Foam
Glass Fiber/ Urethane Foam
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
mm
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
mm
φ21 O.D (Vinyl Chloride)
φ21 O.D (Vinyl Chloride)
φ21 O.D (Vinyl Chloride)
kg
25
25
30
dBA
35/32
35/32
35/32
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
R410A M Series
R410A M Series
Liquid Pipes
Piping
Connections Gas Pipes
Drain Pipe
Machine Weight (Mass)
H5 Sound Level (H/L)
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Safety Devices
Refrigerant Control
Connectable Outdoor Unit
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
Standard Accessories
Drawing No.
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
R410A M Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
3D038816
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
38
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications
SiE39-404
Specifications
Floor Standing Type
Model
H1 Cooling Capacity (19.5°CWB)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
FXLQ40MVE
FXLQ50MVE
kcal/h
4,000
5,000
6,300
Btu/h
15,900
19,900
25,000
kW
4.7
5.8
7.3
kW
4.5
5.6
7.1
kcal/h
4,300
5,400
6,900
Btu/h
17,000
21,500
27,300
kW
5.0
6.3
8.0
Ivory White (5Y7.5/1)
Ivory White (5Y7.5/1)
Ivory White (5Y7.5/1)
Casing Color
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
mm
600×1,140×222
600×1,420×222
600×1,420×222
Rows×Stages×Fin Pitch
mm
3×14×1.5
3×14×1.5
3×14×1.5
Face Area
m²
0.200
0.282
0.282
2D14B13
2D14B20
2D14B20
Sirocco Fan
Model
Type
Fan
Sirocco Fan
Sirocco Fan
W
25×1
35×1
35×1
m³/min
11/8.5
14/11
16/12
Motor Output × Number
of Units
Air Flow Rate (H/L)
cfm
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections
FXLQ63MVE
388/300
494/388
565/424
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber/ Urethane Foam
Glass Fiber/ Urethane Foam
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
Liquid Pipes
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
φ9.5 (Flare Connection)
Gas Pipes
mm
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
φ15.9 (Flare Connection)
Drain Pipe
mm
φ21 O.D (Vinyl Chloride)
φ21 O.D (Vinyl Chloride)
φ21 O.D (Vinyl Chloride)
kg
30
36
36
dBA
38/33
39/34
40/35
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
R410A M Series
R410A M Series
Machine Weight (Mass)
H5 Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable Outdoor Unit
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
Standard Accessories
Drawing No.
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
R410A M Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
3D038816
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Specifications
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
39
Specifications
SiE39-404
Concealed Floor Standing Type
Model
H1 Cooling Capacity (19.5°CWB)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
FXNQ20MVE
FXNQ25MVE
kcal/h
2,000
2,500
3,150
Btu/h
7,900
9,900
12,500
kW
2.3
2.9
3.7
kW
2.2
2.8
3.6
kcal/h
2,200
2,800
3,400
Btu/h
8,500
10,900
13,600
kW
2.5
3.2
4.0
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
Casing Color
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
mm
610×930×220
610×930×220
610×1,070×220
Rows×Stages×Fin Pitch
mm
3×14×1.5
3×14×1.5
3×14×1.5
Face Area
m²
0.159
0.159
0.200
D14B20
D14B20
2D14B13
Model
Type
Fan
Sirocco Fan
Sirocco Fan
Sirocco Fan
W
15×1
15×1
25×1
m³/min
7/6
7/6
8/6
cfm
247/212
247/212
282/212
Motor Output × Number
of Units
Air Flow Rate (H/L)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections
FXNQ32MVE
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber/ Urethane Foam
Glass Fiber/ Urethane Foam
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
Liquid Pipes
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
Gas Pipes
mm
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
Drain Pipe
mm
φ21 O.D (Vinyl Chloride)
φ21 O.D (Vinyl Chloride)
φ21 O.D (Vinyl Chloride)
kg
19
19
23
dBA
35/32
35/32
35/32
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
R410A M Series
R410A M Series
Machine Weight (Mass)
H5 Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable Outdoor Unit
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
Standard Accessories
Drawing No.
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
R410A M Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
3D038817
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
40
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications
SiE39-404
Specifications
Concealed Floor Standing Type
Model
H1 Cooling Capacity (19.5°CWB)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
FXNQ40MVE
FXNQ50MVE
kcal/h
4,000
5,000
6,300
Btu/h
15,900
19,900
25,000
kW
4.7
5.8
7.3
kW
4.5
5.6
7.1
kcal/h
4,300
5,400
6,900
Btu/h
17,000
21,500
27,300
kW
5.0
6.3
8.0
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
Casing Color
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
mm
610×1,070×220
610×1,350×220
610×1,350×220
Rows×Stages×Fin Pitch
mm
3×14×1.5
3×14×1.5
3×14×1.5
Face Area
m²
0.200
0.282
0.282
2D14B13
2D14B20
2D14B20
Sirocco Fan
Model
Type
Fan
Sirocco Fan
Sirocco Fan
W
25×1
35×1
35×1
m³/min
11/8.5
14/11
16/12
Motor Output × Number
of Units
Air Flow Rate (H/L)
cfm
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections
FXNQ63MVE
388/300
494/388
565/424
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber / Urethane Foam
Glass Fiber / Urethane Foam
Glass Fiber / Urethane Foam
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
Liquid Pipes
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
φ9.5 (Flare Connection)
Gas Pipes
mm
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
φ15.9 (Flare Connection)
Drain Pipe
mm
φ21 O.D (Vinyl Chloride)
φ21 O.D (Vinyl Chloride)
φ21 O.D (Vinyl Chloride)
kg
23
27
27
dBA
38/33
39/34
40/35
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
R410A M Series
R410A M Series
Machine Weight (Mass)
H5 Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable Outdoor Unit
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
Standard Accessories
Drawing No.
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
R410A M Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
3D038817
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Specifications
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
41
Specifications
SiE39-404
Ceiling Suspended Cassette Type
Model
Indoor Unit
FXUQ71MV1
FXUQ100MV1
FXUQ125MV1
Connection Unit
BEVQ71MVE
BEVQ140MVE
BEVQ140MVE
kcal/h
7,100
10,000
12,500
Btu/h
28,200
39,700
49,600
kW
8.3
11.6
14.5
kW
8.0
11.2
14.0
kcal/h
7,700
10,800
13,800
Btu/h
30,700
42,700
54,600
kW
9.0
12.5
16.0
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
H1 Cooling Capacity (19.5°CWB)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing Color
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
mm
165×895×895
230×895×895
230×895×895
Rows×Stages×Fin Pitch
mm
3×6×1.5
3×8×1.5
3×8×1.5
Face Area
m²
0.265
0.353
0.353
Model
QTS48A10M
QTS50B15M
QTS50B15M
Type
Turbo Fan
Turbo Fan
Turbo Fan
Motor Output × Number
of Units
Fan
Air Flow Rate (H/L)
W
45×1
90×1
90×1
m³/min
19/14
29/21
32/23
cfm
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Piping
Connections
671/494
1,024/741
1,130/812
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Heat Resistant Foamed Polyethylene,
Regular Foamed Polyethylene
Heat Resistant Foamed Polyethylene,
Regular Foamed Polyethylene
Heat Resistant Foamed Polyethylene,
Regular Foamed Polyethylene
Liquid Pipes
mm
φ9.5 (Flare Connection)
φ9.5 (Flare Connection)
φ9.5 (Flare Connection)
Gas Pipes
mm
φ15.9 (Flare Connection)
φ19.1 (Flare Connection)
φ19.1 (Flare Connection)
Drain Pipe
mm
I.Dφ20×O.Dφ26
I.Dφ20×O.Dφ26
I.Dφ20×O.Dφ26
kg
25
31
31
dBA
40/35
43/38
44/39
Machine Weight (Mass)
H5 Sound Level (H/L)
Safety Devices
Standard Accessories
Thermal Protector for Fan Motor
Thermal Protector for Fan Motor
Thermal Protector for Fan Motor
Operation Manual, Installation
Manual, Drain Hose, Clamp Metal,
Insulation for Fitting, Sealing Pads,
Clamps, Screws, Washers, Holding
Plate.
Operation Manual, Installation
Manual, Drain Hose, Clamp Metal,
Insulation for Fitting, Sealing Pads,
Clamps, Screws, Washers, Holding
Plate.
Operation Manual, Installation
Manual, Drain Hose, Clamp Metal,
Insulation for Fitting, Sealing Pads,
Clamps, Screws, Washers, Holding
Plate.
Drawing No.
4D049395
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
values are normally somewhat higher during actual operation as a result of ambient conditions.
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
BEV Units
Model
Power Supply
Casing
Dimensions: (H×W×D)
mm
Sound Absorbing Thermal Insulation
Material
Piping
Connection
BEVQ125MVE
1 Phase 50Hz 220~240V
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
100×350×225
100×350×225
100×350×225
Flame and Heat Resistant Foamed
Polyethylene
Flame and Heat Resistant Foamed
Polyethylene
Flame and Heat Resistant Foamed
Polyethylene
9.5mm (Flare Connection)
9.5mm (Flare Connection)
9.5mm (Flare Connection)
Gas Pipes
15.9mm (Flare Connection)
15.9mm (Flare Connection)
15.9mm (Flare Connection)
Outdoor Liquid Pipes
Unit
Suction Gas Pipes
9.5mm (Flare Connection)
9.5mm (Flare Connection)
9.5mm (Flare Connection)
15.9mm (Flare Connection)
15.9mm (Flare Connection)
15.9mm (Flare Connection)
Standard Accessories
42
BEVQ100MVE
1 Phase 50Hz 220~240V
Liquid Pipes
Indoor
Unit
Machine Weight (Mass)
Drawing No.
BEVQ71MVE
1 Phase 50Hz 220~240V
kg
3.0
3.0
3.5
Installation manual, Gas piping
connections, Insulation for fitting,
Sealing material, Clamps
Installation manual, Gas piping
connections, Insulation for fitting,
Sealing material, Clamps
Installation manual, Gas piping
connections, Insulation for fitting,
Sealing material, Clamps
4D045387
4D045387
4D045388
: http://splitoff.ru/tehn-doc.html
Specifications
SiE39-404
Specifications
Wall Mounted Type
Model
H1 Cooling Capacity (19.5°CWB)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
FXAQ20MHV1
FXAQ25MHV1
kcal/h
2,000
2,500
3,150
Btu/h
7,900
9,900
12,500
kW
2.3
2.9
3.7
kW
2.2
2.8
3.6
kcal/h
2,200
2,800
3,400
Btu/h
8,500
10,900
13,600
kW
2.5
3.2
4.0
White (3.0Y8.5/0.5)
White (3.0Y8.5/0.5)
White (3.0Y8.5/0.5)
Casing Color
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
mm
290×795×230
290×795×230
290×795×230
Rows×Stages×Fin Pitch
mm
2×14×1.4
2×14×1.4
2×14×1.4
Face Area
m²
0.161
0.161
0.161
QCL9661M
QCL9661M
QCL9661M
Model
Type
Fan
Cross Flow Fan
Cross Flow Fan
Cross Flow Fan
W
40×1
40×1
40×1
m³/min
7.5/4.5
8/5
9/5.5
cfm
265/159
282/177
318/194
Motor Output × Number
of Units
Air Flow Rate (H/L)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections
FXAQ32MHV1
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
Foamed Polystyrene /
Foamed Polyethylene
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
Resin Net (Washable)
Resin Net (Washable)
Liquid Pipes
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
Gas Pipes
mm
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
mm
VP13
(External Dia. 18 Internal Dia. 13)
VP13
(External Dia. 18 Internal Dia. 13)
VP13
(External Dia. 18 Internal Dia. 13)
Drain Pipe
Machine Weight (Mass)
H5 Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable outdoor unit
kg
11
11
11
dBA
35/29
36/29
37/29
Fuse
Fuse
Fuse
—
—
—
R410A M Series
R410A M Series
R410A M Series
Operation Manual, Installation
Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.
Standard Accessories
Drawing No.
Operation Manual, Installation
Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.
Operation Manual, Installation
Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.
3D046711
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length:7.5m, level
difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
Specifications
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
43
Specifications
SiE39-404
Wall Mounted Type
Model
FXAQ40MHV1
H1 Cooling Capacity (19.5°CWB)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
4,000
5,000
Btu/h
15,900
19,900
kW
4.7
5.8
kW
4.5
5.6
kcal/h
4,300
5,400
Btu/h
17,000
21,500
kW
5.0
6.3
White (3.0Y8.5/0.5)
White (3.0Y8.5/0.5)
Casing Color
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
mm
290×1,050×230
290×1,050×230
Rows×Stages×Fin Pitch
mm
2×14×1.4
2×14×1.4
Face Area
m²
0.213
0.213
QCL9686M
QCL9686M
Cross Flow Fan
Cross Flow Fan
Model
Type
Motor Output × Number
of Units
Fan
Air Flow Rate (H/L)
W
43×1
43×1
m³/min
12/9
15/12
cfm
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections
FXAQ50MHV1
kcal/h
424/318
530/424
Direct Drive
Direct Drive
Microprocessor Thermostat for Cooling and Heating
Microprocessor Thermostat for Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
Resin Net (Washable)
Liquid Pipes
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
Gas Pipes
mm
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
mm
VP13
(External Dia. 18 Internal Dia. 13)
VP13
(External Dia. 18 Internal Dia. 13)
Drain Pipe
Machine Weight (Mass)
H5 Sound Level (H/L)
kg
13
13
dBA
39/34
42/36
Fuse
Fuse
Safety Devices
Refrigerant Control
Connectable outdoor unit
—
—
R410A M Series
R410A M Series
Operation Manual, Installation Manual, Installation Panel,
Paper Pattern for Installation, Insulation Tape, Clamps,
screws.
Standard Accessories
Drawing No.
Operation Manual, Installation Manual, Installation Panel,
Paper Pattern for Installation, Insulation Tape, Clamps,
screws.
3D046711
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
BEV Units
Model
BEVQ50MVE
Power Supply
1 Phase 50Hz 220~240V
Casing
Galvanized Steel Plate
Dimensions: (H×W×D)
mm
Sound Absorbing Thermal Insulation Material
Piping
Connection
Indoor
Unit
Liquid Pipes
6.4mm (Flare Connection)
Gas Pipes
12.7mm (Flare Connection)
Outdoor
Unit
Liquid Pipes
6.4mm (Flare Connection)
Suction Gas Pipes
12.7mm (Flare Connection)
Machine Weight
Standard Accessories
Drawing No.
44
100×350×225
Flame and Heat Resistant Foamed Polyethylene
kg
3.0
Installation manual, Gas piping connections, Insulation for fitting, Sealing material, Clamps
4D046708
: http://splitoff.ru/tehn-doc.html
Specifications
SiE39-404
Specifications
Floor Standing Type
Model
H1 Cooling Capacity (19.5°CWB)
FXLQ20MHV1
FXLQ25MHV1
kcal/h
2,000
2,500
3,150
Btu/h
7,900
9,900
12,500
kW
2.3
2.9
3.7
kW
2.2
2.8
3.6
kcal/h
2,200
2,800
3,400
Btu/h
8,500
10,900
13,600
kW
2.5
3.2
4.0
Ivory White (5Y7.5/1)
Ivory White (5Y7.5/1)
Ivory White (5Y7.5/1)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing Color
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
mm
600×1,000×222
600×1,000×222
600×1,140×222
Rows×Stages×Fin Pitch
mm
3×14×1.5
3×14×1.5
3×14×1.5
Face Area
m²
0.159
0.159
0.200
D14B20
D14B20
2D14B13
Model
Type
Fan
FXLQ32MHV1
Sirocco Fan
Sirocco Fan
Sirocco Fan
W
15×1
15×1
25×1
m³/min
7/6
7/6
8/6
cfm
247/212
247/212
282/212
Motor Output × Number
of Units
Air Flow Rate (H/L)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Direct Drive
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber/ Urethane Foam
Glass Fiber/ Urethane Foam
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
mm
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
mm
φ21 O.D (Vinyl Chloride)
φ21 O.D (Vinyl Chloride)
φ21 O.D (Vinyl Chloride)
kg
25
25
30
dBA
35/32
35/32
35/32
Thermal Protector for Fan Motor
Thermal Protector for Fan Motor
Thermal Protector for Fan Motor
—
—
—
R410A M Series
R410A M Series
R410A M Series
Liquid Pipes
Piping
Connections Gas Pipes
Drain Pipe
Machine Weight (Mass)
H5 Sound Level (H/L) (220V)
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Safety Devices
Refrigerant Control
Connectable Outdoor Unit
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
Standard Accessories
Drawing No.
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
3D047065
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Specifications
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
45
Specifications
SiE39-404
Floor Standing Type
Model
FXLQ40MHV1
H1 Cooling Capacity (19.5°CWB)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
4,000
5,000
Btu/h
15,900
19,900
kW
4.7
5.8
kW
4.5
5.6
kcal/h
4,300
5,400
Btu/h
17,000
21,500
kW
5.0
6.3
Ivory White (5Y7.5/1)
Ivory White (5Y7.5/1)
Casing Color
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
mm
600×1,140×222
600×1,420×222
Rows×Stages×Fin Pitch
mm
3×14×1.5
3×14×1.5
Face Area
m²
0.200
0.282
2D14B13
2D14B20
Sirocco Fan
Sirocco Fan
Model
Type
Fan
Motor Output × Number
of Units
Air Flow Rate (H/L)
W
25×1
35×1
m³/min
11/8.5
14/11
cfm
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections
FXLQ50MHV1
kcal/h
388/300
494/388
Direct Drive
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for Cooling and Heating
Glass Fiber/ Urethane Foam
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
Liquid Pipes
mm
φ6.4 (Flare Connection)
φ6.4 (Flare Connection)
Gas Pipes
mm
φ12.7 (Flare Connection)
φ12.7 (Flare Connection)
Drain Pipe
mm
φ21 O.D (Vinyl Chloride)
φ21 O.D (Vinyl Chloride)
kg
30
36
dBA
38/33
39/34
Thermal Protector for Fan Motor
Thermal Protector for Fan Motor
Machine Weight (Mass)
H5 Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable Outdoor Unit
—
—
R410A M Series
R410A M Series
Operation Manual, Installation Manual, Insulation for
Fitting, Drain Hose, Clamps, Screws, Washers, Level
Adjustment Screw.
Standard Accessories
Drawing No.
Operation Manual, Installation Manual, Insulation for
Fitting, Drain Hose, Clamps, Screws, Washers, Level
Adjustment Screw.
3D047065
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
46
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications
SiE39-404
Specifications
Outdoor Air Processing Unit
Model
H1 Cooling Capacity
H1 Heating Capacity
FXMQ125MFV1
FXMQ200MFV1
FXMQ250MFV1
kcal/h
12,000
19,300
24,100
Btu/h
47,800
76,500
95,600
kW
14.0
22.4
28.0
kcal/h
7,700
12,000
15,000
Btu/h
30,000
47,500
59,400
kW
8.9
13.9
17.4
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
Casing
Dimensions: (H×W×D)
Coil (Cross
Fin Coil)
mm
470×744×1,100
470×1,380×1,100
470×1,380×1,100
Rows×Stages×Fin
Pitch
mm
3×26×2.0
3×26×2.0
3×26×2.0
Face Area
m²
Model
Type
Motor Output ×
Number of Units
Fan
W
Air Flow Rate (H/L)
0.65
0.65
D13/4G2DA1
D13/4G2DA1
Sirocco Fan
Sirocco Fan
Sirocco Fan
380×1
380×1
380×1
m³/min
18
28
35
cfm
635
988
1,236
External Static
Pressure H4
Pa
185
225
205
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Glass Fiber
Glass Fiber
H2
H2
H2
Liquid Pipes
9.5mm
(Flare Connection)
9.5mm
(Flare Connection)
9.5mm
(Flare Connection)
Gas Pipes
15.9mm
(Flare Connection)
19.1mm
(Brazing Connection)
22.2mm
(Brazing Connection)
(mm)
PS1B (female thread)
PS1B (female thread)
PS1B (female thread)
kg
86
123
123
dBA
42
47
47
Fuse
Thermal Protector
for Fan Motor
Fuse
Thermal Protector
for Fan Motor
Fuse
Thermal Protector
for Fan Motor
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections
0.28
D13/4G2DA1
Drain Pipe
Machine Weight (Mass)
Sound Level (220V) H3,H4
Safety Devices
Refrigerant Control
Standard Accessories
Connectable Outdoor Units H5,H6
Drawing No.
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Operation Manual, Installation Manual,
Sealing Pads, Screws, Clamps.
Operation Manual, Installation Manual,
Sealing Pads, Connection Pipes,
Screws, Clamps.
Operation Manual, Installation Manual,
Sealing Pads, Connection Pipes,
Screws, Clamps.
RXYQ8~48MY1B
RXYQ8~48MY1B
RXYQ10~48MY1B
3D046147A
3D046147A
3D046147A
Notes:
H1. Specifications are based on the following conditions:
· Cooling: Outdoor temp. of 33°CDB, 28°CWB (68% RH). and discharge temp. of 18°CDB
· Heating: Outdoor temp. of 0°CDB, -2.9°CWB (50% RH). and discharge temp. of 25°CDB
· Equivalent reference piping length: 7.5m (0m Horizontal)
· At 220V
H2. Air intake filter is not supplied, so be sure to install the optional long-life filter or high-efficiency filter.
Prease mount it in the duct system of the suction side. Select its colorimetric method (gravity method)
50% or more.
H3. Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center.
These values (measured at 220V) are normally somewhat higher during actual operation as a result of
ambient conditions.
H4. Valves measured at 220 V.
H5. Within the range that the total capacity of indoor units is 50 to 100%, it is possible to connect to the
outdoor unit.
H6. It is not possible to connect to the 5 HP outdoor unit. Not available for Heat Recovery type and VRV II-S
series.
· This equipment cannot be incorporated into the refrigerant piping system or remote group control of the
VRV II system.
Specifications
: http://splitoff.ru/tehn-doc.html
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
47
Specifications
48
SiE39-404
: http://splitoff.ru/tehn-doc.html
Specifications
SiE39-404
Part 3
Refrigerant Circuit
1. Refrigerant Circuit .................................................................................50
1.1 RXYQ5M (*Products after January, 2004)...........................................50
1.2 RXYQ8, 10, 12M (*Products after January, 2004)...............................52
1.3 RXYQ14, 16M (*Products after January, 2004) ..................................54
1.4 Outdoor air processing unit FXMQ125~250MFV1 .................................56
2. Functional Parts Layout ........................................................................57
2.1 RXYQ5M ................................................................................................57
2.2 RXYQ8, 10, 12M ....................................................................................58
2.3 RXYQ14, 16M ........................................................................................59
3. Refrigerant Flow for Each Operation Mode...........................................60
Refirgerant Circuit
: http://splitoff.ru/tehn-doc.html
49
Refrigerant Circuit
SiE39-404
1. Refrigerant Circuit
1.1
RXYQ5M (*Products after January, 2004)
No. in
refrigerant
Symbol
system
diagram
Name
A
M1C
Inverter compressor (INV)
Inverter compressor is operated on frequencies between 52 Hz and 210 Hz by using
the inverter. The number of operating steps is as follows when Inverter compressor is
operated.
RXYQ5M : 20 steps
D
M1F
Inverter fan
Since the system is of air heat exchanging type, the fan is operated at 8-step rotation
speed by using the inverter.
E
Y1E
Electronic expansion valve
(Main: EV1)
While in heating operation, PI control is applied to keep the outlet superheated degree
of air heat exchanger constant.
G
Y1S
Solenoid valve (Hot gas: SVP) Used to prevent the low pressure from transient falling.
J
Y2S
Solenoid valve (Receiver gas
discharging: SVG)
Used to collect refrigerant to receiver.
K
Y4S
Solenoid valve (Injection)
Used to cool the compressor by injecting refrigerant when the compressor discharge
temperature is high.
M
Y3S
4-way valve
Used to switch the operation mode between cooling and heating.
N
S1NPH High pressure sensor
O
S1NPL Low pressure sensor
Used to detect high pressure.
Used to detect low pressure.
HP pressure switch (For INV
compressor)
In order to prevent the increase of high pressure when a malfunction occurs, this
switch is activated at high pressure of 3.8 MPA or more to stop the compressor
operation.
—
Fusible plug
In order to prevent the increase of pressure when abnormal heating is caused by fire
or others, the fusible part of the plug is molten at a temperature of 70 to 75°C to
release the pressure into the atmosphere.
T
—
Pressure regulating valve 1
(Receiver to discharge pipe)
This valve opens at a pressure of 2 to 2.7 MPa for prevention of pressure increase,
thus resulting in no damage of functional parts due to the increase of pressure in
transportation or storage.
1
R1T
Thermistor (Outdoor air: Ta)
Used to detect outdoor temperature, correct discharge pipe temperature, and others.
2
R2T
Thermistor (Suction pipe: Ts)
Used to detect suction pipe temperature, keep the suction superheated degree
constant in heating operation, and others.
3
R3T
Thermistor (INV discharge
pipe: Tdi)
Used to detect discharge pipe temperature, make the temperature protection control of
compressor, and others.
4
R4T
Thermistor (Heat exchanger
deicer: Tb)
Used to detect liquid pipe temperature of air heat exchanger, determine defrosting
operation, and others.
5
R5T
Thermistor (Sub-cooling heatUsed to judge the refrigerant overcharge at the check operation.
exchanger outlet)
P
S1PH
S
Note:
50
Major Function
Please refer the refrigerant circuit for products before December, 2003 to service manual
Si39-302.
: http://splitoff.ru/tehn-doc.html
Refirgerant Circuit
SiE39-404
Refrigerant Circuit
RXYQ5M
J
Receiver
Filter
Solenoid
S
valve
Heat
exchanger pipe
Filter
D
Solenoid
valve
E
K
Filter
5
Filter
Electronic
expansion valve
Capillary
tube
4
Heat exchanger
1
M
Four way
valve
T
Pressure
regulating valve
N
Oil
separator
Filter
Filter
P
High pressure
switch
3
A
G
Solenoid
valve
High pressure
sensor
Capillary
tube
Compressor
INV
O
2
Low pressure
sensor
Filter
Stop valve (With service port on on-site piping side ø 7.9mm flare connection)
4D040337C
Refirgerant Circuit
: http://splitoff.ru/tehn-doc.html
51
Refrigerant Circuit
1.2
SiE39-404
RXYQ8, 10, 12M (*Products after January, 2004)
No. in
refrigerant
Symbol
system
diagram
Name
A
M1C
Inverter compressor (INV)
B
M2C
Standard compressor 1
(STD1)
D
M1F
Inverter fan
Since the system is of air heat exchanging type, the fan is operated at 8-step rotation
speed by using the inverter.
E
Y1E
Electronic expansion valve
(Main: EV1)
While in heating operation, PI control is applied to keep the outlet superheated degree
of air heat exchanger constant.
F
Y2E
Electronic expansion valve
(Subcool: EV2)
PI control is applied to keep the outlet superheated degree of subcooling heat
exchanger constant.
G
Y1S
Solenoid valve (Hot gas: SVP) Used to prevent the low pressure from transient falling.
H
Y2S
Solenoid valve (Oil
equalization: SVO)
Used for oil equalizing among outdoor units in multiple-outdoor-unit system.
J
Y3S
Solenoid valve (Receiver gas
discharging: SVG)
Used to collect refrigerant to receiver.
L
Y4S
Solenoid valve (Non-operating Used to prevent the accumulation of refrigerant in non-operating outdoor units in the
unit liquid pipe closing: SVSL) case of multi-outdoor unit system.
Y5S
4-way valve
M
Inverter compressor is operated on frequencies between 52 Hz and 210 Hz by using
the inverter, while Standard compressor is operated with commercial power supply
only. The number of operating steps is as follows when Inverter compressor is
operated in combination with Standard compressor.
RXYQ8, 10, 12M: 29 steps
Used to switch the operation mode between cooling and heating.
N
S1NPH High pressure sensor
Used to detect high pressure.
O
S1NPL Low pressure sensor
Used to detect low pressure.
P
S1PH
HP pressure switch (For INV
compressor)
Q
S2PH
HP pressure switch (For STD
compressor 2)
S
—
Fusible plug
U
—
Pressure regulating valve 2
(Liquid pipe to receiver)
V
—
Pressure regulating valve 3
(Equalizing pipe to discharge
pipe)
1
R1T
Thermistor (Outdoor air: Ta)
Used to detect outdoor temperature, correct discharge pipe temperature, and others.
2
R2T
Thermistor (Suction pipe: Ts)
used to detect suction pipe temperature, keep the suction superheated degree
constant in heating operation, and others.
3
R31T
Thermistor (INV discharge
pipe: Tdi)
4
R32T
Thermistor (STD1 discharge
pipe: Tds1)
6
R4T
Thermistor (Heat exchanger
deicer: Tb)
Used to detect liquid pipe temperature of air heat exchanger, determine defrosting
operation, and others.
7
R5T
Thermistor (Subcooling heat
exchanger gas pipe: Tsh)
Used to detect gas pipe temperature on the evaporation side of subcooling heat
exchanger, keep the superheated degree at the outlet of subcooling heat exchanger
constant, and others.
8
R6T
Thermistor (Receiver outlet
liquid pipe: Tl)
Used to detect receiver outlet liquid pipe temperature, prevent the drift between
outdoor units while in heating operation in the case of multiple-outdoor-unit system,
and others.
9
R7T
Thermistor (Oil equalizing
pipe: To)
Used to detect equalizing pipe temperature, opening/closing of the equalizing pipe
stop valve, and others.
Note:
52
Major Function
In order to prevent the increase of high pressure when a malfunction occurs, this
switch is activated at high pressure of 3.8 MPA or more to stop the compressor
operation.
In order to prevent the increase of pressure when abnormal heating is caused by fire
or others, the fusible part of the plug is molten at a temperature of 70 to 75°C to
release the pressure into the atmosphere.
This valve opens at a pressure of 2 to 2.7 MPa for prevention of pressure increase,
thus resulting in no damage of functional parts due to the increase of pressure in
transportation or storage.
used to detect discharge pipe temperature, make the temperature protection control of
compressor, and others.
Please refer the refrigerant circuit for products before December, 2003 to service manual
Si39-302.
: http://splitoff.ru/tehn-doc.html
Refirgerant Circuit
SiE39-404
Refrigerant Circuit
RXYQ8, 10, 12M
Heat
exchanger pipe
8
Capillary
tube
Filter
Filter
Receiver
Solenoid J
valve
Check
valve
S
E
Electronic
expansion valve
Filter
Filter
Pressure
regulating
valve
F
U
Electronic
expansion
valve
Check
valve
L
D
Fan
Solenoid
valve
1
7
Check
valve
6
M
Heat exchanger
Four way
valve
2
V
N
Pressure
regulating
valve
Filter
Solenoid
valve
Capillary tube
Capillary tube
3
A
Q
High pressure
switch
4
Filter
Filter
Compressor
INV
Check
valve
Capillary
tube
G
Check
valve
Oil
separator
P
High pressure
switch
Check
valve
Oil
separator
Filter
Filter
High pressure
sensor
B
Compressor
STD
Filter
Low pressure
O
sensor
9
Filter
Check valve
Solenoid
H
valve
Stop valve (With service port on on-site piping side ø 7.9mm flare connection)
4D044808
Refirgerant Circuit
: http://splitoff.ru/tehn-doc.html
53
Refrigerant Circuit
1.3
SiE39-404
RXYQ14, 16M (*Products after January, 2004)
No. in
refrigerant
Symbol
system
diagram
Name
A
M1C
Inverter compressor (INV)
B
M2C
Standard compressor 1
(STD1)
C
M3C
Standard compressor 1
(STD2)
D
M1F
Inverter fan
Since the system is of air heat exchanging type, the fan is operated at 8-step rotation
speed by using the inverter.
E
Y1E
Electronic expansion valve
(Main: EV1)
While in heating operation, PI control is applied to keep the outlet superheated degree
of air heat exchanger constant.
F
Y2E
Electronic expansion valve
(Subcool: EV2)
PI control is applied to keep the outlet superheated degree of subcooling heat
exchanger constant.
G
Y1S
Solenoid valve (Hot gas: SVP) Used to prevent the low pressure from transient falling.
H
Y2S
Solenoid valve (Oil
equalization: SVO)
Used for oil equalizing among outdoor units in multiple-outdoor-unit system.
J
Y3S
Solenoid valve (Receiver gas
discharging: SVG)
Used to collect refrigerant to receiver.
L
Y4S
Solenoid valve (Non-operating Used to prevent the accumulation of refrigerant in non-operating outdoor units in the
unit liquid pipe closing: SVSL) case of multi-outdoor unit system.
M
Y5S
4-way valve
Inverter compressor is operated on frequencies between 52 Hz and 210 Hz by using
the inverter, while Standard compressor is operated with commercial power supply
only. The number of operating steps is as follows when Inverter compressor is
operated in combination with Standard compressor.
RXYQ14, 16M: 35 steps
Used to switch the operation mode between cooling and heating.
N
S1NPH High pressure sensor
Used to detect high pressure.
O
S1NPL Low pressure sensor
Used to detect low pressure.
P
S1PH
HP pressure switch (For INV
compressor)
Q
S2PH
HP pressure switch (For STD
compressor 2)
R
S3PH
HP pressure switch (For STD
compressor 1)
S
—
Fusible plug
U
—
Pressure regulating valve 2
(Liquid pipe to receiver)
V
—
Pressure regulating valve 3
(Equalizing pipe to discharge
pipe)
1
R1T
Thermistor (Outdoor air: Ta)
Used to detect outdoor temperature, correct discharge pipe temperature, and others.
2
R2T
Thermistor (Suction pipe: Ts)
used to detect suction pipe temperature, keep the suction superheated degree
constant in heating operation, and others.
3
R31T
Thermistor (INV discharge
pipe: Tdi)
4
R32T
Thermistor (STD1 discharge
pipe: Tds1)
5
R33T
Thermistor (STD2 discharge
pipe: Tds2)
6
R4T
Thermistor (Heat exchanger
deicer: Tb)
Used to detect liquid pipe temperature of air heat exchanger, determine defrosting
operation, and others.
7
R5T
Thermistor (Subcooling heat
exchanger gas pipe: Tsh)
Used to detect gas pipe temperature on the evaporation side of subcooling heat
exchanger, keep the superheated degree at the outlet of subcooling heat exchanger
constant, and others.
8
R6T
Thermistor (Receiver outlet
liquid pipe: Tl)
Used to detect receiver outlet liquid pipe temperature, prevent the drift between
outdoor units while in heating operation in the case of multiple-outdoor-unit system,
and others.
9
R7T
Thermistor (Oil equalizing
pipe: To)
Used to detect equalizing pipe temperature, opening/closing of the equalizing pipe
stop valve, and others.
Note:
54
Major Function
In order to prevent the increase of high pressure when a malfunction occurs, this
switch is activated at high pressure of 3.8 MPA or more to stop the compressor
operation.
In order to prevent the increase of pressure when abnormal heating is caused by fire
or others, the fusible part of the plug is molten at a temperature of 70 to 75°C to
release the pressure into the atmosphere.
This valve opens at a pressure of 2 to 2.7 MPa for prevention of pressure increase,
thus resulting in no damage of functional parts due to the increase of pressure in
transportation or storage.
used to detect discharge pipe temperature, make the temperature protection control of
compressor, and others.
Please refer the refrigerant circuit for products before December, 2003 to service manual
Si39-302.
: http://splitoff.ru/tehn-doc.html
Refirgerant Circuit
SiE39-404
Refrigerant Circuit
RXYQ14, 16M
Heat
exchanger
pipe
8
Capillary
tube
Filter
Receiver
Solenoid J
valve
Filter
Check
valve
S
E
Electronic
expansion valve
Filter
Filter
Pressure
regulatin
valve
F
U
Electronic
expansion
valve
Check
valve
L
D
Solenoid
valve
7
Check
valve
6
1
M
Heat exchanger
Four way
valve
V
2
N
Capillary tube
A
Filter
Oil
separator
Filter
4
Filter
Compressor
INV
Check
valve
Capillary
tube
Solenoid
valve
3
Capillary tube
High pressure
switch
G
R
High
pressure
switch
Filter
P
Oil
separator
Oil
separator
Filter
Q
High pressure
switch
Filter
Check
valve
High pressure Pressure
regulatin
sensor
valve
Check
Check
valve
valve
Compressor
STD1 B
C
Capillary
tube
5
Compressor
STD2
Filter
Low pressure O
sensor
Check valve
9
Filter
Solenoid H
valve
Stop valve (With service port on on-site piping side ø 7.9mm flare connection)
4D044809
Refirgerant Circuit
: http://splitoff.ru/tehn-doc.html
55
Refrigerant Circuit
1.4
SiE39-404
Outdoor air processing unit FXMQ125~250MFV1
1.4.1 Refrigerant System
Th4
Gas pipe
connection port
Heat exchanger
Th3
Th2
Filter
C
Fan
Distributor
Capillary
tube
Th1
Solenoid
valve
B
Liquid pipe
connection port
Check
valve
A
Filter
Filter
Electronic
expansion valve
4D018650B
Main Control Equipment
Code
Symbol
Name
A
Y1E
Motorized valve
B
Y1S
Solenoid valve
C
—
Capillary tube
Main function
Used to control the flow rate of refrigerant, and
make the SH control while in cooling or the SC
control while in heating.∗
Used to bypass hot gas while in heating with
thermostat OFF.
Used to reduce pressure from high to low in
bypassing hot gas.
∗SH control: Superheated control of heat exchanger outlet
SC control: Subcooled control of heat exchanger outlet
Thermistor
56
Code
Symbol
Th1
R1T
Th2
R2T
Th3
R3T
Name
Suction air temperature
thermistor
Liquid pipe temperature
thermistor
Gas pipe temperature
thermistor
Th4
R4T
Discharge air
temperature thermistor
Main function
Used to turn ON or OFF the thermostat and select
cooling or heating operation.
Used to control the opening degree of EV (Y1F)
under the SC control.
Used to control the opening degree of EV (Y1E)
under the SH control.
Used to control the electric expansion valve
opening and thermostat ON/OFF so as to keep the
discharge air temperature at the set temperature.
: http://splitoff.ru/tehn-doc.html
Refirgerant Circuit
SiE39-404
Functional Parts Layout
2. Functional Parts Layout
2.1
RXYQ5M
Plan
High pressur switch
(High pressure protection INV)
S1PH
Thermistor
(INV discharge pipe)
R3T
Front View
Fan
Fan motor
Solenoid valve
(Hot gas bypass)
Y1S
Solenoid valve
(Receiver gas discharchgin)
Y4S
Pressure sensor
(High pressure)
S1NPH
Solenoid valve (Injection) Y4S
Electronic expansion valve
Y1E
Thermistor
(subcooling heat
exchanger outlet)
R5T
Thermistor
(heat exchanger cleicen)
R4T
Gas side stop valve
4 way valve
Y3S
Thermistor
(Outdoor air)
R1T
Compressor (INV)
M1C
Liquid side stop valve
Pressure sensor
Thermistor
(Low pressure)
(suction pipe)
S1NPL
R2T
Refirgerant Circuit
: http://splitoff.ru/tehn-doc.html
57
Functional Parts Layout
2.2
SiE39-404
RXYQ8, 10, 12M
Plan
Solenoid valve
(oil equalizing of multi outdoor unit system)
Y2S
High pressure switch
(High pressure protection INV)
S1PH
High pressure switch
(High pressure protection STD1)
S2PH
Front View
Fan motor
M1F
Fan
Solenoid valve
(Hot gas bypass)
Y1S
Solenoid valve
(Receiver gas discharge)
Y3S
Pressure sensor
(High pressure)
S1NPH
Electronic expansion valve
(Subcooling)
Y2E
4 way valve
Y5S
Electronic expansion valve
(Main)
Y1E
Thermistor
(subcooling heat exchanger)
R5T
Thermistor (Suction pipe)
R2T
Thermistor (Outdoor air)
R1T
Solenoid valve
(Non operating unit liquid pipe closing)
Y4S
Thermistor (Receiver liquid pipe)
R6T
Thermistor
(Discharge pipe STD1)
R32T
Thermistor (Oil equalizing)
R7T
Thermistor
(Discharge pipe INV)
R31T
Thermistor (Heat exchanger)
R4T
Gas side stop valve
Compressor (STD1)
M2C
Oil equalizing
stop valve
Liquid side stop valve
58
Compressor (INV)
M1C
Pressure sensor (Low pressure)
S1NPL
: http://splitoff.ru/tehn-doc.html
Refirgerant Circuit
SiE39-404
2.3
Functional Parts Layout
RXYQ14, 16M
Plan
Solenoid valve
(Oil equalizing of multi outdoor system)
Y2S
High pressure switch
(High pressure protection INV)
S1PH
High pressure switch
(High pressure protection STD1)
S2PH
High pressure switch
(High pressure protection STD2)
S3PH
Front View
Fan
Solenoid valve
(Receiver gas discharge)
Y3S
Electronic expansion valve
(Subcooling)
Y2E
Electronic expansion valve (Main)
Y1E
Thermistor
(Subcooling heat exchanger)
R5T
Solenoid valve
(Non operating unit liquid pipe closing)
Y4S
Thermistor (Receiver liquid pipe)
R6T
Oil equalizing stop valve
Liquid stop valve
Thermistor
(Heat exchanger)
R4T
Fan motor
M1F
Pressure sensor
(High pressure)
S1NPH
Solenoid valve
(Hot gas bypass)
Y1S
4 way valve
Y5S
Thermistor (Suction pipe)
R7T
Thermistor (Outdoor air)
R1T
Thermistor
(Discharge pipe STD1)
R32T
Thermistor
(Discharge pipe STD2)
R33T
Compressor (STD2)
M3C
Gas side stop valve
Compressor (STD1)
Thermistor (Suction pipe) Compressor (INV)
M2C
M1C
R2T
Pressure sensor (Low pressure) Thermistor (Discharge pipe INV)
S1NPL
R31T
Refirgerant Circuit
: http://splitoff.ru/tehn-doc.html
59
Refrigerant Flow for Each Operation Mode
SiE39-404
3. Refrigerant Flow for Each Operation Mode
RXYQ5M
Cooling Operation
Indoor unit operation
Fan ON
Fan ON
Fan OFF
" ON "
Heat exchanger
" OFF "
" ON "
Heat exchanger
Heat exchanger
High temperature, high pressure gas
High temperature, high pressure liquid
Low temperature, low pressure
Fan
Fan
Electronic
expansion
valve
Fan
Electronic
expansion
valve
Filter
Filter
Indoor unit
Electronic
expansion
valve
Filter
Filter
Indoor unit
Filter
Filter
Indoor unit
Thermostat "ON"
Thermostat "OFF"
Receiver
Filter
Solenoid
valve
Heat
exchanger pipe
Filter
Fan
Solenoid
valve
Filter
Filter
Electronic
expansion valve
Capillary
tube
Heat exchanger
Four way
valve
High pressure
sensor
Pressure
regulating valve
Oil
separator
Filter
Filter
Solenoid
valve
High pressure
switch
Capillary
tube
Compressor
INV
Low pressure
sensor
Filter
Stop valve (With service port on on-site piping side ø7.9mm flare connection)
4D040337C
60
: http://splitoff.ru/tehn-doc.html
Refirgerant Circuit
SiE39-404
Refrigerant Flow for Each Operation Mode
Cooling Oil Return Operation
Indoor unit operation
Fan ON
Fan OFF
" ON "
" OFF "
Fan OFF
" ON "
Heat exchanger
Heat exchanger
Heat exchanger
Fan
Fan
Fan
High temperature, high pressure gas
High temperature, high pressure liquid
Low temperature, low pressure
EXV : Normal control
EXV : 200 pls
Filter
Filter
Indoor unit
EXV : 200 pls
Filter
Filter
Indoor unit
Filter
Filter
Indoor unit
Thermostat "ON"
Thermostat "OFF"
Filter
Receiver
Solenoid
valve
Heat
exchanger pipe
Filter
Fan
Solenoid
valve
Filter
Filter
Electronic
expansion valve
Capillary
tube
Heat exchanger
Four way
valve
High pressure
sensor
Pressure
regulating valve
Oil
separator
Filter
Filter
Solenoid
valve
High pressure
switch
Capillary
tube
Compressor
INV
Low pressure
sensor
Filter
Stop valve (With service port on on-site piping side ø7.9mm flare connection)
4D040337C
Refirgerant Circuit
: http://splitoff.ru/tehn-doc.html
61
Refrigerant Flow for Each Operation Mode
SiE39-404
Heating Oil Return & Defrost Operation
Indoor unit operation
Fan OFF
Fan OFF
" ON "
Fan OFF
" OFF "
" ON "
Heat exchanger
Heat exchanger
Heat exchanger
Fan
Fan
Fan
High temperature, high pressure gas
High temperature, high pressure liquid
Low temperature, low pressure
EXV : 512 pls
EXV : 512 pls
Filter
Filter
Indoor unit
EXV : 512 pls
Filter
Filter
Indoor unit
Filter
Filter
Indoor unit
Thermostat "ON"
Thermostat "OFF"
Filter
Receiver
Solenoid
valve
Heat
exchanger pipe
Filter
Fan
Solenoid
valve
Filter
Filter
Electronic
expansion valve
Capillary
tube
Heat exchanger
Four way
valve
High pressure
sensor
Pressure
regulating valve
Oil
separator
Filter
Filter
Solenoid
valve
High pressure
switch
Capillary
tube
Compressor
INV
Low pressure
sensor
Filter
Stop valve (With service port on on-site piping side ø7.9mm flare connection)
4D040337C
62
: http://splitoff.ru/tehn-doc.html
Refirgerant Circuit
SiE39-404
Refrigerant Flow for Each Operation Mode
Heating Operation
Indoor unit operation
Fan ON
Fan LL
Fan OFF
" ON "
Heat exchanger
" OFF "
" ON "
Heat exchanger
Heat exchanger
High temperature, high pressure gas
High temperature, high pressure liquid
Low temperature, low pressure
Fan
Fan
Electronic
expansion
valve
Fan
Electronic
expansion
valve
Filter
Filter
Indoor unit
Electronic
expansion
valve
Filter
Filter
Indoor unit
Filter
Filter
Indoor unit
Thermostat "OFF"
Thermostat "ON"
Receiver
Filter
Solenoid
valve
Heat
exchanger pipe
Filter
Fan
Solenoid
valve
Filter
Filter
Electronic
expansion valve
Capillary
tube
Heat exchanger
Four way
valve
High pressure
sensor
Pressure
regulating valve
Oil
separator
Filter
Filter
Solenoid
valve
High pressure
switch
Capillary
tube
Compressor
INV
Low pressure
sensor
Filter
Stop valve (With service port on on-site piping side ø7.9mm flare connection)
4D040337C
Refirgerant Circuit
: http://splitoff.ru/tehn-doc.html
63
Refrigerant Flow for Each Operation Mode
SiE39-404
RXYQ8, 10, 12M
Cooling Operation
Indoor unit operation
Fan ON
Fan ON
Fan OFF
" ON "
Heat exchanger
" OFF "
" ON "
Heat exchanger
Heat exchanger
High temperature, high pressure gas
High temperature, high pressure liquid
Low temperature, low pressure
Fan
Fan
Electronic
expansion
valve
Fan
Electronic
expansion
valve
Filter
Filter
Indoor unit
Electronic
expansion
valve
Filter
Filter
Indoor unit
Filter
Filter
Indoor unit
Thermostat "ON"
Thermostat "OFF"
Heat
exchanger pipe
Filter
Check
valve
Capillary
tube
Filter
Receiver
Solenoid
valve
Filter
Electronic
expansion valve
Filter
Pressure
regulating
valve
Electronic
expansion
valve
Check
valve
Fan
Solenoid
valve
Check
valve
Filter
Four way
valve
Pressure
High pressure
regulating
sensor
valve
Check
valve
High pressure
switch
Oil
separator
Filter
Filter
Capillary tube
Check
valve
Capillary
tube
Solenoid
valve
Capillary tube
Compressor
INV
Oil
separator
Filter
Check
valve
High pressure
switch
Heat exchanger
Compressor
STD
Filter
Low pressure
sensor
Solenoid
valve
Filter
Stop valve (With service port on on-site piping side ø7.9mm flare connection)
64
S
Oil equalizing pipe to other outdoor units
S
Liquid piping to other outdoor units
S
Gas piping to other outdoor units
4D044808
: http://splitoff.ru/tehn-doc.html
Refirgerant Circuit
SiE39-404
Refrigerant Flow for Each Operation Mode
Cooling Oil Return
Indoor unit operation
Fan ON
Fan OFF
" ON "
Fan OFF
" OFF "
" ON "
Heat exchanger
Heat exchanger
Heat exchanger
Fan
Fan
Fan
High temperature, high pressure gas
High temperature, high pressure liquid
Low temperature, low pressure
EXV : 200 pls
EXV : Nornal control
Filter
Filter
Indoor unit
EXV : 200 pls
Filter
Filter
Indoor unit
Filter
Filter
Indoor unit
Thermostat "ON"
Thermostat "OFF"
Heat
exchanger pipe
Capillary
tube
Filter
Filter
Check
valve
Receiver
Solenoid
valve
Filter
Electronic
expansion valve
Filter
Pressure
regulating
valve
Electronic
expansion
valve
Check
valve
Fan
Solenoid
valve
Check
valve
Heat exchanger
Four way
valve
Filter
High pressure
sensor
Check
valve
Check
valve
Capillary
tube
Filter
Capillary tube
Compressor
INV
Filter
Capillary tube
High pressure
switch
Solenoid
valve
High pressure
switch
Oil
separator
Oil
separator
Filter
Filter
Check
valve
Pressure
regulating
valve
Compressor
STD
Filter
Low pressure
sensor
Check valve
Solenoid
valve
Filter
Stop valve (With service port on on-site piping side ø7.9mm flare connection)
Refirgerant Circuit
S
Oil equalizing pipe to other outdoor units
S
Liquid piping to other outdoor units
S
Gas piping to other outdoor units
4D044808
: http://splitoff.ru/tehn-doc.html
65
Refrigerant Flow for Each Operation Mode
SiE39-404
Heating Oil Return & Defrost
Indoor unit operation
Fan OFF
Fan OFF
" ON "
Fan OFF
" OFF "
" ON "
Heat exchanger
Heat exchanger
Heat exchanger
Fan
Fan
Fan
High temperature, high pressure gas
High temperature, high pressure liquid
Low temperature, low pressure
EXV : 512 pls
EXV : 512 pls
Filter
Filter
Indoor unit
EXV : 512 pls
Filter
Filter
Indoor unit
Filter
Filter
Indoor unit
Thermostat "ON"
Thermostat "OFF"
Heat
exchanger pipe
Capillary
tube
Filter
Filter
Check
valve
Receiver
Solenoid
valve
Filter
Electronic
expansion valve
Filter
Pressure
regulating
valve
Electronic
expansion
valve
Check
valve
Fan
Solenoid
valve
Check
valve
Heat exchanger
Four way
valve
Filter
High pressure
sensor
Check
valve
Capillary
tube
High pressure
switch
Filter
Capillary tube
Compressor
INV
Filter
Capillary tube
High pressure
switch
Solenoid
valve
Check
valve
Oil
separator
Oil
separator
Filter
Filter
Check
valve
Pressure
regulating
valve
Compressor
STD
Filter
Low pressure
sensor
Check valve
Solenoid
valve
Filter
Stop valve (With service port on on-site piping side ø7.9mm flare connection)
66
S
Oil equalizing pipe to other outdoor units
S
Liquid piping to other outdoor units
S
Gas piping to other outdoor units
4D044808
: http://splitoff.ru/tehn-doc.html
Refirgerant Circuit
SiE39-404
Refrigerant Flow for Each Operation Mode
Heating Operation
Indoor unit operation
Fan ON
Fan LL
Fan OFF
Heat exchanger
Heat exchanger
Heat exchanger
Fan
Fan
High temperature, high pressure gas
High temperature, high pressure liquid
Low temperature, low pressure
Fan
Electronic expansion valve
Electronic expansion valve
Filter
Filter
Indoor unit
Electronic expansion valve
Filter
Filter
Indoor unit
Filter
Filter
Indoor unit
Thermostat "ON"
Thermostat "OFF"
Heat
exchanger pipe
Capillary
tube
Filter
Check
valve
Receiver
Solenoid
valve
Filter
Filter
Electronic
expansion valve
Filter
Pressure
regulating
valve
Electronic
expansion
valve
Check
valve
Fan
Solenoid
valve
Check
valve
Heat exchanger
Four way
valve
Check
valve
Check
valve
Capillary
tube
Filter
High pressure
switch
Filter
Filter
Capillary tube
Compressor
INV
Check
valve
Solenoid
valve
Capillary tube
High pressure
switch
Pressure
regulating
valve
Oil
separator
Oil
separator
Filter
Filter
High pressure
sensor
Compressor
STD
Filter
Low pressure
sensor
Check valve
Filter
Solenoid
valve
Stop valve (With service port on on-site piping side ø7.9mm flare connection)
Refirgerant Circuit
S
Oil equalizing pipe to other outdoor units
S
Liquid piping to other outdoor units
S
Gas piping to other outdoor units
4D044808
: http://splitoff.ru/tehn-doc.html
67
Refrigerant Flow for Each Operation Mode
SiE39-404
RXYQ14, 16M
Cooling Operation
Indoor unit operation
Fan ON
Fan ON
Fan OFF
" ON "
Heat exchanger
" OFF "
" ON "
Heat exchanger
Heat exchanger
High temperature, high pressure gas
High temperature, high pressure liquid
Low temperature, low pressure
Fan
Fan
Electronic
expansion
valve
Fan
Electronic
expansion
valve
Filter
Filter
Indoor unit
Electronic
expansion
valve
Filter
Filter
Indoor unit
Filter
Filter
Indoor unit
Thermostat "ON"
Thermostat "OFF"
Heat
exchanger pipe
Capillary
tube
Filter
Filter
Check
valve
Receiver
Solenoid
valve
Filter
Electronic
expansion valve
Filter
Pressure
regulating
valve
Electronic
expansion
valve
Check
valve
Fan
Solenoid
valve
Check
valve
Heat exchanger
Four way
valve
Filter
Capillary tube
Check
valve
Capillary
tube
Filter
Capillary tube
Compressor
INV
Oil
separator
Solenoid
valve
Filter
Oil
separator
High pressure
switch
Oil
separator
High pressure
switch
Filter
Check
valve
Filter
Check
valve
Check
valve
Filter
Filter
High pressure Pressure
regulating
sensor
valve
High pressure
switch
Compressor
STD1
Compressor
STD2
Filter
Low pressure
sensor
Check valve
Solenoid
valve
Filter
Stop valve (With service port on on-site piping side ø7.9mm flare connection)
68
S
Oil equalizing pipe to other outdoor units
S
Liquid piping to other outdoor units
S
Gas piping to other outdoor units
4D044809
: http://splitoff.ru/tehn-doc.html
Refirgerant Circuit
SiE39-404
Refrigerant Flow for Each Operation Mode
Cooling Oil Return Operation
Indoor unit operation
Fan ON
Fan OFF
" ON "
Fan OFF
" OFF "
" ON "
Heat exchanger
Heat exchanger
Heat exchanger
Fan
Fan
Fan
High temperature, high pressure gas
High temperature, high pressure liquid
Low temperature, low pressure
EXV : Normal control
EXV : 200 pls
Filter
Filter
Indoor unit
EXV : 200 pls
Filter
Filter
Indoor unit
Filter
Filter
Indoor unit
Thermostat "ON"
Thermostat "OFF"
Heat
exchanger pipe
Capillary
tube
Filter
Filter
Check
valve
Receiver
Solenoid
valve
Filter
Electronic
expansion valve
Filter
Pressure
regulating
valve
Electronic
expansion
valve
Check
valve
Fan
Solenoid
valve
Check
valve
Heat exchanger
Four way
valve
Check
valve
Oil
separator
Filter
Filter
Filter
Capillary tube
Check
valve
Capillary
tube
Solenoid
valve
Capillary tube
Compressor
INV
Oil
separator
High pressure
switch
Oil
separator
High pressure
switch
Filter
Pressure
regulating
valve
Filter
Check
valve
Check
valve
Filter
Filter
High pressure
sensor
High pressure
switch
Compressor
STD1
Compressor
STD2
Capillary
tube
Filter
Low pressure
sensor
Check valve
Solenoid
valve
Filter
Stop valve (With service port on on-site piping side ø7.9mm flare connection)
Refirgerant Circuit
S
Oil equalizing pipe to other outdoor units
S
Liquid piping to other outdoor units
S
Gas piping to other outdoor units
4D044809
: http://splitoff.ru/tehn-doc.html
69
Refrigerant Flow for Each Operation Mode
SiE39-404
Heating Oil Return & Defrost Operation
Indoor unit operation
Fan OFF
Fan OFF
" ON "
Fan OFF
" OFF "
" ON "
Heat exchanger
Heat exchanger
Heat exchanger
Fan
Fan
Fan
High temperature, high pressure gas
High temperature, high pressure liquid
Low temperature, low pressure
EXV : 512 pls
EXV : 512 pls
Filter
Filter
Indoor unit
EXV : 512 pls
Filter
Filter
Indoor unit
Filter
Filter
Indoor unit
Thermostat "ON"
Thermostat "OFF"
Heat
exchanger pipe
Capillary
tube
Filter
Filter
Check
valve
Receiver
Solenoid
valve
Filter
Electronic
expansion valve
Filter
Pressure
regulating
valve
Electronic
expansion
valve
Check
valve
Fan
Solenoid
valve
Check
valve
Heat exchanger
Four way
valve
Check
valve
Capillary
tube
Filter
Filter
Capillary tube
Compressor
INV
Filter
Capillary tube
High pressure
switch
Solenoid
valve
Filter
Oil
separator
Filter
Check
valve
Oil
separator
High pressure
switch
Check
valve
Oil
separator
Check
valve
Filter
Filter
High pressure Pressure
regulating
sensor
valve
High pressure
switch
Compressor
STD1
Compressor
STD2
Capillary
tube
Filter
Filter
Low pressure
sensor
Check valve
Solenoid
valve
Filter
Stop valve (With service port on on-site piping side ø7.9mm flare connection)
S
Oil equalizing pipe to other outdoor units
S
Liquid piping to other outdoor units
S
Gas piping to other outdoor units
4D044809
70
: http://splitoff.ru/tehn-doc.html
Refirgerant Circuit
SiE39-404
Refrigerant Flow for Each Operation Mode
Heating Operation
Indoor unit operation
Fan ON
Fan LL
Fan OFF
Fan OFF
Heat exchanger
Heat exchanger
Heat exchanger
Fan
Fan
High temperature, high pressure gas
High temperature, high pressure liquid
Low temperature, low pressure
Fan
Electronic expansion valve
Electronic expansion valve
Filter
Filter
Indoor unit
Electronic expansion valve
Filter
Filter
Indoor unit
Filter
Filter
Indoor unit
Thermostat "ON"
Thermostat "OFF"
Heat
exchanger pipe
Capillary
tube
Filter
Filter
Check
valve
Receiver
Solenoid
valve
Filter
Electronic
expansion valve
Filter
Pressure
regulating
valve
Electronic
expansion
valve
Check
valve
Fan
Solenoid
valve
Check
valve
Heat exchanger
Four way
valve
Check
valve
Capillary
tube
Filter
Capillary tube
Compressor
INV
Filter
Capillary tube
High pressure
switch
Oil
separator
Solenoid
valve
Check
valve
Filter
Oil
separator
Filter
Oil
separator
High pressure
switch
Filter
Check
valve
Check
valve
Filter
Filter
High pressure Pressure
regulating
sensor
valve
High pressure
switch
Compressor
STD2
Compressor
STD1
Capillary
tube
Filter
Low pressure
sensor
Check valve
Solenoid
valve
Filter
Stop valve (With service port on on-site piping side ø7.9mm flare connection)
Refirgerant Circuit
S
Oil equalizing pipe to other outdoor units
S
Liquid piping to other outdoor units
S
Gas piping to other outdoor units
4D044809
: http://splitoff.ru/tehn-doc.html
71
Refrigerant Flow for Each Operation Mode
72
SiE39-404
: http://splitoff.ru/tehn-doc.html
Refirgerant Circuit
SiE39-404
Part 4
Function
1. Function general ...................................................................................74
1.1 Symbol ...................................................................................................74
1.2 Operation Mode......................................................................................75
2. Basic Control.........................................................................................76
2.1
2.2
2.3
2.4
Normal Operation ...................................................................................76
Compressor PI Control...........................................................................77
Electronic Expansion Valve PI Control...................................................83
Cooling Operation Fan Control...............................................................84
3. Special Control......................................................................................85
3.1
3.2
3.3
3.4
3.5
3.6
3.7
Startup Control .......................................................................................85
Oil Return Operation ..............................................................................86
Defrosting Operation ..............................................................................88
Pump-down Residual Operation ............................................................89
Restart Standby......................................................................................90
Stopping Operation ................................................................................91
Pressure Equalization prior to Startup....................................................93
4. Protection Control .................................................................................94
4.1
4.2
4.3
4.4
4.5
High Pressure Protection Control...........................................................94
Low Pressure Protection Control............................................................95
Discharge Pipe Protection Control .........................................................96
Inverter Protection Control .....................................................................97
STD Compressor Overload Protection...................................................98
5. Other Control.........................................................................................99
5.1
5.2
5.3
5.4
Outdoor Unit Rotation.............................................................................99
Emergency Operation ..........................................................................100
Demand Operation ...............................................................................102
Heating operation prohibition ...............................................................102
6. Outline of Control (Indoor Unit) ...........................................................103
6.1
6.2
6.3
6.4
6.5
Function
Drain Pump Control..............................................................................103
Louver Control for Preventing Ceiling Dirt............................................105
Thermostat Sensor in Remote Controller.............................................106
Freeze Prevention ................................................................................108
Control of outdoor air Processing unit
(Unique Control for Outdoor Air Treatment) .........................................109
: http://splitoff.ru/tehn-doc.html
73
Function general
SiE39-404
1. Function general
1.1
Symbol
Symbol
Electric symbol
Description or function
20S1
Y1R
Four way valve (Energize during heating)
DSH
–
Discharge pie superheat
DSHi
–
Discharge pie superheat of inverter compressor
DSHs
–
Discharge pie superheat of standard compressor
EV
–
Opening of electronic expansion valve
EV1
Y1E
Electronic expansion valve for main heat exchanger
EV2
Y2E
Electronic expansion valve for sub-coolig heat exchanger
HTDi
–
Value of INV compressor discharge pie temperature (R31T) compensated with
outdoor air temperature
HTDs
–
Value of STD compressor discharge pie temperature (R32T, R33T) compensated with
outdoor air temperature
Pc
S1NPH
Value detected by high pressure sensor
Pe
S1NPL
Value detected by low pressure sensor
SH
–
Evaporator outlet superheat
SHS
–
Target evaporator outlet superheat
SVG
Y3S
Solenoid valve for discharging gas from receiver
SVO
Y2S
Solenoid valve for oil equalizing
SVP
Y1S
Solenoid valve for hot gas bypass
SVSL
Y4S
Solenoid valve for non-operating unit liquid pipe closing
Tb
R4T
Heat exchanger outlet temperature at cooling
Tc
–
High pressure equivalent saturation temperature
TcS
–
Target temperature of Tc
Te
–
Low pressure equivalent saturation temperature
TeS
–
Target temperature of Te
Tfin
R1T
Inverter fin temperature
Ts
R2T
Suction pie temperature detected by R2T
Tsh
R5T
Temperature detected by R5T
Tp
–
Calculated value of compressor port temperature
74
: http://splitoff.ru/tehn-doc.html
Function
SiE39-404
1.2
Function general
Operation Mode
Operation in
stop mode
Indoor unit stop or
thermostat OFF
Indoor unit thermostat ON
Malfunction/Standby
Restart standby
(Compressor stop)
Pressure
equalization
prior to startup
Malfunction/
Standby
Indoor unit stop or
thermostat OFF
Startup control
• Cooling startup
control
• Heating startup
control
Indoor unit thermostat ON
Pump-down
residual
operation
Malfunction/Standby
Outdoor unit
rotation
Indoor unit stop or
thermostat OFF
Normal operation
• Compressor PI control
• Motorized valve PI control
• Protection control
Cooling or heating
operation
Malfunction/
Standby
Oil return IN
conditions are met.
Yes
Oil return operation
No
Outdoor unit
rotation
Defrost IN
conditions are met.
Yes
Defrosting operation
No
Temperature
control change
No
Function
Yes
*)
In the event indoor unit stops or the thermostat
turns OFF while in oil return operation or
defrosting operation, pump-down residual
operation is performed on completion of the oil
return operation or defrosting operation.
: http://splitoff.ru/tehn-doc.html
75
Basic Control
SiE39-404
2. Basic Control
2.1
Normal Operation
! Cooling Operation
Actuator
Operation
Compressor
Compressor PI control
Outdoor unit fan
Four way valve
Main motorized valve (EV1)
Subcooling motorized valve (EV2)
Cooling fan control
OFF
1400 pls
PI control
Hot gas bypass valve (SVP)
OFF
Oil equalization valve (SVO)
ON
Receiver gas discharging valve (SVG)
OFF
Non-operating unit liquid pipe stop valve ON
(SVSL)
! Heating Operation
Actuator
⎯
Operation
Compressor
Compressor PI control
Outdoor unit fan
Four way valve
Main motorized valve (EV1)
Subcooling motorized valve (EV2)
STEP8 or 9
ON
PI control
0 pls
Hot gas bypass valve (SVP)
OFF
Oil equalization valve (SVO)
ON
Receiver gas discharging valve (SVG)
OFF
Non-operating unit liquid pipe stop valve ON
(SVSL)
Remarks
Used for high pressure protection control, low
pressure protection control, discharge pipe
temperature protection control, and compressor
operating frequency upper limit control with inverter
protection control.
⎯
⎯
⎯
⎯
This valve turns on with low pressure protection
control.
In the case of multi-outdoor-unit system, this valve
repeats ON/OFF operation at regular intervals of
time.
⎯
Remarks
Used for high pressure protection control, low
pressure protection control, discharge pipe
temperature protection control, and compressor
operating frequency upper limit control with inverter
protection control.
⎯
⎯
⎯
⎯
This valve turns on with low pressure protection
control.
In the case of multi-outdoor-unit system, this valve
repeats ON/OFF operation at regular intervals of
time.
⎯
⎯
HHeating operation is not functional at an outdoor air temperature of 24°C or more.
76
: http://splitoff.ru/tehn-doc.html
Function
SiE39-404
2.2
Basic Control
Compressor PI Control
Compressor PI Control
Carries out the compressor capacity PI control to maintain Te at constant during cooling
operation and Tc at constant during heating operation to ensure stable unit performance.
[Cooling operation]
Controls compressor capacity to adjust Te to
achieve target value (TeS).
Te setting
L
M (Normal)
H
(factory
setting)
3
6
9
Te : Low pressure equivalent saturation temperature
(°C)
TeS : Target Te value
(Varies depending on Te setting, operating
frequency, etc.)
[Heating operation]
Controls compressor capacity to adjust Tc to
achieve target value (TcS).
Tc setting
L
M (Normal)
H
(factory
setting)
43
46
49
Function
Tc : High pressure equivalent saturation temperature
(°C)
TcS : Target Tc value
(Varies depending on Tc setting, operating
frequency, etc.)
: http://splitoff.ru/tehn-doc.html
77
Basic Control
SiE39-404
! Compressor Operating Priority
Each compressor operates in the following order of priority.
In the case of multi-outdoor-unit system, each compressor operates in any of Pattern 1
through Pattern 3 according to the rotation of outdoor units.
Pattern 1
Pattern 2
RXYQ5M
INV: Inverter compressor
STD1: Standard compressor 1
STD2: Standard compressor 2
Pattern 3
RXYQ8,10,12M
RXYQ14,16M
No. 1
No. 1 No. 2
No. 1 No. 2 No. 3
INV
INV
INV
RXYQ18,20,22M
STD1
RXYQ24,26,28M
STD1 STD2
RXYQ30,32M
No. 1 No. 3
No. 2 No. 4
No. 1 No. 3
No. 2 No. 4 No. 5
No. 1 No. 3 No. 5
No. 2 No. 4 No. 6
No. 2 No. 4
No. 1 No. 3
No. 2 No. 4
No. 1 No. 3 No. 5
No. 2 No. 4 No. 6
No. 1 No. 3 No. 5
INV
INV
INV
INV
INV
INV
STD1
STD1
STD1
RXYQ34,36,38M
STD1 STD2
STD1 STD2
STD1 STD2
RXYQ40,42,44M
No. 1
No. 4
No. 2
No. 5
No. 3 No. 6 No. 7
No. 1 No. 4
No. 2 No. 5 No. 7
No. 3 No. 6 No. 8
No. 3
No. 6
No. 1
No. 4
No. 2 No. 5 No. 7
No. 3 No. 6
No. 1 No. 4 No. 7
No. 2 No. 5 No. 8
No. 2
No. 5
No. 3
No. 6
No. 1 No. 4 No. 7
No. 2 No. 5
No. 3 No. 6 No. 8
No. 1 No. 4 No. 7
INV
INV
INV
INV
INV
STD1
INV
STD1
STD1 STD2
STD1
STD1 STD2
STD1 STD2
RXYQ46,48M
No. 1
No. 4 No. 7
No. 2
No. 5 No. 8
No. 3 No. 6 No. 9
No. 3
No. 6 No. 9
No. 1
No. 4 No. 7
No. 2 No. 5 No. 8
No. 2
No. 5 No. 8
No. 3
No. 6 No. 9
No. 1 No. 4 No. 7
INV
STD1 STD2
INV
STD1 STD2
INV
STD1 STD2
*
• In the case of combination of 3 outdoor units, the above diagram shows master unit, slave unit 1, and slave unit 2
from left to right.
• Compressors may operate in any pattern other than those mentioned above according to the operating status.
78
: http://splitoff.ru/tehn-doc.html
Function
SiE39-404
Basic Control
RXYQ5M
STEP
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
RXYQ8,10,12M
INV
52Hz
57Hz
62Hz
68Hz
74Hz
81Hz
88Hz
96Hz
104Hz
110Hz
116Hz
124Hz
133Hz
143Hz
158Hz
165Hz
177Hz
189Hz
202Hz
210Hz
STEP
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
INV
52Hz
57Hz
62Hz
68Hz
74Hz
81Hz
88Hz
96Hz
104Hz
110Hz
116Hz
124Hz
133Hz
143Hz
158Hz
165Hz
177Hz
189Hz
202Hz
210Hz
52Hz
74Hz
96Hz
116Hz
133Hz
158Hz
177Hz
202Hz
210Hz
RXYQ14,16M
STD1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
STEP
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35*
INV
52Hz
57Hz
62Hz
68Hz
74Hz
81Hz
88Hz
96Hz
104Hz
110Hz
116Hz
124Hz
133Hz
143Hz
158Hz
165Hz
177Hz
189Hz
202Hz
210Hz
52Hz
74Hz
96Hz
116Hz
133Hz
158Hz
177Hz
202Hz
210Hz
52Hz
88Hz
124Hz
158Hz
189Hz
210Hz
STD1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
STD2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
∗)Available only on 50Hz
RXYQ18,20,22M
STEP
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
Master unit
INV
52Hz
57Hz
62Hz
68Hz
74Hz
81Hz
88Hz
96Hz
104Hz
110Hz
116Hz
124Hz
133Hz
143Hz
158Hz
165Hz
177Hz
189Hz
202Hz
210Hz
52Hz
74Hz
96Hz
116Hz
133Hz
158Hz
177Hz
202Hz
210Hz
52Hz
88Hz
124Hz
158Hz
189Hz
210Hz
52Hz
88Hz
124Hz
158Hz
189Hz
210Hz
210Hz
RXYQ24,26,28M
Slave unit
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
210Hz
STD unit
No.1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
STD unit
No.2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
STEP
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
Master unit
INV
52Hz
57Hz
62Hz
68Hz
74Hz
81Hz
88Hz
96Hz
104Hz
110Hz
116Hz
124Hz
133Hz
143Hz
158Hz
165Hz
177Hz
189Hz
202Hz
210Hz
52Hz
74Hz
96Hz
116Hz
133Hz
158Hz
177Hz
202Hz
210Hz
52Hz
88Hz
124Hz
158Hz
189Hz
210Hz
52Hz
88Hz
124Hz
158Hz
189Hz
210Hz
52Hz
104Hz
143Hz
189Hz
210Hz
210Hz
Slave unit
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
210Hz
STD unit
No.1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
STD unit
No.2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
STD unit
No.3
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
∗
• Compressors are operated in the order of descending priorities.
• Compressors may operate in a pattern other than those listed in above tables subject to the operating conditions.
• “Master unit”, and “slave unit” in this section are the names for control, and they will be transferred according to the
priority of rotation system.
Function
: http://splitoff.ru/tehn-doc.html
79
Basic Control
SiE39-404
RXYQ30,32M
STEP
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
Master
unit
INV
52Hz
57Hz
62Hz
68Hz
74Hz
81Hz
88Hz
96Hz
104Hz
110Hz
116Hz
124Hz
133Hz
143Hz
158Hz
165Hz
177Hz
189Hz
202Hz
210Hz
52Hz
74Hz
96Hz
116Hz
133Hz
158Hz
177Hz
202Hz
210Hz
52Hz
88Hz
124Hz
158Hz
189Hz
210Hz
52Hz
88Hz
124Hz
158Hz
189Hz
210Hz
52Hz
104Hz
143Hz
189Hz
210Hz
52Hz
104Hz
143Hz
189Hz
210Hz
210Hz
RXYQ34,36,38M
Slave
unit
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
210Hz
STD
unit
No.1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
STD
unit
No.2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
STD
unit
No.3
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
STD
unit
No.4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
STEP
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
Master
unit
INV
52Hz
57Hz
62Hz
68Hz
74Hz
81Hz
88Hz
96Hz
104Hz
110Hz
116Hz
124Hz
133Hz
143Hz
158Hz
165Hz
177Hz
189Hz
202Hz
210Hz
52Hz
74Hz
96Hz
116Hz
133Hz
158Hz
177Hz
202Hz
210Hz
52Hz
88Hz
124Hz
158Hz
189Hz
210Hz
52Hz
88Hz
124Hz
158Hz
189Hz
210Hz
52Hz
104Hz
143Hz
189Hz
210Hz
52Hz
104Hz
143Hz
189Hz
210Hz
52Hz
104Hz
143Hz
189Hz
210Hz
210Hz
Slave
unit1
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
210Hz
Slave
unit2
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
210Hz
STD
unit
No.1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
STD
unit
No.2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
STD
unit
No.3
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
STD
unit
No.4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
∗
• Compressors are operated in the order of descending priorities.
• Compressors may operate in a pattern other than those listed in above tables subject to the operating conditions.
• “Master unit”, and “slave unit” in this section are the names for control, and they will be transferred according to the
priority of rotation system.
80
: http://splitoff.ru/tehn-doc.html
Function
SiE39-404
Basic Control
RXYQ40,42,44M
STEP
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
Master unit INV Slave unit1 INV Slave unit2 INV
52Hz
OFF
OFF
57Hz
OFF
OFF
62Hz
OFF
OFF
68Hz
OFF
OFF
74Hz
OFF
OFF
81Hz
OFF
OFF
88Hz
OFF
OFF
96Hz
OFF
OFF
104Hz
OFF
OFF
110Hz
OFF
OFF
116Hz
OFF
OFF
124Hz
OFF
OFF
133Hz
OFF
OFF
143Hz
OFF
OFF
158Hz
OFF
OFF
165Hz
OFF
OFF
177Hz
OFF
OFF
189Hz
OFF
OFF
202Hz
OFF
OFF
210Hz
OFF
OFF
52Hz
189Hz
OFF
74Hz
189Hz
OFF
96Hz
189Hz
OFF
116Hz
189Hz
OFF
133Hz
189Hz
OFF
158Hz
189Hz
OFF
177Hz
189Hz
OFF
202Hz
189Hz
OFF
210Hz
189Hz
OFF
52Hz
189Hz
189Hz
88Hz
189Hz
189Hz
124Hz
189Hz
189Hz
158Hz
189Hz
189Hz
189Hz
189Hz
189Hz
210Hz
189Hz
189Hz
52Hz
189Hz
189Hz
88Hz
189Hz
189Hz
124Hz
189Hz
189Hz
158Hz
189Hz
189Hz
189Hz
189Hz
189Hz
210Hz
189Hz
189Hz
52Hz
189Hz
189Hz
104Hz
189Hz
189Hz
143Hz
189Hz
189Hz
189Hz
189Hz
189Hz
210Hz
189Hz
189Hz
52Hz
189Hz
189Hz
104Hz
189Hz
189Hz
143Hz
189Hz
189Hz
189Hz
189Hz
189Hz
210Hz
189Hz
189Hz
52Hz
189Hz
189Hz
104Hz
189Hz
189Hz
143Hz
189Hz
189Hz
189Hz
189Hz
189Hz
210Hz
189Hz
189Hz
52Hz
189Hz
189Hz
104Hz
189Hz
189Hz
143Hz
189Hz
189Hz
189Hz
189Hz
189Hz
210Hz
189Hz
189Hz
210Hz
210Hz
210Hz
STD unit No.1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
STD unit No.2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
STD unit No.3
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
STD unit No.4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
STD unit No.5
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
∗
• Compressors are operated in the order of descending priorities.
• Compressors may operate in a pattern other than those listed in above tables subject to on the operating
conditions.
• “Master unit”, “slave unit 1” and “slave unit 2” in this section are the names for control, and they will be transferred
according to the priority of rotation system.
Function
: http://splitoff.ru/tehn-doc.html
81
Basic Control
SiE39-404
RXYQ46,48M
STEP
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67∗
Master unit
INV
52Hz
57Hz
62Hz
68Hz
74Hz
81Hz
88Hz
96Hz
104Hz
110Hz
116Hz
124Hz
133Hz
143Hz
158Hz
165Hz
177Hz
189Hz
202Hz
210Hz
52Hz
74Hz
96Hz
116Hz
133Hz
158Hz
177Hz
202Hz
210Hz
52Hz
88Hz
124Hz
158Hz
189Hz
210Hz
52Hz
88Hz
124Hz
158Hz
189Hz
210Hz
52Hz
104Hz
143Hz
189Hz
210Hz
52Hz
104Hz
143Hz
189Hz
210Hz
52Hz
104Hz
143Hz
189Hz
210Hz
52Hz
104Hz
143Hz
189Hz
210Hz
52Hz
104Hz
143Hz
189Hz
210Hz
210Hz
∗) Only for 50Hz
Slave unit1
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
210Hz
Slave unit2
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
189Hz
210Hz
STD unit No.1
STD unit No.2
STD unit No.3
STD unit No.4
STD unit No.5
STD unit No.6
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
∗
• Compressors are operated in the order of descending priorities.
• Compressors may operate in a pattern other than those listed in above tables subject to on the operating
conditions.
• “Master unit”, “slave unit 1” and “slave unit 2” in this section are the names for control, and they will be transferred
according to the priority of rotation system.
82
: http://splitoff.ru/tehn-doc.html
Function
SiE39-404
2.3
Basic Control
Electronic Expansion Valve PI Control
Main Motorized Valve EV1 Control
Carries out the motorized valve (Y1E) PI control to maintain the evaporator outlet superheated
degree (SH) at constant during heating operation to make maximum use of the outdoor unit
heat exchanger (evaporator).
SH = Ts - Te
SH : Evaporator outlet superheated degree (°C)
Ts : Suction pipe temperature detected by thermistor
R2T (°C)
Te : Low pressure equivalent saturation temperature
(°C)
The optimum initial value of the evaporator outlet superheated degree is 5°C, but varies
depending on the discharge pipe superheated degree of inverter compressor.
Subcooling Motorized Valve EV2 Control
Makes PI control of the motorized valve (Y2E) to keep the superheated degree of the outlet gas
pipe on the evaporator side for the full use of the subcooling heat exchanger.
SH = Tsh -Te
SH : Outlet superheated degree of evaporator (°C)
Tsh : Suction pipe temperature detected with the
thermistor R5T (°C)
Te : Low pressure equivalent saturation temperature
(°C)
Function
: http://splitoff.ru/tehn-doc.html
83
Basic Control
2.4
SiE39-404
Cooling Operation Fan Control
In cooling operation with low outdoor air temperature, this control is used to provide the
adequate amount of circulation air with liquid pressure secured by high pressure control using
outdoor unit fan.
STEP9
Pc<2.8MPa
Pc: HP pressure sensor detection value
Pc>3.3MPa
STEP8-1
Pc>3.1MPa
Pc<2.7MPa
Pc>3.2MPa
STEP8-2
Pc<1.8MPa
Pc>2.7MPa
Fan Steps
STEP7
Pc<1.8MPa
RXYQ5M
Pc>2.7MPa
STEP6
Pc<1.8MPa
Pc>2.7MPa
STEP1
STEP2
STEP3
STEP4
STEP5
STEP6
STEP7
STEP8-2
STEP8-1
STEP9
0rpm
300rpm
320rpm
350rpm
385rpm
470rpm
585rpm
800rpm
800rpm
840rpm
RXYQ
8 and 10M
0rpm
300rpm
320rpm
345rpm
385rpm
465rpm
575rpm
660rpm
785rpm
825rpm
RXYQ
12 to 16M
0rpm
300rpm
325rpm
355rpm
400rpm
500rpm
630rpm
710rpm
880rpm
920rpm
STEP5
Pc<1.8MPa
Pc>2.7MPa
STEP4
Pc<1.8MPa
Pc>2.7MPa
STEP3
Pc<1.8MPa
Pc>2.7MPa
STEP2
Pc<2.3MPa
Pc>2.7MPa
STEP1
84
: http://splitoff.ru/tehn-doc.html
Function
SiE39-404
Special Control
3. Special Control
3.1
Startup Control
3.1.1 Startup Control in Cooling Operation
Actuator
Operation
Remarks
Differential pressure control
Compressor operating frequency
increases by 1 step / 20 sec until
Pc - Pe>0.4 MPa.
Outdoor unit fan
High pressure control
Initial compressor operating frequency
is set to STEP 1.
1-step increase with Pc>2.2 MPa
1-step decrease with Pc<1.8 MPa
Four way valve
OFF
⎯
Main motorized valve (EV1)
1400 pls
⎯
Subcooling motorized valve (EV2)
0 pls
⎯
Hot gas bypass valve (SVP)
ON
⎯
Oil equalization valve (SVO)
ON
In the case of multi-outdoor-unit
system, this valve repeats ON/OFF
operation at regular intervals of time to
equalize the oil level of each outdoor
unit.
Receiver gas discharging valve (SVG)
OFF
⎯
Non-operating unit liquid pipe stop
valve (SVSL)
ON
⎯
Ending conditions
or
Compressor
• 200 sec.
• Pc - Pe>0.4 MPa
∗ In the case of multi-outdoor-unit system, both master and slave units perform the operations listed in the table
above.
∗ Actuators are based on RXYQ16M.
3.1.2 Startup Control in Heating Operation
Actuator
Operation
Remarks
Compressor
Differential pressure control
Compressor operating frequency
increases by 1 step / 20 sec until
Pc - Pe>0.4 MPa.
Outdoor unit fan
STEP9
⎯
Four way valve
ON
⎯
Main motorized valve (EV1)
200 pls
⎯
Subcooling motorized valve (EV2)
0 pls
⎯
Hot gas bypass valve (SVP)
ON
⎯
Oil equalization valve (SVO)
ON
In the case of multi-outdoor-unit
system, this valve repeats ON/OFF
operation at regular intervals of time to
equalize the oil level of each outdoor
unit.
Receiver gas discharging valve (SVG)
OFF
⎯
Non-operating unit liquid pipe stop
valve (SVSL)
ON
⎯
Ending conditions
or
• 200 sec.
• Pc - Pe>0.4 MPa
∗ In the case of multi-outdoor-unit system, both master and slave units perform the operations listed in the table
above.
∗ Actuators are based on RXYQ16M.
Function
: http://splitoff.ru/tehn-doc.html
85
Special Control
3.2
SiE39-404
Oil Return Operation
3.2.1 Oil Return Operation in Cooling Operation
Outdoor unit actuator
Oil return preparation
operation
Oil return operation
Post-oil-return operation
Compressor
Upper limit control
124 Hz + ON + OFF
52 Hz + OFF + OFF
Outdoor unit fan
Fan control
Fan control
Fan control
Four way valve
OFF
OFF
OFF
Main motorized valve (EV1)
1400 pls
1400 pls
1400 pls
Subcooling motorized valve (EV2)
SH control
0 pls
0 pls
Hot gas bypass valve (SVP)
OFF
ON
ON
Oil equalization valve (SVO)
ON
ON
ON
Receiver gas discharging valve
(SVG)
OFF
OFF
OFF
Non-operating unit liquid pipe stop
valve (SVSL)
ON
ON
ON
Ending conditions
2 min.
or
• 6 min.
• Ts - Te<5
10 sec.
* In the case of multi-outdoor-unit system,
Master unit: Performs the operations listed in the table above.
Slave units: Operating units perform the operations listed in the table above.
Non-operating units perform the operations listed in the table above from the oil return operation.
(Non-operating unit stops during “oil return preparation operation”.)
* Actuators are based on RXYQ16M.
Indoor unit actuator
Fan
Electronic expansion valve
86
Cooling oil return operation
Thermostat ON unit
Set Air Volume
Stopping unit
OFF
Thermostat OFF unit
OFF
Thermostat ON unit
Normal opening
Stopping unit
200 pls
Thermostat OFF unit
200 pls
: http://splitoff.ru/tehn-doc.html
Function
SiE39-404
Special Control
3.2.2 Oil Return Operation in Heating Operation
Outdoor Unit Actuator
Oil return preparation
operation
Oil return operation
Post-oil-return operation
Compressor
Upper limit control
124 Hz + ON + OFF
1-step increase from
(74 Hz + OFF + OFF) to
(Pc - Pe>0.4 MPa) time
Outdoor unit fan
STEP8
or
STEP9
OFF
STEP9
Four way valve
ON
OFF
ON
Main motorized valve (EV1)
SH control
1400 pls
180 pls
Subcooling motorized valve (EV2)
0 pls
0 pls
0 pls
Hot gas bypass valve (SVP)
OFF
ON
ON
Oil equalization valve (SVO)
ON
ON
ON
Receiver gas discharging valve
(SVG)
OFF
OFF
OFF
Non-operating unit liquid pipe stop
valve (SVSL)
ON
ON
ON
Ending conditions
2 min.
or
• 6 min.
• Ts - Te<5
or
• 160 sec.
• Pc - Pe>0.4MPa
* In the case of multi-outdoor-unit system,
Master unit: Performs the operations listed in the table above.
Slave units: Operating units perform the operations listed in the table above.
Non-operating units perform the operations listed in the table above from the oil return operation.
(Non-operating unit stops during “oil return preparation operation”.)
* Actuators are based on RXYQ16M.
Indoor unit actuator
Fan
Electronic expansion valve
Heating oil return operation
Thermostat ON unit
OFF
Stopping unit
OFF
Thermostat OFF unit
OFF
Thermostat ON unit
512 pls
Stopping unit
512 pls
Thermostat OFF unit
512 pls
<In condition of oil return operation>
Compressor cumulative operation time > 8 hours
(However, 2 hours after turning power on first time.)
Function
: http://splitoff.ru/tehn-doc.html
87
Special Control
3.3
SiE39-404
Defrosting Operation
Defrost preparation
operation
Outdoor unit actuator
Defrost operation
Post Defrost operation
Compressor
Upper limit control
143 Hz + ON + ON
1-step increase from
(74 Hz + OFF + OFF) to
(Pc - Pe>0.4 MPa)
Outdoor unit fan
STEP8
or
STEP9
OFF
STEP9
Four way valve
ON
OFF
ON
Main motorized valve (EV1)
SH control
1400 pls
200 pls
Subcooling motorized valve (EV2)
0 pls
0 pls
0 pls
Hot gas bypass valve (SVP)
OFF
ON
ON
Oil equalization valve (SVO)
ON
ON
ON
Receiver gas discharging valve
(SVG)
OFF
OFF
OFF
Non-operating unit liquid pipe stop
valve (SVSL)
ON
ON
ON
Ending conditions
2 min.
or
• 12 min.
• Ts >11°C
or
• 160 sec.
• Pc - Pe>0.4MPa
* In the case of multi-outdoor-unit system,
Master unit: Performs the operations listed in the table above.
Slave units: Operating units perform the operations listed in the table above.
Non-operating units perform the operations listed in the table above from the Defrost operation.
(Non-operating unit stops during “Defrost preparation operation”.)
* Actuators are based on RXYQ16M.
Indoor unit actuator
Fan
Electronic expansion valve
During defrost
Thermostat ON unit
OFF
Stopping unit
OFF
Thermostat OFF unit
OFF
Thermostat ON unit
512 pls
Stopping unit
512 pls
Thermostat OFF unit
512 pls
<Defrost starting condition>
Defrost operation is started when the outdoor heat exchanger temperature becomes lower than deicer temperature.
Defrost operation is conducted once in max. 2 hours.
88
: http://splitoff.ru/tehn-doc.html
Function
SiE39-404
3.4
Special Control
Pump-down Residual Operation
3.4.1 Pump-down Residual Operation in Cooling Operation
Actuator
Master unit operation
Slave unit operation
Compressor
210 Hz + OFF + OFF
OFF
Outdoor unit fan
Fan control
OFF
Four way valve
OFF
OFF
Main motorized valve (EV1)
1400 pls
0 pls
Subcooling motorized valve (EV2)
0 pls
0 pls
Hot gas bypass valve (SVP)
ON
OFF
Oil equalization valve (SVO)
ON
OFF
Receiver gas discharging valve (SVG)
ON
ON
Non-operating unit liquid pipe stop
valve (SVSL)
ON
ON
Ending conditions
or
• 5 min.
• Pe<0.5 MPa
• Td>110°C
* Actuators are based on RXYQ16M.
3.4.2 Pump-down Residual Operation in Heating Operation
Actuator
Master unit operation
Slave unit operation
Compressor
124 Hz + OFF + OFF
OFF
Outdoor unit fan
STEP8
STEP5
Four way valve
ON
ON
Main motorized valve (EV1)
0 pls
0 pls
Subcooling motorized valve (EV2)
0 pls
0 pls
Hot gas bypass valve (SVP)
ON
OFF
Oil equalization valve (SVO)
ON
OFF
Receiver gas discharging valve (SVG)
ON
ON
Non-operating unit liquid pipe stop
valve (SVSL)
ON
ON
Ending conditions
or
• 30 sec.
• Pe<0.25 MPa
• Td>110°C
* Actuators are based on RXYQ16M.
Function
: http://splitoff.ru/tehn-doc.html
89
Special Control
3.5
SiE39-404
Restart Standby
Actuator
Operation
Remarks
Compressor
OFF
⎯
Outdoor unit fan
Ta>30°C: STEP5
Ta≤30°C: OFF
⎯
Four way valve
Holds ON
⎯
Main motorized valve (EV1)
0 pls
⎯
Subcooling motorized valve (EV2)
0 pls
⎯
Hot gas bypass valve (SVP)
OFF
In the case of RXYQ5M , this valve
turns ON.
Oil equalization valve (SVO)
ON
In the case of slave units, this valve
turns OFF.
Receiver gas discharging valve (SVG)
OFF
⎯
Non-operating unit liquid pipe stop
valve (SVSL)
ON
⎯
Ending conditions
5 min.
⎯
* Actuators are based on RXYQ16M.
90
: http://splitoff.ru/tehn-doc.html
Function
SiE39-404
3.6
Special Control
Stopping Operation
3.6.1 When System is in Stop Mode
Actuator
Operation
Compressor
OFF
Outdoor unit fan
OFF
Four way valve
Holds ON
Main motorized valve (EV1)
0 pls
Subcooling motorized valve (EV2)
0 pls
Hot gas bypass valve (SVP)
OFF
Oil equalization valve (SVO)
OFF
Receiver gas discharging valve (SVG)
OFF
Non-operating unit liquid pipe stop valve (SVSL)
ON
Ending conditions
Indoor unit thermostat is turned ON.
* Actuators are based on RXYQ16M.
Function
: http://splitoff.ru/tehn-doc.html
91
Special Control
SiE39-404
3.6.2 Stopping Operation of Slave Units During Master Unit is in Operation
With Multi-Outdoor-Unit System
In cooling operation: The system operates in Mode A or Mode B listed in the table below.
Actuator
Mode-A operation
Mode-B operation
Compressor
OFF
OFF
Outdoor unit fan
STEP4
OFF
Four way valve
OFF
Holds ON
Main motorized valve (EV1)
150 pls to 300 pls
0 pls
Subcooling motorized valve (EV2)
0 pls
0 pls
Hot gas bypass valve (SVP)
ON
ON
Oil equalization valve (SVO)
OFF
OFF
Receiver gas discharging valve
(SVG)
OFF
OFF
Non-operating unit liquid pipe stop
valve (SVSL)
OFF
ON
Mode transition conditions
To Mode B when Tc-Tl >0.27×(Tc - Ta) +6
To Mode A when gas shortage signal
is sent from indoor unit
Ending conditions
Slave units are required to operate.
In heating operation: The system operates in Mode A or Mode B listed in the table below.
Actuator
Mode-A operation
Mode-B operation
Compressor
OFF
OFF
Outdoor unit fan
STEP2
STEP2
Four way valve
ON
ON
Main motorized valve (EV1)
0 pls
0 pls
Subcooling motorized valve (EV2)
0 pls
0 pls
Hot gas bypass valve (SVP)
OFF
OFF
Oil equalization valve (SVO)
OFF
OFF
Receiver gas discharging valve
(SVG)
OFF
OFF
Non-operating unit liquid pipe stop
valve (SVSL)
OFF
ON
Mode transition conditions
To Mode B when Tc-mean temperature of
indoor unit liquid pipes>10°C
To Mode A when motorized valve of
operating outdoor unit fully opens.
Ending conditions
Slave units are required to operate.
∗ Mode A or B operation
Operating
unit
Stopping
unit
⎧ Mode A : Operating unit collects refrigerant.
⎨
⎩ Mode B : Stopping unit storage refrigerant.
The changeover operation for mode A and B is performed for the reason that the required refrigerant amount varies
depending on the indoor unit operation capacity.
92
: http://splitoff.ru/tehn-doc.html
Function
SiE39-404
3.7
Special Control
Pressure Equalization prior to Startup
Actuator
Operation
Remarks
Compressor
OFF
—
Outdoor unit fan
Cooling:OFF
Heating:STEP 4
—
Four way valve
Holds ON
—
Main motorized valve (EV1)
0 pls
—
Subcooling motorized valve (EV2)
0 pls
—
Hot gas bypass valve (SVP)
OFF
In the case of RXYQ5M, this valve turns ON.
Oil equalization valve (SVO)
OFF
—
Receiver gas discharging valve
(SVG)
OFF
—
Non-operating unit liquid pipe stop
valve (SVSL)
OFF
—
Ending conditions
10 sec.
In the case of RXYQ5M, 3 min. or Pc-Pe<0.2
MPa
Function
: http://splitoff.ru/tehn-doc.html
93
Protection Control
SiE39-404
4. Protection Control
4.1
High Pressure Protection Control
This high pressure protection control is used to prevent the activation of protection devices due
to abnormal increase of high pressure and to protect compressors against the transient
increase of high pressure.
[In cooling operation]
H
In the case of multi-outdoor-unit system, each outdoor unit performs this control
individually in the following sequence.
High pressure not limited
Pc: HP pressure sensor detection
value for each outdoor unit
Pc>3.48MPa
INV upper limit frequency :
3-step / 10 sec down from
current compressor frequency
INV upper limit frequency = 210 Hz
Pc>3.48MPa
Pc<3.2MPa
High pressure limited
Pc>3.53MPa
INV upper limit frequency:
1-step / 20 sec up from
current compressor frequency
Pc>3.58MPa
STD compressor
standby for 5 mins
High pressure standby
When occurring 3 times within
30 min., HPS is activated without high
pressure standby, thus outputting the
malfunction code “E3”.
[In heating operation]
H
In the case of multi-outdoor-unit system, the entire system performs this control in the
following sequence.
High pressure not limited
Pc: HP pressure sensor detection
value for master unit
Pc>3.38MPa
Pc<3.0MPa
Lower-priority compressor stops.
Pc>3.38MPa
High pressure limited
Pc>3.49MPa
Master unit: 52 Hz+OFF+OFF
Slave unit: All units stop.
Pc>3.58MPa
High pressure standby
94
When occurring 3 times within
30 min., HPS is activated without high
pressure standby, thus outputting the
malfunction code “E3”
: http://splitoff.ru/tehn-doc.html
Function
SiE39-404
4.2
Protection Control
Low Pressure Protection Control
This low pressure protection control is used to protect compressors against the transient
decrease of low pressure.
[In cooling operation]
H
In the case of multi-outdoor-unit system, the entire system performs this control in the
following sequence.
Low pressure not limited
Pe: LP pressure sensor detection
value for master unit
Pe >0.40MPa
Pe <0.35MPa
Low pressure limited
All STD compressors
stop.
Pe <0.25MPa
Master unit:52 Hz+OFF+OFF
Slave unit:Stop
Pe <0.07MPa
When occurring 3 times within 30 min.,
the malfunction code “E4” is output.
Low pressure standby
[In heating operation]
H
In the case of multi-outdoor-unit system, each outdoor unit performs this control
individually in the following sequence.
Low pressure not limited
Pe: LP pressure sensor detection
value for each outdoor unit
Pe <0.16 MPa
&
124 Hz + OFF + OFF
Pe >0.25 MPa
INV upper limit frequency = 210 Hz
Pe <0.16 MPa
Low pressure limited
Pe >0.19 MPa
Pe <0.13 MPa
52 Hz + OFF + OFF
Pe <0.07 MPa
Low pressure standby
Function
INV upper limit frequency: 1-step /
20 sec up from current compressor
frequency
When occurring 3 times within 30 min.,
the malfunction code “E4” is output.
: http://splitoff.ru/tehn-doc.html
95
Protection Control
4.3
SiE39-404
Discharge Pipe Protection Control
This discharge pipe protection control is used to protect the compressor internal temperature
against a malfunction or transient increase of discharge pipe temperature.
H
Each compressor performs the discharge pipe temperature protection control individually
in the following sequence.
[INV compressor]
Discharge pipe temp.
protection control not limited
or
HTdi : Value of INV compressor discharge pipe
temperature (Tdi) compensated with
outdoor air temperature
Tp : Value of compressor port temperature
calculated by Tc and Te, and suction
superheated degree.
HTdi>110°C
Tp>115°C
INV upper limit frequency:
1-step down from current
compressor frequency
&
HTdi<95°C
Tp<100°C
Every 30 sec.
or
HTdi>110°C
Tp>115°C
Every 60 sec.
&
HTdi>130°C
HTdi>115°C
or
for 90 sec.
or more.
Tp>130°C
HTdi<105°C
Tp<115°C
In discharge pipe temp.
protection control
or
INV62 Hz + OFF + OFF
INV upper limit frequency: 1-step up
from current compressor frequency
HTdi>135°C
HTdi>115°C for 10 min. or more.
Discharge pipe
temp.control standby
When occurring 3 times within 100 minutes,
the malfunction code “F3” is output.
[STD compressor]
HTdi : Value of INV compressor discharge pipe
temperature (Tdi) compensated with
outdoor air temperature
Tp : Value of compressor port temperature
calculated by Tc and Te, and suction
superheated degree.
or
• HTds>115°C continues for 5 min. or more.
• HTds>135°C
• Tp>115°C continues for 10 min. or more.
• Tp>130°C
Discharge pipe temp.
protection control not limited
Applicable STD
compressor stops.
10 min.
96
: http://splitoff.ru/tehn-doc.html
Function
SiE39-404
4.4
Protection Control
Inverter Protection Control
Inverter current protection control and inverter fin temperature control are performed to prevent
tripping due to a malfunction, or transient inverter overcurrent, and fin temperature increase.
H
In the case of multi-outdoor-unit system, each INV compressor performs these controls in
the following sequence.
[Inverter overcurrent protection control]
Not limited
200-V unit 400-V unit
Inverter current>Ia
INV upper limit frequency: 1-step down
from current compressor frequency
Inverter current<Ia
& INV upper limit frequency = 210 Hz
Inverter current>Ia
25 A
Ib
26.1 A
Ic
31 A
13.5 A
16.5 A
Inverter current<Ia continues
for 3 min. or more.
INV upper limit frequency: 1-step up from
current compressor frequency
Under inverter current
protection control
or
Ia
Inverter current > Ib continues for 260 sec.
Inverter current > Ic continues for 5 sec.
• When occurring 3 times within 60 min.,
the malfunction code “L8” is output.
• When occurring 3 times within 30 min.,
the malfunction code “L9” is output
Inverter current standby
[Inverter fin temperature control]
Not limited
Tfin>84°C
INV upper limit frequency: 1-step /
1 min down from current compressor
frequency
Tfin>84°C
Under fin temperature
protection control
&
Tfin<81°C
INV upper limit frequency = 210 Hz
Inverter current<81°C continues
for 3 min. or more.
INV upper limit frequency: 1-step / 1 min
up from current compressor frequency
Interval
Tfin>89°C
Fin temp. standby
Function
• When occurring 3 times within 60 min.,
the malfunction code “L4” is output.
: http://splitoff.ru/tehn-doc.html
97
Protection Control
4.5
SiE39-404
STD Compressor Overload Protection
This control is used to prevent abnormal heating due to overcurrent to the compressor resulting
from failures of STD compressor such as locking.
STD compressor ON
Demand to operate.
CT detection current value>A
for more than 3 sec.
200- V unit 400- V unit
A
28.8A
15.0A
STD compressor OFF for 30 min.
When occurring 3 times within 90 minutes,
the malfunction code “E6” is output.
98
: http://splitoff.ru/tehn-doc.html
Function
SiE39-404
Other Control
5. Other Control
5.1
Outdoor Unit Rotation
In the case of multi-outdoor-unit system, this outdoor unit rotation is used to prevent the
compressor from burning out due to unbalanced oil level between outdoor units.
[Details of outdoor unit rotation]
In the case of multi-outdoor-unit system, each outdoor unit is given an operating priority for the
control.
Outdoor unit rotation makes it possible to change the operating priority of outdoor units.
Thus, the system becomes free of compressors that stop over an extended period of time at the
time of partial loading, preventing unbalanced oil level.
[Timing of outdoor unit rotation]
or
After oil return operation
After defrosting operation
At the beginning of the starting control
Example) The following diagram shows outdoor unit rotation in combination of 3 outdoor units.
Starting
control
Normal operation
Oil return operation
or defrosting
operation
Normal operation
Master Slave 1 Slave 2
Outdoor unit
rotation
Priority
1
Priority
2
Master Slave 1 Slave 2
Outdoor unit
rotation
Priority
3
Oil return operation
or defrosting
Normal operation operation
Priority
3
Priority
1
Priority
2
Priority
2
Normal operation
Master Slave 1 Slave 2
Priority
3
Priority
1
Master Slave 1 Slave 2
Outdoor unit
rotation
Priority
2
Priority
3
Priority
1
* “Master unit”, “slave unit 1” and “slave unit 2” in this section are the names for installation.
They are determined in installation work, and not changed thereafter. (These names are
different from “master unit” and “slave unit” for control.)
The outdoor unit connected the control wires (F1 and F2) for the indoor unit should be
designated as master unit
Consequently, The LED display on the main PCB for “master unit”, “slave unit 1” and “slave
unit 2” do not change. (Refer to the page 90.)
Function
: http://splitoff.ru/tehn-doc.html
99
Other Control
5.2
SiE39-404
Emergency Operation
If the compressor cannot operate, this control inhibits any applicable compressor or outdoor unit
from operating to perform emergency operation only with the operative compressor or outdoor
unit.
Caution
"For making a compressor unable to operate due to malfunction, etc., be sure to
conduct the work with emergency operation setting.
Never execute work such as disconnection of the power cable from magnet contactor.
(Otherwise, other normal compressors may malfunction.)
∗ Because the units will be operated in the combination with which oil pressure
equalization between compressors cannot be performed.
5.2.1 Restrictions for Emergency Operation
• In the case of system with 1 outdoor unit installed, only when thermostats of indoor units
having a capacity of 50% or more of the outdoor unit capacity turn ON, the emergency
operation is functional. (If the total capacity of indoor units with thermostat ON is small, the
outdoor unit cannot operate.)
• If the emergency operation is set while the outdoor unit is in operation, the outdoor unit stops
once after pump-down residual operation (a maximum of 5 minutes elapsed).
5.2.2 In the Case of 1-Outdoor-Unit System (RXYQ8 to 16M)
• Emergency operation with settings in service mode
∗ “Inhibition of operation” is set with each compressor.
• To inhibit INV compressor from operating → Set
LED display (7:ON 7:OFF 9:Blink)
setting mode 2 from No. 0 to No. 2.
H1P---H7P
(Procedure)
(1) Press and hold the MODE button (BS1) for 5 sec. or
more.
(2) Press the RETURN button (BS3) once.
(3) Press the SET button (BS2) one.
(4) Press the RETURN button (BS3) twice.
(5) Press the MODE button (BS1) once.
• To inhibit STD1 and STD2 compressors from
operating → Set setting mode 2 from No. 19 to No.
2. (RXYQ8M to RXYQ16M)
(Procedure)
(1) Press and hold the MODE button (BS1) for 5 sec. or
more.
(2) Press the SET button (BS2) 19 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
• To inhibit STD2 compressor from operating → Set
setting mode 2 from No. 19 to No.3.(RXYQ14M)
(Procedure)
(1) Press and hold the MODE button (BS1) for 5 sec. or
more.
(2) Press the SET button (BS2) 19 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) twice.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
100
7777777
7777779 (Factory set)
7777797
7777777
7777777
77
LED display (7:ON 7:OFF 9:Blink)
H1P---H7P
7777777
77
7777
7777
7777779 (Factory set)
7777797
7777777
7777777
77
LED display (7:ON 7:OFF 9:Blink)
H1P---H7P
7777777
77
7777
7777
7777779 (Factory set)
7777799
7777777
7777777
77
: http://splitoff.ru/tehn-doc.html
Function
SiE39-404
Other Control
• With RXYQ14M and 16M, if INV compressor is inhibited from operating, only 1 STD
compressor can operate for reasons of oil equalization.
• With RXYQ14M and 16M, STD1 compressor cannot be inhibited from operating for reasons of
oil equalization.
• When 1 outdoor unit is installed (with RXYQ8M to 16M), automatic backup operation cannot
be performed.
5.2.3 In The Case of Multi-Outdoor-Unit System (RXYQ18 to 48M)
Automatic backup operation
With multi-outdoor-unit system, if a certain outdoor unit system malfunctions (i.e., the system
stops and indoor unit remote controller displays the malfunction), by resetting the system with
the indoor unit remote controller, the applicable outdoor unit is inhibited from operating for 8
hours, thus making it possible to perform emergency operation automatically.
However, in the event any of the following malfunctions occurs, automatic backup operation
can be performed.
Malfunctions under which automatic backup operation can be performed:
• E3, E4, E5, E7
• F3
• H7, H9
• J2, J3, J5, J6, J7, J9, JA, JC
• L3, L4, L5, L8, L9, LC
• U2, UJ
Emergency operation with settings in service mode
∗ “Inhibition of operation” is set with each outdoor unit.
Make the following settings with the master unit. (Setting with the slave unit becomes disabled.)
∗ Discriminate the operating status of the master unit/slave units through the following LED
display.
• To inhibit the master unit from operating → Set
setting mode 2 from No. 38 to No. 2.
(Procedure)
(1) Press and hold the MODE button (BS1) for 5 sec. or
more.
(2) Press the SET button (BS2) 38 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
• To inhibit the slave unit 1 from operating → Set
setting mode 2 from No. 39 to No. 2.
(Procedure)
(1) Press and hold the MODE button (BS1) for 5 sec. or
more.
(2) Press the SET button (BS2) 39 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
Function
LED display (7:ON 7:OFF 9:Blink)
H1P---H7P
7777777
7777
77777
7777779 (Factory set)
7777797
7777777
7777777
77
LED display (7:ON 7:OFF 9:Blink)
H1P---H7P
7777777
7777
77777
7777779 (Factory set)
7777797
7777777
7777777
77
: http://splitoff.ru/tehn-doc.html
101
Other Control
SiE39-404
• To inhibit the slave unit 2 from operating → Set
setting mode 2 from No. 40 to No. 2.
(Procedure)
(1) Press and hold the MODE button (BS1) for 5 sec. or
more.
(2) Press the SET button (BS2) 40 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
LED display (7:ON 7:OFF 9:Blink)
H1P---H7P
7777777
777
77777
7777779 (Factory set)
7777797
7777777
7777777
77
∗
• In the case of multi-outdoor-unit system, “Inhibition of operation” is not set with each
compressor individually.
• In the case of multi-outdoor-unit system, when the above “Inhibition of operation” is set,
outdoor unit rotation is not functional.
Note :
5.3
Reset the power supply during the outdoor unit is stopping to cancel the
automatic backup operation forcibly.
Demand Operation
In order to save the power consumption, the capacity of outdoor unit is saved with control
forcibly by using “Demand 1 Setting” or “Demand 2 Setting”.
To operate the unit with this mode, additional setting of “Continuous Demand Setting” or
external input by external control adapter is required.
[Demand 1 setting]
Setting
Demand 1 setting 1
Demand 1 setting 2 (factory setting)
Demand 1 setting 3
Standard for upper limit of power consumption
Approx. 60%
Approx. 70%
Approx. 80%
[Demand 2 setting]
Setting
Demand 2 setting 2 (factory setting)
Standard for upper limit of power consumption
Approx. 40%
H Other protection control functions have precedence over the above operation.
5.4
Heating operation prohibition
Heating operation is prohibited above 24°C ambient temperature.
102
: http://splitoff.ru/tehn-doc.html
Function
SiE39-404
Outline of Control (Indoor Unit)
6. Outline of Control (Indoor Unit)
6.1
Drain Pump Control
1. The drain pump is controlled by the ON/OFF buttons (4 button (1) - (4) given in the figure
below).
6.1.1 When the Float Switch is Tripped While the Cooling Thermostat is
ON:
Remote control “A3” flashing malfunction stop
ON
Thermostat
(running)
OFF
ON
Float switch
OFF
ON
Drain pump
OFF
5 min.
* 1) Residual operation
5 min. 5 sec.
Malfunction residual
∗ 1. The objective of residual operation is to completely drain any moisture adhering to the fin of
the indoor unit heat exchanger when the thermostat goes off during cooling operation.
6.1.2 When the Float Switch is Tripped During Cooling OFF by
Thermostat:
Enters malfunction treatment if the float switch is not reset within 5 minutes.
Thermostat
(running)
ON
Remote control “A3” flashing malfunction stop
OFF
ON
Float switch
OFF
ON
Drain pump
OFF
5 min.
Function
5 min.
5 sec.
: http://splitoff.ru/tehn-doc.html
103
Outline of Control (Indoor Unit)
SiE39-404
6.1.3 When the Float Switch is Tripped During Heating Operation:
Thermostat
(running)
ON
Remote control “A3” flashing malfunction stop
OFF
ON
Humidifier
OFF
Reset
ON
Float switch
OFF
ON
Drain pump
OFF
5 min.
5 sec.
5 min.
During heating operation, if the float switch is not reset even after the 5 minutes operation, 5
seconds stop, 5 minutes operation cycle ends, operation continues until the switch is reset.
6.1.4 When the Float Switch is Tripped and “AF” is Displayed on the
Remote Controller:
“AF” display (running)
Remote control
display
Enters malfunction treatment
if the float switch is not reset
within 5 minutes.
Remote control “A3” flashing
malfunction stop
ON
Float switch
OFF
1st time
2nd time
3rd time
4th time
5th time
ON
Drain pump
OFF
Note:
104
If the float switch is tripped five times in succession, a drain malfunction is determined to have
occurred. “AF” is then displayed as operation continues.
: http://splitoff.ru/tehn-doc.html
Function
SiE39-404
6.2
Outline of Control (Indoor Unit)
Louver Control for Preventing Ceiling Dirt
We have added a control feature that allows you to select the range of in which air direction can
be adjusted in order to prevent the ceiling surrounding the air discharge outlet of ceiling
mounted cassette type units from being soiled. (This feature is available on double flow, multiflow and corner types.)
Existing position
P0
P1
P2
P3
P4
Ceiling soiling prevention
position
Standard Setting
position
Draft prevention position
(Not for Multi flow type)
P0
P0
P1
P1
P3
P4
P4
P4'
P0
P1
P2
P2
P0'
P1'
P2'
P2
Draft
prevention
position
P0
P4
P3'
P3
P4
P0''
P1''
P2''
P3''
P4''
Same as existing position
Range of direction adjustment
Standard
position
Prohibited
P0'
P1'
P2'
P3'
P4'
Separated into 5 positions
(P1 - 4)
Range of direction adjustment
Dirt
prevention
position
Prohibited
P0''
P1''
P2''
P3''
P4''
Separated into 5 positions
(P2 - 4)
The factory set position is standard position.
Function
(VL012)
: http://splitoff.ru/tehn-doc.html
105
Outline of Control (Indoor Unit)
6.3
SiE39-404
Thermostat Sensor in Remote Controller
Temperature is controlled by both the thermostat sensor in remote controller and air suction
thermostat in the indoor unit. (This is however limited to when the field setting for the thermostat
sensor in remote controller is set to “Use.” )
Cooling
If there is a significant difference in the preset temperature and the suction temperature, fine
adjustment control is carried out using a body thermostat sensor, or using the sensor in the
remote controller near the position of the user when the suction temperature is near the preset
temperature.
Preset temperature
(Ts)
Suction temperature (TH1)
Range in which thermostat sensor
in remote control can be used
Range in which body
thermostat sensor
can be used
Differential
! Ex: When cooling
Assuming the preset temperature in the figure above is 24°C, and the suction
temperature has changed from 18°C to 30°C (A → F):
(This example also assumes there are several other air conditioners, the VRV system is off, and
that temperature changes even when the thermostat sensor is off.)
Body thermostat sensor is used for temperatures from 18°C to 23°C (A → C).
Remote controller thermostat sensor is used for temperatures from 23°C to 27°C (C → E).
Body thermostat sensor is used for temperatures from 27°C to 30°C (E → F).
And, assuming suction temperature has changed from 30°C to 18°C (F → A):
Body thermostat sensor is used for temperatures from 30°C to 25°C (F → D).
Remote controller thermostat sensor is used for temperatures from 25°C to 21°C (D → B).
Body thermostat sensor is used for temperatures from 21°C to 18°C (B → A).
106
: http://splitoff.ru/tehn-doc.html
Function
SiE39-404
Heating
Outline of Control (Indoor Unit)
When heating, the hot air rises to the top of the room, resulting in the temperature being lower
near the floor where the occupants are. When controlling by body thermostat sensor only, the
unit may therefore be turned off by the thermostat before the lower part of the room reaches the
preset temperature. The temperature can be controlled so the lower part of the room where the
occupants are doesn’t become cold by widening the range in which thermostat sensor in remote
controller can be used so that suction temperature is higher than the preset temperature.
Preset temperature
(Ts)
Suction temperature (TH1)
Range in which thermostat sensor
in remote control can be used
Range in which body
thermostat sensor
can be used
Differential
! Ex: When heating
Assuming the preset temperature in the figure above is 24°C, and the suction
temperature has changed from 18°C to 28°C (A → D):
(This example also assumes there are several other air conditioners, the VRV system is off, and
that temperature changes even when the thermostat sensor is off.)
Body thermostat sensor is used for temperatures from 18°C to 25°C (A → C).
Remote controller thermostat sensor is used for temperatures from 25°C to 28°C (C → D).
And, assuming suction temperature has changed from 28°C to 18°C (D → A):
Remote controller thermostat sensor is used for temperatures from 28°C to 23°C (D → B).
Body thermostat sensor is used for temperatures from 23°C to 18°C (B → A).
Function
: http://splitoff.ru/tehn-doc.html
107
Outline of Control (Indoor Unit)
6.4
SiE39-404
Freeze Prevention
Freeze
Prevention by Off
Cycle (Indoor
Unit)
When the temperature detected by liquid pipe temperature thermistor (R2T) of the indoor unit
heat exchanger drops too low, the unit enters freeze prevention operation in accordance with
the following conditions, and is also set in accordance with the conditions given below.
Conditions for starting freeze prevention: Temperature is -1°C or less for total of 40 min., or
temperature is -5°C or less for total of 10 min.
Conditions for stopping freeze prevention: Temperature is +7°C or more for 10 min.
continuously
Ex: Case where temperature is -5°C or less for total of 10 min.
10min.
Freeze prevention operation
10min.
108
Forced OFF by thermostat
: http://splitoff.ru/tehn-doc.html
Function
SiE39-404
6.5
Outline of Control (Indoor Unit)
Control of outdoor air Processing unit
(Unique Control for Outdoor Air Processing Unit)
6.5.1 Selection of Operation Mode (by suction air thermostat)
Objective
Details
To select cooling, heating, or fan operation mode according to the suction air (outdoor air)
temperature.
[Outdoor air processing unit]
Suction temperature (T1) ºC
–5
5
Cooling mode
15
19
Cooling
Fan operation (with thermostat OFF)
"Low outdoor air protection control"
Cooling
Fan operation
Fan stop
Heating mode
43
18
Heating
Fan operation (with thermostat OFF)
Fan operation
Heating
16
Automatic mode
Heating
Blast
(Thermostat
OFF)
Heating
Cooling
Cooling
18
16
Function
: http://splitoff.ru/tehn-doc.html
109
Outline of Control (Indoor Unit)
SiE39-404
6.5.2 Discharge air temperature control
Used to control the EV (electronic expansion valve) opening and thermostat ON/OFF so as to
keep the discharge air temperature at the set temperature.
(1) Cooling operations
T3
Refrigerant
Discharge
air
CPU
Ts
T1
T4
T2
Temp.
Setting
EV
Refrigerant
T1: Temperature detected by suction air thermistor Th1
T2: Temperature detected by liquid pipe temp. thermistor Th2
T3: Temperature detected by gas pipe temp. thermistor Th3
T4: Temperature detected by discharge air thermistor Th4
EV: Electronic expansion valve opening
SH=T3–T2
If the discharge temperature T4
is lower than the discharge
setting temperature Ts
If the discharge temperature
T4 is higher than the discharge
setting temperature Ts
Yes
No
T4 > Ts?
Is EV possible
to open?
Judge if the superheat degree
is not too small when the EV is
opened.
Yes
No
Is
EV possible to
close?
Yes
If yes,
EV is opened.
EV=EV+∆EV
110
Calculate superheat degree.
If yes,
EV is closed.
No
Judge if the superheat degree
is not too large when the EV is
closed.
EV=EV–∆EV
: http://splitoff.ru/tehn-doc.html
Function
SiE39-404
Outline of Control (Indoor Unit)
(2) Heating operations
Refrigerant
Discharge
air
Tc
CPU
(From Outdoor unit)
Ts
T1
T4
T2
Temp.
Setting
EV
Refrigerant
T1: Temperature detected by suction air thermistor Th1
T2: Temperature detected by liquid pipe temp. thermistor Th2
T3: Temperature detected by gas pipe temp. thermistor Th3
T4: Temperature detected by discharge air thermistor Th4
Tc : Outdoor unit condensing temperature
EV: Electronic expansion valve opening
SC=Tc–T2
If the discharge temperature T4
is higher than the discharge
setting temperature Ts
If the discharge temperature
T4 is lower than the discharge
setting temperature Ts
Yes
No
T4 < Ts?
Is EV possible
to open?
Judge if the superheat degree
is not too small when the EV is
opened.
Yes
No
Is
EV possible to
close?
Yes
If yes,
EV is opened
EV=EV+∆EV
Function
Calculate superheat degree.
If yes,
EV is closed.
No
Judge if the superheat degree
is not too large when the EV is
closed.
EV=EV–∆EV
: http://splitoff.ru/tehn-doc.html
111
Outline of Control (Indoor Unit)
SiE39-404
(3) Thermostat OFF by discharge air temperature
<Cooling>
Target discharge air temp. Ts – Discharge air temp. T4
>5 degree continue for 5 minutes.
→Thermostat stops for 1 minute.
<Heating>
Discharge air temp. T4 – Target discharge air temp. Ts >5 degree
⎧
⎪
& ⎨ EV opening is low limit
⎪
⎩
→Thermostat stops for 1 minute.
⎫
⎪ continue for 5
⎬
⎪ minutes
⎭
6.5.3 Low Outdoor Air Temperature Protection Control
Objective
In cooling (or fan operation) or heating, if outdoor air is low in temperature, stop the fan forcibly.
Details
[Cooling and fan operation]
Turn OFF the fan for a period of 60 minutes at a suction temperature of 5 ºC or lower.
In order to monitor the outdoor air temperature, however, turn ON the fan for a period of one
minute and turn OFF the fan again at a temperature of 5 ºC or lower after the said timer
completes the operative period.
Reset the 60-minute timer when the fan stops running.
[Heating]
Turn OFF the fan for a period of 60 minutes at a suction temperature of –5 ºC or lower.
In order to monitor the outdoor air temperature, however, turn ON the fan for a period of one
minute and turn OFF the fan again at a temperature of –5 ºC or lower after the said timer
completes the operative period.
Reset the 60-minute timer when the fan stops running.
* The thermostat will not turn ON in one minute due to the temperature while the fan stops.
! This control shall be disabled at test run both in cooling and heating. (The test run shall be
conducted first.)
112
: http://splitoff.ru/tehn-doc.html
Function
SiE39-404
Part 5
Test Operation
1. Test Operation ....................................................................................114
1.1 Procedure and Outline .........................................................................114
1.2 Operation When Power is Turned On ..................................................117
2. Outdoor Unit PC Board Layout ...........................................................118
3. Field Setting ........................................................................................119
3.1 Field Setting from Remote Controller ...................................................119
3.2 Field Setting from Outdoor Unit............................................................132
Test Operation
: http://splitoff.ru/tehn-doc.html
113
Test Operation
SiE39-404
1. Test Operation
1.1
Procedure and Outline
Follow the following procedure to conduct the initial test operation after installation.
1.1.1 Check work prior to turn power supply on
Check the below items.
2Power wiring
2Control transmission wiring
between units
2Earth wire
Check on refrigerant piping
Check on amount of refrigerant
charge
Is the wiring performed as specified?
Are the designated wires used?
Is the grounding work completed?
Use a 500V megger tester to measure the insulation.
2 Do not use a megger tester for other circuits than 200V (or
240v) circuit.
Are the setscrews of wiring not loose?
Is pipe size proper? (The design pressure of this product is
3.8MPa.)
Are pipe insulation materials installed securely?
Liquid and gas pipes need to be insulated. (Otherwise causes water
leak.)
Are respective stop valves on liquid, gas and oil equalizing lines
securely open?
Is refrigerant charged up to the specified amount?
If insufficient, charge the refrigerant from the service port of stop
valve on the liquid side with outdoor unit in stop mode after turning
power on.
Has the amount of refrigerant charge been recorded on “Record
Chart of Additional Refrigerant Charge Amount”?
(V3055)
1.1.2 Turn power on
Turn outdoor unit power on.
Be sure to turn the power on 6 hours before starting operation to
protect compressors. (to power on clankcase heater)
Carry out field setting on
outdoor PC board
For field settings, refer to “Field Settings” on and after P119.
After the completion of field settings, set to “Setting mode 1”.
Turn indoor unit power on.
114
(V3056)
: http://splitoff.ru/tehn-doc.html
Test Operation
SiE39-404
Test Operation
1.1.3 Check Operation
* During check operation, mount front panel to avoid the misjudging.
* Check operation is mandatory for normal unit operation.
(When the check operation is not executed, alarm code "U3" will be displayed.)
Press and hold the TEST
OPERATION button (BS4) on
outdoor unit PC board for 5
seconds.
The test operation is started automatically.
⎧ The following judgements are conducted within 15 minutes.
⎫
⎪ 2“Check for wrong wiring”
⎪
2“Check
refrigerant
for
over
charge”
⎪
⎪
stop valve for not open”
⎪ 2“Check
⎪
2Pipe length automatic judgement”
⎪ The following indications are conducted while in test operation.
⎪
⎪ 2LED lamp on outdoor unit PC board H2P flickers (test operation) ⎪
⎪ 2Remote controller Indicates “On Centralized Control” on upper ⎪
⎪
⎪
right.
Indicates “Test Operation” on lower left
⎩
⎭
(V3057)
Check on operation
On completion of test operation, LED on outdoor unit PC board displays the following.
H3P ON: Normal completion
H2P and H3P ON: Abnormal completion →Check the indoor unit remote controller for
abnormal display and correct it.
In the case of multi-outdoor-unit system, make setting on the master unit PC board. (Setting
with the slave unit is disabled.)
[LED display in the case of multi-outdoor-unit system] (Same as that in emergency operation)
* Discriminate the operating status of the master unit/slave units through the following LED
display.
LED display (7:ON 7:OFF 9:Blink)
H1P---H7P H8P
7777777
7777 7
Master: 77
Slave 1: 7777777 9
Slave 2: 7777777 7
(Factory set)
Malfunction code
In case of an alarm code displayed on remote controller:
Cause of trouble due to faulty
installation work
Closed stop valve of outdoor unit
Reversed phase in power cable
connection for outdoor unit
Electric power for outdoor or indoor unit
is not supplied. (Including open phase)
Incorrect wiring between units
Refrigerant overcharge
Insufficient refrigerant
Test Operation
Alarm
code
E3
E4
F3
UF
Countermeasure
U1
In case of RXYQ5 to 16M (Single outdoor installation)
Liquid side stop valve
: Open
Gas side stop valve
: Open
Oil equalizing pipe stop valve : Close
In case of RXYQ18 to 48M (Multi outdoor installation)
Liquid side stop valve
: Open
Gas side stop valve
: Open
Oil equalizing pipe stop valve : Open
Change connection of two wires among three for correct phasing.
U4
Check that the power cable for outdoor unit is connected properly.
UF
Check that the wiring between units corresponds correctly to
refrigerant piping system.
Compute again optimum amount of refrigerant to be added based on
the piping length, then, collect the excessive amount by using
refrigerant collector to make the refrigerant amount proper.
- Check that additional charging has been carried out.
- Compute again the refrigerant amount to be added based on the
piping length, and charge proper amount of refrigerant additionally.
E3
F6
UF
E4
F3
: http://splitoff.ru/tehn-doc.html
115
Test Operation
SiE39-404
1.1.4 Confirmation on normal operation
•
•
•
•
116
Conduct normal unit operation after the check operation has been completed.
(When outdoor air temperature is 24ºC or higher, the unit can not be operated with heating
mode. See the instruction manual attached.)
Confirm that the indoor/outdoor units can be operated normally.
(When an abnormal noise due to liquid compression by the compressor can be heard, stop
the unit immediately, and turn on the crankcase heater to heat up it sufficiently, then start
operation again.)
Operate indoor unit one by one to check that the corresponding outdoor unit operates.
Confirm that the indoor unit discharges cold air (or warm air).
Operate the air direction control button and flow rate control button to check the function of
the devices.
: http://splitoff.ru/tehn-doc.html
Test Operation
SiE39-404
1.2
Test Operation
Operation When Power is Turned On
1.2.1 When Turning On Power First Time
The unit cannot be run for up to 12 minutes to automatically set the master power and address
(indoor-outdoor address, etc.).
Status
Outdoor unit
Test lamp H2P .... Blinks
Can also be set during operation described above.
Indoor unit
If ON button is pushed during operation described above, the “UH”
malfunction indicator blinks.
(Returns to normal when automatic setting is complete.)
1.2.2 When Turning On Power The Second Time and Subsequent
Tap the RESET button on the outdoor unit PC board. Operation becomes possible for about 2
minutes. If you do not push the RESET button, the unit cannot be run for up to 10 minutes to
automatically set master power.
Status
Outdoor unit
Test lamp H2P .... Blinks
Can also be set during operation described above.
Indoor unit
If ON button is pushed during operation described above, the operation lamp
lights but the compressor does not operate. (Returns to normal when
automatic setting is complete.)
1.2.3 When an Indoor Unit or Outdoor unit Has Been Added, or Indoor or
Outdoor Unit PC Board Has Been Changed
Be sure to push and hold the RESET button for 5 seconds. If not, the addition cannot be
recognized. In this case, the unit cannot be run for up to 12 minutes to automatically set the
address (indoor-outdoor address, etc.)
Status
Outdoor unit
Test lamp H2P .... ON
Can also be set during operation described above.
Indoor unit
If ON button is pushed during operation described above, the “UH” or “U4”
malfunction indicator blinks. (Returns to normal when automatic setting is
complete.)
Caution When the 400 volt power supply is applyed to "N" phase by mistake,
replace Inverter P.C.B (A2P) and control transformer (T1R, T2R) in
switch box together.
(V0847)
Test Operation
: http://splitoff.ru/tehn-doc.html
117
Outdoor Unit PC Board Layout
SiE39-404
2. Outdoor Unit PC Board Layout
Outdoor unit PC board
(2) Set mode display (LED)
(3) Mode setting switch
H1P H2P H3P H4P H5P H6P H7P
BS1
B S2
BS3
B S4
BS5
MODE
SET
RETURN
TEST
RESET
H8P
(1) Microcomputer normal monitor
HAP
1
2
DS 3
1 2 3 4 1 2 3 4
DS 1
DS2
(4) Local setting switch
Connection terminal for transmission use
A
B
C
Switch cool/heat
F1 F2 F1 F2 Q1 Q2
IndoorOutdoor
OutdoorOutdoor
Multi outdoor
(V3054)
(1) Microcomputer normal monitor
This monitor blinks while in normal operation, and turns on or off when a malfunction occurs.
(2) Set mode display (LED)
LEDs display mode according to the setting.
(3) Mode setting switch
Used to change mode.
(4) Local setting switch
Used to make local settings.
118
: http://splitoff.ru/tehn-doc.html
Test Operation
SiE39-404
Field Setting
3. Field Setting
3.1
Field Setting from Remote Controller
Individual function of indoor unit can be changed from the remote controller. At the time of
installation or after service inspection / repair, make the local setting in accordance with the
following description.
Wrong setting may cause malfunction.
(When optional accessory is mounted on the indoor unit, setting for the indoor unit may be
required to change. Refer to information in the option handbook.)
3.1.1 Wired Remote Controller <BRC1A61, 62>
UNIT NO.
MODE NO.
SECOND
CODE NO.
FIELD
SET
MODE
FIRST
CODE NO.
(V0292)
1. When in the normal mode, press the “
” button for a minimum of four seconds, and the
FIELD SET MODE is entered.
2. Select the desired MODE NO. with the “
” button (2).
3. During group control, when setting by each indoor unit (mode No. 20, 22 and 23 have been
selected), push the “
” button (3) and select the INDOOR UNIT NO to be set. (This
operation is unnecessary when setting by group.)
4. Push the “
” upper button (4) and select FIRST CODE NO.
5. Push the “
” lower button (5) and select the SECOND CODE NO.
6. Push the “
” button (6) once and the present settings are SET.
7. Push the “
” button (7) to return to the NORMAL MODE.
(Example)
If during group setting and the time to clean air filter is set to FILTER CONTAMINATION,
HEAVY, SET MODE NO. to “10” FIRST CODE NO. to “0”, and SECOND CODE NO. to “02”.
Test Operation
: http://splitoff.ru/tehn-doc.html
119
Field Setting
SiE39-404
3.1.2 Wireless Remote Controller - Indoor Unit
BRC7C type
MODE NO.
FIELD SET MODE
3
4
5
SECOND CODE NO.
FIRST CODE NO.
2
1, 6
(V2770)
1. When in the normal mode, push the
button for 4 seconds or more, and operation
then enters the “field set mode.”
2. Select the desired “mode No.” with the
button.
3. Pushing the
button, select the first code No.
4. Pushing the
button, select the second code No.
5. Push the timer
button and check the settings.
6. Push the
button to return to the normal mode.
(Example)
When setting the filter sign time to “Filter Dirtiness-High” in all group unit setting, set the Mode
No. to “10”, Mode setting No. to “0” and setting position No. to “02”.
120
: http://splitoff.ru/tehn-doc.html
Test Operation
SiE39-404
Field Setting
3.1.3 Simplified Remote Controller
BRC2A51
MODE NO.
FIRST
CODE NO.
UNIT NO.
SECOND
CODE NO.
(V0294)
1. Remove the upper part of remote controller.
2. When in the normal mode, press the [BS6] BUTTON (2) (field set), and the FIELD SET
MODE is entered.
3. Select the desired MODE No. with the [BS2] BUTTON (3) (temperature setting s) and the
[BS3] BUTTON (3) (temperature setting t).
4. During group control, when setting by each indoor unit (mode No. 20, 22, and 23 have been
selected), push the [BS8] (4) BUTTON (unit No.) and select the INDOOR UNIT NO. to be
set. (This operation is unnecessary when setting by group.)
5. Push the [BS9] BUTTON (5) (set A) and select FIRST CODE NO.
6. Push the [BS10] BUTTON (6) (set B) and select SECOND CODE NO.
7. Push the [BS7] BUTTON (7) (set/cancel) once and the present settings are SET.
8. Push the [BS6] BUTTON (8) (field set) to return to the NORMAL MODE.
9. (Example) If during group setting and the time to clean air filter is set to FILTER
CONTAMINATION - HEAVY, SET MODE NO. to “10”, FIRST CODE NO. to “0”, and
SECOND CODE NO. to “02”.
Test Operation
: http://splitoff.ru/tehn-doc.html
121
Field Setting
SiE39-404
3.1.4 Setting Contents and Code No. – VRV Indoor unit
VRV
Mode Setting
Setting Contents
system No. Switch
No.
indoor Note 2
unit
0
Filter contamination heavy/
settings 10(20)
light (Setting for display
time to clean air filter)
(Sets display time to clean
air filter to half when there is
heavy filter contamination.)
12(22)
13(23)
15(25)
1
Long life filter type
2
Super
long life
filter
Light
02
Approx.
10,000
hrs.
Heavy
Approx.
5,000
hrs.
Long life
filter
Approx.
2,500
hrs.
Approx.
1,250
hrs.
Standard
filter
Approx.
200
hrs.
Approx.
100
hrs.
03
04
—
—
—
Long life filter
Super long life
filter
—
Thermostat sensor in remote controller
Use
No use
—
3
Display time to clean air filter
calculation (Set when filter sign is not
to be displayed.)
Display
No display
—
0
Optional accessories output selection
(field selection of output for adaptor for
wiring)
Indoor unit
turned ON by
thermostat
1
ON/OFF input from outside (Set when
ON/OFF is to be controlled from
outside.)
Forced OFF
2
Thermostat differential changeover
(Set when remote sensor is to be
used.)
1°C
LL
Operation output
Malfunction
output
ON/OFF control
—
—
0.5°C
—
—
3
OFF by thermostat fan speed
4
Automatic mode differential (automatic
temperature differential setting for VRV
system heat recovery series cool/heat)
01:0
5
Power failure automatic reset
Not equipped
Equipped
—
—
0
High air outlet velocity
(Set when installed in place with ceiling
higher than 2.7 m.)
N
H
S
—
1
Selection of air flow direction
(Set when a blocking pad kit has been
installed.)
F (4 directions)
T (3 directions)
W (2 directions)
—
3
Air flow direction adjustment (Set at
installation of decoration panel.)
Equipped
Not equipped
4
Field set air flow position setting
Draft prevention
Standard
Ceiling Soiling
prevention
—
5
Field set fan speed selection
(fan speed control by air discharge
outlet for phase control)
Standard
Optional
accessory 1
Optional
accessory 2
—
Set fan speed
02:1
03:2
04:3
—
05:4
—
06:5
07:6
08:7
—
1
Thermostat OFF excess humidity
Not equipped
Equipped
—
—
2
Direct duct connection
(when the indoor unit and heat reclaim
ventilation unit are connected by duct
directly.) ∗Note 6
Not equipped
Equipped
—
—
3
Drain pump humidifier interlock
selection
Not equipped
Equipped
—
—
5
Field set selection for individual
ventilation setting by remote controller
Not equipped
Equipped
—
—
6
Field set selection for individual
ventilation setting by remote controller
Not equipped
Equipped
—
—
Notes:
122
Second Code No.(Note 3)
01
1. Settings are made simultaneously for the entire group, however, if you select the mode No.
inside parentheses, you can also set by each individual unit. Setting changes however
cannot be checked except in the individual mode for those in parentheses.
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so
they cannot be set individually. Setting changes also cannot be checked.
3. Marked
are factory set.
4. Do not make settings other than those described above. Nothing is displayed for functions
the indoor unit is not equipped with.
5. “88” may be displayed to indicate the remote controller is resetting when returning to the
normal mode.
6. If the setting mode to “Equipped”, heat reclaim ventilation fan conducts the fan residual
operation by linking to indoor unit.
: http://splitoff.ru/tehn-doc.html
Test Operation
SiE39-404
Field Setting
3.1.5 Applicable range of Field setting
Ceiling mounted cassette type
Slim
Ceiling
Ceiling mounted
Double Corner mounted built-in
flow
type
duct
type
type
Multi
flow
FXFQ
FXZQ FXCQ FXKQ
Ceiling Ceiling Wall
Floor
mounted suspended mounted standing
duct
type
type
type
type
Concealed
Floor
standing
type
New
Ceiling
suspended
cassette
type
Outdoor
air
processing
unit
FXDQ
FXSQ
FXMQ
FXHQ
FXAQ
FXLQ
FXNQ
FXUQ
FXMQMF
Filter sign
"
"
"
"
"
"
"
"
"
"
"
"
"
Ultra long life filter
sign
"
"
"
—
—
—
—
—
—
—
—
—
—
Remote controller
thermostat sensor
"
"
"
"
"
"
"
"
"
"
"
"
—
Set fan speed when
thermostat OFF
"
"
"
"
"
"
"
"
"
"
"
"
—
Air flow adjustment
Ceiling height
"
—
—
—
—
—
—
"
—
—
—
"
—
Air flow direction
"
"
—
—
—
—
—
—
—
—
—
"
—
Air flow direction
adjustment
(Down flow operation)
—
—
—
"
—
—
—
—
—
—
—
—
—
Air flow direction
adjustment range
"
"
"
"
—
—
—
—
—
—
—
—
—
Field set fan speed
selection
"
—
—
—
"∗1
—
—
"
—
—
—
—
—
Discharge air temp.
(Cooling)
—
—
—
—
—
—
—
—
—
—
—
—
"
Discharge air temp.
(Heating)
—
—
—
—
—
—
—
—
—
—
—
—
"
∗1 Static pressure selection
Test Operation
: http://splitoff.ru/tehn-doc.html
123
Field Setting
SiE39-404
3.1.6 Detailed Explanation of Setting Modes
Filter Sign Setting
If switching the filter sign ON time, set as given in the table below.
Set Time
Filter Specs.
Setting
Contamination Light
Contamination Heavy
Standard
Long Life
Ultra Long Life Filter
200 hrs.
100 hrs.
2,500 hrs.
1,250 hrs.
10,000 hrs.
5,000 hrs.
Ultra-Long-Life Filter Sign Setting
When a Ultra-long-life filter is installed, the filter sign timer setting must be changed.
Setting Table
Mode No.
10 (20)
Setting Switch No.
1
Setting Position No.
01
02
03
Setting
Long-Life Filter
Ultra-Long-Life Filter (1)
—
Fan Speed Changeover When Thermostat is OFF
By setting to “Set Fan Speed,” you can switch the fan speed to the set fan speed when the
heating thermostat is OFF.
∗ Since there is concern about draft if using “fan speed up when thermostat is OFF,” you should
take the setup location into consideration.
Setting Table
Mode No.
12(22)
First Code No.
3
Second Code No.
01
02
Setting
LL Fan Speed
Set Fan Speed
Auto restart after power failure reset
For the air conditioners with no setting for the function (same as factory setting), the units will be
left in the stop condition when the power supply is reset automatically after power failure reset
or the main power supply is turned on again after once turned off. However, for the air
conditioners with the setting, the units may start automatically after power failure reset or the
main power supply turned on again ( return to the same operation condition as that of before
power failure).
For the above reasons, when the unit is set enabling to utilize “Auto restart function after power
failure reset”, utmost care should be paid for the occurrence of the following situation.
Caution 1. The air conditioner starts operation suddenly after power failure reset or
the main power supply turned on again. Consequently, the user might be
surprised (with question for the reason why).
2. In the service work, for example, turning off the main power switch during
the unit is in operation, and turning on the switch again after the work is
completed start the unit operation (the fan rotates).
124
: http://splitoff.ru/tehn-doc.html
Test Operation
SiE39-404
Field Setting
Air Flow Adjustment - Ceiling height
Make the following setting according to the ceiling height. The setting position No. is set to “01”
at the factory.
! In the Case of FXAQ, FXHQ
Mode No.
Setting Switch
No.
13(23)
0
Setting Position
Setting
No.
01
Wall-mounted type: Standard
02
Wall-mounted type: Slight increase
03
Wall-mounted type: Normal increase
! In the Case of FXFQ25~80
Mode
No.
13 (23)
First Second
Ceiling height
code
code
Setting
4-way Outlets
3-way Outlets
2-way Outlets
No.
No.
01
Standard (N)
Lower than 2.7 m Lower than 3.0 m Lower than 3.5 m
0
02
High Ceiling (H) Lower than 3.0 m Lower than 3.3 m Lower than 3.8 m
03
Higher Ceiling (S) Lower than 3.5 m Lower than 3.5 m
—
! In the Case of FXFQ100~125
Mode
No.
13 (23)
First Second
Ceiling height
code
code
Setting
4-way Outlets
3-way Outlets
2-way Outlets
No.
No.
01
Standard (N)
Lower than 3.2 m Lower than 3.6 m Lower than 4.2 m
0
02
High Ceiling (H) Lower than 3.6 m Lower than 4.0 m Lower than 4.2 m
03
Higher Ceiling (S) Lower than 4.2 m Lower than 4.2 m
—
! In the Case of FXUQ71~125M
Mode
No.
13 (23)
First Second
Ceiling height
code
code
Setting
4-way Outlets
3-way Outlets
2-way Outlets
No.
No.
01
Standard (N)
Lower than 2.7 m Lower than 3.0 m Lower than 3.5 m
0
02
High Ceiling (H) Lower than 3.0 m Lower than 3.5 m Lower than 3.8 m
03
Higher Ceiling (S) Lower than 3.5 m Lower than 3.8 m
—
Air Flow Direction Setting
Set the air flow direction of indoor units as given in the table below. (Set when optional air outlet
blocking pad has been installed.) The second code No. is factory set to “01.”
Setting Table
Mode No.
First Code No.
13 (23)
1
Second Code
No.
01
02
03
Setting
F : 4-direction air flow
T : 3-direction air flow
W : 2-direction air flow
Setting of Air Flow Direction Adjustment
Only the model FXKQ has the function.
When only the front-flow is used, sets yes/no of the swing flap operation of down-flow.
Setting Table
Setting
Down-flow operation: Yes
Down-flow operation: No
Test Operation
Mode No.
13 (23)
First Code No.
3
: http://splitoff.ru/tehn-doc.html
Second Code No.
01
02
125
Field Setting
SiE39-404
Setting of Air Flow Direction Adjustment Range
Make the following air flow direction setting according to the respective purpose.
Setting Table
Mode No.
13 (23)
First Code No.
4
Second Code No.
01
02
03
Setting
Upward (Draft prevention)
Standard
Downward (Ceiling soiling
prevention)
Air flow rate switching at discharge grille for field air flow rate switching
When the optional parts (high performance filter, etc.) is installed, sets to change fan speed for
securing air flow rate.
Follow the instruction manual for the optional parts to enter the setting numbers.
Setting of the static pressure selection (for FXDQ model)
126
Model No.
First Code No.
13 (23)
5
Second Code No.
01
02
External static pressure
Standard (15Pa)
High static pressure (44Pa)
: http://splitoff.ru/tehn-doc.html
Test Operation
SiE39-404
Field Setting
3.1.7 Outdoor Air Processing Unit-Field Setting (Remote Controller)
Mode Setting
SW
No.
No.
0
10
(20)
3
1
12
(22)
5
3
14
(24)
4
Setting
contents
Stain of filter
Filtering
time
cumulation
External
ON/OFF
input
Power
failure
automatic
reset
Discharge
temperature
(cooling)
Discharge
temperature
(heating)
02
03
04
05
2500hr
1250hr
—
—
—
—
—
—
10
11
12
13
14
15
—
—
—
—
—
—
—
Display
No
display
—
—
—
—
—
—
—
—
—
—
—
—
—
Forced
stop
Forced
input
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Not
equipped Equipped
13°C
14
15
16
17
18
19
20
21
22
23
24
25
25
25
18°C
19
20
21
22
23
24
25
26
27
28
29
30
30
30
Note) Bold face in
Test Operation
Setting position No.
06 07 08 09
01
indicates the default setting.
: http://splitoff.ru/tehn-doc.html
127
Field Setting
SiE39-404
3.1.8 Centralized Control Group No. Setting
BRC1A Type
Set the group number of each group of the indoor unit from the remote controller. (In case of no
remote controller, also connect the remote controller and set the group No. Then, remove the
remote controller.)
1. Turn ON the power of the indoor unit and central remote controller.
(Unless the power is ON, no setting can be made.)
Check that the installation and electrical wiring are correct before turning the power supply
ON.
(When the power supply is turned ON, all LCD appear once and the unit may not accept the
operation for about one minute with the display of “88”.)
2. While in the normal mode, hold down the “
” button for a minimum of 4 seconds.
The remote controller will enter the FIELD SET MODE.
3. Select the MODE No. “00” with the “
” button.
4. Use the “
” button to select the group No. for each group.
5. (Group numbers increase in the order of 1-00, 1-01, ... 1-15, 2-00, ... 4-15.)
6. Press “
” to set the selected group No.
7. Press “
” to return to the NORMAL MODE.
MODE NO.
GROUP NO.
FIELD SET
MODE
(V0293)
Note:
! For simplified remote controller, see the following.
! For setting group No. of HRV and wiring adaptor for other air conditioners, etc., refer to the
instruction manual attached.
NOTICE
Enter the group No. and installation place of the indoor unit into the attached installation table.
Be sure to keep the installation table with the operation manual for maintenance.
128
: http://splitoff.ru/tehn-doc.html
Test Operation
SiE39-404
Field Setting
! Group No. setting by wireless remote controller for centralized control
1. When in the normal mode, push
button for 4 seconds or more, and operation then
enters the “field set mode.”
2. Set mode No. “00” with
button.
3. Set the group No. for each group with
button (advance/backward).
BRC7C Type
4. Enter the selected group numbers by pushing
button.
5. Push
button and return to the normal mode.
BRC7C Type
MODE NO.
FIELD SET MODE
3
4
GROUP NO.
2
1, 5
(V0916)
Group No. Setting
Example
Indoor/Outdoor Outdoor/Outdoor
Centoral Remote
Control
Indoor/Outdoor Outdoor/Outdoor
F1 F2
F1 F2
F1 F2
F1 F2 P1 P2
RC
1-00
F1 F2 P1 P2
F1 F2
F1 F2 P1 P2
Main RC
RC Sub
1-01
F1 F2 P1 P2
F1 F2
F1 F2 P1 P2
RC
1-02
F1 F2 P1 P2
F1 F2 P1 P2
Group Control by Remote Control
(automatic unit address)
F1 F2 P1 P2
No Remote Control
1-03
Caution
Test Operation
RC
1-04
(V0917)
When turning the power supply on, the unit may often not accept any operation while "88" is
displaying after all indications were displayed once for about 1 minute on the liquid crystal
display. This is not an operative fault.
: http://splitoff.ru/tehn-doc.html
129
Field Setting
SiE39-404
3.1.9 Setting of Operation Control Mode from Remote Controller
(Local Setting)
The operation control mode is compatible with a variety of controls and operations by limiting
the functions of the operation remote controller. Furthermore, operations such as remote
controller ON/OFF can be limited in accordance with the combination conditions. (Refer to
information in the table below.)
Centralized controller is normally available for operations. (Except when centralized monitor is
connected)
3.1.10 Contents of Control Modes
Twenty modes consisting of combinations of the following five operation modes with
temperature and operation mode setting by remote controller can be set and displayed by
operation modes 0 through 19.
# ON/OFF control impossible by remote controller
Used when you want to turn on/off by central remote controller only.
(Cannot be turned on/off by remote controller.)
# OFF control only possible by remote controller
Used when you want to turn on by central remote controller only, and off by remote controller
only.
# Centralized
Used when you want to turn on by central remote controller only, and turn on/off freely by
remote controller during set time.
# Individual
Used when you want to turn on/off by both central remote controller and remote controller.
# Timer operation possible by remote controller
Used when you want to turn on/off by remote controller during set time and you do not want
to start operation by central remote controller when time of system start is programmed.
130
: http://splitoff.ru/tehn-doc.html
Test Operation
SiE39-404
Field Setting
How to Select
Operation Mode
Example
ON by remote
controller
(Unified ON by
central remote
controller)
Whether operation by remote controller will be possible or not for turning on/off, controlling
temperature or setting operation mode is selected and decided by the operation mode given on
the right edge of the table below.
OFF by remote
controller
(Unified OFF by
central remote
controller)
OFF by
remote
controller
Temperature
control by
remote
controller
Operation mode
setting by
remote controller
↓
↓
↓
↓
↓
Rejection
Rejection
Rejection
Acceptance
Acceptance
Control mode
ON/OFF control
impossible by
remote controller
OFF control only
possible by
remote controller
Centralized
Individual
Timer operation
possible by
remote controller
Control
mode is "1."
(VL069)
Control by remote controller
Control mode
Operation
OFF
Temperature
Operation
control
mode setting
Unified operation,
Unified OFF,
individual operation
individual stop by
by central remote
central remote
controller, or
controller, or timer
operation controlled stop
by timer
Rejection (Example) Rejection (Example)
Rejection
Rejection
Acceptance
0
(Example)
Rejection
10
Acceptance Acceptance 1(Example)
(Example)
(Example)
Rejection
11
Acceptance
Rejection
Acceptance
2
Rejection
12
Acceptance Acceptance
3
Rejection
13
Acceptance
Rejection
Acceptance
4
Rejection
14
Acceptance Acceptance
5
Rejection
15
Acceptance
Rejection
Acceptance
6
Rejection
16
Acceptance Acceptance
7 ∗1
Rejection
17
Acceptance
Acceptance
Rejection
Acceptance
8
(During timer at ON (During timer at ON
Rejection
18
position only)
position only)
Acceptance Acceptance
9
Rejection
19
Do not select “timer operation possible by remote controller” if not using a remote controller.
Operation by timer is impossible in this case.
∗1. Factory setting
When the operation
stop, temperature
setting and operation
mode setting by remote
control are rejected,
is
displayed on the
remote control.
(VL070)
Test Operation
: http://splitoff.ru/tehn-doc.html
131
Field Setting
3.2
SiE39-404
Field Setting from Outdoor Unit
3.2.1 Field Setting from Outdoor Unit
! Setting by dip switches
The following field settings are made by dip switches on PC board.
Dipswitch
Setting item
Description
Setting
ON
to set cool / heat select by remote controller
DS1-1
Cool / Heat select Used
equipped with outdoor unit.
OFF (Factory set)
No.
Caution
ON
DS1-2
~DS1-4
OFF (Factory set)
DS2-1
~4
DS3-1,
2
Not used
Do not change the factory settings.
ON
OFF (Factory set)
Not used
Do not change the factory settings.
ON
OFF (Factory set)
Not used
Do not change the factory settings.
DIP switch Setting after changing the main P.C.Board(A1P) to spare parts P.C.B.
When you change the main P.C.Board(A1P) to spare parts P.C.B., please carry out the following
setting.
ON
OFF
ON
OFF
1 2 3 4
DS1
1 2 3 4
DS2
DIP Switch Detail
DS No.
Item
DS1-1 Cool/Heat change
over setting
ON
Contents
The Cool/Heat change over setting is carried out by
COOL/HEAT changeover remote controller fitted to
outdoor unit.
The Cool/Heat change over setting is not carried out
by COOL/HEAT changeover remote controller fitted
to outdoor unit.
200V (mainly domestic Japan)
OFF
400V (mainly overseas)
ON
OFF
DS1-2 Power supply
specification
DS1-3 Cooling only/Heatpump setting
DS1-4 New/previous unit
setting
ON
Cooling only
OFF
Heat-pump
ON
• Production after January 2004
OFF (Spare
parts PCB)
DS2-1 Domestic Japan or
overseas setting
OFF (Spare
parts PCB)
DS2-2 HP setting
(Horse power)
Factory setting
DS2-3
of spare parts
PCB are all
DS2-4
OFF
(
)
DS2-2
DS2-3
DS2-4
• Production before December 2003 :OFF
• Overseas
ON
:ON
:ON
• Domestic Japan :OFF
5
OFF
OFF
OFF
8
OFF
ON
OFF
10
ON
ON
OFF
12
OFF
OFF
ON
14
ON
OFF
ON
16
OFF
ON
ON
HP
∗ If the DS1-4,DS2-1 setting(refrigerant classification) has not been carried out, error code
“UA” is displayed and unit can not be operated.
Refer “DS1-4, DS2-1~4 setting detail” on next page.
132
: http://splitoff.ru/tehn-doc.html
Test Operation
SiE39-404
Field Setting
“Detail of DS1-4, DS2-1~4 setting”
Previous unit
Test Operation
Mfg. No.
Setting method (
represents the position of switches)
On
HEAT
PUNP(5HP)
RXYQ5MY1B
6300001~6300272 Off
HEAT
PUNP(8HP)
RXYQ8MY1B
6300001~6300491 Off
HEAT
PUNP(10HP)
RXYQ10MY1B
6300001~6301014 Off
HEAT
PUNP(12HP)
RXYQ12MY1B
6300001~6300276 Off
HEAT
PUNP(14HP)
RXYQ14MY1B
6300001~6300314 Off
HEAT
PUNP(16HP)
RXYQ16MY1B
6300001~6300500 Off
Set DS2-1 to ON.
On
Set DS2-1 and DS2-3 to ON.
On
Set DS2-1, DS2-2 and DS2-3
to ON.
On
Set DS2-1 and DS2-4 to ON.
On
Set DS2-1, DS2-2 and DS2-4
to ON.
On
Set DS2-1, DS2-3 and DS2-4
to ON.
New unit
Mfg. No.
Setting method (
represents the position of switches)
HEAT
PUNP(5HP)
RXYQ5MY1B
6300273~
On
Off
Set DS1-4 and DS2-1 to ON.
HEAT
PUNP(8HP)
RXYQ8MY1B
6300492~
On
Off
Set DS1-4, DS2-1 and DS2-3
to ON.
HEAT
PUNP(10HP)
RXYQ10MY1B
6301015~
On
Off
Set DS1-4, DS2-1, DS2-2 and
DS2-3 to ON.
HEAT
PUNP(12HP)
RXYQ12MY1B
6300277~
On
Off
Set DS1-4, DS2-1 and DS2-4
to ON.
HEAT
PUNP(14HP)
RXYQ14MY1B
6300315~
On
Off
Set DS1-4, DS2-1, DS2-2 and
DS2-4 to ON.
HEAT
PUNP(16HP)
RXYQ16MY1B
6300501~
On
Off
Set DS1-4, DS2-1, DS2-3 and
DS2-4 to ON.
: http://splitoff.ru/tehn-doc.html
133
Field Setting
SiE39-404
! Setting by pushbutton switches
The following settings are made by pushbutton switches on PC board.
In case of multi-outdoor unit system, various items should be set with the master unit.
(Setting with the slave unit is disabled.)
The master unit and slave unit can be discriminated with the LED indication as shown below.
Master unit
Slave unit 1
Slave unit 2
H1P
H2P
H3P
H4P
H5P
H6P
H7P
H8P
7
7
7
7
7
7
8
7
7
7
7
7
7
7
7
7
7
7
7
7
7
8
9
7
(Factory setting)
BS1
BS2
BS3
BS4
BS5
MODE
SET
RETURN
TEST
RESET
(V2760)
There are the following three setting modes.
$ Setting mode 1 (H1P off)
Initial status (when normal) : Used to select the cool/heat setting. Also indicates during
“abnormal”, “low noise control” and “demand control”.
% Setting mode 2 (H1P on)
Used to modify the operating status and to set program addresses, etc. Usually used in
servicing the system.
& Monitor mode (H1P blinks)
Used to check the program made in Setting mode 2.
! Mode changing procedure
Using the MODE button, the modes can be changed as follows.
Push and hold the BS1
(MODE button) for 5 seconds.
Setting mode 2
(Normal)
Push the BS1 (MODE button)
one time.
Setting mode 1
Monitor mode
Push the BS1 (MODE button) one time. MODE
MODE
MODE
Off
On
H1P
Blinking
H1P
H1P
(V2761)
! Mode changing procedure
‘Set): Select mode with BS2 (SET button) in each selection step.
Setting mode 1
Press BS1 (MODE button) for more than 5sec.
(Initial condition)
Press BS1 (MODE button)
Setting mode 2
Monitor mode
Setting item selection (Set)
Check item selection (Set)
Press BS3
Press BS3
(RETURN button)
(RETURN button)
Setting condition
selection (Set)
Contents display
Press BS3
Press BS3
(RETURN button)
(RETURN button)
Setting condition
(Contents) display
Press BS3
(RETURN button)
Press BS1
(MODE button)
Press BS1
(MODE button)
(V2762)
134
: http://splitoff.ru/tehn-doc.html
Test Operation
SiE39-404
Field Setting
a. “Setting mode 1”
No.
“Normally, “Setting mode 1” is set.
In case of other status, push MODE
button (BS1) one time and set to
“Setting mode 1”.
<Selection of setting items>
Push the SET button (BS2) and set
LED display to a setting item you
want.
Setting (displaying) item
1
Display for malfunction /
preparing / test run
2
C/H selector (individual)
3
C/H selector (Master)
4
C/H selector (Slave)
5
Low noise operation
6
Demand operation
LED display example
H3P H4P H5P H6P
H1P
H2P
∗
7
7
8
7
7
7
7
∗
∗
7
7
7
7
7
7
7
7
7
7
8
7
7
7
8
7
7
7
7
7
8
7
7
7
7
7
7
7
7
7
7
7
7
"
"
∗ Setting No. 1, 5, 6 are the present status display only.
H7P
Display for malfunction/preparing/test-run
Normal
7
7
7
Malfunction
Regarding setting item No. 1,5,6,
only the present status is displayed.
For the respective description, refer
to the table shown on lower right.
The cool/heat selection setting can
be changed on setting item 2, 3, 4.
→ After setting, push the RETURN
button (BS3) and decide the
item.
Preparing/Test-run
7
8
9
8
8
8
7
7
7
7
7
7
7
7
7
7
7
7
7
7
8
8
7
7
7
7
7
8
7
7
7
7
7
8
Display during low noise operation
Normal
7
7
During low noise operation
H3P to H5P LED
display changes
depending on
setting No. 2, 3, 4.
Display during demand operation
Normal
When the RETURN button (BS3) is
pushed, the status becomes the initial
status of “Setting mode 1”.
7
7
During demand operation
7
7
8
8
7
7
7
7
H3P to H5P LED
display changes
depending on
setting No. 2, 3, 4.
(V2763)
8 : ON
7 : OFF
9 : Blinking
Test Operation
: http://splitoff.ru/tehn-doc.html
135
Field Setting
SiE39-404
b. “Setting mode 2”
No.
Push and hold the MODE button
(BS1) for 5 seconds and set to
“Setting mode 2”.
0
EMG (Emergency
operation 1)
1
Cool/heat unified
address
Low noise/demand
address
Indoor unit forced
fan H
Indoor unit forced
operation
Te setting
Tc setting
Defrost changeover
setting
Sequential
operation setting
External low noise
setting / Demand
setting
AIRNET address
High static pressure
setting
2
<Selection of setting items>
5
Push the SET button (BS2) and set
the LED display to a setting item
shown in the table on the right.
↓
Push the RETURN button (BS3) and
decide the item. (The present setting
condition is blinked.)
6
8
9
10
11
12
13
<Selection of setting conditions>
Push the SET button (BS2) and set
to the setting condition you want.
↓
Push the RETURN button (BS3) and
decide the condition.
18
19
20
21
Push the RETURN button (BS3) and
set to the initial status of “Setting
mode 2”.
∗ If you become unsure of how to
proceed, push the MODE button
(BS1) and return to setting mode 1.
(V2764)
Emergency
operation
(STD compressor
operation
prohibited)
Additional
refrigerant charge
operation setting
Refrigerant
collection mode
setting
22
Night-time low
noise setting
25
Low noise setting
Description
Operates by Standard compressor only when inverter
compressor malfunctions. Temporary operation until the
compressor is replaced. Since the comfortability is
extremely deteriorated, immediately replace the
compressor. (This setting is not applicable to RXYQ5M.)
Sets address for cool/heat unified operation.
Address for low noise/demand operation
Allows forced operation of indoor unit fan while unit is
stopped. (H tap)
Allows forced operation of indoor unit.
Target evaporation temperature for cooling
Target condensation temperature for heating
Changes the temperature condition for defrost and sets to
quick defrost or slow defrost.
Sets sequential operation
Reception of external low noise or demand signal
Set address for AIRNET.
Make this setting in the case of operating in high static
pressure mode with diffuser duct mounted.
Used to operate system only with inverter compressor
when STD compressor malfunctions. This is a temporary
operation extremely impairing comfortable environment.
Therefore, prompt replacement of the compressor is
required.
(This operation, however, is not set with RXYQ5M.)
Carries out additional refrigerant charge operation.
Sets to refrigerant collection mode.
Sets automatic nighttime low noise operation in a simple
way.
The operating time is based on “Starting set” and “Ending
set”.
Sets low noise level when the low noise signal is input
from outside.
Night-time low
noise control
starting setting
Night-time low
noise control
ending setting
Power transistor
check mode
∗Check after
disconnection of
compressor wires
Sets starting time of nighttime low noise operation.
(Nighttime low noise setting is also required.)
29
Capacity
precedence setting
30
Demand setting 1
32
Normal demand
setting
If the capacity control is required, the low noise control is
automatically released by this setting during carrying out
low noise operation and nighttime low noise operation.
Changes target value of power consumption when
demand control 1 is input.
Normally enables demand control 1 without external
input. (Effective to prevent a problem that circuit breaker
of small capacity is shut down due to large load.
26
27
28
136
Setting item
Sets ending time of nighttime low noise operation.
(Nighttime low noise setting is also required.)
Used for trouble diagnosis of DC compressor. Since the
waveform of inverter is output without wiring to the
compressor, it is convenient to probe whether the trouble
comes from the compressor or PC board.
: http://splitoff.ru/tehn-doc.html
Test Operation
SiE39-404
Field Setting
No.
38
39
40
Test Operation
Setting item
Emergency
operation
(Setting for the
master unit
operation
prohibition in multioutdoor-unit
system)
Emergency
operation
(Setting for the
slave unit 1
operation
prohibition in multioutdoor-unit
system)
Emergency
operation
(Setting for the
slave unit 2
operation
prohibition in multioutdoor-unit
system)
Description
Used to temporarily prohibit the applicable outdoor unit
from operating should there be any faulty part in multioutdoor-unit system. Since the comfortable environment
is extremely impaired, prompt replacement of the part is
required.
: http://splitoff.ru/tehn-doc.html
137
Field Setting
SiE39-404
Setting item display
No.
0
1
Setting item
EMG (emergency
operation)
INV compressor
operation inhibited.
Cool / Heat
Unified address
MODE
H1P
TEST
H2P
IND
H3P
C/H selection
Master Slave
H4P
H5P
Low
noise
H6P
Setting condition display
Demand
H7P
Normal operation
8
8
7
7
7
7
7
7
7
7
7
7
7
8
Emergency operation
Address
0
Binary number
1
(6 digits)
~
31
2
Low noise/demand
address
8
7
7
7
7
8
7
Address
0
Binary number
1
(6 digits)
6
Indoor forced fan H
Indoor forced
operation
8
7
7
7
8
7
8
8
7
7
7
8
8
7
External low noise/demand:
NO
8788888
8777778 ∗
8777787
8777778 ∗
8777787
8777877
8777787 ∗
8777778
8777877
8777787 ∗
8777778
8777877
8777787 ∗
8777778
8777778
8777787 ∗
8777778 ∗
External low noise/demand:
YES
8777787
Normal operation
Indoor forced fan H
Normal operation
Indoor forced operation
High
8
Te setting
8
7
7
8
7
7
7
Normal (factory setting)
Low
High
9
Tc setting
8
7
7
8
7
7
8
Normal (factory setting)
Low
Quick defrost
10 Defrost setting
8
7
7
8
7
8
7
Normal (factory setting)
Slow defrost
Sequential operation
11 setting
External low noise/
12 demand setting
13 Airnet address
8
8
8
7
7
7
7
7
7
8
8
8
7
8
8
8
7
7
8
7
8
OFF
ON
Address
0
Binary number
1
(6 digits)
8
7
8
7
7
8
7
High static pressure setting:
OFF
8788888
8777778 ∗
High static pressure setting:
ON
8777787
OFF
Emergency
operation
19 (STD compressor is
inhibited to operate.)
8
Additional refrigerant
20 operation setting
8
7
8
7
8
7
7
21 Refrigerant recovery
mode setting
8
7
8
7
8
7
8
7
8
7
7
8
8
STD 1, 2 operation: Inhibited
STD 2 operation: Inhibited
Refrigerant charging: OFF
Refrigerant charging: ON
Refrigerant recovery: OFF
Refrigerant recovery: ON
OFF
Night-time low noise
22 setting
8
7
8
7
8
8
7
Level 1 (outdoor fan with 8 step or lower)
Level 2 (outdoor fan with 7 step or lower)
Level 3 (outdoor fan with 6 step or lower)
Level 1 (outdoor fan with 8 step or lower)
25 Low noise setting
8
7
8
8
7
7
8
Level 2 (outdoor fan with 7 step or lower)
Level 3 (outdoor fan with 6 step or lower)
138
8777777 ∗
8777778
~
63
18 High static pressure
setting
8788888
8777777 ∗
8777778
~
31
5
∗ Factory set
8777778 ∗
8777787
8777777 ∗
8777778
∗
8777777 ∗
8777778
8777787
8777778 ∗
8777787
8777778 ∗
8777787
8777777 ∗
8777778
8777787
8777788
8777778
8777787 ∗
8777877
: http://splitoff.ru/tehn-doc.html
Test Operation
SiE39-404
Field Setting
Setting item display
No.
Setting item
MODE
H1P
TEST
H2P
8
7
IND
H3P
C/H selection
Master
Slave
H4P
H5P
Low
noise
H6P
Demand
H7P
8
7
Setting condition display
About 20:00
Night-time low noise
26 operation start
setting
8
8
7
About 22:00 (factory
About 24:00
About 6:00
27
Night-time low noise
operation end setting
8
7
8
8
7
8
8
About 7:00
About 8:00 (factory setting)
28
29
Power transistor
check mode
8
7
8
8
8
7
7
Capacity
precedence setting
8
7
8
8
8
7
8
8
7
8
8
8
8
7
OFF
ON
OFF
ON
60 % demand
30 Demand setting 1
70 % demand
80 % demand
32 Continuous demand
setting
8
8
7
7
7
7
7
Emergency
operation
(Master unit with
38 multi-outdoor-unit
system is inhibited to
operate.)
8
8
7
7
8
8
7
Emergency
operation
unit 1 with
39 (Slave
multi-outdoor-unit
system is inhibited to
operate.)
8
Emergency
operation
unit 2 with
40 (Slave
multi-outdoor-unit
system is inhibited to
operate.)
8
Test Operation
OFF
ON
OFF
Master unit operation: Inhibited
OFF
8
7
7
8
8
OFF
7
8
7
7
8777787
8777778 ∗
8
Slave unit 1 operation: Inhibited
8
∗ Factory set
8777778
8777787 ∗
8777877
8777778
8777787
8777877 ∗
8777778 ∗
8777787
8777778 ∗
8777787
8777778
8777787 ∗
8777877
8777778 ∗
8777787
8777778 ∗
8777787
8777778 ∗
7
Slave unit 2 operation: Inhibited
8777787
: http://splitoff.ru/tehn-doc.html
139
Field Setting
SiE39-404
c. Monitor mode
No.
To enter the monitor mode, push the
MODE button (BS1) when in “Setting
mode 1”.
<Selection of setting item>
Push the SET button (BS2) and set
the LED display to a setting item.
<Confirmation on setting contents>
Push the RETURN button (BS3) to
display different data of set items.
0
Number of units for sequential
starting, and others
1
C/H unified address
2
Low noise/demand address
3
Not used
4
Airnet address
5
Number of connected indoor units
H2P
H3P
H4P
H5P
H6P
H7P
9
9
9
9
9
9
9
9
9
9
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
8
8
7
7
7
7
8
8
8
8
7
7
7
7
8
8
7
7
8
8
7
7
7
8
7
8
7
8
7
8
7
8
See below
Lower 6 digits
Number of connected BS units
7
8
Number of outdoor units
9
Number of connected BS units
10
Number of connected BS units
9 7 7 8 7 8 7
Lower 4 digits:
lower
11
Number of zone units (excluding
outdoor and BS unit)
9 7 7 8 7 8 8
Lower 6 digits
12
Number of terminal blocks
9 7 7 8 8 7 7
Lower 4 digits:
upper
13
Number of terminal blocks
9 7 7 8 8 7 8
Lower 4 digits:
lower
14
Contents of malfunction (the
latest)
8 7 7 8 8 8 7
Malfunction
code table
Contents of malfunction
8 7 7 8 8 8 8
Refer page
171, 172.
(1 cycle before)
Contents of malfunction
(2 cycle before)
20
Contents of retry (the latest)
21
Contents of retry (1 cycle before)
22
Contents of retry (2 cycle before)
8
8
8
8
7
7
7
7
8
8
8
8
7
7
7
7
7
8
8
8
7
7
7
8
Lower 4 digits:
upper
7
7
8
7
Setting item 0 Display contents of “Number of units for sequential start,
and others”
Number of units for sequential
start
1 unit
2 units
3 units
(V2765)
EMG operation /backup
operation setting
ON
Defrost select setting
Short
OFF
Medium
Long
Te setting
H
M
L
Tc setting
H
M
L
140
Data display
Number of connected zone units
(excluding outdoor and BS unit)
16
∗ Push the MODE button (BS1) and
returns to “Setting mode 1”.
H1P
6
15
Push the RETURN button (BS3) and
switches to the initial status of
“Monitor mode”.
LED display
Setting item
9
9
9
9
9
9
9
9
9
9
9
9
9
9
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
9
8
7
7
7
7
7
7
7
7
7
7
7
: http://splitoff.ru/tehn-doc.html
7
7
7
8
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
8
9
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
8
9
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
8
9
7
Test Operation
SiE39-404
Field Setting
Push the SET button and match with the LEDs No. 1 - 15, push the RETURN button, and
enter the data for each setting.
H Data such as addresses and number of units is expressed as binary numbers; the two
ways of expressing are as follows:
9 797997
16
32
4
8
1
2
In $ the address is 010110 (binary number), which translates to
16 + 4 + 2 = 22 (base 10 number). In other words, the address is
22.
977 7979
64 16
No.12 128 32
977 7997
4
No.13
8
The No. 1 cool/heat unified address is expressed as a binary
number consisting of the lower 6 digits. (0 - 63)
1
2
The number of terminal blocks for No. 12 and 13 is expressed as
an 8-digit binary number, which is the combination of four upper,
and four lower digits for No. 12 and 13 respectively. (0 - 128)
In % the address for No. 12 is 0101, the address for No. 13 is
0110, and the combination of the two is 01010110 (binary
number), which translates to 64 + 16 + 4 + 2 = 86 (base 10
number). In other words, the number of terminal block is 86.
H See the preceding page for a list of data, etc. for No. 0 - 22.
Test Operation
: http://splitoff.ru/tehn-doc.html
141
Field Setting
SiE39-404
3.2.2 Cool / Heat Mode Switching
There are the following 5 cool/heat switching modes.
$ Set cool/heat separately for each outdoor unit system by indoor unit remote controller.
% Set cool/heat separately for each outdoor unit system by cool/heat switching remote
controller.
& Set cool/heat for more than one outdoor unit system simultaneously in accordance with
unified master outdoor unit by indoor unit remote controller.
' Set cool/heat for more than one outdoor unit system simultaneously in accordance with
unified master outdoor unit by cool/heat switching remote controller.
$ Set Cool/Heat Separately for Each Outdoor System by Indoor Unit Remote Controller
# It does not matter whether or not there is outdoor - outdoor unit wiring.
# Set outdoor unit PC board DS1-1 to “indoor” (factory set).
# Set cool/heat switching to “individual” for “Setting mode 1” (factory set).
MODE
C/H SELECT
TEST
Malfnc.
L.N.O.P.
IND
MASTER
DEMAND
SLAVE
C/H SELECT
Dip SW.
DS1-1
C/H SELECT R.C.
Indoor unit
OUT-MULTI
Indoor unit
(V3058)
142
: http://splitoff.ru/tehn-doc.html
Test Operation
SiE39-404
Field Setting
% Set Cool / Heat Separately for Each Outdoor Unit System by Cool/Heat Switching Remote Controller
# It does not matter whether or not there is outdoor - outdoor unit wiring.
# Set outdoor unit PC board DS1-1 to “outdoor” (factory set).
# Set cool/heat switching to “individual” for “Setting mode 1” (factory set).
C/H SELECT
TEST
MODE
Malfnc.
IND
MASTER
SLAVE
L.N.O.P.
DEMAND
C/H SELECT
Dip SW.
DS1-1
C/H SELECT R.C.
C/H select
remote
control
OUT-MULTI
Indoor unit
Indoor unit
(V3058)
Test Operation
: http://splitoff.ru/tehn-doc.html
143
Field Setting
SiE39-404
OFF
C/H SELECT
IND
MASTER
SLAVE
L.N.O.P.
SLAVE
DEMAND
MASTER
TEST
C/H SELECT
IND
MODE
L.N.O.P.
CENTRAL C/H
SELECTOR
TEST
MODE
Adapter for outside control of outdoor units
DEMAND
& Set Cool / Heat for More Than One Outdoor Unit System Simultaneously in Accordance with Unified
Master Outdoor Unit by Indoor Unit Remote Controller
# Install the outdoor unit external control adapter on either the outdoor-outdoor, indooroutdoor, or transmission line.
# Set outdoor unit PC board DS1-1 to “Indoor” (factory set).
# In setting mode 1, set the outdoor unit you want to give cool/heat selection permission to as
the group master, and set the other outdoor units as group slave units.
# Set the outdoor unit external control adapter SS1 to Unified (factory set) or Cool, and SS2 to
No (factory set).
ON
C/H SELECT
C/H SELECT
DE
BOTH C/H
FUNCTION
OUT-MULTI
C/H SELECT R.C.
SLAVE
Multi
MASTER
DEMAND
C/H SELECT
IND
C/H SELECT
C/H SELECT
OUT-MULTI
C/H SELECT R.C.
To indoor unit
L.N.O.P.
SLAVE
TEST
MASTER
L.N.O.P.
TEST
MODE
C/H SELECT
IND
MODE
To indoor unit
<Slave unit>
<Master unit>
Multi
C/H
OUT-MULTI
C/H SELECT R.C.
TERMINAL
ADDRESS
DEMAND
CENTRAL
NO.
C/H SELECT R.C.
OUT-MULTI
To indoor unit
Multi outdoor units connection
144
: http://splitoff.ru/tehn-doc.html
Test Operation
SiE39-404
Field Setting
' Set Cool / Heat for More Than One Outdoor Unit System Simultaneously in Accordance with Unified
Master Outdoor Unit by Cool/Heat Switching Remote Controller
# Add and change the following items to &.
H Install cool/heat switching remote controller on the group master outdoor unit.
H Set SS1 on the group master outdoor unit PC board.
Supplementation on & and '.
When switching cool/heat for each adapter PC board with the use of more than one adapter PC
board, set the address of the adapter PC board DS1 and DS2 so that it matches the unified
cool/heat address of outdoor unit PC board.
C/H group address
C/H group address
Adapter PCB
No. 0
Outdoor unit
group master
No. 0
Outdoor unit
group slave
No. 0
Outdoor unit
group slave
No. 0
C/H group address
Adapter PCB
No. 2
Test Operation
Outdoor unit
group master
No. 2
Outdoor unit
group slave
No. 2
Adapter PCB
No. 1
Outdoor unit
group master
No. 1
Outdoor unit
group slave
No. 1
C/H group address
Outdoor unit
group slave
No. 2
Adapter PCB
No. 3
Outdoor unit
group master
No. 3
: http://splitoff.ru/tehn-doc.html
Outdoor unit
group slave
No. 3
145
Field Setting
SiE39-404
Address setting for & and ' (Set lower 5 digits with binary number.) [No.0 to No.31]
Address
No.
No. 0
No. 1
No. 2
No. 3
No. 4
Outdoor unit PCB LED
Set with setting mode 2
87
77777
87
77778
87
77787
87
77788
87
77877
0
1
1
2
2
3
3
4
4
~
No. 31
DS1
0
~
~
No. 30
Adapter PCB
DS2
87
88887
87
88888
30
30
31
8 ON 7 OFF
31
Upper position (ON)
lower position (OFF)
(The shaded part shows knob)
(V2724)
146
: http://splitoff.ru/tehn-doc.html
Test Operation
SiE39-404
Field Setting
3.2.3 Setting of Low Noise Operation and Demand Operation
Setting of Low Noise Operation
By connecting the external contact input to the low noise input of the outdoor unit external
control adapter (optional), you can lower operating noise by 2-3 dB.
A. When the low noise operation is carried out by external instructions (with the use
of the outdoor unit external control adapter)
1. Set “External low noise / Demand YES/NO setting” to “External low noise / Demand YES”.
(Set by Setting Mode 2)
2. Set “External low noise level setting” on the outdoor unit PC board, as the need arises.
(Lower noise operation can be carried out by “Mode 2” than by “Mode 1”, and by “Mode 3”
than by “Mode 2”.)
3. Set “Capacity precedence setting” on the outdoor unit PC board, as the need arises.
(If set to “ON”, when air conditioning load gets higher, the low noise instructions are
neglected to switch to normal operation.) (Set by Setting Mode 2)
B. When the low noise operation is carried out automatically at night (The outdoor unit
external control adapter is not required)
1. Set “Night-time low noise setting” on the outdoor unit PC board. (Set by Setting Mode 2)
(Lower noise operation can be carried out by “Mode 2” than by “Mode 1”, and by “Mode 3”
than by “Mode 2”.)
2. Set “Night-time low noise start setting” on the outdoor unit PC board, as the need arises.
(Set by Setting Mode 2)
(Since the time is presumed in accordance with the outdoor temperature, the starting time is
a target only.)
3. Set “Night-time low noise end setting” on the outdoor unit PC board, as the need arises.
(Set by Setting Mode 2)
(Since the time is presumed in accordance with the outdoor temperature, the ending time is
a target only.)
4. Set “Capacity precedence setting” on the outdoor unit PC board, as the need arises.
(Set by Setting Mode 2)
(If set to “ON”, when air conditioning load gets higher, the status is switched to normal
operation even at night.)
Test Operation
: http://splitoff.ru/tehn-doc.html
147
Field Setting
SiE39-404
Image of operation in the case of A
If capacity precedence is set in
‘Capacity precedence setting’, the
fan speed will be increased
according to the load of air
conditioning when load is heavier.
Operation sound
Rated operation
sound
Operation sound of
mode 1
Operation sound of
mode 2
Operation sound of
mode 3
Operation sound during low
noise mode is instructed can
be set with ‘External low
noise level setting’ (Factory
setting is ‘Mode 2’.)
Low noise mode instruction
Low noise of approx. 2 to 3 dB
(The power consumption may
be increased by about 10%)
Low noise of approx. 3 to 5 dB
(The power consumption may
be increased by about 20%)
Low noise of approx. 5 to 8 dB
(The power consumption may
be increased by about 30%)
Operation sound level set with ‘External low noise setting’
(V3078)
Image of operation in the case of B
If capacity precedence is set in ‘Capacity
precedence setting’, the fan speed will be
increased according to the load of air
conditioning when load is heavier.
Operation sound
Time set with ‘Night-time low noise start setting’
Time set with ‘Night-time low noise end setting’
Rated operation
sound
Operation sound during
night-time low noise mode
is instructed can be set with
‘Night-time low noise level
setting’.
(Factory setting is ‘OFF’.)
Night-time
Operation sound of
mode 1
Operation sound of
mode 2
Operation sound of
mode 3
Operation sound level set with
‘Night-time low noise start setting’
PM 8:00 PM 10:00 PM 0:00
AM 6:00 AM 7:00 AM 8:00
Set with ‘Night-time low noise start setting’
(Factory setting is ‘PM 10:00’.)
Set with ‘Night-time low noise end setting’
(Factory setting is ‘AM 8:00’.)
(V3079)
Image of operation in the case of A, B
Operation sound
Time set with ‘Night-time low noise start setting’
If capacity precedence is set in ‘Capacity
precedence setting’, the fan speed will be
increased according to the load of air
Time set with ‘Night-time low noise end setting’
conditioning when load is heavier.
Rated operation
sound
* Night time
Operation sound
of mode 1
Operation sound
of mode 2
Operation sound
of mode 3
Low noise mode instructing
Operation sound set with
‘External los noise setting’
* Low noise mode
instructing
* Operation sound
level set with
‘Night-time low noise
setting’
* Operation sound set with
‘External low noise setting’
PM 8:00 PM 10:00 PM 0:00
Set with ‘Night-time low noise start setting’
(Factory setting is ‘PM 10:00’.)
148
Operation sound during low noise
mode is instructed can be set with
‘External low noise level setting’.
(Factory setting is ‘Mode 2’.)
Operation sound during night-time
low noise mode is instructed can
be set with ‘Night-time low noise
level setting’.
(Factory setting is ‘Off’.)
AM 6:00 AM 7:00 AM 8:00
Set with ‘Night-time low noise end setting’
(Factory setting is ‘AM 8:00’.)
: http://splitoff.ru/tehn-doc.html
When external low noise
instruction is received during
the operation with night-time
low noise mode, Mode 2
precedes Mode 1 and Mode 3
precedes Mode 2.
(V3080)
Test Operation
SiE39-404
Field Setting
Setting of Demand Operation
By connecting the external contact input to the demand input of the outdoor unit external control
adapter (optional), the power consumption of unit operation can be saved suppressing the
compressor operating condition.
A. When the demand operation is carried out by external instructions (with the use of the
outdoor unit external control adapter).
! Set the "External low noise/Demand YES/NO setting" switch on the outdoor unit PCB to the
"External low noise/Demand YES".
(Set by Setting Mode 2)
! Set the "Demand 1 level setting " on the outdoor unit PCB, as the need arises.
(During the demand level 1 instruction, the power consumption can be saved to 80 %, 70 %
or 60 % of the rated value respectively.)
B. When the continuous demand operation is carried out. (Use of the outdoor unit
external control adapter is not required.)
! Set the "Continuous demand setting" on the outdoor unit PCB.
! If the "Continuous demand setting" is set to the "Continuous demand 1 fixing", set the
"Demand 1 setting " on the outdoor unit PCB, as the need arises.
(During the continuous demand level 1 operation, the power consumption can be saved to
80 %, 70 % or 60 % of the rated value respectively.)
Test Operation
: http://splitoff.ru/tehn-doc.html
149
Field Setting
SiE39-404
Image of operation in the case of A
Power consumption
The power
consumption during
the demand level 1
instructing can be
set with the
"Demand 1 level
setting".
("70 % of rated
power consumption"
has been set at
Rated power consumption
80 % of rated power consumption
70 % of rated power consumption
60 % of rated power consumption
Demand level 1 instructing Demand level 2 instructing Demand level 3 instructing
Power consumption set by
"Demand 1 level setting".
40 % of rated power consumption
Forced thermostat OFF
(Fan operation)
(V3081)
Image of operation in the case of B
Power consumption
When the
"Continuous demand
setting" is set to ON
("OFF" has been set
at factory.) , the
power consumption
can be set with the
"Demand 1 level
setting". ("70 % of
rated power
consumption" has
been set at factory.)?
Rated power consumption
80 % of rated power consumption
70 % of rated power consumption
60 % of rated power consumption
40 % of rated power consumption The power consumption set with "Demand 1 level setting".
Forced thermostat OFF
(Fan operation)
(V3082)
Image of operation in the case of A and B
The power
consumption can be
set with the
"Demand 1 level
setting". ("70 % of
rated power
consumption" has
been set at factory.)
Power consumption
Rated power consumption
80 % of rated power consumption
70 % of rated power consumption
60 % of rated power consumption
The power consumption set with "Demand 1 level setting".
40 % of rated power consumption
Forced thermostat OFF
(Fan operation)
HDemand level 2 instructing HDemand level 3 instructing
HDuring continuous demand operation,
when the external demand instruction is
received repeatedly, the instruction with
higher demand level has the precedence.
(V3083)
150
: http://splitoff.ru/tehn-doc.html
Test Operation
SiE39-404
Field Setting
Detailed Setting Procedure of Low Noise Operation and Demand Control
1. Setting mode 1 (H1P off)
$ In setting mode 2, push the BS1 (MODE button) one time. → Setting mode 2 is entered and
H1P lights.
During the setting mode 1 is displayed, “In low noise operation” and “In demand control” are
displayed.
2. Setting mode 2 (H1P on)
$ In setting 1, push and hold the BS1 (MODE button) for more than 5 seconds. → Setting
mode 2 is entered and H1P lights.
% Push the BS2 (SET button) several times and match the LED display with the Setting No.
you want.
& Push the BS3 (RETURN button) one time, and the present setting content is displayed.
→ Push the BS2 (SET button) several times and match the LED display with the setting
content (as shown below) you want.
' Push the BS3 (RETURN button) two times. → Returns to $.
( Push the BS1 (MODE button) one time. → Returns to the setting mode 1 and turns H1P off.
Test Operation
: http://splitoff.ru/tehn-doc.html
151
Field Setting
SiE39-404
%
$
Setting
No.
Setting
contents
&
Setting No. indication
Setting No. indication
Setting
contents
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
22
Night-time
low noise
setting
"
)
)
)
)
)
)
"
)
"
)
"
"
)
H1P H2P H3P H4P H5P H6P H7P
OFF
(Factory
setting)
"
)
)
)
)
)
)
"
"
"
"
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
*
*
)
*
*
*
*
"
)
)
)
)
*
)
"
"
)
)
)
)
)
)
)
)
)
*
*
)
"
)
)
)
*
)
)
"
"
"
)
)
)
)
)
)
)
)
)
)
)
*
)
*
)
*
)
)
AM 8:00
(Factory
setting)
"
)
)
)
)
)
*
Low noise
precedence
(Factory
setting)
"
)
)
)
)
)
)
Capacity
precedence
"
)
)
)
)
*
)
60 % of
rated power
consumption
"
)
)
)
)
)
*
70 % of
rated power
consumption
(Factory
setting)
"
)
)
)
)
*
)
80 % of
rated power
consumption
"
)
)
)
*
)
)
OFF
(Factory
setting)
"
)
)
)
)
)
*
Continuous
demand 1
fixed
"
)
)
)
)
*
)
NO
(Factory
set)
"
)
)
)
)
)
"
YES
"
)
)
)
)
"
)
Mode 1
Mode 2
Mode 3
25
External
low noise
setting
"
Night-time
low noise
start setting
"
)
"
"
)
)
"
Mode 1
Mode 2
(Factory
setting)
Mode 3
26
)
"
"
)
"
)
PM 8:00
PM 10:00
(Factory
setting)
PM 0:00
27
29
30
32
12
"
Night-time
low noise
end setting
"
"
)
"
"
AM 6:00
AM 7:00
Capacity
precedence
setting
"
Demand
setting 1
"
Continuous
demand
setting
"
External
low noise /
Demand
setting
"
Setting mode indication section
152
)
)
)
)
)
"
"
)
)
"
"
)
"
"
"
)
"
)
"
)
)
Setting No. indication section
"
)
)
)
Setting contents indication (Initial setting)
Set contents indication section
: http://splitoff.ru/tehn-doc.html
Test Operation
SiE39-404
Field Setting
3.2.4 Setting of Refrigerant Additional Charging Operation
When additional refrigerant is not charged all with outdoor unit in stop mode, operate the
outdoor unit and charge the liquid refrigerant from the service port of liquid stop value. The
additional charging operation is activated by pushbutton switch on the outdoor unit PC board.
[Additional refrigerant charge total flow]
[Additional refrigerant charge total flow]
STEP 1
Confirm LIQ & SUCTION and
Oil equalizing Stop valve closed.
Additional
charge
Turn off the power.
without
Compressor
operation
Charge through Service port of
LIQ. Stop valve.
YES
Is all refrigerant charged?
Open LIQ & SUCTION Stop
valve.
STEP 2
Additional
Open Gas Stop valve.
(Liquid side stop valve : close
Oil equalizing valve : open
in case of multi outdoor
connection system.)
Disconnect charge hose.
charge
with
Compressor
operation
Start additional refrigerant
charge mode.
(Setting Mode 2 : Refer
operation procedure detail on
next page.)
Is all refrigerant charged?
END of charge method.
YES
Open LIQUID Stop valve.
NO
STOP refrigerant charge model
(V2892)
Test Operation
: http://splitoff.ru/tehn-doc.html
153
Field Setting
SiE39-404
[Operation procedure detail]
$ After turning the respective remote switch of indoor and outdoor units off and charging the
refrigerant, turn on the power of indoor and outdoor units.
Do not fail to turn the power off and charge the refrigerant with outdoor unit in stop mode
before adding the refrigerant following this procedure, otherwise resulting in trouble.
% Fully open the stop valve on the gas side and oil equalizing valve for multi outdoor
connection, and do not fail to fully close the stop valve on the liquid side. (If the stop valve on
the liquid side is open, the refrigerant cannot be charged.)
& In Setting mode 2 (H1P : ON) with outdoor unit in stop mode, Set “A Additional refrigerant
charging operation” switch to ON to start the operation. (H2P turns to display TEST
OPERATION (blinks), and “TEST OPERATION” and “IN CENTRALIZED CONTROL” are
displayed on the remote controller.)
' When the refrigerant is charged up to the specified amount, press the RETURN button
(BS3) to stop charging.
The charging operation is automatically stopped after operating for a maximum of about 30
minutes.
If the charging is not complete within 30 minutes, set the A Additional refrigerant charging
operation again to start charging. When the charging immediately stops even by restarting,
the refrigerant is charged excessively. The refrigerant cannot be charged any more.
( Do not fail to fully open the stop valve on the liquid side as soon as disconnecting the
refrigerant charging hose.
(The piping may be burst due to the liquid sealing.)
[Operation state]
• Compressor frequency : 210Hz
• Y1S, Y2S Solenoid valve : Open
• Outdoor unit fan : High pressure control
• Indoor unit expansion valve (All unit) : 1024 pulse
• Indoor unit fan : H tap
3.2.5 Setting of Refrigerant Recovery Mode
When carrying out the refrigerant collection on site, fully open the respective expansion valve of
indoor and outdoor units
[Operation procedure]
$ In setting mode 2 with units in stop mode, set “B Refrigerant Recovery / Vacuuming mode”
to ON. The respective expansion valve of indoor and outdoor units are fully opened. (H2P
turns to display “TEST OPERATION” (blinks), “TEST OPERATION” and “IN CENTRALIZED
CONTROL” are displayed on the remote controller, and the operation is prohibited.
% Collect the refrigerant using a refrigerant recovery unit. (See the instruction attached to the
refrigerant recovery unit for more detal.)
& Press Mode button “BS1” once and reset “Setting Mode 2”.
154
: http://splitoff.ru/tehn-doc.html
Test Operation
SiE39-404
Field Setting
3.2.6 Setting of Vacuuming Mode
In order to perform vacuuming operation at site, fully open the expansion valves of indoor and
outdoor units to turn on some solenoid valves.
[Operating procedure]
$ With Setting Mode 2 while the unit stops, set (B) Refrigerant recovery / Vacuuming mode to
ON. The expansion valves of indoor and outdoor units fully open and some of solenoid
valves open.
(H2P blinks to indicate the test operation, and the remote controller displays "Test
Operation" and "In Centralized control", thus prohibiting operation.)
After setting, do not cancel “Setting Mode 2” until completion of Vacuuming operation.
% Use the vacuum pump to perform vacuuming operation.
& Press Mode button “BS1” once and reset “Setting Mode 2”.
3.2.7 Check Operation
To prevent any trouble in the period of installation at site, the system is provided with a test
operation mode enabling check for incorrect wiring, stop valve left in closed, coming out (or
misplacing with suction pipe thermistor) of discharge pipe thermistor and judgment of piping
length, refrigerant overcharging, and learning for the minimum opening degree of motorized valve.
CHECK OPERATION FUNCTION
LED display (H1P~H7P) (8:ON
Unit stopping
9:BLINKING 3:OFF)
3383333
Press the TEST button for 5 seconds.
Step 1
Pressure equalizing
3933338
10 sec to 10 minutes
Step 2
Cooling start control
3933383
20 sec to 2 minutes
Step 3
Stability waiting operation
3933388
10 minutes
Step4~6
Judgement function
3933833
• Stop valve close check
• Wrong wiring check
• Refrigerant over change check
• Piping length check
3933838
3933883
3 minutes
Step 7
Pump down residual operation
Step 8
Standby for restarting
3933888
5 minutes
3938333
5 minutes
Completion
3.2.8 Power Transistor Check Operation
When the inverter system malfunctions (malfunction of inverter, INV compressor), to locate
where the malfunction occurs, switching to the power transistor check mode of inverter in the
service mode setting enables not to judge the position detection signal malfunction but to output
waveform only during inverter operation. (The waveform can be checked by disconnecting the
wiring of compressor.)
Note:
Test Operation
Be sure to disconnect the compressor wiring when conducting the check operation mentioned
above.
When the output voltage is approx. 50 V (10 Hz) and the voltage balance between phases U-V,
V-W, W-U is within ±5%, the inverter PCB is normal.
: http://splitoff.ru/tehn-doc.html
155
Field Setting
156
SiE39-404
: http://splitoff.ru/tehn-doc.html
Test Operation
SiE39-404
Part 6
Troubleshooting
1. Troubleshooting by Remote Controller ...............................................160
1.1
1.2
1.3
1.4
The INSPECTION / TEST Button.........................................................160
Self-diagnosis by Wired Remote Controller .........................................161
Self-diagnosis by Wireless Remote Controller .....................................162
Operation of The Remote Controller’s Inspection /
Test Operation Button ..........................................................................165
1.5 Remote Controller Service Mode .........................................................166
1.6 Remote Controller Self-Diagnosis Function .........................................168
2. Troubleshooting by Indication on the Remote Controller ....................173
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
2.10
2.11
2.12
2.13
2.14
2.15
2.16
2.17
2.18
2.19
2.20
2.21
2.22
2.23
2.24
2.25
2.26
2.27
2.28
2.29
2.30
Troubleshooting
“A0” Indoor Unit: Error of External Protection Device ...........................173
“A1” Indoor Unit: PC Board Defect.........................................................174
“A3” Indoor Unit: Malfunction of Drain Level Control System (S1L) ......175
“A6” Indoor Unit: Fan Motor (M1F) Lock, Overload...............................177
“A7” Indoor Unit: Malfunction of Swing Flap Motor (MA) .......................178
“A9” Indoor Unit: Malfunction of Moving Part of Electronic
Expansion Valve (20E).........................................................................180
“AF” Indoor Unit: Drain Level above Limit..............................................182
“AJ” Indoor Unit: Malfunction of Capacity Determination Device ..........183
“C4” Indoor Unit: Malfunction of Thermistor (R2T)
for Heat Exchanger ..............................................................................184
“C5” Indoor Unit: Malfunction of Thermistor (R3T) for Gas Pipes..........185
“C9” Indoor Unit: Malfunction of Thermistor (R1T) for Suction Air.........186
“CJ” Indoor Unit: Malfunction of Thermostat Sensor
in Remote Controller ............................................................................187
“E1” Outdoor Unit: PC Board Defect ......................................................188
“E3” Outdoor Unit: Actuation of High Pressure Switch ..........................189
“E4” Outdoor Unit: Actuation of Low Pressure Sensor ..........................190
“E5” Compressor Motor Lock ................................................................191
“E6” Compressor Motor Overcurrent/Lock ............................................192
“E7” Malfunction of Outdoor Unit Fan Motor..........................................193
“E9” Outdoor Unit: Malfunction of Moving Part of Electronic
Expansion Valve (Y1E, Y2E)................................................................195
“F3” Outdoor Unit: Abnormal Discharge Pipe Temperature ..................197
“F6” Refrigerant Overcharged ...............................................................198
“H7” Abnormal Outdoor Fan Motor Signal .............................................199
“H9” Outdoor Unit: Malfunction of Thermistor for Outdoor Air (R1T).....200
“J2” Current Sensor Malfunction...........................................................201
“J3” Outdoor Unit: Malfunction of Discharge Pipe Thermistor
(R3, R31~33T) .....................................................................................202
“J5” Outdoor Unit: Malfunction of Thermistor (R2T)
for Suction Pipe ....................................................................................203
“J6” Outdoor Unit: Malfunction of Thermistor (R4T) for
Outdoor Unit Heat Exchanger ..............................................................204
“J8” Malfunction of Oil Equalizing Pipe Thermistor (R7T).....................205
“J9” Malfunction of Receiver Gas Pipe Thermistor (R5T).....................206
“JA” Outdoor Unit: Malfunction of Discharge Pipe Pressure Sensor.....207
: http://splitoff.ru/tehn-doc.html
157
SiE39-404
2.31 “JC” Outdoor Unit: Malfunction of Suction Pipe Pressure Sensor .........208
2.32 “L4” Outdoor Unit: Malfunction of Inverter Radiating
Fin Temperature Rise...........................................................................209
2.33 “L5” Outdoor Unit: Inverter Compressor Abnormal ...............................210
2.34 “L8” Outdoor Unit: Inverter Current Abnormal.......................................211
2.35 “L9” Outdoor Unit: Inverter Start up Error..............................................212
2.36 “LC” Outdoor Unit: Malfunction of Transmission Between Inverter
and Control PC Board ..........................................................................213
2.37 “P1” Outdoor Unit: Inverter Over-Ripple Protection ...............................215
2.38 “P4” Outdoor Unit: Malfunction of Inverter Radiating Fin
Temperature Rise Sensor ....................................................................216
2.39 “UO” Low Pressure Drop Due to Refrigerant Shortage or
Electronic Expansion Valve Failure......................................................217
2.40 “U1” Reverse Phase, Open Phase.........................................................218
2.41 “U2” Power Supply Insufficient or Instantaneous Failure ......................219
2.42 “U3” Check Operation not executed ......................................................221
2.43 “U4” Malfunction of Transmission Between Indoor Units ......................222
2.44 “U5” Malfunction of Transmission Between Remote Controller
and Indoor Unit.....................................................................................224
2.45 “U7” Malfunction of Transmission Between Outdoor Units ....................225
2.46 “U8” Malfunction of Transmission Between Master and
Slave Remote Controllers ....................................................................227
2.47 “U9” Malfunction of Transmission Between Indoor and Outdoor Units
in the Same System .............................................................................228
2.48 “UA” Excessive Number of Indoor Units ................................................230
2.49 “UC” Address Duplication of Central Remote Controller ........................231
2.50 “UE” Malfunction of Transmission Between Central
Remote Controller and Indoor Unit.......................................................232
2.51 “UF” Refrigerant System not Set, Incompatible Wiring/Piping ...............234
2.52 “UH” Malfunction of System, Refrigerant System
Address Undefined...............................................................................235
3. Troubleshooting (OP: Central Remote Controller) ..............................236
3.1 “UE” Malfunction of Transmission Between Central
Remote Controller and Indoor Unit.......................................................236
3.2 “M1” PC Board Defect ............................................................................237
3.3 “M8” Malfunction of Transmission Between Optional Controllers
for Centralized Control .........................................................................238
3.4 “MA” Improper Combination of Optional Controllers
for Centralized Control .........................................................................239
3.5 “MC” Address Duplication, Improper Setting ..........................................241
4. Troubleshooting (OP: Schedule Timer)...............................................242
4.1 “UE” Malfunction of Transmission Between Central Remote
Controller and Indoor Unit ....................................................................242
4.2 “M1” PC Board Defect ............................................................................244
4.3 “M8” Malfunction of Transmission Between Optional Controllers
for Centralized Control .........................................................................245
4.4 “MA” Improper Combination of Optional Controllers
for Centralized Control .........................................................................246
4.5 “MC” Address Duplication, Improper Setting ..........................................248
5. Troubleshooting (OP: Unified ON/OFF Controller) .............................249
5.1 Operation Lamp Blinks .........................................................................249
158
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
5.2 Display “Under Host Computer Integrate Control” Blinks
(Repeats Single Blink)..........................................................................251
5.3 Display “Under Host Computer Integrate Control” Blinks
(Repeats Double Blink) ........................................................................254
Troubleshooting
: http://splitoff.ru/tehn-doc.html
159
Troubleshooting by Remote Controller
SiE39-404
1. Troubleshooting by Remote Controller
1.1
The INSPECTION / TEST Button
The following modes can be selected by using the [Inspection/Test Operation] button on the
remote control.
Indoor unit settings can be made
• Filter sign time
• Air flow direction
• Others
Local
setting
mode
Depress Inspection/Test Operation button
for more than 4 seconds.
Service data can be obtained.
•
Malfunciton code history
Service
• Temperature data of various sections
mode
Service settings can be made.
• Forced fan ON
• Air flow direction/volume setting
Depress Inspection/Test Operation button
for more than 4 seconds.
Press Inspection/Test Operation button once.
Normal
mode
Press Inspection/Test Operation button once.
Or after 30 minutes
Press Inspection/Test Operation
button once.
After 10 seconds
Following codes can be checked.
• Malfunction codes
• Indoor model code
• Outdoor model code
Inspection
mode
Test
operation
mode
Thermostat is forcibly turned on.
Press Inspection/Test Operation
button once.
160
: http://splitoff.ru/tehn-doc.html
(V0815)
Troubleshooting
SiE39-404
1.2
Troubleshooting by Remote Controller
Self-diagnosis by Wired Remote Controller
Explanation
If operation stops due to malfunction, the remote controller’s operation LED blinks, and
malfunction code is displayed. (Even if stop operation is carried out, malfunction contents are
displayed when the inspection mode is entered.) The malfunction code enables you to tell what
kind of malfunction caused operation to stop. See page 168 for malfunction code and
malfunction contents.
Inspection
display
Displays the
malfunction code.
Inspection/
test buttom
(SL025)
Troubleshooting
: http://splitoff.ru/tehn-doc.html
161
Troubleshooting by Remote Controller
1.3
SiE39-404
Self-diagnosis by Wireless Remote Controller
In the Case of
BRC7C ~ Type
If equipment stops due to a malfunction, the operation indicating LED on the light reception
section flashes.
The malfunction code can be determined by following the procedure described below. (The
malfunction code is displayed when an operation error has occurred. In normal condition, the
malfunction code of the last problem is displayed.)
1. Press the INSPECTION/TEST button to select “Inspection.”
The equipment enters the inspection mode. The “Unit” indication lights and the Unit No.
display shows flashing “0” indication.
2. Set the Unit No.
Press the UP or DOWN button and change the Unit No. display until the buzzer (*1) is
generated from the indoor unit.
*1 Number of beeps
3 short beeps : Conduct all of the following operations.
1 short beep : Conduct steps 3 and 4.
Continue the operation in step 4 until a buzzer remains ON. The continuous buzzer indicates
that the malfunction code is confirmed.
Continuous beep : No abnormality.
3. Press the MODE selector button.
The left “0” (upper digit) indication of the malfunction code flashes.
4. Malfunction code upper digit diagnosis
Press the UP or DOWN button and change the malfunction code upper digit until the
malfunction code matching buzzer (*2) is generated.
! The upper digit of the code changes as shown below when the UP and DOWN buttons are
pressed.
‘Advance’ button
‘Backward’ button
*2 Number of beeps
Continuous beep : Both upper and lower digits matched. (Malfunction code confirmed)
2 short beeps : Upper digit matched.
1 short beep : Lower digit matched.
5. Press the MODE selector button.
The right “0” (lower digit) indication of the malfunction code flashes.
6. Malfunction code lower digit diagnosis
Press the UP or DOWN button and change the malfunction code lower digit until the
continuous malfunction code matching buzzer (*2) is generated.
162
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Remote Controller
! The lower digit of the code changes as shown below when the UP and DOWN buttons are
pressed.
‘Advance’ button
Troubleshooting
‘Backward’ button
: http://splitoff.ru/tehn-doc.html
163
Troubleshooting by Remote Controller
SiE39-404
Normal status
Enters inspection mode from normal
status when the INSPECTION/TEST
button is pressed.
1 Press INSPECTION/TEST button.
If no button is pressed for
1 minute, equipment
returns to normal status.
3 Press
MODE
selector
button.
When MODE selector
button is pressed or no
button is pressed for 1
minute, equipment
returns to normal status.
If no button is pressed for
1 minute, equipment
returns to normal status.
5 Press MODE selector button.
(SF008)
164
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
1.4
Troubleshooting by Remote Controller
Operation of The Remote Controller’s Inspection / Test
Operation Button
Unit
Malfunction code
Inspection
Normal display (No display)
Inspection/test
operation
0
L0
Malfunction code blinks when a malfunction occurs.
Push the button.
Unit
Malfunction code
Inspection
0
L0
Inspection mode
Inspection/test
operation
0 7 1...
F...
C...
J...
Example of capacity code display
Capacity code
Indoor unit system code
Indoor unit type code
Progression code
Display
Example model
FXCQ25
028
FXFQ63
071
Push the button.
Indoor unit system code
Product classification
System classification
1
VRV system
(VAV indoor unit)
2
VRV system
Outdoor air processing unit
F
VRV system
Standard indoor unit
H
VRV system
New ceilling suspended cassette
Display
071
FCJ
Indoor unit model code display
Indoor unit type code
Inspection/test
operation
–––
AA1
Indoor unit model code display
Inspection/test
operation
Push the button.
Test operation
Test operation mode
Inspection/test
operation
Push the button.
Type
Display
Push the button.
Model
A
Wall mounted
FXAQ
C
Double flow
FXCQ
E
Corner
FXKQ
F
Multi flow
FXFQ
H
Ceiling suspended
FXHQ
J
Built-in
FXSQ
L
Floor standing
FXLQ
P
Concealed ceiling duct
FXMQ
L
Concealed floor standing type
FXNQ
6
Multi flow 600×600
FXZQ
3
Slim Ceilling mounted duct
FXDQ
5
New ceilling suspended cassette
FXUQ
Outdoor model code
Display
Type
AA1
VRV System Inverter K Series
Model
RSXYP
RXYP
AA3
R407C VRV PLUS Series
A92
VRV Heat Recovery Series
AA5
High COP type R407C L Series
RSXYP-L
AAA
VRV II
RXYQ-M
RSEYP
(V2775)
Troubleshooting
: http://splitoff.ru/tehn-doc.html
165
Troubleshooting by Remote Controller
1.5
SiE39-404
Remote Controller Service Mode
How to Enter the
Service Mode
Normal operation
mode
Field set
mode
Push the
button for 4 seconds or longer.
Service
mode
Push the
button for 4 seconds or longer.
(VFO020)
Service Mode
Operation
Method
166
1. Select the mode No.
Set the desired mode No. with the
button.
(For wireless remote controller, Mode 43 only can be set.)
2. Select the unit No. (For group control only)
Select the indoor unit No. to be set with the time mode
. (For wireless remote controller,
button.)
3. Make the settings required for each mode. (Modes 41, 44, 45)
In case of Mode 44, 45, push
button to be able to change setting before setting work.
(LCD “code” blinks.)
For details, refer to the table in next page.
4. Define the setting contents. (Modes 44, 45)
Define by pushing the timer
button.
After defining, LCD “code” changes blinking to ON.
5. Return to the normal operation mode.
Push the
button one time.
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Remote Controller
Mode
No
40
Function
Malfunction
hysteresis display
Contents and operation method
Display malfunction hysteresis.
The history No. can be changed with the
button.
Remote controller display example
Unit 1
40
Malfunction code
2-U4
Malfunction code
Hystory No: 1 - 9
1: Latest
(VE007)
41
Display of sensor
and address data
Display various types of data.
Select the data to be displayed with the
button.
Sensor data
0: Thermostat sensor in remote controller.
1: Suction
2: Liquid pipe
3: Gas pipe
Address data
4: Indoor unit address
5: Outdoor unit address
6: BS unit address
7: Zone control address
8: Cool/heat group address
9: Demand / low noise address
Sensor data display
Unit No.
Sensor type
41
1 1
27
Temperature °C
Address display
Unit No.
Address type
41
1 8
1
Address
(VE008)
43
Forced fan ON
Manually turn the fan ON by each unit. (When
you want to search for the unit No.)
By selecting the unit No. with the
button,
you can turn the fan of each indoor unit on
(forced ON) individually.
Unit 1
43
(VE009)
44
Individual setting
Set the fan speed and air flow direction by each
unit
Select the unit No. with the time mode
button.
Set the fan speed with the
button.
Set the air flow direction with the
button.
Unit 1
Code
1 3
Fan speed 1: Low
3: High
44
Air flow direction
P0 - P4
(VE010)
45
Unit No. transfer
Transfer unit No.
Select the unit No. with the
button.
Set the unit No. after transfer with the
button.
Present unit No.
Unit
1
0 2
Code
45
Unit No. after
transfer
(VE011)
46
47
This function is not used by VRV ll R410A Heat Pump 50Hz.
Troubleshooting
: http://splitoff.ru/tehn-doc.html
167
Troubleshooting by Remote Controller
1.6
SiE39-404
Remote Controller Self-Diagnosis Function
The remote controller switches are equipped with a self diagnosis function so that more
appropriate maintenance can be carried out. If a malfunction occurs during operation, the
operation lamp, malfunction code and display of malfunctioning unit No. let you know the
contents and location of the malfunction.
When there is a stop due to malfunction, the contents of the malfunction given below can be
diagnosed by a combination of operation lamp, INSPECTION display of the liquid crystal display
and display of malfunction code. It also lets you know the unit No. during group control.
Operation lamp
Inspection display
Display of indoor unit for which a
malfunction has been detected
Malfunction code
(VL050)
168
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Indoor
Unit
Troubleshooting by Remote Controller
Malfunction Operation Inspection
code
lamp
display
A0
9
9
A1
9
9
A3
9
9
A6
9
9
A7
8
7
A9
9
9
Outdoor
Unit
Outdoor
Unit
Troubleshooting
Unit No.
Malfunction contents
9
9
9
9
9
9
Error of external protection device
PC board defect, E2 PROM defect
Malfunction of drain level control system (33H)
Fan motor (MF) lock, overload
Malfunction of swing flap motor (MA)
Malfunction of moving part of electronic expansion
valve (20E)
Drain level about limit
Malfunction of air filter maintenance
Malfunction of capacity setting
Malfunction of thermistor (R2T) for heat exchange
(loose connection, disconnection, short circuit,
failure)
Malfunction of thermistor (R3T) for gas pipes (loose
connection, disconnection, short circuit, failure)
Malfunction of thermistor (R1T) for air inlet (loose
connection, disconnection, short circuit, failure)
Malfunction of thermostat sensor in remote controller
PC board defect
Actuation of high pressure switch
Actuation of low pressure sensor
Compressor motor lock
Standard compressor lock or over current
Malfunction of outdoor unit fan motor
Malfunction of moving part of electronic expansion
valve (Y1E~3E)
Abnormal discharge pipe temperature
Refrigerant overcharged
Malfunction of High pressure switch
Malfunction of Low pressure switch
Abnormal outdoor fan motor signal
Malfunction of thermistor (R1T) for outdoor air (loose
connection, disconnection, short circuit, failure)
Current sensor malfunction
Malfunction of discharge pipe thermistor (R31~33T)
(loose connection, disconnection, short circuit,
failure)
Malfunction of thermistor (R2T) for suction pipe
(loose connection, disconnection, short circuit,
failure)
Malfunction of thermistor (R4T) for heat exchanger
(loose connection, disconnection, short circuit,
failure)
Malfunction of header thermistor
Malfunction of thermistor (R7T) for oil equalizing pipe.
(loose connection, disconnection, short circuit,
failure)
Malfunction of receiver gas pipe thermistor (R5T)
Malfunction of discharge pipe pressure sensor
Malfunction of suction pipe pressure sensor
Inverter system error
Malfunction of inverter radiating fin temperature rise
Inverter compressor motor grounding, short circuit
Compressor motor coil grounding on short circuit
Inverter current abnormal
Inverter start up error
AF
AH
AJ
C4
8
8
9
9
7
7
9
9
9
9
9
9
C5
9
9
9
C9
9
9
9
CJ
E1
E3
E4
E5
E6
E7
E9
8
9
9
9
9
9
9
9
8
9
9
9
9
9
9
9
8
9
9
9
9
9
9
9
F3
F6
H3
H4
H7
H9
9
9
8
9
9
9
9
9
7
9
9
9
9
9
9
9
9
9
J2
J3
9
9
9
9
9
9
J5
9
9
9
J6
9
9
9
J7
J8
9
9
9
9
9
9
J9
JA
JC
L0
L4
L5
L6
L8
L9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
: http://splitoff.ru/tehn-doc.html
Page
Referred
173
174
175
177
178
180
182
—
183
184
185
186
187
188
189
190
191
192
193
195
197
198
—
—
199
200
201
202
203
204
—
205
206
207
208
—
209
210
—
211
212
169
Troubleshooting by Remote Controller
SiE39-404
Malfunction Operation Inspection
code
lamp
display
Outdoor
Unit
System
Centralized
Control
and
Schedule
Timer
Heat
Reclaim
Ventilation
Unit No.
Malfunction contents
Page
Referred
Malfunction of power unit
Malfunction of transmission between inverter and
control PC board
Inverter over-ripple protection
Malfunction of inverter radiating fin temperature rise
sensor
Low pressure drop due to refrigerant shortage or
electronic expansion valve failure
Reverse phase / open phase
Power supply insufficient or instantaneous failure
Check operation is not conducted.
Malfunction of transmission between indoor and
outdoor units
Malfunction of transmission between remote
controller and indoor unit
Failure of remote controller PC board or setting
during control by remote controller
Malfunction of transmission between outdoor units
Malfunction of transmission between master and
slave remote controllers (malfunction of slave remote
controller)
Malfunction of transmission between indoor unit and
outdoor unit in the same system
Excessive number of indoor units etc.
Address duplication of central remote controller
Malfunction of transmission between central remote
controller and indoor unit
—
213
LA
LC
9
9
9
9
9
9
P1
P4
9
9
9
9
9
9
U0
8
7
9
U1
U2
U3
U4
9
9
9
9
9
9
9
9
9
9
9
9
U5
9
9
9
U5
7
8
7
U7
U8
9
9
9
9
9
7
U9
9
9
9
UA
UC
UE
9
8
9
9
8
9
9
8
9
UF
9
9
9
UH
9
9
9
M1
8 or 7
9
9
M8
8 or 7
9
9
MA
8 or 7
9
9
MC
8 or 7
9
9
64
65
68
6A
6A
6F
6H
94
8
8
8
8
9
8
8
9
7
7
7
7
9
7
7
9
9
9
9
9
9
9
9
9
Refrigerant system not set, incompatible wiring /
piping
Malfunction of system, refrigerant system address
undefined
PC board defect
Malfunction of transmission between optional
controllers for centralized control
Improper combination of optional controllers for
centralized control
Address duplication, improper setting
Indoor unit’s air thermistor error
Outside air thermistor error
Damper system alarm
Damper system + thermistor error
Malfunction of simple remote controller
Malfunction of door switch or connector
Internal transmission error
215
216
217
218
219
221
222
224
224
225
227
228
230
231
232
236
242
234
235
237
244
238
245
239
246
241
248
—
—
—
—
—
—
—
—
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.
170
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Remote Controller
Malfunction code indication by outdoor unit PCB
Monitor mode
Contents of malfunction
To enter the monitor mode, push the
MODE button (BS1) when in “Setting
mode 1”.
Malfunction
code
Abnormal discharge pressure
HPS activated
E3
Abnormal suction pressure
Abnormal Pe
E4
Compressor lock
Detection of INV compressor lock
E5
Activation of OC
Detection of STD1 compressor lock
E6
* Refer P.124 for Monitor mode.
Detection of STD2 compressor lock
Over load, over current,
Instantaneous over current of DC fan motor
abnormal lock of outdoor unit fan motor
Detection of DC fan motor lock
Malfunction of electronic expansion valve
EV1
E7
E9
EV2
<Selection of setting item>
EV3
Push the SET button (BS2) and set
the LED display to a setting item.
Abnormal position signal of outdoor unit fan motor Abnormal position signal of DC fan motor
Faulty sensor of outdoor air temperature
Faulty Ta sensor
Abnormality in water system of heat storage unit
HJ
Transmission error between heat storage unit and controller
HF
Abnormal discharge pipe temperature
Abnormal Td
F3
Abnormal heat exchanger temperature
Refrigerant over charge
F6
Faulty current sensor
Faulty CT1 sensor
J2
Faulty CT2 sensor
<Confirmation of malfunction 1>
Faulty sensor of discharge pipe temperature
Push the RETURN button (BS3)
once to display "First digit" of
malfunction code.
Faulty Tdi sensor
J3
Faulty Tds1 sensor
Faulty Tds2 sensor
<Confirmation of malfunction 2>
Push the SET button (BS2) once to
display "Second digit" of malfunction
code.
H9
HC
Faulty sensor of heat storage unit
* Refer P.124 for Monitor mode.
H7
Detail
description
on next
page.
Faulty sensor of suction pipe temperature
Faulty Ts sensor
J5
Faulty sensor of heat exchanger temperature
Faulty Tb sensor
J6
Faulty sensor of receiver temperature
Faulty Tl sensor
J7
Faulty sensor of oil pressure equalizing pipe temperature
Faulty To sensor
J8
Faulty sensor of subcool heat exchanger temperature
Faulty Tsh sensor
J9
Faulty sensor of discharge pressure
Faulty Pc sensor
JA
Faulty sensor of suction pressure
Faulty Pe sensor
JC
Inverter radiation fin temperature rising
Over heating of inverter radiation fin temperature
L4
DC output over current
Inverter instantaneous over current
L5
Electronic thermal switch
Electronic thermal switch 1
L8
Electronic thermal switch 2
Out-of-step
Speed down after startup
Lightening detection
Stall prevention (Current increasing)
Stall prevention (Limit time)
L9
Stall prevention (Faulty startup)
Abnormal wave form in startup
Out-of-step
<Confirmation of malfunction 3>
Push the SET button (BS2) once to
display "master or slave1 or slave2"
and "malfunction location".
Transmission error between inverter and outdoor unit
Inverter transmission error
LC
Open phase/Power supply imbalance
Imbalance of inverter power supply voltage
P1
Faulty temperature sensor inside switch box
Faulty thermistor of inverter box
P3
Faulty temperature sensor of inverter radiation fin
Faulty thermistor of inverter fin
P4
Incorrect combination of inverter and fan driver
Incorrect combination of inverter and fan driver
PJ
Gas shortage
Gas shortage alarm
U0
Reverse phase
Reverse phase error
U1
Abnormal power supply voltage
Insufficient inverter voltage
U2
Inverter open phase (phase T)
Charging error of capacitor in inverter main circuit
No implementation of test-run
U3
Transmission error between indoor and outdoor unit
I/O transmission error
U4
Transmission error between outdoor units, transmission error
O/O transmission error
U7
Indoor unit system malfunction in other system or
U9
between thermal storage units, duplication of IC address
Push the RETURN button (BS3) and
switches to the initial status of
“Monitor mode”.
Transmission error of other system
other unit of own system
Erroneous on-site setting
Abnormal connection with excessive number of indoor units
UA
Conflict of refrigerant type in indoor units
∗ Push the MODE button (BS1) and
returns to “Setting mode 1”.
Troubleshooting
Faulty system function
Incorrect wiring (Auto address error)
Transmission error in accessory devices, conflict
Malfunction of multi level converter, abnormality in
UJ
in wiring and piping, no setting for system
conflict check
UF
: http://splitoff.ru/tehn-doc.html
UH
171
Troubleshooting by Remote Controller
Malfunction
SiE39-404
Confirmation of malfunction 1
code
LED1
LED2
LED3
LED4
LED5
E3
.
7
8
7
7
Confirmation of malfunction 2
Confirmation of malfunction 3
LED6
LED7
LED1
LED2
LED3
LED4
LED5
LED6
LED7
LED1
LED2
LED3
LED6
LED7
.
.
.
.
.
.
.
.
8
8
8
8
8
8
7
7
7
7
7
7
7
7
7
7
7
7
7
.
.
.
.
.
.
7
7
.
.
.
.
7
.
7
7
.
.
.
.
.
.
.
8
8
8
8
8
8
8
8
8
8
8
8
7
7
7
7
.
7
7
7
7
.
7
.
.
8
7
.
7
7
.
.
.
.
.
.
.
.
.
8
8
8
8
8
8
8
8
7
7
7
7
7
7
7
7
7
.
.
.
.
7
7
7
.
7
.
.
.
7
.
7
.
7
7
7
.
.
.
.
.
.
7
.
.
.
7
7
J3
.
8
7
7
7
.
.
J5
.
.
.
.
.
.
.
.
.
.
8
8
8
8
8
8
8
8
8
8
7
7
7
7
7
7
7
7
7
7
7
7
7
.
.
.
.
7
7
.
.
.
.
7
7
7
.
.
.
7
7
.
.
7
7
.
7
7
7
7
.
7
.
7
.
7
7
7
.
7
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
7
.
.
7
7
7
7
7
7
7
7
.
7
.
.
7
7
7
7
7
7
7
7
7
7
.
7
.
.
7
7
7
7
7
7
.
7
.
7
.
7
7
7
7
7
7
7
7
7
7
.
8
7
.
7
7
.
.
8
8
7
7
.
.
.
.
.
.
.
.
8
8
8
8
8
8
8
8
7
7
7
7
7
7
7
7
.
7
7
7
.
7
7
7
.
7
7
.
.
7
7
7
7
7
.
7
7
7
7
.
7
.
.
7
.
7
.
7
.
.
.
.
.
.
.
.
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
.
.
.
8
8
8
7
7
7
7
7
7
7
.
.
.
7
.
.
7
.
.
.
.
8
8
8
8
8
8
7
7
7
7
7
7
U9
.
8
7
.
7
7
.
.
8
8
7
7
UA
.
8
7
.
7
.
7
.
8
8
7
7
UH
.
.
.
7
8
7
8
7
8
8 : ON
.
.
.
7
.
.
.
7
.
.
.
.
.
.
.
8
8
8
8
8
8
7
7
7
7
7
7
E4
E5
E6
E7
E9
H7
.
7
8
7
.
7
7
.
7
8
7
.
7
.
.
7
8
7
.
.
7
H9
HC
HJ
HF
F3
F6
J2
J6
J7
J8
J9
JA
JC
L4
L5
L8
L9
LC
P1
.
7
8
.
7
7
7
.
7
8
.
7
7
.
P3
P4
PJ
U0
U1
U2
U3
U4
U7
UJ
UF
8 : ON
. : Blink
7 : OFF
Malfunction code 1st
digit display section
. : Blink
7 : OFF
Malfunction code 2nd
digit display section
LED4
Master
Slave 1
Slave 2
172
: http://splitoff.ru/tehn-doc.html
LED5
7 7
7 .
. 7
Malfunction
location
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
2. Troubleshooting by Indication on the Remote
Controller
2.1
“A0” Indoor Unit: Error of External Protection Device
Remote
Controller
Display
A0
Applicable
Models
All indoor unit models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
! Actuation of external protection device
! Improper field set
! Defect of indoor unit PC board
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
External
protection device is
connected to terminals T1
and T2 of the indoor
unit terminal
block.
YES
Actuation of external protection
device.
NO
ON/OFF
input from
outside (mode No. 12,
first code No. 1) has been
set to external protection
device input (second
code No. 03)
by remote
controller.
NO
YES
Change the second code No. to
"01" or "02" .
Indoor unit PC board replacement.
(V2776)
Troubleshooting
: http://splitoff.ru/tehn-doc.html
173
Troubleshooting by Indication on the Remote Controller
2.2
SiE39-404
“A1” Indoor Unit: PC Board Defect
Remote
Controller
Display
A1
Applicable
Models
All indoor unit models
Method of
Malfunction
Detection
Check data from E²PROM.
Malfunction
Decision
Conditions
When data could not be correctly received from the E²PROM
E²PROM : Type of nonvolatile memory. Maintains memory contents even when the power
supply is turned off.
Supposed
Causes
! Defect of indoor unit PC board
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Turn power supply OFF, then
power ON again.
Does
the system return
to normal?
NO
YES
External factor other than
malfunction (for example,
noise etc.).
Replace the indoor unit PC
board.
(V2777)
174
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
2.3
Troubleshooting by Indication on the Remote Controller
“A3” Indoor Unit: Malfunction of Drain Level Control
System (S1L)
Remote
Controller
Display
A3
Applicable
Models
FXCQ, FXFQ, FXZQ, FXSQ, FXKQ, FXDQ, FXMQ, FXUQ, FXHQ (Option), FXMQ200,250M
(Option), FXAQ (Option), FXMQ-MF (Option)
Method of
Malfunction
Detection
By float switch OFF detection
Malfunction
Decision
Conditions
When rise of water level is not a condition and the float switch goes OFF.
Supposed
Causes
!
!
!
!
!
!
Troubleshooting
220~240V power supply is not provided
Defect of float switch or short circuit connector
Defect of drain pump
Drain clogging, upward slope, etc.
Defect of indoor unit PC board
Loose connection of connector
: http://splitoff.ru/tehn-doc.html
175
Troubleshooting by Indication on the Remote Controller
SiE39-404
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is power supply
220~240V provided?
NO
Provide 220~240V power
supply.
YES
The float
switch is connected to
X8A of the indoor unit
PC board.
NO
A short
circuit connector is
connected to
X8A.
NO
Connect either a short circuit
connector or float switch and
turn on again.
YES
The float
switch contact is
forming a short circuit
(continuity check
with X8A or X15A
disconnected)
YES
Becomes
normal when X8A of
the indoor unit PC board
is short circuited
NO
Defect of indoor unit PC board.
YES
Loose connection of connector.
NO
Water builds up
in the drain pan.
NO
YES
YES
The drain
pump is connected
to X25A or terminals Y1
and Y2 of the
indoorunit PC
board.
The float switch
functions normally.
NO
Replace float switch.
Modify the float switch's
connection and turn on again.
NO
Connect the drain pump and
turn on again.
YES
The drain
pump works when
the power supply is reset
for the indoor
unit.
YES
Check the drain piping for
clogging or upward slope, etc.
NO
The voltage
of terminals Y1
and Y2 or X25A is
220~240 V (within
5minutes of resetting
the power
supply).
NO
Replace indoor unit PC board.
YES
Replace the drain pump or
check for dirt, etc.
(V2778)
176
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
2.4
Troubleshooting by Indication on the Remote Controller
“A6” Indoor Unit: Fan Motor (M1F) Lock, Overload
Remote
Controller
Display
A6
Applicable
Models
All indoor units
Method of
Malfunction
Detection
Detection by failure of signal for detecting number of turns to come from the fan motor
Malfunction
Decision
Conditions
When number of turns can’t be detected even when output voltage to the fan is maximum
Supposed
Causes
! Fan motor lock
! Disconnected or faulty wiring between fan motor and PC board
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the
wiring from the fan
motor securely connected
to connectors on the
indoor unit PC
board?
NO
Connect the wiring and turn on
again.
YES
Wiring
between the
indoor unit PC board and
fan motor is
disconnected.
YES
Fix the wiring and turn on again.
NO
Does the fan motor run?
NO
YES
Replace the indoor unit PC board.
Replace the fan motor.
(V2779)
Troubleshooting
: http://splitoff.ru/tehn-doc.html
177
Troubleshooting by Indication on the Remote Controller
2.5
SiE39-404
“A7” Indoor Unit: Malfunction of Swing Flap Motor (MA)
Remote
Controller
Display
A7
Applicable
Models
FXCQ, FXHQ, FXKQ
Method of
Malfunction
Detection
Utilizes ON/OFF of the limit switch when the motor turns.
Malfunction
Decision
Conditions
When ON/OFF of the microswitch for positioning cannot be reversed even though the swing flap
motor is energized for a specified amount of time (about 30 seconds).
Supposed
Causes
!
!
!
!
178
Defect of swing motor
Defect of connection cable (power supply and limit switch)
Defect of air flow direction adjusting flap-cam
Defect of indoor unit PC board
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is power supply
220~240V provided?
NO
Provide 220~240V power
supply.
YES
Indoor unit
is a model equipped
with a swing flap
function
NO
Replace indoor unit PC board.
YES
The swing
motor works when
the power supply is turned
off and then back
on.
YES
The connector
is connected to X9A of
the indoor unit PC
board.
NO
Connect the connector to X9A
and turn on again.
YES
NO
The limit switch
functions normally.
NO
Replace swing motor.
YES
After
turning
the swing-flap
ON and then
stopping with the
remote controller, the
voltage of X6A of the indoor
unit PC board is 220 ~ 240
VAC (60 Hz) / 220 VAC
(50 Hz) when turnedon
again (within 30
seconds of
turning on
again).
The connecting
cable is short-circuited
or disconnected.
YES
Replace the limit switch
connecting cable.
NO
NO
Replace indoor unit PC board.
YES
The connecting cable
has no continuity.
YES
Replace the power supply
connecting cable.
NO
NO
When
the air flow
direction flap's cam
mechanism is disconnected
from the swing motor,
operation is normal
when turned
on again.
Replace swing motor.
YES
Take the cam mechanism
apart, reassemble and turn on
again.
(V2780)
Troubleshooting
: http://splitoff.ru/tehn-doc.html
179
Troubleshooting by Indication on the Remote Controller
2.6
SiE39-404
“A9” Indoor Unit: Malfunction of Moving Part of Electronic
Expansion Valve (20E)
Remote
Controller
Display
A9
Applicable
Models
All indoor unit models
Method of
Malfunction
Detection
Detection by failure of signal for detecting number of turns to come from the fan motor
Malfunction
Decision
Conditions
When number of turns can’t be detected even when output voltage to the fan is maximum
Supposed
Causes
! Malfunction of moving part of electronic expansion valve
! Defect of indoor unit PC board
! Defect of connecting cable
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
The
electronic
expansion valve is
connected to X7A of the
indoor unit PC
board.
NO
After connecting, turn the power
supply off and then back on.
YES
Normal
when coil check
(∗1) of the moving part of
the electronic expansion
valve is
checked.
NO
Replace the moving part of the
electronic expansion valve.
YES
The connecting
cable is short-circuited or
disconnected.
YES
Replace the connecting cable.
NO
If you turn the power supply off
and turn on again, and it still does
not help, replace the indoor unit
PC board.
(V2781)
180
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
∗1: Coil check method for the moving part of the electronic expansion valve
Discount the electronic expansion valve from the PC board and check the continuity between
the connector pins.
(Normal)
Pin No.
1. White
2. Yellow
3. Orange
4. Blue
1. White
2. Yellow
×
3. Orange
"
Approx.
300Ω
×
4. Blue
×
"
Approx.
300Ω
×
5. Red
"
Approx.
150Ω
×
"
Approx.
150Ω
×
5. Red
6. Brown
×
"
Approx.
150Ω
×
"
Approx.
150Ω
×
6. Brown
": Continuity
×: No continuity
Troubleshooting
: http://splitoff.ru/tehn-doc.html
181
Troubleshooting by Indication on the Remote Controller
2.7
SiE39-404
“AF” Indoor Unit: Drain Level above Limit
Remote
Controller
Display
AF
Applicable
Models
FXCQ, FXFQ, FXZQ, FXSQ, FXKQ, FXMQ, FXDQ, FXMQ-MF, FXUQ
Method of
Malfunction
Detection
Water leakage is detected based on float switch ON/OFF operation while the compressor is in
non-operation.
Malfunction
Decision
Conditions
When the float switch changes from ON to OFF while the compressor is in non-operation.
Supposed
Causes
! Humidifier unit (optional accessory) leaking
! Defect of drain pipe (upward slope, etc.)
! Defect of indoor unit PC board
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Field drain
YES
piping has a defect such as
upward sloping.
Modify the drain piping.
NO
A humidifier
unit (optional accessory)
is installed on the
indoor unit.
YES
Check if the humidifier unit is
leaking.
NO
Defect of indoor unit PC board.
(V2782)
182
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
2.8
Troubleshooting by Indication on the Remote Controller
“AJ” Indoor Unit: Malfunction of Capacity Determination
Device
Remote
controller display
AJ
Applicable
Models
All indoor unit models
Method of
Malfunction
Detection
Capacity is determined according to resistance of the capacity setting adaptor and the memory
inside the IC memory on the indoor unit PC board, and whether the value is normal or abnormal
is determined.
Malfunction
Decision
Conditions
Operation and:
1. When the capacity code is not contained in the PC board’s memory, and the capacity setting
adaptor is not connected.
2. When a capacity that doesn’t exist for that unit is set.
Supposed
Causes
! You have forgotten to install the capacity setting adaptor.
! Defect of indoor unit PC board
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
The indoor
unit PC board was replaced
with a replacement
PC board.
NO
Replace the indoor unit PC board.
YES
The indoor
unit is a model that
requires installation of a
capacity setting adaptor
when replacing the
PC board.
YES
NO
Replace the indoor unit PC board.
Install a capacity setting adaptor.
(V2783)
Troubleshooting
: http://splitoff.ru/tehn-doc.html
183
Troubleshooting by Indication on the Remote Controller
2.9
SiE39-404
“C4” Indoor Unit: Malfunction of Thermistor (R2T) for Heat
Exchanger
Remote
Controller
Display
C4
Applicable
Models
All indoor unit models
Method of
Malfunction
Detection
Malfunction detection is carried out by temperature detected by heat exchanger thermistor.
Malfunction
Decision
Conditions
When the heat exchanger thermistor becomes disconnected or shorted while the unit is running.
Supposed
Causes
! Defect of thermistor (R2T) for liquid pipe
! Defect of indoor unit PC board
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Connector
is connected to X12A
of the indoor unit PC
board.
NO
Connect the thermistor and turn
on again.
YES
Resistance
is normal when
measured after
NO
disconnecting the thermistor
(R2T) from the indoor
unit PC board
(3.5kΩ~
360kΩ)
YES
Replace the thermistor (R2T).
Replace the indoor unit PC board.
(V2784)
∗2: Refer to thermistor resistance / temperature characteristics table on P311.
184
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
2.10 “C5” Indoor Unit: Malfunction of Thermistor (R3T) for Gas
Pipes
Remote
Controller
Display
C5
Applicable
Models
All indoor unit models
Method of
Malfunction
Detection
Malfunction detection is carried out by temperature detected by gas pipe thermistor.
Malfunction
Decision
Conditions
When the gas pipe thermistor becomes disconnected or shorted while the unit is running.
Supposed
Causes
! Defect of indoor unit thermistor (R3T) for gas pipe
! Defect of indoor unit PC board
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Connector is
connected to X11A of
the indoor unit PC
board.
NO
Connect the thermistor and turn
on again.
YES
Resistance
is normal when
measured after
NO
disconnecting the thermistor
(R3T) from the indoor
unit PC board.
(0.6kΩ~
360kΩ)
YES
Replace the thermistor (R3T).
Replace the indoor unit PC board.
(V2785)
∗2: Refer to thermistor resistance / temperature characteristics table on P311.
Troubleshooting
: http://splitoff.ru/tehn-doc.html
185
Troubleshooting by Indication on the Remote Controller
SiE39-404
2.11 “C9” Indoor Unit: Malfunction of Thermistor (R1T) for
Suction Air
Remote
Controller
Display
C9
Applicable
Models
AII indoor unit models
Method of
Malfunction
Detection
Malfunction detection is carried out by temperature detected by suction air temperature
thermistor.
Malfunction
Decision
Conditions
When the suction air temperature thermistor becomes disconnected or shorted while the unit is
running.
Supposed
Causes
! Defect of indoor unit thermistor (R1T) for air inlet
! Defect of indoor unit PC board
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Connector
is connected to X13A of
the indoor unit PC
board.
YES
NO
Resistance
is normal when
measured after
NO
disconnecting the thermistor
(R1T) from the indoor
unit PC board.
(7.2kΩ~
112kΩ)
YES
Connect the thermistor and turn
on again.
Replace the thermistor (R1T).
Replace the indoor unit PC board.
(V2786)
∗2: Refer to thermistor resistance / temperature characteristics table on P311.
186
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
2.12 “CJ” Indoor Unit: Malfunction of Thermostat Sensor in
Remote Controller
Remote
Controller
Display
CJ
Applicable
Models
AII indoor unit models
Method of
Malfunction
Detection
Malfunction detection is carried out by temperature detected by remote controller air
temperature thermistor. (Note1)
Malfunction
Decision
Conditions
When the remote controller air temperature thermistor becomes disconnected or shorted while
the unit is running.
Supposed
Causes
! Defect of remote controller thermistor
! Defect of remote controller PC board
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Turn power supply OFF, then
power ON again.
Is "CJ"
displayed on the remote
controller?
NO
YES
Replace remote controller.
External factor other than
equipment malfunction.
(for example, noise etc.)
(V2787)
Note:
In case of remote controller thermistor malfunction, unit is still operable by suction air thermistor
on indoor unit.
∗2: Refer to thermistor resistance / temperature characteristics table on P311.
Troubleshooting
: http://splitoff.ru/tehn-doc.html
187
Troubleshooting by Indication on the Remote Controller
SiE39-404
2.13 “E1” Outdoor Unit: PC Board Defect
Remote
Controller
Display
E1
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Check data from E²PROM
Malfunction
Decision
Conditions
When data could not be correctly received from the E²PROM
E²PROM : Type of nonvolatile memory. Maintains memory contents even when the power
supply is turned off.
Supposed
Causes
! Defect of outdoor unit PC board (A1P)
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Turn off the power once and
turn on again.
Return to normal?
NO
YES
External factor other than
malfunction (for example,
noise etc.).
Replace the outdoor unit
main P.C. Board A1P.
(V3064)
188
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
2.14 “E3” Outdoor Unit: Actuation of High Pressure Switch
Remote
Controller
Display
E3
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Abnormality is detected when the contact of the high pressure protection switch opens.
Malfunction
Decision
Conditions
Error is generated when the HPS activation count reaches the number specific to the operation
mode.
Supposed
Causes
!
!
!
!
!
Actuation of outdoor unit high pressure switch
Defect of High pressure switch
Defect of outdoor unit PC board
Instantaneous power failure
Faulty high pressure sensor
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Are the HPS
connectors connected
to the outdoor main
P.C.Board?
H1
YES
Contact
S1PH or S2PH
is open.
NO
Connect the connector and
operate again.
YES
Actuation of high pressure switch.
H1
NO
Operation
is normal when turned
on again by remote
controller.
YES
There was an instantaneous
power failure or a past safety
device actuated. Re-check
refrigerant system.
NO
Replace outdoor unit PC board
A1P.
(V3065)
H1: Actuation of high pressure switch (HPS)
• The outdoor unit PC board’s connector is disconnected.
• Is the outdoor unit heat exchanger dirty?
• Defect of outdoor fan
• Is the refrigerant over-charged?
• Faulty high pressure sensor
Troubleshooting
: http://splitoff.ru/tehn-doc.html
189
Troubleshooting by Indication on the Remote Controller
SiE39-404
2.15 “E4” Outdoor Unit: Actuation of Low Pressure Sensor
Remote
Controller
Display
E4
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Error is generated when the low pressure is dropped under specific pressure.
Supposed
Causes
!
!
!
!
Abnormal drop of low pressure (Lower than 0.07MPa)
Defect of low pressure sensor
Defect of outdoor unit PC board
Stop valve is not opened.
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
NO
Is stop valve opened?
Open stop valve.
YES
Low pressure
at stop due to malfunction
is 0.07 MPa.
YES
Out of gas, refrigerant system
clogging, wiring and piping wrong
connection, stop valve closed,
electronic expantion valve fully
close malfunction.
NO
Measure
the voltage (VL)
of X45A pin No. (2) - (3)
of outdoor PC board (A2P).∗1 YES
Is the relationship
between low
voltage and VL
normal?
Replace the low pressure sensor.
NO
Replace outdoor unit PC board A1P.
(V2791)
∗1: Voltage measurement point
Outdoor unit PC board A1P
+5V
Red
Black
GND
Microcomputer
A/D input
White
*2 Measure voltage (DC) within this space.
Low pressure sensor
X45A
(blue)
(V2792)
∗2: Refer to pressure sensor, pressure / voltage characteristics table on P313.
190
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
2.16 “E5” Compressor Motor Lock
Remote
Controller
Display
E5
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Inverter PC board takes the position signal from UVWN line connected between the inverter and
compressor, and detects the position signal pattern.
Malfunction
Decision
Conditions
The position signal with 3 times cycle as imposed frequency is detected when compressor
motor operates normally, but 2 times cycle when compressor motor locks. When the position
signal in 2 times cycle is detected.
Supposed
Causes
!
!
!
!
!
Compressor lock
High differential pressure (0.5MPa or more)
Incorrect UVWN wiring
Faulty inverter PC board
Stop valve is left in closed.
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Check the installation
conditions.
Is the stop valve open?
NO
Open the stop valve.
YES
Is the UVWN wiring
normal?
NO
Connect correctly.
YES
Is high
differential pressure
starting? (0.5MPa
or more)
NO
Check and see
whether compressor is
short-circuited or
ground.
YES
YES
Remedy the cause.
Replace the compressor.
NO
Are inverter
output voltages the same
for 3 phases?
NO
Replace the inverter PC
board (A2P).
YES
Does low or
high pressure vary
even instantaneously when
restarting
compressor?
NO
YES
Replace the compressor.
(V2793)
Troubleshooting
: http://splitoff.ru/tehn-doc.html
191
Troubleshooting by Indication on the Remote Controller
SiE39-404
2.17 “E6” Compressor Motor Overcurrent/Lock
Remote
Controller
Display
E6
Applicable
Models
Outdoor unit
Method of
Malfunction
Detection
Detects the overcurrent with current sensor (CT).
Malfunction
Decision
Conditions
Malfunction is decided when the detected current value exceeds the below mentioned value for
2 seconds.
! 400 V unit : 15.0 A
Supposed
Causes
!
!
!
!
!
Closed stop value
Obstacles at the discharge port
Improper power voltage
Faulty magnetic switch
Faulty compressor
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the stop valve open?
NO
Open the stop valve.
YES
Obstacle
exists around the air
discharge port.
YES
Remove the obstacle.
NO
Is the power
supply voltage
normal?
YES
Is the
magnetic switch
(52C) normal?
YES
NO
NO
Correct the power voltage.
Replace the magnetic
switch.
Replace the compressor.
(V3051)
192
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
2.18 “E7” Malfunction of Outdoor Unit Fan Motor
Remote
Controller
Display
E7
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Malfunction of fan motor system is detected according to the fan speed detected by hall IC
when the fan motor runs.
Malfunction
Decision
Conditions
! When the fan runs with speed less than a specified one for 15 seconds or more when the fan
motor running conditions are met
! When connector detecting fan speed is disconnected
! When malfunction is generated 4 times, the system shuts down.
Supposed
Causes
! Malfunction of fan motor
! The harness connector between fan motor and PC board is left in disconnected, or faulty
connector
! Fan does not run due to foreign matters tangled
! Clearing condition: Operate for 5 minutes (normal)
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Caution
Connector
of fan motor is
disconnected.
YES
Connect the connector.
NO
Harness connector
between compressor
inverter PCB and fan
inverter PCB
(A2P, A3P) is
disconnected.
YES
Connect the harness
connector.
NO
Is there any
obstacle around
the fan?
NO
Can the fan
be turned smoothly
with hand after disconnect
the connector of
fan motor?
YES
Remove the obstacle.
NO
Replace the fan motor of
outdoor unit.
YES
1A
(V3076)
Troubleshooting
: http://splitoff.ru/tehn-doc.html
193
Troubleshooting by Indication on the Remote Controller
SiE39-404
Troubleshooting
1A
Check No. 12
Check on pulse input of
position signal of fan inverter
PCB
Is the LED
(HAP) on fan inverter
PCB blinking?
NO
Replace the fan inverter
PCB.
YES
Check No. 8
Check on connector of fan
motor (Power supply cable)
Are the
resistance values
between phases of
U, V, W balanced?
Is there any short
circuiting between
phases of
U, V, W?
NO
Replace the fan motor of
outdoor unit.
YES
Check No. 9
Check on connector of fan
motor (Signal wire)
Is the
resistance value
between Vcc and UVW,
and GND and UVW
balanced?
NO
YES
Replace the fan motor of
outdoor unit.
Replace the fan inverter
PCB.
(V3077)
Note:
194
Refer check 8, 9 and 12 to P.255~256.
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
2.19 “E9” Outdoor Unit: Malfunction of Moving Part of
Electronic Expansion Valve (Y1E, Y2E)
Remote
Controller
Display
E9
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Check disconnection of connector
Check continuity of expansion valve coil
Malfunction
Decision
Conditions
Error is generated under no common power supply when the power is on.
Supposed
Causes
! Defect of moving part of electronic expansion valve
! Defect of outdoor unit PC board (A1P)
! Defect of connecting cable
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Turn power supply off, and
turn power supply on again.
Return to normal?
YES
External factor other than
malfunction (for example, noise
etc.).
NO
Electronic
expansion valve is
connected to X26A and
X28A of outdoor unit
PC board
(A1P).
NO
* X26A only for RXYQ5M
After connecting, turn the power
off and then back on again.
YES
Normal
when coil
check (∗1) of the moving
part of the electronic
expansion valve is
checked.
NO
Replace the moving part of the
electronic expansion valve.
YES
The connecting
cable is short-circuited or
disconnected.
NO
YES
Replace the connecting cable.
Replace outdoor unit PC board
A1P.
(V3067)
Troubleshooting
: http://splitoff.ru/tehn-doc.html
195
Troubleshooting by Indication on the Remote Controller
SiE39-404
∗1 Coil check method for the moving part of the electronic expansion valve
Disconnect the electronic expansion valve from the PC board and check the continuity between
the connector pins.
(Normal)
Pin No.
1. White
2. Yellow
3. Orange
4. Blue
5. Red
6. Brown
1. White
2. Yellow
×
3. Orange
*
×
4. Blue
×
*
×
5. Red
"
×
"
×
6. Brown
×
"
×
"
×
* : Continuity Approx. 300Ω
" : Continuity Approx. 150Ω
× : No continuity
196
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
2.20 “F3” Outdoor Unit: Abnormal Discharge Pipe
Temperature
Remote
Controller
Display
F3
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Abnormality is detected according to the temperature detected by the discharge pipe
temperature sensor.
Malfunction
Decision
Conditions
! When the discharge pipe temperature rises to an abnormally high level
! When the discharge pipe temperature rises suddenly
Supposed
Causes
! Faulty discharge pipe temperature sensor
! Faulty connection of discharge pipe temperature sensor
! Faulty outdoor unit PCB
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Discharge pipe
temperature is 115°C
or higher.
YES
Out of gas, compression defect,
etc. Defect of the refrigerant
system.
NO
Are
the characteristics
of the discharge pipe
thermistor normal?
(3.5~400KΩ)
YES
NO
Replace the discharge pipe
thermistor.
Replace outdoor unit PC board
A2P.
(V3068)
∗2: Refer to thermistor resistance / temperature characteristics table on P311.
Troubleshooting
: http://splitoff.ru/tehn-doc.html
197
Troubleshooting by Indication on the Remote Controller
SiE39-404
2.21 “F6” Refrigerant Overcharged
Remote
Controller
Display
F6
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Refrigerant overcharge is detected from the receiver gas pipe temperature during test
operation.
Malfunction
Decision
Conditions
When the receiver gas pipe temperature is lower than evaporating temperature during test
operation.
Supposed
Causes
! Refrigerant overcharge
! Disconnection of the receiver gas pipe thermistor
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the
receiver gas pipe
temperature thermistor
installed the gas relief
pipe on top of
receiver?
NO
Install thermistor correctly.
YES
Is the
characteristic of the
receiver gas pipe
thermistor
normal?
YES
NO
Replace thermistor.
Refrigerant overcharged.
(V2797)
198
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
2.22 “H7” Abnormal Outdoor Fan Motor Signal
Remote
Controller
Display
H7
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Detection of abnormal signal from fan motor.
Malfunction
Decision
Conditions
In case of detection of abnormal signal at starting fan motor.
Supposed
Causes
! Abnormal fan motor signal (circuit malfunction)
! Broken, short or disconnection connector of fan motor connection cable
! Fan Inverter PC board malfunction
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Turn power off.
Is the fan
motor connector
NO
X2A connected to PC board
for Fan inverter
correctly?
Connect correctly.
YES
Check of fan motor connector.
(H1)
The
resistance of
fan motor read wire
connector pins between
Vcc-UVW and
GND-UVW
balanced?
NO
Replace fan motor.
YES
Replace fan inverter PC Board.
(A3P)
(V3069)
H1: Disconnect connector (X2A) and measure the following resistance.
X2A
5 Gray
GND
4 Pink
Vcc
3 Orange
W
2 Blue
V
1 Yellow
U
Measure the
resistance
between
Vcc-UVW and
GND-UVW.
(V2799)
Troubleshooting
: http://splitoff.ru/tehn-doc.html
199
Troubleshooting by Indication on the Remote Controller
SiE39-404
2.23 “H9” Outdoor Unit: Malfunction of Thermistor for Outdoor
Air (R1T)
Remote
Controller
Display
H9
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
The abnormal detection is based on current detected by current sensor.
Malfunction
Decision
Conditions
When the outside air temperature sensor has short circuit or open circuit.
Supposed
Causes
! Defect of thermistor (R1T) for outdoor air
! Defect of outdoor unit PC board (A1P)
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Connector is
connected to X44A of
outdoor PC board
(A1P).
NO
Connect the thermistor and turn
on again.
YES
Resistance
is normal when
measured after
disconnecting the thermistor
(R1T) from the outdoor
unit PC board.
(3.5kΩ~
360kΩ)
YES
NO
Replace the thermistor (R1T)
Replace outdoor unit PC board
A1P.
(V3070)
The alarm indicator is displayed when the fan only is being used also.
∗2: Refer to thermistor resistance / temperature characteristics table on P311.
200
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
2.24 “J2” Current Sensor Malfunction
Remote
Controller
Display
J2
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Malfunction is detected according to the current value detected by current sensor.
Malfunction
Decision
Conditions
When the current value detected by current sensor becomes 5A or lower, or 40A or more during
standard compressor operation.
Supposed
Causes
! Faulty current sensor
! Faulty outdoor unit PC board
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the
connector for
current sensor
connected to X30A, X31A
on outdoor unit
PC board
(A1P)?
NO
Connect the connector, and
operate unit again.
YES
Is the
current sensor
mounted on the T-phase
wire?
YES
NO
Mount the current sensor correctly,
and operate unit again.
Replace current sensor and outdoor
unit PC board.
(V3071)
Troubleshooting
: http://splitoff.ru/tehn-doc.html
201
Troubleshooting by Indication on the Remote Controller
SiE39-404
2.25 “J3” Outdoor Unit: Malfunction of Discharge Pipe
Thermistor (R3, R31~33T)
Remote
Controller
Display
J3
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by discharge pipe temperature
thermistor.
Malfunction
Decision
Conditions
When a short circuit or an open circuit in the discharge pipe temperature thermistor is detected.
Supposed
Causes
! Defect of thermistor (R31T, R32T or R33T) for outdoor unit discharge pipe
! Defect of outdoor unit PC board (A1P)
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Connector
is connected to X34A
of outdoor unit
PC board
(A1P).
NO
Connect the thermistor and turn
on again.
YES
Resistance
is normal when
measured after
disconnecting the thermistor
R31, 32T or R33T from the
outdoor unit PC board.
(3.5kΩ~
400kΩ)
NO
YES
Replace the thermistor (R31, 32T
or R33T)
Replace outdoor unit PC board
A1P.
(V3072)
The alarm indicator is displayed when the fan is being used also.
Note:
202
5 HP class ··· R3T
8~12 HP class ··· R31T, R32T
14, 16Hp class ··· R31T, R32T and R33T
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
2.26 “J5” Outdoor Unit: Malfunction of Thermistor (R2T) for
Suction Pipe
Remote
Controller
Display
J5
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by the suction pipe temperature
thermistor.
Malfunction
Decision
Conditions
When a short circuit or an open circuit in the suction pipe temperature thermistor is detected.
Supposed
Causes
! Defect of thermistor (R2T) for outdoor unit suction pipe
! Defect of outdoor unit PC board (A1P)
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Connector
is connected to
X25A, of outdoor unit
PC board.
(A1P)
NO
Connect the thermistor and turn
on again.
YES
Resistance
is normal when
measured after
NO
disconnecting the thermistor
(R2T) from the outdoor
unit PC board.
(3.5kΩ ~
360kΩ)
YES
Replace the thermistor R2T.
Replace outdoor unit PC board
A1P.
(V3073)
∗2: Refer to thermistor resistance / temperature characteristics table on P311.
Troubleshooting
: http://splitoff.ru/tehn-doc.html
203
Troubleshooting by Indication on the Remote Controller
SiE39-404
2.27 “J6” Outdoor Unit: Malfunction of Thermistor (R4T) for
Outdoor Unit Heat Exchanger
Remote
Controller
Display
J6
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by the heat exchanger thermistor.
Malfunction
Decision
Conditions
When a short circuit or an open circuit in the heat exchange thermistor is detected.
Supposed
Causes
! Defect of thermistor (R4T) for outdoor unit coil
! Defect of outdoor unit PC board (A1P)
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Connector
is connected to X37A
of outdoor unit PC
board (A1P).
NO
Connect the thermistor and turn
on again.
YES
Resistance
is normal when
measured after
NO
disconnecting the thermistor
R4T from the indoor
unit PC board.
(3.5kΩ~
360kΩ)
YES
Replace the thermistor R4T.
Replace outdoor unit PC board
A1P.
(V3074)
∗2: Refer to thermistor resistance / temperature characteristics table on P311.
204
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
2.28 “J8” Malfunction of Oil Equalizing Pipe Thermistor (R7T)
Remote
Controller
Display
J8
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Malfunction is detected according to the temperature detected by oil equalizing pipe thermistor.
Malfunction
Decision
Conditions
When the oil equalizing pipe thermistor is short circuited or open.
Supposed
Causes
! Faulty oil equalizing pipe thermistor (R7T)
! Faulty outdoor unit PC board
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is
the connector
for oil equalizing
pipe thermistor
connected to X37A on
outdoor unit PC
board (A1P)?
NO
Connect thermistor and operate
unit again.
YES
Is the
resistance
measured after
removing the thermistor
(R7T) from outdoor unit PC
board normal?
(3.5 kΩ to
360 kΩ)
YES
NO
Replace thermistor (R7T).
Replace outdoor unit PC board
(A1P).
(V3075)
∗2: Refer to thermistor resistance / temperature characteristics table on P311.
Troubleshooting
: http://splitoff.ru/tehn-doc.html
205
Troubleshooting by Indication on the Remote Controller
SiE39-404
2.29 “J9” Malfunction of Receiver Gas Pipe Thermistor (R5T)
Remote
Controller
Display
J9
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Malfunction is detected according to the temperature detected by receiver gas pipe thermistor.
Malfunction
Decision
Conditions
When the receiver gas pipe thermistor is short circuited or open.
Supposed
Causes
! Faulty receiver gas pipe thermistor (R5T)
! Faulty outdoor unit PC board
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is
the connector
for oil equalizing
pipe thermistor
connected to X37A on
outdoor unit PC
board (A1P)?
NO
Connect thermistor and operate
unit again.
YES
Is the
resistance
measured after
removing the thermistor
(R7T) from outdoor unit PC
board normal?
(3.5 kΩ to
360 kΩ)
YES
NO
Replace thermistor (R7T).
Replace outdoor unit PC board
(A1P).
(V3075)
∗2: Refer to thermistor resistance / temperature characteristics table on P311.
206
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
2.30 “JA” Outdoor Unit: Malfunction of Discharge Pipe Pressure
Sensor
Remote
Controller
Display
JA
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Malfunction is detected from the pressure detected by the high pressure sensor.
Malfunction
Decision
Conditions
When the discharge pipe pressure sensor is short circuit or open circuit.
Supposed
Causes
! Defect of high pressure sensor system
! Connection of low pressure sensor with wrong connection.
! Defect of outdoor unit PC board.
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
The high
pressure sensor is
connected to X46A of
outdoor unit PC
board (A1P).
NO
Connect the high pressure sensor
and turn on again.
YES
The
relationship
between the ∗1
VH and high pressure
YES
is normal (see ∗2) when
voltage is measured between
X46A pins (1) and (3) of
outdoor unit PC
board (A1P)
(see ∗1).
Replace outdoor unit PC board
A1P.
NO
Replace the high pressure sensor.
(V2806)
∗1: Voltage measurement point
Outdoor unit PC board A2P
+5V
Red
Black
GND
White
Microcomputer
A/D input
High pressure sensor
X46A
*2 Measure DC voltage here.
(V2807)
∗2: Refer to pressure sensor, pressure / voltage characteristics table on P313.
Troubleshooting
: http://splitoff.ru/tehn-doc.html
207
Troubleshooting by Indication on the Remote Controller
SiE39-404
2.31 “JC” Outdoor Unit: Malfunction of Suction Pipe Pressure
Sensor
Remote
Controller
Display
JC
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Malfunction is detected from pressure detected by low pressure sensor.
Malfunction
Decision
Conditions
When the suction pipe pressure sensor is short circuit or open circuit.
Supposed
Causes
! Defect of low pressure sensor system
! Connection of high pressure sensor with wrong connection.
! Defect of outdoor unit PC board.
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
The low
pressure sensor is
connected to X45A (blue)
of outdoor unit PC
board (A1P).
NO
Connect low pressure sensor
property and restart system.
YES
The
relationship
between the ∗1
VH and low pressure is
normal (see ∗2) when voltage
is measured between X45A pins
(2) and (3) of outdoor unit
PC board (A1P)
(see ∗1).
YES
Replace outdoor unit PC board
A1P.
NO
Replace the low pressure sensor.
(V2808)
∗1: Voltage measurement point
Outdoor unit PC board A2P
+5V
Low pressure sensor
X45A
Red
Black
GND
Microcomputer
A/D input
White
*2 Measure voltage here.
(V2809)
∗2: Refer to pressure sensor, pressure/voltage characteristics table on P313.
208
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
2.32 “L4” Outdoor Unit: Malfunction of Inverter Radiating Fin
Temperature Rise
Remote
Controller
Display
L4
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Fin temperature is detected by the thermistor of the radiation fin.
Malfunction
Decision
Conditions
When the temperature of the inverter radiation fin increases above 89°C.
Supposed
Causes
! Actuation of fin thermal (Actuates above 89°C)
! Defect of inverter PC board
! Defect of fin thermistor
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Temperature
of the radiator fin rises.
Actuates at min.
89 °C
YES
NO
Resistance
check of the radiator fin
thermistor
Abnormal
Defect of power unit radiation.
• Intake port is clogged
• Radiator fin is dirty
• Outdoor temperature is high
Replace the thermistor.
Normal
NO
Is reset possible?
YES
Replace the inverter PC board
Reset and operate.
(V2811)
∗2: Refer to thermistor resistance / temperature characteristics table on P311.
Troubleshooting
: http://splitoff.ru/tehn-doc.html
209
Troubleshooting by Indication on the Remote Controller
SiE39-404
2.33 “L5” Outdoor Unit: Inverter Compressor Abnormal
Remote
Controller
Display
L5
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Malfunction is detected from current flowing in the power transistor.
Malfunction
Decision
Conditions
When an excessive current flows in the power transistor.
(Instantaneous overcurrent also causes activation.)
Supposed
Causes
! Defect of compressor coil (disconnected, defective insulation)
! Compressor start-up malfunction (mechanical lock)
! Defect of inverter PC board
Troubleshooting
Compressor inspection
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
The compressor's
coil is disconnected or the
insulation is
defective.
YES
Replace the compressor.
NO
Disconnect the connection
between the compressor and
inverter. Make the power
transistor check mode setting
ON by service mode.
Inverter
output
voltage check
Inverter output
voltage is not balanced.
(Normal if within ±10V)
Must be measured
when frequency
is stable.
YES
Replace the inverter unit.
NO
There is
instantenious power
drop.
NO
YES
Correct power supply.
Compressor inspection
Inspect according to the diagnosis
procedure for odd noises, vibration
and operating status of the
compressor.
(V2812)
Higher voltage than actual is displayed when the inverter output voltage is checked by tester.
210
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
2.34 “L8” Outdoor Unit: Inverter Current Abnormal
Remote
Controller
Display
L8
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Malfunction is detected by current flowing in the power transistor.
Malfunction
Decision
Conditions
When overload in the compressor is detected.
Supposed
Causes
! Compressor overload
! Compressor coil disconnected
! Defect of inverter PC board
Troubleshooting
Output current check
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
The secondary
current of the inverter is
higher than 15A
for each phase.
YES
Compressor overload
Inspection of the compressor and
refrigerant system is required.
NO
Compressor
inspection The
compressor's coil is
disconnected.
YES
Replace the compressor.
Disconnect the the connection
between the compressor and
inverter. Make the power
transistor check mode setting
ON by service mode.
NO
Inverter
output
voltage check
Inverter output voltage
is not balanced.
(Normal if within ±10V)
Must be measured
when frequency
is stable.
NO
Replace the inverter PC board.
YES
After turning
on again, "L8" blinks
again.
YES
NO
Reset and restart.
Compressor inspection
Inspect according to the diagnosis
procedure for odd noises, vibration
and operating status of the
compressor.
(V2813)
Troubleshooting
: http://splitoff.ru/tehn-doc.html
211
Troubleshooting by Indication on the Remote Controller
SiE39-404
2.35 “L9” Outdoor Unit: Inverter Start up Error
Remote
Controller
Display
L9
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Malfunction is detected from current flowing in the power transistor.
Malfunction
Decision
Conditions
When overload in the compressor is detected during startup
Supposed
Causes
! Defect of compressor
! Pressure differential start
! Defect of inverter PC board
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
The difference
between high and low
pressure when starting
is above
0.2MPa.
NO
Unsatisfactory pressure
equalization
Check refrigerant system.
YES
Disconnect the connection
between the compressor and
inverter. Make the power
transistor check mode ON by
service mode.
Inverter
output
voltage check
Inverter output voltage
is not balanced.
(Normal if within ±10V)
Must be measured
when frequency
is stable.
NO
Replace the inverter PC board
YES
After turning
on again, "L9" blinks
again.
YES
NO
Reset and restart.
Compressor inspection
Inspect according to the diagnosis
procedure for odd noises, vibration
and operating status of the
compressor.
(V2814)
212
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
2.36 “LC” Outdoor Unit: Malfunction of Transmission Between
Inverter and Control PC Board
Remote
Controller
Display
LC
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Check the communication state between inverter PC board and control PC board by microcomputer.
Malfunction
Decision
Conditions
When the correct communication is not conducted in certain period.
Supposed
Causes
!
!
!
!
!
Troubleshooting
Malfunction of connection between the inverter PC board and outdoor control PC board
Defect of outdoor control PC board (transmission section)
Defect of inverter PC board
Defect of noise filter
External factor (Noise etc.)
: http://splitoff.ru/tehn-doc.html
213
Troubleshooting by Indication on the Remote Controller
SiE39-404
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Are the
connectors
between the main
PC board (A1P),
fan drive PC board (A3P)
and inverter PC board
(A2P) connected
securely?
NO
Connect transmission wiring and
turn on again.
YES
The
transmission
wiring between the
outdoor unit PC board,
fan drive board and
inverter unit is
disconnected.
YES
Fix the disconnection and turn on
again.
NO
The
microcomputer
monitor (green) on
fan drive board is
blinking.
NO
Check connection of the connector.
YES
The
microcomputer
monitor (green) on
the inverter P.C.B
is blinking.
YES
Defect of outdoor main PC board
or defect of inverter PC board.
NO
The voltage
between red and
white of X1A on the inverter
unit is 220 ~ 240 V.
YES
Replace inverter PC board.
When the LC malfunction occur
again, replace control PC board.
NO
Check the noise filter (Z1F) for
disconnection, and check the
power supply wiring or the inverter
PC board.
(V2815)
214
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
2.37 “P1” Outdoor Unit: Inverter Over-Ripple Protection
Remote
Controller
Display
P1
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Imbalance in supply voltage is detected in PC board.
Malfunction
Decision
Conditions
When the resistance value of thermistor becomes a value equivalent to open or short circuited
status.
! Malfunction is not decided while the unit operation is continued.
"P1" will be displayed by pressing the inspection button.
Supposed
Causes
!
!
!
!
!
!
Open phase
Voltage imbalance between phases
Defect of main circuit capacitor
Defect of inverter PC board
Defect of K1M
Improper main circuit wiring
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Imbalance
in supplied voltage is
in excess of 14 V
(Y1). ∗1
YES
Open phase?
NO
NO
Is
the voltage
imbalance applied to the
inverter in excess of
14 V (Y1)?
∗2
NO
YES
<When voltage monitoring is possible:>
Using a device capable of
constant recording of power
supply voltage record
power supply voltage
between 3 phases (L1 ~ L2,
L2 ~ L3, L3~L1) for about
one continuous week.
YES
Open phase
Normalize field cause.
Fix power supply voltage
imbalance.
Part or wiring defect
After turning the power supply
OFF, check and repair the
main circuit wiring or parts.
(1) Loose or disconnected
wiring between power
supply and inverter
(2) K1M contact disposition,
fusion or contact is poor.
(3) Loose or disconnected
noise filter
∗1. Measure voltage at the X1M power supply
terminal block.
∗2. Measure voltage at terminals L1, L2 and L3 of
the diode module inside the inverter while the
compressor is running.
Power supply voltage imbalance
measure
Explanation for users ∗In accordance with "notification of inspection results" accompanying spare parts.
Give the user a copy of "notification of inspection results"and leave
it up to him to improve the imbalance.
Be sure to explain to the user that
there is a "power supply imbalance"
for which DAIKIN is not responsible.
(V2816)
Troubleshooting
: http://splitoff.ru/tehn-doc.html
215
Troubleshooting by Indication on the Remote Controller
SiE39-404
2.38 “P4” Outdoor Unit: Malfunction of Inverter Radiating Fin
Temperature Rise Sensor
Remote
Controller
Display
P4
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Resistance of radiation fin thermistor is detected when the compressor is not operating.
Malfunction
Decision
Conditions
When the resistance value of thermistor becomes a value equivalent to open or short circuited
status.
! Malfunction is not decided while the unit operation is continued.
"P4" will be displayed by pressing the inspection button.
Supposed
Causes
! Defect of radiator fin temperature sensor
! Defect of inverter PC board
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Measure the resistance of
radiation fin thermistor.
Is the
resistance of thermistor
correct?
NO
YES
NO
Is the resetting possible?
YES
Replace inverter PC board.
(Thermistor can not be removed
from inverter PC board)
Replace inverter PC board.
After resetting, restart.
(V2818)
∗2: Refer to thermistor resistance / temperature characteristics table on P311.
216
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
2.39 “UO” Low Pressure Drop Due to Refrigerant Shortage or
Electronic Expansion Valve Failure
Remote
Controller
Display
U0
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Short of gas malfunction is detected by discharge pipe temperature thermistor.
Malfunction
Decision
Conditions
Microcomputer judge and detect if the system is short of refrigerant.
HMalfunction is not decided while the unit operation is continued.
Supposed
Causes
!
!
!
!
Out of gas or refrigerant system clogging (incorrect piping)
Defect of pressure sensor
Defect of outdoor unit PC board (A1P)
Defect of thermistor R2T or R4T
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Cooling
YES
YES
NO
NO
The suction
pipe temperature minus
coil temperature is 20 °C
or higher.
Low pressure
is 0.1 MPa
or less.
The
voltage
of X45A pins (2)
and (3) on main
outdoor unit PC board
(A1P) is 0.8 VDC or less.
(Low pressure
sensor output
voltage)
∗2
NO
YES
YES
Out of gas, closing of stop
valve or refrigerant system is
clogged. Requires check of
refrigerant system.
Replace main outdoor unit
PC board (A1P).
Replace low pressure sensor.
Out of gas or refrigerant
system is clogged. Requires
check of refrigerant system.
NO
Resistance
is normal when
measured with the
suction pipe thermistor
(R2T) and coil thermistor
(R4T) disconnected
from the outdoor
unit PC
board.
∗1
YES
NO
Replace the thermistor.
Replace the outdoor unit PC
board (A1P).
(V2819)
∗1: Refer to thermistor resistance / temperature characteristics table on P311.
∗2: Refer to pressure sensor, pressure / voltage characteristics table on P313.
Troubleshooting
: http://splitoff.ru/tehn-doc.html
217
Troubleshooting by Indication on the Remote Controller
SiE39-404
2.40 “U1” Reverse Phase, Open Phase
Remote
Controller
Display
U1
Applicable
Models
H3 phase outdoor unit only
Method of
Malfunction
Detection
Detection is based on the voltage in main circuit capacitor for inverter and supply voltage.
The phase of each phase are detected by reverse phase detection circuit and right phase or
reverse phase are judged.
Malfunction
Decision
Conditions
Supposed
Causes
! Power supply reverse phase
! Power supply open phase
! Defect of outdoor PC board A1P
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
There
is an open phase
at the power supply
terminal section (X1M)
of the outdoor
unit.
YES
Fix the open phase. Requires
inspection of field power supply
section.
NO
Operation
is normal if one
place of power supply
line phase is
replaced.
NO
YES
Reverse phase
Counter measure of the problem is
completed by phase replacement.
Replace outdoor unit PC board
A1P.
(V2820)
218
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
2.41 “U2” Power Supply Insufficient or Instantaneous Failure
Remote
Controller
Display
U2
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Detection of voltage of main circuit capacitor built in the inverter and power supply voltage.
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
!
!
!
!
!
!
!
Power supply insufficient
Instantaneous failure
Open phase
Defect of inverter PC board
Defect of outdoor control PC board
Defect of K1M.
Main circuit wiring defect
: http://splitoff.ru/tehn-doc.html
219
Troubleshooting by Indication on the Remote Controller
SiE39-404
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is
connection
wire connected
between the connector
X21A and X6A?
NO
Repair wiring.
YES
Turn on again.
NO
Turn K1M ON.
YES
The voltage
between the P2
(or P3) and N3 terminals
is 380 VDC (Y1) or
more when the
compressor is
running.
YES
Is
220 ~ 240 V of
power reaching the
K1M coil?
YES
Replace K1M.
NO
NO
Does
the voltage
between terminals
YES
P2(or P3) and N3 gradually
rise to 556 VDC (Y1)
after turning
on?
Replace the inverter PC
board.
NO
Is
220 ~ 240 V
at the connector X1A of
inverter PC
board.
YES
Replace the inverter PC
board.
NO
Is
220 ~ 240 V
at the connector X1A of
outdoor PC board
side?
YES
NO
Replace the outdoor unit
PC board (A1P).
Check the transmission
wiring between the
outdoor unit PC board
and inverter unit.
Replace the inverter
PC board.
Monitor field power
supply.
(V2821)
220
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
2.42 “U3” Check Operation not executed
Remote
Controller
Display
U3
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Check operation is executed or not
Malfunction
Decision
Conditions
Malfunction is decided when the unit starts operation without check operation.
Supposed
Causes
! Check operation is not executed.
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Has the
check operation
performed on Outdoor
unit P.C.B?
NO
Press the BS4 on P.C. board on
the master outdoor unit for 5
seconds or more to execute check
YES
Replace the main P.C. board on
the outdoor unit.
(V3052)
Troubleshooting
: http://splitoff.ru/tehn-doc.html
221
Troubleshooting by Indication on the Remote Controller
SiE39-404
2.43 “U4” Malfunction of Transmission Between Indoor Units
Remote
Controller
Display
U4
Applicable
Models
All model of indoor unit
RXYQ5~48M
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor and outdoor units is normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
! Indoor to outdoor, outdoor to outdoor transmission wiring F1, F2 disconnection, short circuit
or wrong wiring
! Outdoor unit power supply is OFF
! System address doesn’t match
! Defect of indoor unit PC board
! Defect of outdoor unit PC board
222
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Has
the indoor
or outdoor unit PC
board been replaced,
or has the indoor - outdoor
or outdoor - outdoor unit
transmission wiring
been
modified?
YES
Push and hold the RESET
button on the master outdoor
unit PC Board for 5 seconds.
∗ The unit will not operate for
up to 12 minutes.
NO
All
indoor unit
remote controllers of the
same refrigerant system
display
"U4."
YES
NO
Is indoor
- outdoor and outdoor outdoor unit transmission
wiring normal?
YES
Replace the indoor unit PC
Board.
NO
Fix the indoor/outdoor unit
transmission wiring.
Reset the power supply.
Outdoor
unit PC board
microcomputer monitor
(HAP) blinks.
NO
YES
The
voltage between
terminals L1 and N of the
outdoor unit PC board
is 220~240 V.
Supply 220~240 V.
YES
The fuse on
the outdoor unit's PC
board is burnt.
NO
The
secondary voltage
of the transformer is
about 22 V.
YES
NO
NO
Operation
ready lamp (H2P) is
blinking.
YES
Replace the fuse.
NO
Replace the transformer.
replacement
Replace outdoor unit PC
board. (A1P)
YES
Lamp does
not go off for 12 minutes
or more.
NO
Is
indoor - outdoor
and outdoor - outdoor unit
transmission wiring
normal?
YES
YES
Push and hold the RESET
button on the outdoor unit PC
board for 5 seconds.
NO
Fix the indoor/outdoor unit
transmission wiring.
Replace the outdoor unit PC
Board (A1P).
(V2822)
Troubleshooting
: http://splitoff.ru/tehn-doc.html
223
Troubleshooting by Indication on the Remote Controller
SiE39-404
2.44 “U5” Malfunction of Transmission Between Remote
Controller and Indoor Unit
Remote
Controller
Display
U5
Applicable
Models
All models of indoor units
Method of
Malfunction
Detection
In case of controlling with 2-remote controller, check the system using microcomputer is signal
transmission between indoor unit and remote controller (main and sub) is normal.
Malfunction
Decision
Conditions
Normal transmission does not continue for specified period.
Supposed
Causes
!
!
!
!
!
Malfunction of indoor unit remote controller transmission
Connection of two main remote controllers (when using 2 remote controllers)
Defect of indoor unit PC board
Defect of remote controller PC board
Malfunction of transmission caused by noise
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Using
2-remote controllers
control.
YES
NO
All indoor
PC board microcomputer
monitors blink.
NO
YES
NO
NO
YES
Multi-core cable
is used for the indoor
unit remote controller
transmission
wiring.
SS1 of
both remote controllers
is set to "MASTER."
Operation
returns to normal when
the power is turned off
momentarily.
YES
YES
NO
Set one remote controller to
"SLAVE"; turn the power
supply off once and then back
on.
Replace indoor unit PC
board.
There is possibility of
malfunction caused by noise.
Check the surrounding area
and turn on again.
Switch to double-core
independent cable.
replacement
Defect of remote controller PC
board or indoor unit PC board.
Replace whichever is
defective.
(V2823)
224
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
2.45 “U7” Malfunction of Transmission Between Outdoor Units
Remote
Controller
Display
U7
Applicable
Models
All models of indoor units
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor unit and remote controller is normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
! Improper connection of transmission wiring between outdoor unit and outdoor unit outside
control adaptor
! Improper cool/heat selection
! Improper cool/heat unified address (outdoor unit, external control adaptor for outdoor unit)
! Defect of outdoor unit PC board (A1P)
! Defect of outdoor unit outside control adaptor
! Improper connection of transmission wiring between outdoor units of multi outdoor unit
connection.
Troubleshooting
: http://splitoff.ru/tehn-doc.html
225
Troubleshooting by Indication on the Remote Controller
SiE39-404
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the
outdoor units multi
connection transmission
wiring normal?
YES
Is the
indoor / outdoor unit
transmission wiring
normal?
YES
C/H SELECT is set to "IND".
NO
Fix the outdoor units multi
connection transmission
wiring and reset power.
NO
Fix the indior / outdoor unit
transmission wiring.
YES
Replace the outdoor unit PC
Board (A1P).
NO
Cool / heat selection is
unified.
NO
Set C/H SELECT to "IND."
YES
C/H SELECT
is set to "MASTER."
YES
NO
C/H SELECT
is set to "SLAVE."
YES
Check
and see if the following items
are normal.
The cool / heat unified
address for outdoor units in
outdoor - outdoor unit
transmission is duplicated.
Set the address correctly.
NO
Fix the problem.
YES
Outdoor unit outside control adaptor
•Is there continuity?
•Does the cool/heat unified address match?
Outdoor unit (unified master unit)
•Is there continuity?
•Does the cool/heat unified address match?
YES
Does a
malfunction occur when
the cool / heat selector is
set to "IND?"
YES
NO
Replace the outdoor unit
outside control adaptor.
replacement
Replace the outdoor unit PC
board (A1P).
(V2824)
226
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
2.46 “U8” Malfunction of Transmission Between Master and
Slave Remote Controllers
Remote
Controller
Display
U8
Applicable
Models
All models of indoor units
Method of
Malfunction
Detection
In case of controlling with 2-remote controller, check the system using microcomputer if signal
transmission between indoor unit and remote controller (main and sub) is normal.
Malfunction
Decision
Conditions
Normal transmission does not continue for specified period.
Supposed
Causes
! Malfunction of transmission between main and sub remote controller
! Connection between sub remote controllers
! Defect of remote controller PC board
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Using 2-remote
controllers control.
NO
YES
SS1
of both remote controllers is
setto "SUB."
YES
SS1
of remote controller PC boards
is set to "MAIN."
NO
Set SS1 to "MAIN"; the
power supply off once and
then back on.
YES
NO
Turn the power off and then
back on. If a malfunction
occurs, replace the remote
controller PC board.
Set one remote controller to
"MAIN"; the power supply off
once and then back on.
(V2825)
Troubleshooting
: http://splitoff.ru/tehn-doc.html
227
Troubleshooting by Indication on the Remote Controller
SiE39-404
2.47 “U9” Malfunction of Transmission Between Indoor and
Outdoor Units in the Same System
Remote
Controller
Display
U9
Applicable
Models
All models of indoor units
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
228
!
!
!
!
Malfunction of transmission within or outside of other system
Malfunction of electronic expansion valve in indoor unit of other system
Defect of PC board of indoor unit in other system
Improper connection of transmission wiring between indoor and outdoor unit
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
"U9"
has been displayed for 2
minutes or more.
YES
Re-diagnose by display after
passage of 2 minutes or more.
NO
Turn on all indoor units.
NO
The "UA"
display blinks on the
remote controllers of other
units within the same
refrigerant
system.
YES
Refer to failure diagnosis for "UA"
malfunction code.
NO
The "A1"
display blinks on
the remote controllers of
otherunits within the same
refrigerant
system.
YES
Refer to failure diagnosis for "A1"
malfunction code.
NO
The "A9"
display blinks on
the remote controllers of
otherunits within the same
refrigerant
system.
YES
Refer to failure diagnosis for "A9"
malfunction code.
YES
Refer to failure diagnosis for "U4"
malfunction code.
NO
The "U4"
display blinks on
the remote controllers of
otherunits within the same
refrigerant
system.
NO
Refer to failure diagnosis for "U5"
malfunction code.
(V2826)
Troubleshooting
: http://splitoff.ru/tehn-doc.html
229
Troubleshooting by Indication on the Remote Controller
SiE39-404
2.48 “UA” Excessive Number of Indoor Units
Remote
Controller
Display
UA
Applicable
Models
All models of indoor unit
RXYQ5~48M
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
!
!
!
!
Excess of connected indoor units
Defect of outdoor unit PC board (A1P)
Mismatching of the refrigerant type of indoor and outdoor unit.
Setting of outdoor P.C. board was not conducted after replacing to spare parts P.C. board.
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the outdoor
P.C. board replaced
to spare parts P.C.
board ?
YES
The refrigerant classification has
not been set yet. Please set as per
page 117.
NO
The total
of indoor units
displaying "UA" and
indoor units connected to the NO
same refrigerant system is
within connectable
number of
unit∗
There are too many indoor units
within the same refrigerant
system.
YES
Push and hold the RESET
button on the outdoor unit
PC board for 5 seconds.
Does a malfunction occur?
NO
Normal
YES
Does the
refrigerant type of indoor
and outdoor unit
match?
YES
NO
Matches the refrigerant type of
indoor and outdoor unit.
Replace outdoor unit PC board
(A1P).
(V2827)
∗ The number of indoor units that can be connected to a single outdoor unit system depends on
the type of outdoor unit.
230
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
2.49 “UC” Address Duplication of Central Remote Controller
Remote
Controller
Display
UC
Applicable
Models
All models of indoor unit
Centralized controller
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
! Address duplication of centralized remote controller
! Defect of indoor unit PC board
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Optional
controllers for
centralized control are
connected to the
indoor unit.
YES
Address duplication of central
remote controller
The setting must be changed so
that the central remote control
address is not duplicated.
NO
Replace indoor unit PC board.
(V2828)
Troubleshooting
: http://splitoff.ru/tehn-doc.html
231
Troubleshooting by Indication on the Remote Controller
SiE39-404
2.50 “UE” Malfunction of Transmission Between Central
Remote Controller and Indoor Unit
Remote
Controller
Display
UE
Applicable
Models
All models of indoor units
Centralized controller
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor unit and centralized remote controller is
normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
! Malfunction of transmission between optional controllers for centralized control and indoor
unit
! Connector for setting master controller is disconnected.
! Failure of PC board for centralized remote controller
! Defect of indoor unit PC board
232
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Has
an indoor unit once
connected been remove
or its address
changed?
YES
Reset power supply
simultaneously for all optional
controllers for centralized
control.
NO
Is
the power supply
turned on for indoor units
displaying
malfunction?
NO
Turn indoor unit's power
supply.
YES
Is
transmission wiring
disconnected or
wired incorrectly?
NO
Fix the wiring correctly.
YES
Is
transmission with
all indoor units
malfunctioning?
NO
YES
YES
Is
the transmission
wiring with the master
controller disconnected
or wired
incorrectly?
Is the group
No. of malfunctioning
indoor units set?
NO
NO
Set the group No.
correctly.
Replace indoor unit PC
board.
Fix the wiring correctly.
YES
Is the
master controller's
connector for setting
master controller
disconnected?
YES
NO
Connect the connector
correctly.
Replace the central PC
board.
(V2829)
Troubleshooting
: http://splitoff.ru/tehn-doc.html
233
Troubleshooting by Indication on the Remote Controller
SiE39-404
2.51 “UF” Refrigerant System not Set, Incompatible Wiring/
Piping
Remote
Controller
Display
UF
Applicable
Models
All models of indoor units
RXYQ5~48M
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
! Improper connection of transmission wiring between outdoor unit and outdoor unit outside
control adaptor
! Failure to execute wiring check operation
! Defect of indoor unit PC board
Supposed
Causes
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Are the stop
valves openned?
NO
Open stop valve.
YES
Is the
test operation
(Wiring check operation)
carried out?
NO
YES
Is
indoor - outdoor
and outdoor - outdoor unit
transmission wiring
normal?
YES
Is indoor
YES
-outdoor and outdoorReplace indoor unit PC board.
outdoor unit transmission
wiring normal?
NO
NO
After fixing incorrect wiring,
push and hold the RESET
button on the master outdoor
unit PC board for 5 seconds.
∗ The unit will not run for up to
12 minutes.
Test operation may not have
been carried out successfully.
(V2830)
Note:
234
Test operation may not be successful if carried out after the outdoor unit has been off for more
than 12 hours, or if it is not carried out after running all connected indoor units in the fan mode
for at least an hour.
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting by Indication on the Remote Controller
2.52 “UH” Malfunction of System, Refrigerant System Address
Undefined
Remote
Controller
Display
UH
Applicable
Models
All models of indoor units
RXYQ5~48M
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
! Improper connection of transmission wiring between outdoor unit and outdoor unit outside
control adaptor
! Defect of indoor unit PC board
! Defect of outdoor unit PC board (A1P)
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is
electricity
being introduce for
YES
the first time after
installationor after an indoor
or outdoorunit PC
board has been
replaced?
NO
Is
indoor - outdoor and
outdoor - outdoor unit
transmission wiring
normal?
NO
Normal
YES
YES
After fixing incorrect wiring,
push and hold the RESET
button on the master outdoor
unit PC board for 5 seconds.
∗ The unit will not run for up to
12 minutes.
YES
After fixing incorrect wiring,
push and hold the RESET
button on the outdoor unit
PC board for 5 seconds
Replace whichever is
defective.
Does a malfunction
occur?
Does
a malfunction
occur even after 12
minutes elapses from the
time when electricity is
introducedto indoor
and outdoor
units?
NO
Normal
YES
Does
a "UH" malfunction occur
for all indoor units in
the system?
YES
NO
Replace indoor unit PC board.
Replace outdoor unit PC
board (A1P).
(V2831)
Troubleshooting
: http://splitoff.ru/tehn-doc.html
235
Troubleshooting (OP: Central Remote Controller)
SiE39-404
3. Troubleshooting (OP: Central Remote Controller)
3.1
“UE” Malfunction of Transmission Between Central
Remote Controller and Indoor Unit
Remote
Controller
Display
UE
Applicable
Models
All models of indoor units
RXYQ5~48M
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor unit and central remote controller is
normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
!
!
!
!
Malfunction of transmission between optional controllers for centralized control and indoor unit
Connector for setting master controller is disconnected.
Failure of PC board for central remote controller
Defect of indoor unit PC board
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Has
an indoor unit once
connected been remove
or its address
changed?
YES
Reset power supply
simultaneously for all optional
controllers for centralized
control.
NO
Is the
power supply turned
on for indoor units displaying
malfunction?
NO
Turn indoor unit's power
supply.
YES
Is
transmission wiring
disconnected or wired
incorrectly?
NO
Fix the wiring correctly.
YES
Is transmission
with all indoor units
malfunctioning?
NO
YES
YES
Is the
transmission wiring
with the master controller
disconnected or wired
incorrectly?
Is the group
No. of malfunctioning
indoor units set?
NO
NO
Set the group No. correctly.
Replace indoor unit PC
board.
Fix the wiring correctly.
YES
Is the
master controller's
connector for setting
master controller
disconnected?
YES
NO
Connect the connector
correctly.
Replace the central PC board.
(V2832)
236
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
3.2
Troubleshooting (OP: Central Remote Controller)
“M1” PC Board Defect
Remote
Controller
Display
M1
Applicable
Models
Centralized remote controller
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
! Defect of central remote controller PC board
Troubleshooting
Replace the central remote controller PC board.
Troubleshooting
: http://splitoff.ru/tehn-doc.html
237
Troubleshooting (OP: Central Remote Controller)
3.3
SiE39-404
“M8” Malfunction of Transmission Between Optional
Controllers for Centralized Control
Remote
Controller
Display
M8
Applicable
Models
Centralized remote controller
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
! Malfunction of transmission between optional controllers for centralized control
! Defect of PC board of optional controllers for centralized control
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Has a once
connected optional
controller for centralized
control been disconnected
or its address
changed?
YES
Reset power supply simultaneously
for all optional controllers for
centralized control.
NO
Is
the power supply
turned on for all optional
controllers for
centralized
control?
NO
Turn on power supply for all
optional controllers for centralized
control.
YES
Is
the reset switch
of all optional controllers
for centralized control set
to ''normal?''
NO
Set reset switch to "normal."
YES
Is
transmission wiring
disconnected or wired
incorrectly?
NO
YES
Fix the wiring correctly.
The PC board of one of the
optional controllers for centralized
control is defective. Try turning
on/off using each optional
controllers for centralized control,
and replace the PC board of the
one that is unable to control the
indoor unit.
(V2833)
238
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
3.4
Troubleshooting (OP: Central Remote Controller)
“MA” Improper Combination of Optional Controllers for
Centralized Control
Remote
Controller
Display
MA
Applicable
Models
Centralized remote controller
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
! Improper combination of optional controllers for centralized control
! More than one master controller is connected
! Defect of PC board of optional controller for centralized control
: http://splitoff.ru/tehn-doc.html
239
Troubleshooting (OP: Central Remote Controller)
SiE39-404
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is
the wiring adaptor for
electrical appendices
connected?
Cannot be used in
combination with a wiring
adaptor for electrical
appendices. Remove the
wiring adaptor for electrical
appendices and reset the
power supply for all optional
controllers for centralized
control simultaneously.
YES
NO
Is a schedule timer
connected?
YES
Is a data station
connected?
NO
NO
Is a parallel interface
connected?
NO
Is the
schedule timer's
individual/combined
connector
connected?
Schedule timer and data
station cannot be used in
combination. Disconnect
YES either the schedule timer or
data station and reset the
power supply for all optional
controllers for centralized
control simultaneously.
Schedule timer and parallel
YES interface cannot be used in
combination. Disconnect
either the schedule timer or
parallel interface and reset
the power supply for all
optional controllers for
centralized control
simultaneously.
Disconnect the schedule
YES timer's individual / combined
connector and reset the
power supply for all optional
controllers for centralized
control simultaneously.
NO
Are
there two
or more optional
controllers for centralized
control connected with the
connector for setting
master
control?
Arrange so that the
connector for setting master
control is connected to one
controller for centralized
control and reset the power
supply for all optional
controllers for centralized
control simultaneously.
YES
NO
Reset the power supply for
all optional controllers for
centralized control
simultaneously.
240
If the malfunction is still not cleared:
Disconnect the connector for
setting master control from
the master controller,
connect to another optional
controller for centralized
control and simultaneously
reset all optional controllers
for centralized control again.
The controller connected by
the connector for setting
master control when the
malfunction is cleared is
defective and must be
replaced.
(V2834)
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
3.5
Troubleshooting (OP: Central Remote Controller)
“MC” Address Duplication, Improper Setting
Remote
Controller
Display
MC
Applicable
Models
Central remote controller
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
! Address duplication of centralized remote controller
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Are
two or more central
remote controllers
connected?
NO
YES
Disconnect all central remote
controllers except one and
reset the power supply of the
central remote controller.
Reset power supply of the
central remote controller.
(V2835)
Troubleshooting
: http://splitoff.ru/tehn-doc.html
241
Troubleshooting (OP: Schedule Timer)
SiE39-404
4. Troubleshooting (OP: Schedule Timer)
4.1
“UE” Malfunction of Transmission Between Central
Remote Controller and Indoor Unit
Remote
Controller
Display
UE
Applicable
Models
Schedule timer
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor unit and centralized remote controller is
normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
! Malfunction of transmission between central remote controller and indoor unit
! Disconnection of connector for setting master controller (or individual/combined switching
connector)
! Defect of schedule timer PC board
! Defect of indoor unit PC board
242
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting (OP: Schedule Timer)
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Has
an indoor unit
once connected been
removeor its address
changed?
YES
Reset power supply
simultaneously for all optional
controllers for centralized
control.
NO
Is
the power supply
turned on for indoor
units displaying
malfunction?
NO
Turn indoor unit's power
supply.
YES
Is
transmission wiring
disconnected or wired
incorrectly?
YES
Fix the wiring correctly.
NO
Is
transmission with all
indoor units
malfunctioning?
NO
YES
YES
Is
the transmission
wiring with the master
controller disconnected or
wired incorrectly?
Is the group
No. of malfunctioning
indoor units set?
YES
NO
Set the group No. correctly.
Replace indoor unit PC board.
Fix the wiring correctly.
NO
Is the
master controller's
connector for setting
master controller
disconnected?
NO
YES
Connect the connector
correctly.
Replace the central PC board.
(V2836)
Troubleshooting
: http://splitoff.ru/tehn-doc.html
243
Troubleshooting (OP: Schedule Timer)
4.2
SiE39-404
“M1” PC Board Defect
Remote
Controller
Display
M1
Applicable
Models
Schedule timer
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
! Defect of schedule timer PC board
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Reset power supply.
Does the
system return to normal?
NO
YES
External factor other
than equipment
malfunction (noise etc.)
Replace the indoor unit
PC board.
(V2837)
244
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
4.3
Troubleshooting (OP: Schedule Timer)
“M8” Malfunction of Transmission Between Optional
Controllers for Centralized Control
Remote
Controller
Display
M8
Applicable
Models
All models of indoor units, schedule timer
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
! Malfunction of transmission between optional controllers for centralized control
! Defect of PC board of optional controllers for centralized control
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Has a
once connected
optional controller for
centralized control been
disconnected or
its address
changed?
YES
Reset power supply
simultaneously for all optional
controllers for centralized control.
NO
Is
the power supply
turned on for all optional
controllers for
centralized
control?
NO
Turn on power supply for all
optional controllers for centralized
control.
YES
Is
the reset switch
of all optional controllers
for centralized control
set to "normal" ?
NO
Set reset switch to "normal."
YES
Is
transmission wiring
disconnected or wired
incorrectly?
YES
NO
Fix the wiring correctly.
The PC board of one of the
optional controllers for centralized
control is defective. Try turning
on/off using each optional
controllers for centralized control,
and replace the PC board of the
one that is unable to control the
indoor unit.
(V2838)
Troubleshooting
: http://splitoff.ru/tehn-doc.html
245
Troubleshooting (OP: Schedule Timer)
4.4
SiE39-404
“MA” Improper Combination of Optional Controllers for
Centralized Control
Remote
Controller
Display
MA
Applicable
Models
All models of indoor units, schedule timer
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
246
! Improper combination of optional controllers for centralized control
! More than one master controller is connected.
! Defect of PC board of optional controller for centralized control
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting (OP: Schedule Timer)
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the wiring
adaptor for electrical
appendices
connected?
YES
NO
Is the schedule
timer connected?
YES
Is a data station
connected?
YES
NO
NO
Is a parallel interface
connected?
YES
NO
Is the schedule
timer's individual/combined
connector connected?
YES
Cannot be used in
combination with a wiring
adaptor for electrical
appendices. Remove the
wiring adaptor for electrical
appendices and reset the
power supply for all optional
controllers for centralized
control simultaneously.
Schedule timer and data
station cannot be used in
combination. Disconnect
either the schedule timer or
data station and reset the
power supply for all optional
controllers for centralized
control simultaneously.
Schedule timer and parallel
interface cannot be used in
combination. Disconnect either
the schedule timer or parallel
interface and reset the power
supply for all optional
controllers for centralized
control simultaneously.
Disconnect the schedule
timer's individual / combined
connector and reset the
power supply for all optional
controllers for centralized
control simultaneously.
NO
Are
there two or
more optional
controllers
for centralized control
connected with the
connector for setting
master
control?
Arrange so that the connector
for setting master control is
connected to one controller
for centralized control and
reset the power supply for all
optional controllers for
centralized control
simultaneously.
YES
NO
Reset the power supply for
all optional controllers for
centralized control
simultaneously.
If the malfunction is still not cleared:
Disconnect the connector for
setting master control from
the master controller, connect
to another optional controller
for centralized control and
simultaneously reset all
optional controllers for
centralized control again. The
controller connected by the
connector for setting master
control when the malfunction
is cleared is defective and
must be replaced.
(V2839)
Troubleshooting
: http://splitoff.ru/tehn-doc.html
247
Troubleshooting (OP: Schedule Timer)
4.5
SiE39-404
“MC” Address Duplication, Improper Setting
Remote
Controller
Display
MC
Applicable
Models
All models of indoor units,
schedule timer
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
! Address duplication of optional controller for centralized control
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Are two or more
centralized controller
connected?
NO
YES
Disconnect all centralized
controller except one and reset
the centralized controller timer’s
power supply.
Reset the power supply for the
centralized controller.
(V2840)
248
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting (OP: Unified ON/OFF Controller)
5. Troubleshooting (OP: Unified ON/OFF Controller)
5.1
Operation Lamp Blinks
Remote
Controller
Display
Operation lamp blinks
Applicable
Models
All models of indoor units
Unified ON/OFF controller
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
!
!
!
!
!
Malfunction of transmission between optional controller and indoor unit
Connector for setting master controller is disconnected
Defect of unified ON/OFF controller
Defect of indoor unit PC board
Malfunction of air conditioner
: http://splitoff.ru/tehn-doc.html
249
Troubleshooting (OP: Unified ON/OFF Controller)
SiE39-404
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is a
malfunction
code displayed on the
remote controller?
YES
Diagnose the cause with the
air conditioner's failure
diagnosis manual.
NO
Has a
once connected
indoor unit been removed
or its address
changed?
YES
Reset power supply for all
optional controllers for
centralized control
simultaneously.
NO
Is the
power supply for
the indoor unit displaying
a malfunction
turned
on?
YES
Is
transmission wiring
disconnected or wired
incorrectly?
NO
Is
transmission
with all indoor units
malfunctioning?
NO
YES
NO
YES
Is the
transmission
wiring with the master
controller disconnected or
wired incorrectly?
Turn the power supply of the
indoor unit on.
Fix the wiring correctly.
Is
the group
No. of malfunctioning
indoor units
set?
YES
NO
Set the group No.
correctly.
Replace indoor unit PC board.
NO
Fix the wiring correctly.
YES
Is the
master
controller's connector for
setting master controller
disconnected.
YES
Connect the connector
correctly.
NO
Replace the central PC board.
(V2841)
250
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
5.2
Troubleshooting (OP: Unified ON/OFF Controller)
Display “Under Host Computer Integrate Control” Blinks
(Repeats Single Blink)
Remote
Controller
Display
“under host computer integrated control” (Repeats single blink)
Applicable
Models
Unified ON/OFF controller
Central controller, Schedule timer
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
!
!
!
!
!
Address duplication of central remote controller
Improper combination of optional controllers for centralized control
Connection of more than one master controller
Malfunction of transmission between optional controllers for centralized control
Defect of PC board of optional controllers for centralized control
: http://splitoff.ru/tehn-doc.html
251
Troubleshooting (OP: Unified ON/OFF Controller)
SiE39-404
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Caution
Has a once
connected optional
controller for centralized
control been disconnected
or itsaddress
changed?
YES
Reset power supply
simultaneously for all optional
controllers for centralized
control.
NO
Is the
power supply
turned on for all
optional controllers for
centralized
control?
NO
Turn on power supply for all
optional controllers for
centralized control.
YES
Is the
reset switch
of all optional controllers
for centralized
control set to
"normal"?
NO
Set reset switch to
"normal."
YES
Is
transmission wiring
disconnected or wired
incorrectly?
NO
Is
a central remote
controller or schedule timer
connected?
YES
YES
Fix the wiring correctly.
Is the
central remote
controller or schedule
timer displaying a
malfunction?
YES
Refer to failure diagnosis for
central remote controller or
schedule timer.
NO
NO
Are
two or more unified
ON / OFF controllers
connected?
NO
YES
Is the setting
of the unified
ON / OFF controller's
switch for setting
each address
duplicated?
YES
NO
Correct the setting of the
unified ON / OFF controller's
switch for setting each
address and reset the power
supply of the unified ON /
OFF controller.
2A
252
(V2842)
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Troubleshooting (OP: Unified ON/OFF Controller)
2A
Is the
wiring adaptor for
electrical appendices
connected?
NO
Is a schedule timer
connected?
YES
YES
Is a data station
connected?
NO
YES
NO
Is a parallel interface
connected?
YES
NO
Is the
schedule timer's
individual/combined
connector
connected?
NO
Are
there two or
more optional
controllers for centralized
control connected with the
connector for setting
master
control?
YES
YES
Cannot be used in
combination with a wiring
adaptor for electrical
appendices. Remove the
wiring adaptor for electrical
appendices and reset the
power supply for all optional
controllers for centralized
control simultaneously.
Schedule timer and data
station cannot be used in
combination. Disconnect
either the schedule timer or
data station and reset the
power supply for all optional
controllers for centralized
control simultaneously.
Schedule timer and parallel
interface cannot be used in
combination. Disconnect
either the schedule timer or
parallel interface and reset the
power supply for all optional
controllers for centralized
control simultaneously.
Disconnect the schedule
timer's individual / combined
connector and reset the power
supply for all optional
controllers for centralized
control simultaneously.
Arrange so that the connector
for setting master control is
connected to one controller for
centralized control and reset
the power supply for all
optional controllers for
centralized control
simultaneously.
NO
Reset the power supply for
all optional controllers for
centralized control
simultaneously.
If the malfunction is still not cleared:
Disconnect the connector for
setting master control from
the master controller, connect
to another optional controller
for centralized control and
simultaneously reset all
optional controllers for
centralized control again. The
controller connected by the
connector for setting master
control when the malfunction
is cleared is defective and
must be replaced.
(V2843)
Troubleshooting
: http://splitoff.ru/tehn-doc.html
253
Troubleshooting (OP: Unified ON/OFF Controller)
5.3
SiE39-404
Display “Under Host Computer Integrate Control” Blinks
(Repeats Double Blink)
Remote
Controller
Display
“under host computer integrated control” (Repeats double blink)
Applicable
Models
Unified ON/OFF controller
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
! Central control address (group No.) is not set for indoor unit.
! Improper address setting
! Improper wiring of transmission wiring
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the central
NO
control address (group No.)
set for the
indoor unit?
Set by remote controller the
central control address for all
indoor units connected to the
central control line.
YES
Is the switch
for setting each address
set correctly?
NO
Set the switch for setting each
address correctly and
simultaneously reset the power
YES
Is
the transmission
wiring disconnected or
wired incorrectly?
NO
YES
Fix the wiring correctly.
Replace the PC board of the
(V2844)
254
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Check No. 8
Check No. 9
Troubleshooting
Troubleshooting (OP: Unified ON/OFF Controller)
Check on connector of fan motor (Power supply cable)
(1) Turn off the power supply.
Measure the resistance between phases of U,V,W at the motor side connectors (three-core
wire) to check that the values are balanced and there is no short circuiting, while connector
or relay connector is disconnected.
Red
U
White
V
Black
W
Measure the resistance
values between phases
U,V,W.
(1) Turn off the power supply.
(2) Measure the resistance between Vcc and each phase of U,V,W, and GND and each phase
at the motor side connectors (five-core wire) to check that the values are balanced within the
range of ± 20 %, while connector or relay connector is disconnected.
5 Gray
GND
4 Pink
Vcc
3 Orange
W
2 Blue
V
1 Yellow
U
Measure the resistance
values between Vcc
and U,V,W, and GND
and U,V,W.
: http://splitoff.ru/tehn-doc.html
255
Troubleshooting (OP: Unified ON/OFF Controller)
Check No. 12
SiE39-404
Check on pulse input of position signal of fan inverter PCB
(1) Disconnect the connector X2A while power supply OFF and operation OFF.
(2) Is the voltage between pins No. 4 and 5 on X2A approx. 15 V after power supply is turned
on?
(3) Connect the connector X2A while power supply OFF and operation OFF.
(4) Check below conditions when the fan motor is rotated one turn manually under the condition
of operation OFF after power supply is turned ON.
Are the pulse (approx. 0 V and 5 V) generated 4 times between No. 1 and 5 on X2A?
Are the pulse (approx. 0 V and 5 V) generated 4 times between No. 2 and 5 on X2A?
Are the pulse (approx. 0 V and 5 V) generated 4 times between No. 3 and 5 on X2A?
The condition (2) dose not appear → Faulty PCB → Replacing the PCB
The conditions (4) do not appear → Faulty hall IC → Replacing fan motor of outdoor unit
256
5 Gray
GND
4 Pink
Vcc (approx. 15 V)
3 Orange
Position signal W
2 Blue
Position signal V
1 Yellow
Position signal U
: http://splitoff.ru/tehn-doc.html
Troubleshooting
SiE39-404
Part 7
Replacement procedure
for INV compressor,
VRV II (RXYQ5M to 48M)
1. Replacement procedure for INV compressor,
VRV II (RXYQ5M-48M) .......................................................................258
1.1 Replacement procedure .......................................................................258
: http://splitoff.ru/tehn-doc.html
Replacement procedure for INV compressor, VRV II (RXYQ5M to 48M)
257
Replacement procedure for INV compressor, VRV II (RXYQ5M-48M)
SiE39-404
1. Replacement procedure for INV compressor,
VRV II (RXYQ5M-48M)
1.1
Replacement procedure
Equalizing seat outlet pipe
(1) Collect the refrigerant by using refrigerant
Suction pipe
recovery unit.
(Since the setting on outdoor unit PCB is required
for refrigerant recovery, refer to the warning plate Discharge pipe
"Precautions in service work" attached on the
INV
switch box cover.)
compressor
(2) Remove the sound insulator mat covering the
Oil equalizing
faulty compressor, and disconnect the power
pipe
cable from terminal board of the compressor.
Equalizing seat
(3) Disconnect the brazing sections of suction pipe
and discharge pipe by using brazing torch after
Bolts
the refrigerant has been collected completely.
(4) Pinch the oil pressure equalizing pipe of the faulty
Cushion
compressor at the lower part of the brazed joint as
rubber
shown in figure 1, and cut it between the pinched
section and brazed joint in order to prevent
residual oil from discharging.
(5) Remove three bolts at cushion rubber section to
Brazed section
take out the faulty compressor outside the unit.
(6) Check that no oil remains in the oil pressure
equalizing pipe as shown in figure 2, then remove
2. Cut
the cut pipe from the brazed joint with brazing
1. Pinch
torch.
(7) Install the new compressor in the unit.
(Be sure to insert the cushion rubbers before
tightening the fixing bolts of compressor.)
Equalizing seat
(8) Remove the rubber caps put on the suction and
discharge pipe of the new compressor to release
Fig. 1
the sealing nitrogen gas.
(Take note that oil may spout due to the pipe
inside pressure if the plug put on the equalizing
seat is removed before removing of rubber cap.)
(9) Remove the plug put on the equalizing seat of the
new compressor.
Oil pressure equalizing pipe
(10) Install the outlet pipe on the equalizing seat of the
new compressor.
Brazed section
(11) Braze the equalizing seat outlet pipe to the oil
pressure equalizing pipe with brazing torch.
* Since an O-ring is put in the equalizing seat, be
Remove
sure to maintain the parts around O-ring in cool.
(12) Braze the suction and discharge pipe with brazing
Cut section
torch to the compressor.
* Check that no oil remains in the oil pressure
(13) Conduct air tight test to check the piping system is
equalizing pipe before removing of the cut
free from leakage.
pipe.
(14) Connect power cable to the terminal board of
Fig. 2
compressor and cover the compressor with sound
insulator mat.
(15) Conduct vacuum drying.
(Since the setting on outdoor unit PCB is required for vacuum drying, refer to the warning
plate “Precautions in service work” attached on the switch box cover.)
(16) Charge refrigerant after the completion of vacuum drying, and check the function of
compressor with cooling or heating operation.
258
: http://splitoff.ru/tehn-doc.html
Replacement procedure
for INV compressor, VRV II (RXYQ5M to 48M)
SiE39-404
Part 8
Appendix
1. Piping Diagrams..................................................................................260
1.1 Outdoor Unit .........................................................................................260
1.2 Indoor Unit............................................................................................263
2. Wiring Diagrams for Reference...........................................................269
2.1 Outdoor Unit .........................................................................................269
2.2 Field Wiring ..........................................................................................272
2.3 Indoor Unit............................................................................................275
3. List of Electrical and Functional Parts .................................................293
3.1 Outdoor Unit .........................................................................................293
3.2 Indoor Side ...........................................................................................295
4. Option List ...........................................................................................301
4.1 Option List of Controllers......................................................................301
4.2 Option Lists (Outdoor Unit)...................................................................303
5. Piping Installation Point.......................................................................304
5.1 Piping Installation Point ........................................................................304
5.2 The Example of A Wrong Pattern.........................................................305
6. Selection of Pipe Size, Joints and Header ..........................................306
6.1 RXYQ5MY1B, RXYQ8MY1B, RXYQ10MY1B, RXYQ12MY1B,
RXYQ14MY1B, RXYQ16MY1B ...........................................................306
6.2 RXYQ18MY1B, RXYQ20MY1B, RXYQ22MY1B, RXYQ24MY1B,
RXYQ26MY1B, RXYQ28MY1B, RXYQ30MY1B, RXYQ32MY1B,
RXYQ34MY1B, RXYQ36MY1B, RXYQ38MY1B, RXYQ40MY1B,
RXYQ42MY1B, RXYQ44MY1B, RXYQ46MY1B, RXYQ48MY1B .......308
7. Thermistor Resistance / Temperature Characteristics........................311
8. Pressure Sensor .................................................................................313
9. Method of Replacing The Inverter’s Power Transistors
and Diode Modules .............................................................................314
Appendix
: http://splitoff.ru/tehn-doc.html
259
Piping Diagrams
SiE39-404
1. Piping Diagrams
1.1
Outdoor Unit
RXYQ5MY1B
Receiver
Filter
Solenoid
valve
Heat
exchanger pipe
Filter
Fan
Solenoid
valve
Filter
Capillary
tube
Filter
Electronic
expansion valve
Heat exchanger
Four way
valve
Pressure
regulating valve
High pressure
switch
Filter
Filter
Solenoid
valve
High pressure
switch
Capillary
tube
Compressor
Low pressure
sensor
Filter
Stop valve (with service port on on-site piping side ∅ 7.9 mm flare connection)
4D040337C
260
: http://splitoff.ru/tehn-doc.html
Appendix
SiE39-404
Piping Diagrams
RXYQ8MY1B
RXYQ10MY1B
RXYQ12MY1B
Solenoid
valve
Capillary
tube
Filter
Receiver
Heat
exchanger pipe
Check
valve
Filter
Filter
Electronic
expansion valve
Filter
Pressure
regulating
valve
Check
valve
Electronic
expansion
valve
Fan
Solenoid
valve
Check
valve
Check
valve
Capillary
tube
High pressure
switch
Filter
Filter
Pressure
regulating
valve
Oil
separator
Filter
Check
valve
Capillary tube
Compressor
Solenoid
valve
Capillary tube
High pressure
switch
Heat exchanger
High pressure
sensor
Check
valve
Oil
separator
Filter
Filter
Four way
valve
Compressor
Filter
Low pressure
sensor
Check valve
Filter
Solenoid
valve
Stop valve (with service port on on-site piping side ∅ 7.9mm flare connection)
4D044808
Appendix
: http://splitoff.ru/tehn-doc.html
261
Piping Diagrams
SiE39-404
RXYQ14MY1B
RXYQ16MY1B
Heat
exchanger pipe
Capillary
tube
Filter
Filter
Receiver
Solenoid
valve
Filter
Check
valve
Electronic
expansion valve
Filter
Pressure
regulating
valve
Electronic
expansion
valve
Check
valve
Fan
Solenoid
valve
Check
valve
Heat exchanger
Four way
valve
Check
valve
Filter
Oil
separator
Filter
Oil
separator
Filter
Filter
Capillary tube
Compressor
High pressure
switch
Solenoid
valve
Capillary tube
High pressure
switch
Check
valve
Oil
separator
Filter
Filter
Filter
High pressure Pressure
sensor
regulating
valve
Check
Check
valve
valve
High pressure
switch
Compressor
Compressor
Capillary
tube
Capillary
tube
Filter
Low pressure
sensor
Filter
Check valve
Solenoid
valve
Stop valve (with service port on on-site piping side ∅ 7.9mm flare connection).
4D044809
262
: http://splitoff.ru/tehn-doc.html
Appendix
SiE39-404
1.2
Piping Diagrams
Indoor Unit
FXCQ, FXZQ, FXFQ, FXKQ, FXSQ, FXMQ, FXHQ, FXAQ, FXLQ, FXNQ
Gas piping connection port
Heat exchanger
Flare connection: ø 15.9 or less
Attached piping: Above ø 19.1
R3T
R1T
Fan
R2T
Liquid piping connection port
(Flare connection)
Filter
Electronic
Filter
expansion valve
DU220-602D
R1T : Thermistor for suction air temperature
R2T : Thermistor for liquid line temperature
R3T : Thermistor for gas line temperature
Capacity
20 / 25 / 32 / 40 / 50M
63 / 80 / 100 / 125M
200M
250M
Appendix
GAS
φ12.7
φ15.9
φ19.1
φ22.2
(mm)
Liquid
φ6.4
φ9.5
φ9.5
φ9.5
: http://splitoff.ru/tehn-doc.html
263
Piping Diagrams
SiE39-404
FXDQ
Gas side
Liquid side
Electronic
expansion valve
Filter
Filter
Fan
Indoor heat exchanger
4D043864A
! Refrigerant pipe connection port diameters
Model
FXDQ20N / 25N / 32N / 40N / 50NVE
FXDQ63NVE
264
Gas
φ12.7
φ15.9
(mm)
Liquid
φ6.4
φ9.5
: http://splitoff.ru/tehn-doc.html
Appendix
SiE39-404
Piping Diagrams
FXMQ125/200/250MFV1
Gas pipe
connection port
Heat exchanger
Filter
Capillary
tube
Distributor
Fan
Solenoid
valve
Filter
Filter
Liquid pipe
connection port
Check
valve
Electronic
expansion valve
4D018650B
! Refrigerant pipe connection port diameters
Model
FXMQ125MFV1
FXMQ200MFV1
FXMQ250MFV1
Appendix
Gas
φ15.9
φ19.1
φ22.2
(mm)
Liquid
φ9.5
φ9.5
φ9.5
: http://splitoff.ru/tehn-doc.html
265
Piping Diagrams
SiE39-404
FXUQ + BEVQ
Indoor unit
Indoor heat exchanger
Field piping ø 9. 5C1220T-0
Filter
To
outdoor unit
Field piping ø 15.9 C1220T-0
Indoor unit
4D037995B
Connection Unit
iquid piping
onnection port
Gas piping
onnection port
Electronic
expansion valve
Filter
Filter
Liquid piping
connection port
Gas piping
connection port
4D034127B
266
: http://splitoff.ru/tehn-doc.html
Appendix
SiE39-404
Piping Diagrams
FXAQ + BEVQ
Indoor unit
Gas pipe
connection port
Heat exchanger
Fan
Liquid pipe
connection port
Filter
4D047084
Connection Unit
Liquid piping
connection port
Gas piping
connection port
Filter
Electronic
expansion valve
Filter
Liquid piping
connection port
Gas piping
connection port
4D034127B
Appendix
: http://splitoff.ru/tehn-doc.html
267
Piping Diagrams
SiE39-404
FXLQ + BEVQ
Indoor unit
Gas pipe
connection port
Heat exchanger
Fan
Liquid pipe
connection port
Filter
4D047084
Connection Unit
Liquid piping
connection port
Gas piping
connection port
Filter
Electronic
expansion valve
Filter
Liquid piping
connection port
Gas piping
connection port
4D034127B
268
: http://splitoff.ru/tehn-doc.html
Appendix
Appendix
Notes:
1. This wiring diagram is applied only to the outdoor unit.
2.
: Field wiring.
3.
: Terminal strip
: Connector
: Terminal
: Protective earth (Screw)
4. When using the option adaptor, refer to the installation manual.
5. Refer to the installation manual, for connection wiring to indoor-outdoor
transmission F1 • F2, outdoor-outdoor transmission F1 • F2.
6. Refer to “Operation cauton label” (on switch box cover), how to use BS1~BS5 and DS1 • 2 switch.
7. When operation, don’t short circuit for protection device. (S1PH)
8. Colors BLK: black, RED: red, BLU: blue, WHT: white, PNK: pink, YLW: yellow, BNR: brown, GRN: green,
ORG: orange.
HAP
K1M
K1R
K2R
K3R
K6R
C1, 4
DS1, 2
E1HC
F1U
F1U, 2U
H1P~8P
L1-RED
A1P
A2P
A3P
A4P
BS1~5
Heat
S2S
Cool
Heat
S1S
Fan
L2-WHT
L3-BLK
N-BLU
Printed circuit board (Main)
Printed circuit board (INV)
Printed circuit board (Fan)
Printed circuit board (Noise filter)
Push button switch
(mode, set, return, test, reset)
Capacitor
Dip switch
Crankcase heater
Fuse (250V, 5A, 훾) (A4P)
Fuse (250V, 10A, 훾) (A1P)
Pilotlamp (Service monitor-orange)
[H2P] prepare, test ------- flickering
malfunction detection ---- light up
Pilot lamp (Service monitor-green)
Magnetic contactor (M1C)
Magnetic relay
Magnetic relay (K1M)
Magnetic relay (Y1S)
Magnetic relay (Y2S)
K9R
K11R
K13R
L1R
M1C
M1F
PS
Q1RP
R1
R10
R133
R3, 4
R1T
R1T
R2T
R3T
R4T
R5T
S1NPH
S1NPL
Magnetic relay (Y4S)
Magnetic relay (Y3S)
Magnetic relay (E1HC)
Reactor
Motor (Compressor)
Motor (Fan)
Switching power supply
Phase reversal detect circuit
Resistor (Current limiting)
Resistor (Current sensor)
Resistor (Current sensor)
Resistor
Thermistor (Air) (A1P)
Thermistor (Fin) (A2P)
Thermistor (Suction)
Thermistor (M1C discharge)
Thermistor (Heat exc. deicer)
Thermistor (Heat exc. outlet)
Pressure sensor (High)
Pressure sensor (Low)
Pressure switch (High)
Transformer (220-240V/20V)
Safety devices input
Power module (A2P)
Power module (A3P)
Terminal strip (Power supply)
Terminal strip (Control) (A1P)
Electronic expansion valve
Solenoid valve (Hot gas)
Solenoid valve (Receiver gas purge)
Solenoid valve (4 way valve)
Solenoid valve (injection)
Noise filter (Ferrite core)
Noise filter (With surge absorber)
(Back)
Switch box
(Front)
: http://splitoff.ru/tehn-doc.html
3D038590E
Cool/Heat selector (KRC19-26A)
Selector switch (Fan/Cool • Heat)
S1S
Selector switch (Cool/Heat)
S2S
S1PH
T1R
V1CP
V1R
V1R
X1M
X1M
Y1E
Y1S
Y2S
Y3S
Y4S
Z1C~5C
Z1F
Outdoor (F1) (F2)
Indoor (F1) (F2)
Note: 5
In-Out Out-Out
Cool/Heat selector (Optional accessory)
Cool
Cool/Heat selector
2.1
Detail of M1C
Power supply
380-415V 3N~50Hz
SiE39-404
Wiring Diagrams for Reference
2. Wiring Diagrams for Reference
Outdoor Unit
RXYQ5MY1B
269
270
Detail of M1C
Notes:
1. This wiring diagram is applied only to the outdoor unit.
2.
: Field wiring.
3.
: Terminal strip
: Connector
: Terminal
: Protective earth (Screw)
4. When using the option adaptor, refer to the installation manual.
5. Refer to the installation manual, for connection wiring to indoor-outdoor
transmission F1 • F2, outdoor-outdoor transmission F1 • F2, outdoor-multi transmission Q1 • Q2.
6. Refer to “Operation cauton label” (on switch box cover), how to use BS1~BS5 and DS1 • 2 switch.
7. When operation, don’t short circuit for protection device. (S1PH • 2PH)
8. Colors BLK: black, RED: red, BLU: blue, WHT: white, PNK: pink, YLW: yellow, BRN: brown, GRY: gray,
GRN: green, ORG: orange.
Detail of M2C
Power supply
380-415V 3N~50Hz
Cool
Heat
L2-WHT
L3-BLK
N-BLU
Printed circuit board (Main)
K11R
K13R
Printed circuit board (INV)
Printed circuit board (Fan)
K14R
Printed circuit board (Noise filter) L1R
Printed circuit board (Current sensor) M1C, M2C
Push button switch
M1F
(mode, set, return, test, reset)
PS
C1, 4
Capacitor
Q1RP
DS1, 2
Dip switch
R1
E1HC, 2HC Crankcase heater
R10
F1U
Fuse (250V, 5A, 훾) (A4P)
R133
F1U, 2U Fuse (250V, 10A, 훾) (A1P)
R3, 4
H1P~8P Pilotlamp (Service monitor-orange) R1T
[H2P] prepare, test ------- flickering R1T
malfunction detection ---- light up
R2T
HAP
Pilot lamp (Service monitor-green) R31T, R32T
K1M, K2M Magnetic contactor (M1C • 2C)
R4T
K1R
Magnetic relay (K2M) (A1P)
R5T
Magnetic relay (A2P)
R6T
K1R
K2R
Magnetic relay (K1M)
R7T
K3R
Magnetic relay (Y1S)
S1NPH
K4R
Magnetic relay (Y2S)
S1NPL
S1PH, 2PH
K6R
Magnetic relay (Y3S)
T1A
Magnetic relay (Y4S)
K8R
L1-RED
A1P
A2P
A3P
A4P
A5P
BS1~5
Heat
S2S
S1S
Fan
Magnetic relay (Y5S)
Magnetic relay (E1HC)
Magnetic relay (E2HC)
Reactor
Motor (Compressor)
Motor (Fan)
Switching power supply
Phase reversal detect circuit
Resistor (Current limiting)
Resistor (Current sensor)
Resistor (Current sensor)
Resistor
Thermistor (Air) (A1P)
Thermistor (Fin) (A2P)
Thermistor (Suction)
Thermistor (M1C, 2C discharge)
Thermistor (Heat exc. deicer)
Thermistor (Heat exc. outlet)
Thermistor (Liq. pipe receiver)
Thermistor (Oil pipe)
Pressure sensor (High)
Pressure sensor (Low)
Pressure switch (High)
Current sensor
Indoor (F1) (F2)
Transformer (220-240V/20V)
Safety devices input
Power module (A2P)
Power module (A3P)
Terminal strip (Power supply)
Terminal strip (Control) (A1P)
Electronic expansion valve (Main)
Electronic expansion valve (Subcool)
Solenoid valve (Hot gas)
Solenoid valve (Out-multi oil)
Solenoid valve (Receiver gas purge)
Solenoid valve (Liquid pipe)
Solenoid valve (4 way valve)
Noise filter (Ferrite core)
Noise filter (With surge absorber)
(Back)
Switch box
: http://splitoff.ru/tehn-doc.html
3D44772
Cool/Heat selector (KRC19-26A)
Selector switch (Fan/Cool • Heat)
S1S
Selector switch (Cool/Heat)
S2S
T1R
V1CP
V1R
V1R
X1M
X1M
Y1E
Y2E
Y1S
Y2S
Y3S
Y4S
Y5S
Z1C~6C
Z1F
Outdoor (Q1) (Q2)
Outdoor (F1) (F2)
Note: 5
In-Out Out-Out Out-Multi
Cool/Heat selector (Optional accessory)
Cool
Cool/Heat selector
is connector color for printed circuit board.
is connector color for component.
is discrimination color for component lead wire
(Front)
Wiring Diagrams for Reference
SiE39-404
RXYQ8MY1B
RXYQ10MY1B
RXYQ12MY1B
Appendix
Appendix
Detail of M1C
Notes:
1. This wiring diagram is applied only to the outdoor unit.
2.
: Field wiring.
3.
: Terminal strip
: Connector
: Terminal
: Protective earth (Screw)
4. When using the option adaptor, refer to the installation manual.
5. Refer to the installation manual, for connection wiring to indoor-outdoor
transmission F1 • F2, outdoor-outdoor transmission F1 • F2, outdoor-multi transmission Q1 • Q2.
6. Refer to “Operation cauton label” (on switch box cover), how to use BS1~BS5 and DS1 • 2 switch.
7. When operation, don’t short circuit for protection device. (S1PH • S3PH)
8. Colors BLK: black, RED: red, BLU: blue, WHT: white, PNK: pink, YLW: yellow, BRN: brown, GRY: gray,
GRN: green, ORG: orange.
Detail of M2C
Detail of M3C
Power supply
380-415V 3N~50Hz
Cool
Heat
S1S
Fan
Magnetic relay (Y5S)
Magnetic relay (E1HC)
Magnetic relay (E2HC)
Magnetic relay (E3HC)
Reactor
Motor (Compressor)
Motor (Fan)
Switching power supply
Phase reversal detect circuit
Resistor (Current limiting)
Resistor (Current sensor)
Resistor (Current sensor)
Resistor
Thermistor (Air) (A1P)
Thermistor (Fin) (A2P)
Thermistor (Suction)
Thermistor (M1C~3C discharge)
Thermistor (Heat exc. deicer)
Thermistor (Heat exc. outlet)
Thermistor (Liq. pipe receiver)
Thermistor (Oil pipe)
Pressure sensor (High)
Pressure sensor (Low)
Pressure switch (High)
Current sensor (A5P, A6P)
Transformer (220-240V/20V)
Safety devices input
Power module (A2P)
Power module (A3P)
Terminal strip (Power supply)
Terminal strip (Control) (A1P)
Electronic expansion valve (Main)
Electronic expansion valve (Subcool)
Solenoid valve (Hot gas)
Solenoid valve (Out-multi oil)
Solenoid valve (Receiver gas purge)
Solenoid valve (Liquid pipe)
Solenoid valve (4 way valve)
Noise filter (Ferrite core)
Noise filter (With surge absorber)
(Back)
Switch box
: http://splitoff.ru/tehn-doc.html
3D044773
3D044773
Cool/Heat selector (KRC19-26A)
Selector switch (Fan/Cool • Heat)
S1S
S2S
Selector switch (Cool/Heat)
T1R
V1CP
V1R
V1R
X1M
X1M
Y1E
Y2E
Y1S
Y2S
Y3S
Y4S
Y5S
Z1C~7C
Z1F
Outdoor (Q1) (Q2)
Outdoor (F1) (F2)
Indoor (F1) (F2)
Note: 5
In-Out Out-Out Out-Multi
Cool/Heat selector (Optional accessory)
Heat
S2S
L2-WHT
L3-BLK
N-BLU
Printed circuit board (Main)
K11R
Printed circuit board (INV)
K13R
Printed circuit board (Fan)
K14R
Printed circuit board (Noise filter) K15R
Printed circuit board (Current sensor) L1R
Push button switch
M1C, 3C
(mode, set, return, test, reset)
M1F
C1, 4
Capacitor
PS
DS1, 2
Dip switch
Q1RP
E1HC, 3HC Crankcase heater
R1
F1U
Fuse (250V, 5A, 훾) (A4P)
R10
F1U, 2U Fuse (250V, 10A, 훾) (A1P)
R133
H1P~8P Pilotlamp (Service monitor-orange) R3, 4
[H2P] prepare, test ------- flickering R1T
malfunction detection ---- light up
R1T
HAP
Pilotlamp (Service monitor-green) R2T
K1M~3M Magnetic contactor (M1C • 3C)
R31~33T
K1R
Magnetic relay (K2M) (A1P)
R4T
K1R
Magnetic relay (A2P)
R5T
K2R
Magnetic relay (K3M) (A1P)
R6T
K2R
Magnetic relay (K1M) (A2P)
R7T
K3R
Magnetic relay (Y1S)
S1NPH
K4R
Magnetic relay (Y2S)
S1NPL
K6R
Magnetic relay (Y3S)
S1PH~3PH
K8R
Magnetic relay (Y4S)
T1A
L1-RED
A1P
A2P
A3P
A4P
A5P, 6P
BS1~5
Cool
Cool/Heat selector
is connector color for printed circuit board.
is connector color for component.
is discrimination color for component lead wire
(Front)
SiE39-404
Wiring Diagrams for Reference
RXYQ14MY1B
RXYQ16MY1B
271
Main switch
272
Fuse
Switch
2 wires cable
(Transmission line)
Fuse
Switch
Fuse
Switch
Indoor units
2 wires cable
(Power line)
2 wires cable
(Transmission line)
Outdoor units
Notes 1) All wiring, components and materials to be procured on
the site must comply with the applicable local and
national codes.
2) Use copper conductors only.
3) As for details, see wiring diagram.
4) Install circuit breaker for safety.
5) All field wiring and components must be provided by
licensed electrician.
2 wires cable
(Power line)
Fuse
Switch
2 wires cable
(Transmission line)
2 wires cable
(Power line)
Fuse
Switch
2 wires cable
(Transmission line)
6) Unit shall be grounded in compliance with the applicable local and national codes.
7) Wiring shown are general points-of-connection guides only and are not intended for or to
include all details for a specific installation.
8) Be sure to install the switch and the fuse to the power line of each equipment.
9) Install the main switch that can interrupt all the power souces in an integrated manner
because this system consists of the equipment utilizing the multiple power sources.
3D040746C
2.2
2 wires cable
(Power line)
Power supply
Wiring Diagrams for Reference
SiE39-404
Field Wiring
RXYQ5~16MY1B
: http://splitoff.ru/tehn-doc.html
Appendix
Appendix
Main
switch
Fuse
2 wires cable
(Power line)
Switch
Fuse
: http://splitoff.ru/tehn-doc.html
Fuse
Switch
Fuse
Switch
2 wires cable
(Transmission line)
Fuse
Switch
2 wires cable
(Power line)
2 wires cable
(Transmission line)
Fuse
Switch
2 wires cable
(Power line)
Main
switch
Power supply
Fuse
Switch
2 wires cable
(Transmission line)
[Unit 2]
2 wires cable
(Power line)
Fuse
Switch
2 wires cable
(Transmission line)
Indoor units
[Unit 1]
2 wires cable
(Transmission line)
Outdoor units
2 wires cable
(Power line)
Fuse
Switch
3D040747B
2 wires cable
(Transmission line)
When the power source is connected in series between the units.
6) Unit shall be grounded in compliance with the applicable local and national codes.
7) Wiring shown are general points-of-connection guides only and are not intended for or
to include all details for a specific installation.
8) Be sure to install the switch and the fuse to the power line of each equipment.
9) Install the main switch that can interrupt all the power souces in an integrated manner
because this system consists of the equipment utilizing the multiple power sources.
10) The capacity of UNIT1 must be larger than UNIT2 when the power source is connected
in series between the units.
2 wires cable
(Power line)
[Unit 2]
2 wires cable
(Transmission line)
2 wires cable
(Power line)
Indoor units
2 wires cable
(Transmission line)
Switch
2 wires cable
(Power line)
Fuse
2 wires cable
(Transmission line)
Switch
Fuse
[Unit 1]
2 wires cable
(Transmission line)
Outdoor units
When the power source is suppled to each outdoor unit individually
Switch
Power supply
Notes 1) All wiring, components and materials to be procured on
the site must comply with the applicable local and
national codes.
2) Use copper conductors only.
3) As for details, see wiring diagram.
4) Install circuit breaker for safety.
5) All field wiring and components must be provided by
licensed electrician.
SiE39-404
Wiring Diagrams for Reference
RXYQ18, 20, 22, 24, 26, 28, 30, 32MY1B
273
274
Fuse
Fuse
Fuse
2 wires cable
(Power line)
Switch
[Unit 2]
Fuse
2 wires cable
(Power line)
Switch
Fuse
2 wires cable
(Transmission line)
[Unit 3]
2 wires cable
(Transmission line)
Switch
2 wires cable
(Transmission line)
2 wires cable
(Power line)
Indoor units
2 wires cable
(Transmission line)
Fuse
2 wires cable
(Power line)
Fuse
Switch
[Unit 1]
2 wires cable
(Transmission line)
Outdoor units
Fuse
2 wires cable
(Power line)
Switch
Fuse
2 wires cable
(Transmission line)
2 wires cable
(Power line)
2 wires cable
(Power line)
Fuse
3D040748B
Switch
Fuse
Switch
[Unit 3]
2 wires cable
(Transmission line)
[Unit 2]
2 wires cable
(Transmission line)
2 wires cable
(Transmission line)
Indoor units
[Unit 1]
2 wires cable
(Transmission line)
Outdoor units
When the power source is connected in series between the units.
Switch
2 wires cable
(Power line)
2 wires cable
(Transmission line)
Fuse
Switch
Main
switch
Power supply
6) Unit shall be grounded in compliance with the applicable local and national codes.
7) Wiring shown are general points-of-connection guides only and are not intended for or
to include all details for a specific installation.
8) Be sure to install the switch and the fuse to the power line of each equipment.
9) Install the main switch that can interrupt all the power souces in an integrated manner
because this system consists of the equipment utilizing the multiple power sources.
10) Unit 1 must be RXYQ16MY1B when the power source is connected in series between
the units. (In case of RXYQ34MY1B, RXYQ14MY1B.)
When the power source is suppled to each outdoor unit individually
Switch
2 wires cable
(Transmission line)
Switch
Switch
Main
switch
Power supply
Notes 1) All wiring, components and materials to be procured on
the site must comply with the applicable local and
national codes.
2) Use copper conductors only.
3) As for details, see wiring diagram.
4) Install circuit breaker for safety.
5) All field wiring and components must be provided by
licensed electrician.
Wiring Diagrams for Reference
SiE39-404
RXYQ34, 36, 38, 40, 42, 44, 46, 48MY1B
: http://splitoff.ru/tehn-doc.html
Appendix
Thermo switch
(M1F embedded)
Thermistor (Air)
Thermistor (Coil)
Float switch
Limit switch
(Swing flap)
Transformer (220-240V/22V)
Terminal block (Power)
Terminal block (Control)
Electronic expansion
valve
Infrared remote control
R1T Thermistor (Air)
SS1 Selector switch
(Main/Sub)
Receiver/display unit
(Attached to
infrared remote control)
A2P Printed circuit board
A3P Printed circuit board
BS1 Push button (On/off)
H1P Light emitting diode
(On-red)
H2P Light emitting diode
(Timer-green)
Appendix
(Wiring adaptor for
electorical appendices)
(Infrared remote
control)
X23A Connector
H3P Light emitting diode
(Filter sign-red)
H4P Light emitting diode
(Defrost-orange)
SS1 Selector switch
(Main/sub)
SS2 Selector switch
(wireless address set)
Connector for optional parts
X18A Connector
Power supply
220-240V 220V
~
~
50Hz
60Hz
Infrared remote control
(Optional accessory)
Note 4
3D039556A
Electric parts box
Note 5
Input from outside
Note 3
Transmission wiring
central remote control
Note 4 Receiver/display unit
(Infrared remote control)
2.3
Notes 1.
: Terminal block,
,
: Connector,
: Terminal
2.
: Field wiring
3. In case using central remote control, connect it to the unit in accordance
with the attached instruction manual.
4. X23A is connected when the infrared remote control kit is being used.
5. When connecting the input wires from outside, forced off or on/off control
operation can be selected by remote control.
In details, refer to the installation manual attached the unit.
6. Symbols shows as follows.
(PNK: pink, WHT: white, YLW: yellow, ORG: orange, BLU: blue, BLK: black,
RED: red, BRN: brown, GRN: green)
Indoor unit
Q1M
Printed circuit board
Capacitor (M1F)
R1T
Fuse (훾, 5A, 250V) R2T•R3T
Light emitting diode S1L
(Service monitor-green) S1Q
K1R-K3R Magnetic relay (M1F)
KAR Magnetic relay (M1S) T1R
KPR Magnetic relay (M1P) X1M
M1F Motor (Indoor fan)
X2M
M1P Motor (Drain pump) Y1E
M1S Motor (Swing flap)
A1P
C1R
F1U
HAP
SiE39-404
Wiring Diagrams for Reference
Indoor Unit
FXCQ20M / 25M / 32M / 63MVE
: http://splitoff.ru/tehn-doc.html
275
276
(Wiring adaptor for
electorical appendices)
(Infrared remote
control)
X23A Connector
H1P Light emitting diode
(On-red)
H2P Light emitting diode
(Timer-green)
H3P Light emitting diode
(Filter sign-red)
H4P Light emitting diode
(Defrost-orange)
SS1 Selector switch
(Main/sub)
SS2 Selector switch
(wireless address set)
Connector for optional parts
X18A Connector
Notes 1.
: Terminal block,
,
: Connector,
: Terminal
2.
: Field wiring
3. In case using central remote control, connect it to the unit in accordance with
the attached instruction manual.
4. X23A is connected when the infrared remote control kit is being used.
5. When connecting the input wires from outside, forced off or on/off control
operation can be selected by remote control.
In details, refer to the installation manual attached the unit.
6. Symbols shows as follows.
(PNK: pink, WHT: white, YLW: yellow, ORG: orange, BLU: blue, BLK: black,
RED: red, BRN: brown, GRN: green)
7. Use copper conductors only.
Indoor unit
S1L Float switch
Printed circuit board S1Q Limit switch
Capacitor (M1F)
(Swing flap)
Fuse (훾, 5A, 250V) T1R Transformer (220-240V/22V)
Light emitting diode X1M Terminal block (Power)
(Service monitor-green) X2M Terminal block (Control)
K1R-K3R Magnetic relay (M1F) Y1E Electronic expansion
KAR Magnetic relay (M1S)
valve
KPR Magnetic relay (M1P)
Infrared remote control
M1F Motor (Indoor fan)
R1T Thermistor (Air)
M1P Motor (Drain pump)
SS1 Selector switch
M1S Motor (Swing flap)
(Main/Sub)
Receiver/display unit
Q1M Thermo switch
(Attached to
(M1F embedded)
infrared remote control)
R1T Thermistor (Air)
A2P Printed circuit board
R2T•R3T Thermistor (Coil)
A3P Printed circuit board
BS1 Push button (On/off)
A1P
C1R
F1U
HAP
Power supply
220-240V 220V
~
~
50Hz
60Hz
Infrared remote control
(Optional accessory)
Note 4
3D039557A
Electric parts box
Note 5
Input from outside
Note 3
Transmission wiring
central remote control
Note 4 Receiver/display unit
(Infrared remote control)
Wiring Diagrams for Reference
SiE39-404
FXCQ40M / 50M / 80M/ 125MVE
: http://splitoff.ru/tehn-doc.html
Appendix
Printed circuit board
Capacitor (M1F)
Fuse (훾, 5A, 250V)
Light emitting diode (Service
monitor-green)
KPR Magnetic relay (M1P)
M1F Motor (Indoor fan)
M1P Motor (Drain pump)
M1S Motor (Swing flap)
Q1M Thermal protector (M1F embedded)
R1T Thermistor (Air)
R2T Thermistor (Coil-liquid)
R3T Thermistor (Coil-gas)
S1L Float switch
T1R Transformer (220-240V/22V)
V1TR Triac
X1M Terminal block
X2M Terminal block
Y1E Electronic expansion valve
Wired remote control
R1T Thermistor (Air)
SS1 Selector switch (Main/Sub)
Infrared remote control
(Receiver/display unit)
A3P Printed circuit board
A4P Printed circuit board
A1P
C1
F1U
HAP
Push button (On/off)
Light emitting diode
(On-red)
H2P Light emitting diode
(Timer-green)
H3P Light emitting diode
(Filter sign-red)
H4P Light emitting diode
(Defrost-orange)
SS1 Selector switch
(Main/sub)
SS2 Selector switch
(wireless address set)
Connector for optional parts
X16A Connector
(Adaptor for wiring)
X18A Connector
(Wiring adaptor for
electorical appendices)
BS1
H1P
Appendix
Receiver/display unit
: Connector
Note: 3
: Field wiring
2. In case using central remote control, connect it to the unit in accordance with the attached installation manual.
3. X23A is connected when the infrared remote control kit is being used.
4. When connecting the input wires from outside, forced off or on/off control operation can be selected by remote control.
In details, refer to the installation manual attached the unit.
5. Remote control model varies according to de combination system, confirm engineering materials and catalogs, etc.
before connecting.
6. Symbols shows as follows: RED; red, BLK: black, WHT: white, YLW: yellow, PNK: pink, ORG: orange, GRN: green,
BLU: blue.
,
Notes:
1.
: Terminal
Note: 3
Power supply
220-240V 220V
~
~
50Hz
60Hz
Wired remote
control
3D038359
Input from outside
Note: 4
Transmission wiring
central remote control
Note: 2
SiE39-404
Wiring Diagrams for Reference
FXZQ20M / 25M / 32M / 40M / 50MVE
: http://splitoff.ru/tehn-doc.html
277
278
Indoor unit
H2P Light emitting diode
(On-red)
H1P Light emitting diode
PC Power circuit
Z1F Noise filter
valve
Y1E Electronic expansion
Power supply
220-240V 220V
~
~
50Hz
60Hz
: Terminal block
,
: Connector
: Field wiring
2. In case using central remote control, connect it to the unit in accordance
with the attached installation manual.
3. X24A is connected when the infrared remote control kit is being used.
4. When connecting the input wires from outside, forced off or on/off control
operation can be selected by remote control.
In details, refer to the installation manual attached the unit.
Notes:
1.
SS1 Selector switch (Main/Sub)
R1T Thermistor (Air)
Wired remote control
control adaptor)
X35A Connector (Group
(Adaptor for wiring)
X33A Connector
(Infrared remote control)
X24A Connector
X2M Terminal block
X1M Terminal block
(wireless address set)
Connector for optional parts
S1L Float switch
R3T Thermistor (Coil-gas)
SS2 Selector switch
(Main/sub)
R2T Thermistor (Coil-liquid)
R1T Thermistor (Air)
(Defrost-orange)
SS1 Selector switch
M1S Motor (Swing flap)
M1P Motor (Drain pump)
(Timer-green)
(Service monitor-green) H3P Light emitting diode
KPR Magnetic relay (M1P)
(Filter sign-red)
M1F Motor (Indoor fan)
H4P Light emitting diode
HAP Light emitting diode
F1U Fuse (훾, 5A, 250V)
(Temperature sensor unit)
A4P Printed circuit board
BS1 Push button (On/off)
A6P Printed circuit board
A2P Printed circuit board
(Control)
A5P Printed circuit board
Receiver/display unit (Attached
to infrared remote control
(Power supply)
A1P Printed circuit board
Note: 3
Note: 4
Switch box
(Indoor unit)
Wired remote control
Transmission wiring
central remote control
Note: 2
Input from outside
Receiver/display unit
(Infrared remote control)
5. Remote control model varies according to de combination system, confirm
engineering materials and catalogs, etc. before connecting.
6. Confirm the method of setting the selector switch (SS1, SS2) of wired
remote control and infrared remote control by installation manual and
engineering data, etc.
7. Symbols shows as follows: RED; red, BLK: black, WHT: white, YLW: yellow,
GRN: green, ORG: orange, BRN: brown, PNK: pink, GRY: gray, BLU: blue.
Note: 3
3D039600A
Wiring Diagrams for Reference
SiE39-404
FXFQ25M / 32M / 40M / 50M / 63M / 80M / 100M / 125MVE
: http://splitoff.ru/tehn-doc.html
Appendix
Appendix
Indoor unit
Fuse (훾, 5A, 250V)
Light emitting diode
C1R
F1U
HAP
Thermistor (Air)
X16A Connector (Adaptor for wiring)
X18A Connector (Wiring adaptor
Motor (Indoor fan)
Motor (Drain pump)
Motor (Swing flap)
Thermo switch
(M1F embedded)
M1F
M1P
M1S
Q1M
valve
Note: 5
Power supply
220-240V 220V
~
~
50Hz
60Hz
: Terminal block,
,
: Connector,
: Terminal
Notes: 1.
2.
: Field wiring
3. In case using central remote control, connect it to the unit in accordance with the
attached installation manual.
4. When connecting the input wires from outside, forced off or on/off control operation
can be selected by remote control.
In details, refer to the installation manual attached the unit.
5. In case high E.S.P. operation, change over the wiring connection from X2A to X3A.
6. Symbols shows as follows. (PNK: pink, WHT: white, YLW: yellow, ORG: orange,
BLU: blue, BLK: black, RED: red, BRN: brown, GRY: gray)
7. Use copper conductors only.
for electorical appendices)
Connector for optional parts
SS1 Selector switch (Main/Sub)
R1T Thermistor (Air)
Wired remote control
Magnetic relay (M1P)
KPR
Electronic expansion
Terminal block (Control)
Terminal block (Power)
Transformer (220-240V/22V)
Limit switch (Swing flap)
Float switch
Magnetic relay (M1S)
Y1E
X2M
X1M
T1R
S1Q
S1L
R2T•R3T Thermistor (Coil)
R1T
KAR
K1R-K3R Magnetic relay (M1F)
(Service monitor-green)
Terminal board
Capacitor (M1F)
A2P
Printed circuit board
A1P
Wired remote control
(Optional accessory)
3D039564A
Note: 4
Input from outside
Note: 2
Transmission wiring
central remote control
Electric parts box
SiE39-404
Wiring Diagrams for Reference
FXKQ25M / 32M / 40M / 63MVE
: http://splitoff.ru/tehn-doc.html
279
280
Fuse (F5A/250V)
Light emitting diode
C1
F1U
HAP
Electronic expansion valve
Connector (Adaptor for wiring)
Connector (Wiring adaptor
X16A
X18A
,
: Connector
: Terminal
Control box
220V
~
60Hz
Power supply
220-240V
~
50Hz
2.
: Field wiring
3. In case using central remote control, connect it to the unit in accordance with the attached installation manual.
4. Remote control model varies according to the combination system, confirm engineering materials and catalogs, etc. before connecting.
5. When connecting the input wires from outside, forced off or on/off control operation can be selected by remote control.
In details, refer to the installation manual attached the unit.
6. Symbols shows as follows: RED: red, BLK: black, WHT: white, YLW: yellow, PRP: purple, GRY: gray, BLU: blue, PNK: pink, ORG:
orange, GRN: green.
1.
Notes:
Selector switch (Main/Sub)
Connector for optional parts
SS1
for electrical appendices)
Thermistor (Air)
R1T
Wired remote control
Z1C•Z2C Noise filter (Ferrite core)
Terminal block
Y1E
Float switch
S1L
Terminal block
Thermistor (Coil-2)
R3T
X2M
Thermistor (Coil-1)
R2T
X1M
Thermistor (Air)
R1T
Transformer (220V/22V)
Thermal protector (M1F embedded)
Q1M
Phase control circuit
Motor (Drain pump)
M1P
V1TR
Motor (Indoor fan)
M1F
T1R
Magnetic relay (M1P)
KPR
(Service monitor-green)
Printed circuit board
Capacitor (M1F)
A1P
Wired remote
control
3D045500A
Transmission wiring
central remote control
Note: 3
Note: 5
Input from outside
Wiring Diagrams for Reference
SiE39-404
FXDQ20N / 25N / 32N / 40N / 50N / 63NVE
: http://splitoff.ru/tehn-doc.html
Appendix
Appendix
(80 • 100 • 125 Type)
High E.S.P. operation
(20 • 25 • 32 • 40 • 50 • 63 Type)
High E.S.P. operation
Low E.S.P. operation
Note 6
(20 • 25 • 32 Type)
40 • 50 • 63 • 80
100 • 125 Type
Separate power supply
220-240V 220V
~
~
50Hz 60Hz
Notes:
1.
: Terminal block,
,
: Connector,
: Terminal
2.
: Field wiring
(80 • 100 • 125 Type)
3. In case using central remote control, connect it to the unit in accordance
with the attached instruction manual.
4. When connecting the input wires from outside, forced off or on/off control operation can be selected by remote control.
In details, refer to the installation manual attached the unit.
5. In case installing the electric heater, execute the additional wiring for heater circuit (K1M, E1H), In this case, the main power
supply has to be supplied independently.
6. In case high of low E.S.P. operation, change over the wiring connection from X4A (of A2P) to X3A of X5A.
7. Symbols shows as follows. (PNK; pink, WHT: white, YLW: yellow, GRY: gray, ORG: orange, BLU: blue, BLK: black, RED: red,
BRN: brown, GRN: green)
8. Use copper conductors only.
Optional parts
Indoor unit
E1H
Printed circuit board
Electric heater
A2P
F1U-F3U Fuse (훾, 5A, 250V)
Terminal board
C1R
Hu
Capacitor (M1F)
Humidifier
F1U
K1M
Fuse (훾, 5A, 250V)
Magnetic relay (E1H)
HAP
S1H
Light emitting diode
Humidistat
(Service monitor-green) X3M
Terminal block (E1H)
K1R-K3R Magnetic relay (M1P)
Wired remote control
KPR
Magnetic relay (M1P)
R1T
Thermistor (Air)
M1F
Motor (Indoor fan)
SS1
Selector switch (Main/Sub)
M1P
Motor (Drain pump)
Adaptor for wiring
Q1M
Thermal switch
F1U-F3U Fuse (훾, 5A, 250V)
(M1F embedded)
KCR
Magnetic relay
R1T
Thermistor (Air)
KFR
Magnetic relay
R2T•R3T Thermistor (Coil)
KHR
Magnetic relay (E1H)
S1L
Float switch
KHuR Magnetic relay (Hu)
T1R
Transformer (220-240V/22V) Connector for optional parts
X1M
Terminal block (Power)
X16A Connector (Adaptor for wiring)
X2M
Terminal block (Control) X18A Connector (Wiring adaptor
Y1E
for electrical appendices)
Electronic expansion valve
A1P
Terminals for
operation
indicator
Electric parts box
Note: 3
Transmission wiring
central remote control
Note: 4
Input from outside
Adaptor for wiring
(Optional accessory)
Wired remote control
(Optional accessory)
Fan
operation
Compressor
operation
(20 • 25 • 32 • 40 • 50 • 63 Type)
Power supply
220-240V 220V
~
~
50Hz 60Hz
3D039561A
SiE39-404
Wiring Diagrams for Reference
FXSQ20M / 25M / 32M / 40M / 50M / 63M / 80M / 100M / 125MVE
: http://splitoff.ru/tehn-doc.html
281
282
X2M
Y1E
40 • 50 • 63 • 80 Type
Fuse (훾, 10A, 250V)
Electronic expansion
Terminal block (Control)
Terminal block (Power)
Transformer (220-240V/22V)
Connector for optional parts
X18A Connector (Wiring adaptor
Motor (Indoor fan)
Thermo switch
(M1F embedded)
M1F
Q1M
Note 5
Power supply
220-240V 220V
~
~
50Hz 60Hz
Notes:
1.
: Terminal block,
,
: Connector,
: Terminal
2.
: Field wiring
3. In case using central remote control, connect it to the unit in accordance with the attached instruction manual.
4. When connecting the input wires from outside, forced off or on/off control operation can be selected by remote control.
In details, refer to the installation manual attached the unit.
5. In case high of low E.S.P. operation, change the wiring connection of X2A as shown upper figure.
6. Symbols shows as follows. (PNK; pink, WHT: white, YLW: yellow, ORG: orange, BLU: blue, BLK: black, RED: red,
BRN: brown)
7. Use copper conductors only.
for electorical appendices)
Thermistor (Air)
(Main/Sub)
R1T
Light emitting diode
HAP
valve
Optional parts
(Service monitor-green) M1P Motor (Drain pump)
Wired remote control
K1R-K3R Magnetic relay (M1F)
SS1 Selector switch
KPR Magnetic relay (M1P)
100 • 125 Type
X1M
Fuse (훾, 5A, 250V)
F1U
F1U
T1R
Capacitor (M1F)
C1R
Float switch
S1L
Terminal board
Thermistor (Air)
A2P
R1T
R2T•R3T Thermistor (Coil)
Indoor unit
Printed circuit board
A1P
Wired remote control
(Optional accessory)
Note: 3
Transmission wiring
central remote control
Note: 4
Input from outside
Electric parts box
3D039620A
Wiring Diagrams for Reference
SiE39-404
FXMQ40M / 50M / 63M / 80M / 100M / 125MVE
: http://splitoff.ru/tehn-doc.html
Appendix
Appendix
Indoor unit
Printed circuit board
Magnetic contactor (M1F • 2F)
Magnetic contactor (M1F • 2F)
Magnetic relay (M1F • 2F)
Magnetic relay (M1P)
Motor (Indoor fan)
K3M
K1R-K3R
KPR
M1F•M2F
SS1
R1T
M1P
Y1E
X4M
Selector switch (Main/Sub)
Connector for optional parts
Thermistor (Air)
Optional parts
Motor (Drain pump)
Wired remote control
Electronic expansion valve
Terminal block (Control)
X2M-X3M Terminal block
Terminal block (Power)
Transformer (220-240V/22V)
(Static pressure)
Selector switch
Thermistor (Coil)
Thermistor (Air)
: Terminal block
X8A
Connector (Float switch)
,
: Connector
X18A
Connector (Wiring adaptor for
: Short circuit connector
electorical appendices)
: Terminal
2.
: Field wiring
3. In case using central remote control, connect it to the unit in accordance with the
attached instruction manual.
4. When connecting the input wires from outside, forced off or on/off control operation
can be selected by remote control.
In details, refer to the installation manual attached the unit.
5. In case installing the drain pump, remove the short circuit connector of X8A and
execute the additional wiring for float switch and drain pump.
6. Symbols shows as follows. (PNK; pink, WHT: white, YLW: yellow,
ORG: orange, BLU: blue, BLK: black, RED: red, BRN: brown)
7. Use copper conductors only.
8. In case high E.S.P. operation, change the switch (SS) for “H”.
Notes:
1.
(M1F • 2F embedded)
Q1M•Q2M Thermo switch
Magnetic contactor (M1F • 2F)
(Service monitor-green)
K2M
X1M
Light emitting diode
K1M
T1R
Fuse (훾, 5A, 250V)
HAP
SS
R2T•R3T
R1T
F1U
C1R•C2R Capacitor (M1F • 2F)
A1P
Power supply
220-240V 220V
~
~
50Hz 60Hz
Wired remote control
(Optional accessory)
3D039621A
Note: 3
Transmission wiring
central remote control
Note: 4
Input from outside
Electric parts box
SiE39-404
Wiring Diagrams for Reference
FXMQ200M / 250MVE
: http://splitoff.ru/tehn-doc.html
283
Indoor unit
Printed circuit board
Capacitor (M1F)
Fuse (훾, 5A, 250V)
Light emitting diode
(Service monitor-green)
KAR Magnetic relay (L1S)
KPR Magnetic relay (M1P)
M1F Motor (Indoor fan)
M1S Motor (Swing flap)
Q1M Thermo switch (M1F embedded)
R1T Thermistor (Air)
R2T Thermistor (Coil liquid)
R3T Thermistor (Coil gas)
S1Q Limit switch (Swing flap)
T1R Transformer (220-240V/22V)
X1M Terminal block (Power)
X2M Terminal block (Control)
Y1E Electronic expansion valve
PC Phase control circuit
Optional parts
M1P Motor (Drain pump)
Wired remote control
R1T Thermistor (Air)
SS1 Selector switch (Main/Sub)
Receiver/Display unit (Attached to
infrared remote control
A2P Printed circuit board
A3P Printed circuit board
BS1 Push botton (On/off)
H1P Light emitting diode (On-red)
H2P Light emitting diode
(Timer-green)
A1P
C1R
F1U
HAP
284
Power supply
220-240V 220V
~
~
50Hz 60Hz
: Terminal block,
,
: Connector
: Short circuit connector
2.
: Field wiring
3. In case using central remote control, connect it to the unit in
accordance with the attached instruction manual.
4. X23A is connected when the infrared remote control kit is being
used.
5. When connecting the input wires from outside, forced off or on/off
control operation can be selected by remote control. In details,
refer to the installation manual attached the unit.
6. In case installing the drain pump, remove the short circuit
connector of X8A and execute the additional wiring for float switch
and drain pump.
7. Symbols shows as follows.
(PNK; pink, WHT: white, YLW: yellow, ORG: orange, BLU: blue,
BLK: black, RED: red)
8. Use copper conductors only.
Notes:
1.
Light emitting diode (Filter
sign-red)
H4P Light emitting diode
(Defrost-orange)
SS1 Selector switch (Main/sub)
SS2 Selector switch (Wireless
address set)
Connector for optional parts
X8A Connector (Float switch)
X18A Connector (Wiring adaptor for
electrical appendices)
X23A Connector (Infrared remote
control)
H3P
Electric parts box
Wired remote control
(Optional accessory)
3D039801C
Note: 3
Transmission wiring
central remote control
Note: 5
Input from outside
Note: 4
Receiver/display unit
(infrared remote control)
Wiring Diagrams for Reference
SiE39-404
FXHQ32M / 63M / 100MVE
: http://splitoff.ru/tehn-doc.html
Appendix
Appendix
Fuse (훾, 3A, 250V)
Light emitting diode
F1U
HAP
Thermistor (Coil liquid pipe)
Thermistor (Coil gas pipe)
Terminal block (Control)
Terminal block (Power)
Electronic expansion valve
Power circuit
R2T
R3T
X1M
X2M
Y1E
PC
Power supply
SS1 Selector switch (Main/sub)
Selector switch
(infrared remote control)
Wired remote control
R1T Thermistor (Air)
Selector switch (Main/sub)
SS2
(Defrost-orange)
Light emitting diode
(Filter sign-red)
SS1
H4P
Note: 7
Wired remote
control
Transmission wiring
central remote control
Note: 2
Note: 4
Input from outside
Receiver/display unit
(infrared remote control)
: http://splitoff.ru/tehn-doc.html
3D034206A
4. When connecting the input wires from outside,
forced off or on/off control operation can be
selected by remote control. In details, refer to the
installation manual attached the unit.
5. Remote control model varies according to the
combination system, confirm engineering data and
catalogs, etc. before connecting.
6. Confirm the method of setting the selector switch
(SS1, SS2) of wired remote control and infrared
remote control by installation manual and
engineering data, etc.
7. X24A is connected when the wiress remote control
kit is being used.
Note: 7
X35A Connector (Group control adaptor)
X15A Connector (Float switch)
Connector for optional parts
: Field wiring
: Connector
2. In case using central remote control, connect it to the unit in
accordance with the attached installation manual.
3. Symbols shows as follows: RED: red, WHT: white, GRN: green,
PNK: pink, YLW: yellow, BLK: black, ORG: orange, BRN: brown,
BLU: blue
(Timer-green)
Light emitting diode
Light emitting diode
H2P
H3P
Light emitting diode (On-red)
H1P
: Connector
Push botton (On/off)
BS1
: Terminal
Notes:
1.
Printed circuit board
A3P
Control box
(Indoor unit)
Front
PC
Printed circuit board
Side
220-240V 220V
~
~
50Hz
60Hz
A2P
infrared remote control
Receiver/Display unit (Attached to
Motor (Indoor fan)
Thermistor (Air)
R1T
Motor (Swing flap)
M1F
M1S
(Service monitor-green)
Indoor unit
Printed circuit board
A1P
SiE39-404
Wiring Diagrams for Reference
FXAQ20M / 25M / 32MVE / 40M / 50M / 63MVE
285
286
Terminal block (Control
Electronic expansion valve
Wired remote control
R1T Thermistor (Air)
SS1 Selector switch (Main/sub)
Connector for optional parts
X18A Connector (Wiring adaptor for
electorical appendices)
X2M
Y1E
1.
: Terminal block,
,
: Connector,
:Terminal
2.
: Field wiring
3. In case using central remote control, connect it to the unit in
accordance with the attached instruction manual.
4. When connection the input wires from outside, forced off or on/off
control operation can be selected by remote control, in details,
refer to the installation manual attached the unit.
5. Symbols shows as follows. (PNK: pink, WHT: white, YLW: yellow,
ORG: orange, BLU: blue, BLK: black, RED: red, BRN: brown)
6. Use copper conductors only.
Notes:
Indoor unit
Printed circuit board
Capacitor (M1F)
Fuse (훾, 5A, 250V)
Light emitting diode
(Service monitor-green)
K1R-K3R Magnetic relay (M1F)
Motor (Indoor fan)
M1F
Q1M
Thermo switch
(M1F embedded)
R1T
Thermistor (Air)
R2T•R3T Thermistor (Coil)
T1R
Transformer (220-240V/22V)
X1M
Terminal block (Power)
A1P
C1P
F1U
HAP
Power supply
220-240V 220V
~
~
50Hz
60Hz
Wired remote control
(Optional accessory)
: http://splitoff.ru/tehn-doc.html
3D039826A
Electric parts box
Note: 3
Transmission wiring
central remote control
Note: 4
Input from outside
Wiring Diagrams for Reference
SiE39-404
FXLQ20M / 25M / 32M / 40M / 50M / 63MVE
FXNQ20M / 25M / 32M / 40M / 50M / 63MVE
Appendix
Appendix
M1S
M1F
M1P
Q1M
R1T
R2T
RyA
RyP
S1Q
S1L
SS1
V1TR
X1M
X2M
RC
TC
HBP
C1
HAP
A1P
A2P
Indoor unit
Printed circuit board
Printed circuit board
(Transformer 220-240V/16V)
Capacitor (M1F)
Light emitting diode
(Service monitor-green)
Light emitting diode
(Service monitor-green)
Motor (Swing flap)
Motor (Indoor fan)
Motor (Drain pump)
Thermo switch (M1F embedded)
Thermistor (Air)
Thermistor (Coil)
Magnetic relay (M1A)
Magnetic relay (M1P)
Limit switch (Swing flap)
Float switch
Selector Switch (Emergency)
Phase control circuit
Terminal strip
Terminal strip
Signal receiver
Signal transmission circuit
Wired remote control
R1T Thermistor (Air)
SS1 Selector switch (Main/sub)
Receiver/display unit (Attached to
infrared remote control)
A3P Printed circuit board
A4P Printed circuit board
BS1 Push button (On/off)
H1P Light emitting diode
(On-red)
H2P Light emitting diode
(Timer-green)
H3P Light emitting diode
(Filter sign-red)
H4P Light emitting diode
(Defrost-orange)
SS1 Selector switch (Main/sub)
SS2 Selector switch
(infrared address set)
Connector for optional parts
X24A Connector (Infrared remote control)
X30A Connector (Interface adaptor for
sky air series)
X35A Connector (Group control adaptor)
: Terminal
: Connector
2.
: Field wiring
3. The BEV unit shows an outline, please refer to a wiring diagram of
BEV unit pasting in detail.
4. In case using central remote control, connect it to the unit in
accordance with the attached installation manual.
5. X24A is connected when het infrared remote control kit is being
used.
6. Remote control model varies according to the combination system,
confirm engineering materials and catalogs, etc. before
connecting.
7. Confirm the method of setting the selector switch (SS1, SS2) of
wired remote control and infrared remote control by installation
manual and engineering data, etc.
8. Symbols shows as follows: RED: red, BLK: black, WHT: white,
YLW: yellow, GRN: green, BLU: blue.
Notes:
1.
Note:3
BEV unit
50
~
220-240V
Power supply
RC
Indoor unit
TC
Note: 5
Control box
3D044973
Wired remote
control
Receiver/display unit
SiE39-404
Wiring Diagrams for Reference
FXUQ71M / 100M / 125MV1
: http://splitoff.ru/tehn-doc.html
287
288
Thermistor (Coil liquid)
Selector switch (Emergency)
R2T
SS1
Signal receiver circuit
Signal transmission circuit
RC
TC
Selector switch
(infrared address set)
SS2
Connector
X24A (infrared remote control)
Connector
X35A (Group control adaptor)
X15A Connector (Float switch)
Connector for optional parts
Selector switch (Main/sub)
SS1
H4P (Defrost-orange)
Light emitting diode
H3P (Filter sign-red)
Light emitting diode
H2P (Timer-green)
Light emitting diode
H1P Light emitting diode (On-red)
Push button (On/off)
Printed circuit board
A3P
BS1
Printed circuit board
A2P
Receiver/display unit
infrared remote control
Power circuit
PC
X2M Terminal block (Power)
X1M Terminal block (Control)
Thermistor (Air)
R1T
M1S Motor (Swing flap)
M1F Motor (Indoor fan)
HBP
HAP
Fuse (훾, 3A, 250V)
F1U
Light emitting diode
(Service monitor green)
Light emitting diode
(On-green)
Printed circuit board
A1P
Selector switch (Main/sub)
Thermistor (Air)
Wired remote control
220-240V
~
50
Power supply
Notes:
1.
: Terminal,
: Connector,
: Field wiring
2. Remote control model varies according to the combination
system, confirm engineering materials and catalogs, etc.
before connecting.
3. X24A is connected when the infrared remote control kit is
being used.
4.
: Shows short circuit connector.
5. Symbols shows as follows: RED: red, WHT: white,
GRN: green, BLK: black, ORG: orange, BRN: brown, BLU:
blue, YLW: yellow.
6. Confirm the method of setting the selector switch (SS1, SS2)
of wired remote control and infrared remote control by
installation manual and engineering data, etc.
7. The BEV unit shows an outline, please refer to a wiring
diagram of BEV unit pasting in detail.
8. In case using central remote control, connect it to the unit in
accordance with the attached installation manual.
Note: 7
BEV unit
SS1
R1T
RC
TC
PC
Note: 3
Forwarding of setting point
Norm.
Emg.
Note: 4
Side
: http://splitoff.ru/tehn-doc.html
3D046348A
Control box (Indoor)
Front
Wired remote control
Note: 8
Transmission wiring
central remote control
Receiver/display unit
(Attached to infrared
remote control)
Wiring Diagrams for Reference
SiE39-404
FXAQ20MH / 25MH / 32MH / 40MH / 50MHV1
Appendix
Indoor unit
Printed circuit board
Capacitor (M1F)
Light emitting diode
(Service monitor green)
H2P
Light emitting diode
(Service monitor green)
M1F
Motor (Indoor fan)
Thermo switch (135°)
Q1M
(M1F embedded)
Thermistor (Air)
R1T
Thermistor (Coil)
R2T
RyF1, 3, 4 Magnetic relay (M1F)
SS1
Selector switch
(Emergency)
T1R
Transformer (220-240V/22V)
X1M
Terminal block (Power)
X2M
Terminal block (Control)
RC
Signal receiver circuit
TC
Signal transmission circuit
Wired remote control
Thermistor (Air)
R1T
Selector switch (Main/sub)
SS1
Connector for optional parts
X30A
Connector
(Interface adaptor for
sky air series)
Connector
X33A
(Adaptor for wiring)
Connector
X35A
(Group control adaptor)
A1P
C1R
H1P
Appendix
220-240V
~
50
Notes:
1.
: Terminal,
: Connector,
: Field wiring
2. Remote control model varies according to the combination
system, confirm engineering materials and catalogs, etc. before
connecting.
3.
: Shows short circuit connector.
4. Symbols shows as follows: RED: red, WHT: white,
BLK: black, ORG: orange, BRN: brown, BLU: blue, YLW: yellow.
5. Confirm the method of setting the selector switch (SS1, SS2) of
wired remote control and infrared remote control by installation
manual and engineering data, etc.
6. The BEV unit shows an outline, please refer to a wiring diagram
of BEV unit pasting in detail.
7. In case using central remote control, connect it to the unit in
accordance with the attached installation manual.
Note: 6
BEV unit
Power supply
RC
TC
Control box
Emg. Norm.
3D046787A
Wired remote control
(Optional accessory)
SiE39-404
Wiring Diagrams for Reference
FXLQ20MH / 25MH / 32MH / 40MH / 50MHV1
: http://splitoff.ru/tehn-doc.html
289
Wiring Diagrams for Reference
SiE39-404
FXMQ125MF / 200MF / 250MFV1
Electric parts box
Power supply
~ 50Hz 220-240V
In case of
FXMQ
200 • 250MFV1
Note: 4
Input from outside
Note: 2
Transmission wiring,
central remote control
Note: 3
Wired remote control
(Optional accessory)
In case of FXMQ125MFV1
Drain pump kit
(Optional accessory)
Note: 3
A1P
C1, C2
F1U
HAP
K1M
K1R
KPR
KSR
M1F
Q1M
R1T
R2T
R3T
R4T
T1R
Indoor unit
Printed circuit board
Capacitor (M1F)
Fuse (훾, 5A, 250V) (A1P)
Light emitting diode
(Service monitor green)
Magnetic relay (M1F)
Magnetic relay (M1F)
Magnetic relay (M1P)
Magnetic relay (Y1S)
Motor (Fan)
Thermal protector
(M1F embedded 135°C)
Thermistor (Suction air)
Thermistor (Coil, liquid)
Thermistor (Coil, gas)
Thermistor (Discharge air)
Transformar (220-240V/22V)
X1M
X2M
X3M
X51A, X52A
Y1E
Y1S
Terminal block (Power)
Terminal block (Control)
Terminal block
Connector
Electric expansion valve
solenoid valve (Hot gas)
M1P
S1L
Optional parts
Motor (Drain pump)
Float switch (Drain pump)
SS1
Wired remote control
Selector switch (Main/sub)
X18A
Connector for optional parts
Connector (Wiring adaptor
for electrical appendices)
Notes:
1.
: Terminal block,
,
: Connector,
: Terminal,
: Short circuit connector,
: Field wiring.
2. In case using central remote control, connect it to the unit in accordance
with the attached installation manual.
3. In case installing the drain pump kit, remove the short circuit connector of
X8A and execute the additional wiring for float switch and drain pump.
4. In case connecting the input wires from outside, forced off or on/off control
operation can be selected by remote control.
In details, refer tot the installation manual attached to the unit.
5. Do not remove short circuit connector of X9A.
3D044996B
290
: http://splitoff.ru/tehn-doc.html
Appendix
SiE39-404
Wiring Diagrams for Reference
BEVQ50MVE
BEV unit
A1P
Printed circuit board
A2P
Power supply printed circuit
Power supply
50
60
~
~
220-240V 220-240V
board assy (220-240V/16V)
F1U
Fuse (훾, 10A, 250V)
HAP
Light emitting diode
(Service monitor-green)
R3T
Thermistor (Gas)
SS1
Selector switch (M/S)
X1M
Terminal strip (Power)
X2M
Terminal strip (Transmission)
Y1E
Electronic expansion valve
Z1C • Z2C
Z3C • Z4C
To indoor unit
Noise filter
Control box
To outdoor unit
Notes:
1.
: Terminal,
: Connector
2.
: Field wiring.
3. This wiring diagram only shows the BEV unit.
See the wiring diagrams and installation manuals for the wiring and settings for the indoor, outdoor.
4. See the indoor unit’s wiring diagram when installing optional parts for the indoor unit.
5. Only one indoor unit may be connected to the BEV unit.
See the indoor unit’s wiring diagram for when connecting the remote control.
6. Always use the sky air connection adapter for the indoor unit when using a central control unit.
Refer to the manual attached the unit when connecting. (In FXAQ~MHV1, it is unnecessary.)
7. Cool/heat changeover of indoor units connected to BEV unit cannot be carried out.
In case of a system with BEV unit only, cool/heat selector is required.
8. Connect the attached thermistor to the R3T.
9. Symbols show as follows. (BLU: blue, RED: red, WHT: white, BLK: black)
3D046579A
Appendix
: http://splitoff.ru/tehn-doc.html
291
Wiring Diagrams for Reference
SiE39-404
BEVQ71M / 100M / 125MVE
BEV unit
A1P
Printed circuit board assy
A2P
Power supply printed circuit
Power supply
50
60
~
~
220-240V 220-240V
board assy (220-240V/16V)
F1U
Fuse (훾, 10A, 250V)
HAP
Light emitting diode
(Service monitor-green)
R3T
Thermistor (Gas)
SS1
Selector switch (M/S)
X1M
Terminal strip (Power)
X2M
Terminal strip (Transmission)
Y1E
Electronic expansion valve
Z1C • Z2C
Z3C • Z4C
To indoor unit
Noise filter
Control box
Notes:
1.
: Terminal,
: Connector
To outdoor unit
2.
: Field wiring.
3. This wiring diagram only shows the BEV unit.
See the wiring diagrams and installation manuals for the wiring and settings for the indoor, outdoor, and
BS units.
4. See the indoor unit’s wiring diagram when installing optional parts for the indoor unit.
5. Only one indoor unit may be connected to the BEV unit.
See the indoor unit’s wiring diagram for when connecting the remote control.
6. Always use the sky air connection adapter for the indoor unit when using a central control unit.
Refer to the manual attached the unit when connecting.
7. Cool/heat changeover of indoor units connected to BEV unit cannot be carried out unless they are
connected to BS unit.
In case of a system with BEV unit only, cool/heat selector is required.
8. Set the SS1 to “M” only for the BEV unit connected to the indoor unit which is to have cool/heat switching
capability, when connecting the BS unit.
The “M/S” on the SS1 stands for “Main/sub”.
This is set to “S” when shipped from the factory.
9. Connect the attached thermistor to the R3T.
10. Symbols show as follows. (BLU: blue, RED: red, WHT: white, BLK: black)
3D044901A
292
: http://splitoff.ru/tehn-doc.html
Appendix
SiE39-404
List of Electrical and Functional Parts
3. List of Electrical and Functional Parts
3.1
Outdoor Unit
3.1.1 RXYQ5~16MY1B
*Valve in ( ) are for RXYQ5MY1B
Item
Compressor
Name
Inverter
STD.1
STD.2
Symbol
Type
Output
Type
Output
Type
Output
M1C
RXYQ5MY1B
JT1FCVDKYR
3.2kW
M2C
—
M3C
Model
RXYQ8MY1B
JT1FCVDKTYR
1.2kW
RXYQ10MY1B
JT1FCVDKTYR
2.7kW
JT170FCKYE
4.5kW
JT170FCKYE
4.5kW
—
Crankcase heater (INV)
E1HC
240V 33W
Crankcase heater (STD.1)
E2HC
—
240V 33W
Crankcase heater (STD.2)
E3HC
—
OC protection device for STD
—
—
15A
compressor
Fan motor
Motor
M1F
0.35kw
0.75kw
OC protection device
—
1.6A
3.2A
Functional parts Electronic expansion Cooling
Y1E
1400pls
0pls
valve (Main)
Heating
PI control
Electronic expansion Cooling
Y2E
—
PI control
valve (Subcool)
Heating
0pls
Solenoid valve (Hot gas)
Y1S
TEV1620DQ2
Solenoid valve (External multi oil)
Y2S
—
TEV1620DQ2
Solenoid valve (Receiver gas
Y3S (Y2S)
VPV-603D
discharge)
Solenoid valve (Non-operating
Y4S
—
VPV-803DXF
unit liquid pipe close)
4 way valve
Y5S (Y3S)
VHV0310
VT40110
Solenoid valve (Injection)
(Y4S)
TEV1620DQ2
—
PressurePressure switch (INV)
S1PH
PS80 ON : 3.8+0/-0.15MPa OFF : 2.85±0.15MPa
related parts
Pressure switch (STD1)
S2PH
—
PS80
ON : 3.8+0/-0.15MPa
OFF : 2.85±0.15MPa
Pressure switch (STD2)
S3PH
—
Fusible plug
—
FPGD-3D 70 to 75°C
Pressure sensor (HP)
S1NPH
PS8051A 0 to 4.15MPa
Pressure sensor (LP)
S1NPL
PS8051A -0.1 to 1.7MPa
Thermistor
INV
For fin
R1T
3.5 to 360Ω
PCB
Main
For outdoor air
R1T
3.5 to 360Ω
PCB
For suction pipe
R2T
3.5 to 360Ω
For discharge pipe
R31T
3.5 to 400Ω
(INV)
(R3T)
For discharge pipe
R32T
3.5 to 400Ω
(STD.1)
For discharge pipe
R33T
3.5 to 400Ω
(STD.2)
For heat exchanger
R4T
3.5 to 360Ω
For subcooling heat
R5T
3.5 to 360Ω
exchanger
For receiver liquid pipe
R6T
3.5 to 360Ω
For oil equalizing pipe
R7T
3.5 to 360Ω
Others
Fuse (A1P)
F1, 2U
250VAC 10A Class B
Appendix
: http://splitoff.ru/tehn-doc.html
293
List of Electrical and Functional Parts
Item
Compressor
SiE39-404
Name
Inverter
STD.1
STD.2
Type
Output
Type
Output
Type
Output
Crankcase heater (INV)
Crankcase heater (STD.1)
Crankcase heater (STD.2)
OC protection device for STD
compressor
Fan motor
Motor
OC protection device
Functional parts Electronic expansion Cooling
valve (Main)
Heating
Electronic expansion Cooling
valve (Subcool)
Heating
Solenoid valve (Hot gas)
Solenoid valve (External multi oil)
Solenoid valve (Receiver gas
discharge)
Solenoid valve (Non-operating
unit liquid pipe close)
4 way valve
PressurePressure switch (INV)
related parts
Pressure switch (STD1)
Pressure switch (STD2)
Thermistor
Others
294
RXYQ12MY1B
Model
RXYQ14MY1B
RXYQ16MY1B
M1C
JT1FCVDKTYR
4.2kW
JT1FCVDKTYR
2.0kW
JT1FCVDKTYR
3.0kW
M2C
JT170FCKYE
4.5kW
JT170FCKYE
4.5kW
JT170FCKYE
4.5kW
M3C
—
JT170FCKYE
4.5kW
JT170FCKYE
4.5kW
Symbol
Fusible plug
Pressure sensor (HP)
Pressure sensor (LP)
INV
For fin
PCB
Main
For outdoor air
PCB
For suction pipe
For discharge pipe
(INV)
For discharge pipe
(STD.1)
For discharge pipe
(STD.2)
For heat exchanger
For subcooling heat
exchanger
For receiver liquid pipe
For equalizing pipe
Fuse (A1P)
E1HC
E2HC
E3HC
—
M1F
—
Y1E
—
240V 33W
240V 33W
240V 33W
15A
Y1S
Y2S
Y3S
0.75kw
3.2A
0pls
PI control
PI control
0pls
TEV1620DQ2
TEV1620DQ2
VPV-603D
Y4S
VPV-803DXF
Y2E
Y5S
S1PH
S2PH
S3PH
—
S1NPH
S1NPL
R1T
VT40110
VT60100
PS80 ON : 3.8+0/-0.15MPa OFF : 2.85±0.15MPa
PS80 ON : 3.8+0/-0.15MPa OFF : 2.85±0.15MPa
—
PS80
ON : 3.8+0/-0.15MPa
OFF : 2.85±0.15MPa
FPGD-3D 70 to 75°c
PS8051A 0 to 4.15MPa
PS8051A -0.1 to 1.7MPa
3.5 to 360Ω
R1T
R2T
R31T
3.5 to 360Ω
3.5 to 360Ω
3.5 to 400Ω
R32T
3.5 to 400Ω
R33T
3.5 to 400Ω
R4T
R5T
3.5 to 360Ω
3.5 to 360Ω
R6T
R7T
F1, 2U
3.5 to 360Ω
3.5 to 360Ω
250VAC 10A Class B
: http://splitoff.ru/tehn-doc.html
Appendix
SiE39-404
3.2
List of Electrical and Functional Parts
Indoor Side
3.2.1 Indoor Unit
Model
Parts Name
Remote
Controller
Symbol
FXFQ25
MVE
FXFQ32
MVE
FXFQ40
MVE
FXFQ50
MVE
Wired Remote
Controller
FXFQ80
MVE
Option
BRC7E61W
M1F
Option
DC380V 30W 8P
DC 380V 120W 8P
Drain Pump
M1P
AC220-240V (50Hz) AC220V (60Hz)
PLD-12230DM
Thermal Fuse 145°C
Swing Motor
M1S
MP35HCA[3P007482-1]
Stepping Motor DC16V
Thermistor (Suction Air)
R1T
In PCB A4P or wired remote controller
Thermistor (for Heat
Thermistors Exchanger High Temp.)
R3T
ST8605-5 φ8 L1000
20kΩ (25°C)
R2T
ST8602A-5 φ6 L1000
20kΩ (25°C)
Motors
Thermistor (Heat
Exchanger)
Others
FXFQ100 FXFQ125 Remark
MVE
MVE
BRC1A61
Wireless Remote
Controller
Fan Motor
FXFQ63
MVE
Float Switch
S1L
FS-0211B
Fuse
F1U
250V 5A φ5.2
Thermal Fuse
TFu
—
Transformer
T1R
—
Model
Parts Name
Remote
Controller
Symbol
FXCQ
20MVE
FXCQ
25MVE
FXCQ
32MVE
FXCQ
40MVE
FXCQ
50MVE
FXCQ
63MVE
FXCQ
80MVE
FXCQ Remark
125MVE
Wired Remote
Controller
BRC1A61
Option
Wireless Remote
Controller
BRC7C62
Option
AC 220~240V 50Hz
Fan Motor
M1F
1φ10W
1φ15W
1φ20W
Thermal Fuse 152°C
Motors
1φ30W
—
Drain Pump
M1P
Swing Motor
M1S
MT8-L[3PA07509-1]
AC200~240V
Thermistor (Suction Air)
R1T
ST8601-6 φ4 L1250
20kΩ (25°C)
Thermistors Thermistor (for Heat
Exchanger High Temp.)
R3T
ST8605-6 φ8 L1250
20kΩ (25°C)
Thermistor (Heat
Exchanger)
R2T
ST8602A-5 φ6 L1000
20kΩ (25°C)
Float Switch
S1L
FS-0211B
Fuse
F1U
250V 5A φ5.2
Transformer
T1R
TR22H21R8
Appendix
1φ85W
87°C : ON
AC220-240V (50Hz) AC220V (60Hz)
PLD-12230DM
Thermal Fuse 145°C
Others
1φ50W
Thermal protector 135°C : OFF
: http://splitoff.ru/tehn-doc.html
295
List of Electrical and Functional Parts
SiE39-404
Model
Parts Name
Remote
Controller
Symbol
FXZQ
20MVE
FXZQ
25MVE
FXZQ
32MVE
Wired Remote
Controller
FXZQ
40MVE
Remark
FXZQ
50MVE
BRC1A61
Option
Wireless Remote
Controller
BRC7E530W
AC 220~240V 50Hz
Fan Motor
M1F
1φ55W 4P
Thermal Fuse 135°C
C1
4.0µ F 400VAC
Drain Pump
M1P
AC220-240V (50Hz)
PLD-12230DM
Thermal Fuse 145°C
Swing Motor
M1S
MP35HCA [3P080801-1]
AC200~240V
Thermistor (Suction Air)
R1T
ST8601A-1 φ4 L250
20kΩ (25°C)
Thermistor (for Heat
Thermistors Exchanger High Temp.)
R3T
ST8605-3 φ8 L630
20kΩ (25°C)
Thermistor (Heat
Exchanger)
R2T
ST8602A-3 φ6 L630
20kΩ (25°C)
Float Switch
S1L
FS-0211
Fuse
F1U
250V 5A φ5.2
Transformer
T1R
TR22H21R8
Motors
Others
Capacitor, fan motor
Model
Parts Name
Remote
Controller
Symbol
FXKQ
25MVE
FXKQ
32MVE
FXKQ
40MVE
Wired Remote
Controller
BRC1A61
Wireless Remote
Controller
BRC4C61
Remark
FXKQ
63MVE
Option
AC 220~240V 50Hz
Fan Motor
M1F
1φ15W 4P
1φ20W 4P
Thermal Fuse 146°C
Motors
Drain Pump
M1P
AC 220-240V (50Hz)
PLD-12200DM
Thermal Fuse 145°C
Swing Motor
M1S
MP35HCA [3P080801-1]
AC200~240V
Thermistor (Suction Air)
R1T
ST8601-13 φ4 L630
20kΩ (25°C)
Thermistor (for Heat
Thermistors Exchanger High Temp.)
R3T
ST8605-7 φ8 L1600
20kΩ (25°C)
R2T
ST8602A-7 φ6 L1600
20kΩ (25°C)
Thermistor (Heat
Exchanger)
Others
296
1φ45W 4P
Thermal protector 120°C : OFF
ON
Float Switch
S1L
FS-0211B
Fuse
F1U
250V 5A φ5.2
Transformer
T1R
TR22H21R8
: http://splitoff.ru/tehn-doc.html
105°C :
Appendix
SiE39-404
List of Electrical and Functional Parts
Model
Parts Name
Remote
Controller
Symbol
FXDQ
20MVE
FXDQ
25MVE
FXDQ
32MVE
FXDQ
40MVE
Wired Remote
Controller
BRC1A62
Wireless Remote
Controller
BRC4C62
FXDQ
50MVE
FXDQ
63MVE
Remark
Option
AC 220~240V 50Hz
Fan Motor
1φ62W
M1F
1φ130W
Thermal protector
130°C: OFF, 83°C: ON
Motors
Drain Pump
M1P
AC220-240V (50Hz)
PLD-12230DM
Thermal Fuse 145°C
Thermistor (Suction Air)
R1T
ST8601-1 φ4 L=250
20kΩ (25°C)
Thermistors Thermistor (for Heat
Exchanger High Temp.)
R3T
ST8605-4 φ8 L=800
20kΩ (25°C)
R2T
ST8602A-4 φ6 L=800
20kΩ (25°C)
Thermistor (Heat
Exchanger)
Others
Float Switch
S1L
FS-0211E
Fuse
F1U
250V 5A φ5.2
Transformer
T1R
TR22H21R8
Parts Name
Remote
Controller
Symbol
Model
Remark
FXSQ
FXSQ
FXSQ
FXSQ
FXSQ
FXSQ
FXSQ
FXSQ
FXSQ
20MVE 25MVE 32MVE 40MVE 50MVE 63MVE 80MVE 100MVE 125MVE
Wired Remote
Controller
BRC1A62
Wireless Remote
Controller
BRC4C62
Option
AC 220~240V 50Hz
Fan Motor
M1F
Motors
1φ50W
1φ65W
1φ85W
1φ125
W
Thermal Fuse 152°C
Drain Pump
M1P
AC220-240V (50Hz)
PLD-12230DM
Thermal Fuse 145°C
Thermistor (Suction Air)
R1T
ST8601-4 φ4 L800
20kΩ (25°C)
Thermistor (for Heat
Thermistors Exchanger High Temp.)
R3T
ST8605-7 φ8 L1600
20kΩ (25°C)
R2T
ST8602A-6 φ6 L1250
20kΩ (25°C)
Thermistor (Heat
Exchanger)
Others
Appendix
Float Switch
S1L
FS-0211B
Fuse
F1U
250V 5A φ5.2
Transformer
T1R
TR22H21R8
1φ225W
Thermal protector
135°C : OFF 87°C : ON
: http://splitoff.ru/tehn-doc.html
297
List of Electrical and Functional Parts
SiE39-404
Model
Parts Name
Remote
Controller
Symbol
FXMQ
40MVE
FXMQ
50MVE
FXMQ
63MVE
FXMQ
80MVE
FXMQ
FXMQ
FXMQ
FXMQ Remark
100MVE 125MVE 200MVE 250MVE
Wired Remote
Controller
BRC1A62
Wireless Remote
Controller
BRC4C62
Option
AC 220~240V 50Hz
Fan Motor
M1F
1φ100W
Motors
1φ160W
1φ270W
Thermal protector 135°C : OFF
7µ F
400V
1φ380W×2
10µ F
400V
8µ F
400V
10µ F
400V
12µ F
400V
Capacitor for Fan Motor
C1R
Thermistor (Suction Air)
R1T
ST8601A-5 φ4 L1000
20kΩ (25°C)
ST8601A-13
φ4 L630
Thermistor (for Heat
Thermistors Exchanger High Temp.)
R3T
ST8605A-4 φ8 L800
20kΩ (25°C)
ST8605A-5
φ8 L1000
R2T
ST8602A-4 φ6 L800
20kΩ (25°C)
ST8602A-6
φ6 L1250
Thermistor (Heat
Exchanger)
Others
Float switch
S1L
Fuse
F1U
Transformer
T1R
5µ F-400V
1φ430W
87°C : ON
FS-0211
250V 5A φ5.2
250V 10A φ5.2
250V 10A
TR22H21R8
Model
Parts Name
Remote
Controller
Symbol
FXHQ
32MVE
FXHQ
63MVE
Wired Remote
Controller
Remark
FXHQ
100MVE
BRC1A61
Wireless Controller
Option
BRC7E63W
AC 220~240V/220V 50Hz/60Hz
Fan Motor
M1F
Capacitor for Fan Motor
C1R
1φ63W
1φ130W
Thermal protector 130°C : OFF
Motors
Swing Motor
M1S
MT8-L[3P058751-1]
AC200~240V
Thermistor (Suction Air)
R1T
ST8601A-1 φ4 L250
20kΩ (25°C)
Thermistor (for Heat
Thermistors Exchanger High Temp.)
R3T
ST8605-6 φ8 L = 1250
20kΩ (25°C)
R2T
ST8602A-6 φ6 L = 1250
20kΩ (25°C)
Thermistor (Heat
Exchanger)
Others
80°C : ON
9.0µF-400V
3.0µF-400V
ST8605-6 φ8 L = 1250
20kΩ (25°C)
ST8602A-6 φ6 L = 1250
20kΩ (25°C)
Fuse
F1U
250V 5A φ5.2
Transformer
T1R
TR22H21R8
Model
Parts Name
Remote
Controller
Symbol
FXAQ
20MVE
FXAQ
25MVE
FXAQ
32MVE
FXAQ
40MVE
FXAQ
50MVE
FXAQ
63MVE
Remark
Wired Remote
Controller
BRC1A61
Option
Wireless Remote
Controller
BRC7E618
Option
AC 220~240V 50Hz
Fan Motor
M1F
Motors
1φ40W
1φ43W
Thermal protector 130°C : OFF
MP24[3SB40333-1]
AC200~240V
MSFBC20C21 [3SB40550-1]
AC200~240V
Swing Motor
M1S
Thermistor (Suction Air)
R1T
ST8601-2 φ4 L400
20kΩ (25°C)
Thermistors Thermistor (for Heat
Exchanger High Temp.)
R3T
ST8605-2 φ8 L400
20kΩ (25°C)
R2T
ST8602-2 φ6 L400
20kΩ (25°C)
Thermistor (for Heat
Exchanger)
Others
298
80°C : ON
Float Switch
S1L
OPTION
Fuse
F1U
250V 5A φ5.2
: http://splitoff.ru/tehn-doc.html
Appendix
SiE39-404
List of Electrical and Functional Parts
Model
Parts Name
Remote
Controller
Symbol
FXLQ
20MVE
FXLQ
25MVE
FXLQ
32MVE
FXLQ
40MVE
Wired Remote
Controller
BRC1A62
Wireless Remote
Controller
BRC4C62
FXLQ
50MVE
FXLQ
63MVE
Remark
Option
AC 220~240V 50Hz
Motors
Fan Motor
M1F
1φ15W
1φ25W
Thermal protector 135°C : OFF
Capacitor for Fan Motor
C1R
1.0µF-400V
0.5µF-400V
1.0µF-400V
Thermistor (Suction Air)
R1T
ST8601-6 φ4 L1250
20kΩ (25°C)
Thermistor (for Heat
Thermistors Exchanger High Temp.)
R3T
ST8605-9 φ8 L2500
20kΩ (25°C)
R2T
ST8602A-9 φ6 L2500
20kΩ (25°C)
Thermistor (for Heat
Exchanger)
Others
1φ35W
120°C : ON
Fuse
F1U
AC250V 5A
Transformer
T1R
TR22H21R8
1.5µF-400V
2.0µF-400V
FXNQ
50MVE
FXNQ
63MVE
Model
Parts Name
Remote
Controller
Symbol
FXNQ
20MVE
FXNQ
25MVE
FXNQ
32MVE
FXNQ
40MVE
Wired Remote
Controller
BRC1A62
Wireless Remote
Controller
BRC4C62
Remark
Option
AC 220~240V 50Hz
Motors
Fan Motor
M1F
1φ15W
1φ25W
Thermal protector 135°C : OFF
Capacitor for Fan Motor
C1R
1.0µF-400V
0.5µF-400V
1.0µF-400V
Thermistor (Suction Air)
R1T
ST8601-6 φ4 L1250
20kΩ (25°C)
Thermistor (for Heat
Thermistors Exchanger High Temp.)
R3T
ST8605-9 φ8 L2500
20kΩ (25°C)
R2T
ST8602A-9 φ6 L2500
20kΩ (25°C)
Thermistor (for Heat
Exchanger)
Others
Appendix
1φ35W
120°C : ON
Fuse
F1U
AC250V 5A
Transformer
T1R
TR22H21R8
1.5µF-400V
: http://splitoff.ru/tehn-doc.html
2.0µF-400V
299
List of Electrical and Functional Parts
Parts Name
Remote
Controller
Symbol
SiE39-404
Model
FXUQ71MV1
FXUQ100MV1
Wired Remote
Controller
Wireless Remote
Controller
FXUQ125MV1
Remark
BRC1A61
Option
BRC7C528W
Option
AC 220~240V 50Hz
Fan Motor
M1F
1φ45W
1φ90W
Thermal protector 130°C
Motors
Thermistors
Others
Drain Pump
M1P
AC220-240V (50Hz) AC220V (60Hz)
PJV-1426
Swing Motor
M1S
MT8-L[3PA07572-1]
AC200~240V
Thermistor (Suction Air)
R1T
ST8601-1 φ4 L=250
20kΩ (25°C)
Thermistor (Heat
Exchanger)
R2T
ST8602A-4 φ6 L=800
20kΩ (25°C)
Float Switch
S1L
FS-0211B
Parts Name
Remote
Controller
Thermal protector 130°C : OFF
Symbol
83°C : ON
Model
FXMQ125MFV1
Wired Remote
Controller
FXMQ200MFV1
FXMQ250MFV1
Remark
BRC1A62
Wireless Remote
Controller
Option
—
AC200~240V 50Hz
Fan Motor
M1F
1φ380W
Motors
Solenoid
valve
Thermistors
Others
300
Thermal protector 135°C : OFF
10µ F
400V×2
87°C : ON
10µ F
400V
Capacitor for Fan Motor
C1R
Solenoid valve
(Hot gas)
Y1S
Body: VPV-603D
Coil: NEV-MOAJ532C1 AC220-240V
Thermistor (Suction Air)
R1T
ST8601-13 φ4 L=630
20kΩ (25°C)
Thermistor (for Heat
Exchanger High Temp.)
R3T
ST8605-6 φ8 L=1250
20kΩ (25°C)
Thermistor (Heat
Exchanger)
R2T
ST8602A-2 φ6 L=1250
20kΩ (25°C)
Thermistor (for
discharge air)
R4T
ST8605-8 L=2000
20kΩ (25°C)
Float switch
S1L
Option
Fuse
F1U
250V 5A φ5.2
Transformer
T1R
TR22H21R8
16µ F
400V
: http://splitoff.ru/tehn-doc.html
Appendix
SiE39-404
Option List
4. Option List
4.1
Option List of Controllers
Operation Control System Optional Accessories
No.
Type
Item
Wireless
FXCQ-M FXFQ-M
FXZQ-M FXKQ-M
BRC7C62
BRC7E530W
FXSQ-M
FXMQ-M
FXHQ-M FXAQ-M(H)
FXLQ-M(H)
FXNQ-M
FXMQ-MF
BRC7E63W
BRC4C62
—
BRC4C62
BRC7C528W
BRC4C62
BRC1A62
BRC1A61
BRC1A62
BRC1A61
Simplified remote
controller
—
BRC2A51
—
BRC2A51
—
BRC2A51
—
4
Remote controller for
hotel use
—
BRC3A61
—
BRC3A61
—
BRC3A61
—
5
Remote
controller
2
Set back time clock
3
Wired
BRC4C61
FXUQ-M
BRC1A61
1
BRC7E61W
FXDQ
BRC7E618
BRC1A62
BRC15A61
—
Adaptor for wiring
HKRP1B61
HKRP1B59
HKRP1B57
KRP1B61
HKRP1B56
—
KRP1B61
KRP1B3
—
KRP1B61
6-1
Wiring adaptor for
electrical appendices (1)
HKRP2A61
HKRP2A62
HKRP2A62
KRP2A61
HKRP2A53
HKRP2A62
KRP2A61
HKRP2A62
HKRP2A61
KRP2A61
6-2
Wiring adaptor for
electrical appendices (2)
HKRP4A51
HKRP4A53
HKRP4A53
KRP4A51
HKRP4A54
HKRP4A53
KRP4A51
HKRP4A52
HKRP4A51
KRP4A51
7
Remote sensor
KRCS01-1
—
8
Installation box for
adaptor PCB
Note 2, 3
KRP1B96
Note 2, 3
KRP1D98
Note 4, 6
KRP1B101
—
Note 4, 6
KRP1B101
KRP1B97
Note 3
KRP1C93
Note 2, 3
KRP4A93
H
DTA104A62
H
DTA104A61
KRCS01-1
Note 5
KRP4A91
9
Central remote controller
DCS302C61
9-1
Electrical box with earth
terminal (3 blocks)
KJB311A
10
Unified on/off controller
DCS301B61
10-1
Electrical box with earth
terminal (2 blocks)
KJB212A
10-2
Noise filter (for
electromagnetic interface
use only)
KEK26-1
11
Schedule timer
12
External control adaptor
for outdoor unit (Must be
installed on indoor units)
—
—
—
—
DST301B61
H
DTA104A61
HDTA104A62
DTA104A61
H
DTA104A53
—
DTA104A61
DTA104A61
Note
1. Installation box (No.8) is necessary for each adaptor marked H.
2. Up to 2 adaptors can be fixed for each installation box.
3. Only one installation box can be installed for each indoor unit.
4. Up to 2 installation boxes can be installed for each indoor unit.
5. Installation box (No. 8) is necessary for second adaptor.
6. Installation box (No. 8) is necessary for each adaptor.
Various PC Boards
No.
Part name
1
Adaptor for wiring
2
DIII-NET Expander Adaptor
Appendix
Model No.
KRP1B56
KRP1B57
KRP1B59
KRP1B61
KRP1B3
DTA109A51
Function
! PC board when equipped with auxiliary electric heater in the indoor unit.
! Up to 1024 units can be centrally controlled in 64 different groups.
! Wiring restrictions (max. length: 1000m, total wiring length: 2000m, max. number of
branches: 16) apply to each adaptor.
: http://splitoff.ru/tehn-doc.html
301
Option List
SiE39-404
System Configuration
No.
Part name
Model No.
Function
1
Central remote controller
DCS302C61
! Up to 64 groups of indoor units (128 units)can be connected, and ON/OFF, temperature
setting and monitoring can be accomplished individually or simultaneously. Connectable up
to “2” controllers in one system.
2
Unified ON/OFF controller
DCS301B61
! Up to 16 groups of indoor units (128 units) can be turned, ON/OFF individually or
simultaneously, and operation and malfunction can be displayed. Can be used in
combination with up to 8 controllers.
3
Schedule timer
DST301B61
! Programmed time weekly schedule can be controlled by unified control for up to 64 groups
of indoor units (128 units). Can turn units ON/OFF twice per day.
4
Unification adaptor for computerized
control
HDCS302A52
! Interface between the central monitoring board and central control units
5
Interface adaptor for SkyAir-series
HDTA102A52
6
Central control adaptor kit
HDTA107A55
7
Wiring adaptor for other air-conditioner
HDTA103A51
! Adaptors required to connect products other than those of the VRV System to the highspeed DIII-NET communication system adopted for the VRV System.
! To use any of the above optional controllers, an appropriate adaptor must be installed on
the product unit to be controlled.
8
DIII-NET
Expander adaptor
9
Mounting plate
DTA109A51
KRP4A92
! Up to 1,024 units can be centrally controlled in 64 different groups.
! Wiring restrictions (max. length : 1,000m, total wiring length : 2,000m, max. number of
branches : 16) apply to each adaptor.
! Fixing plate for DTA109A51
Note:
Installation box for H adaptor must be procured on site.
Building management system
No.
1-1
2
intelligent Touch Controller
intelligent Manager
ECO 21
3-1
3-2
Communication
Line
2-1
3
4
7
8
9-1
9-2
13
Contact/analog signal
5
6
Model No.
Without
PPD
DCS601B51
With
PPD
DCS601B51
DCS002B51
Electrical box with earth terminal (4blocks)
Number of
units to be
connected
KJB411A
128 units
DAM602A52
192 units
DAM602A53
256 units
DAM602A51
512 units
DAM602A51x2
768 units
DAM602A51x3
1024 units
DAM602A51x4
Function
Air-Conditioning management system that can be controlled by a compact all-inone unit.
PPD: Power Proportional Distribution function
• Auto cool/heat change-over •Temperature limitation
• Multilingual (English, French, German, Spanish, Italian, or Chinese)
Wall embedded switch box.
Air conditioner management system (featuring minimized engineering) that can
be controlled by personal computers.
Optional DIII Ai unit
DAM101A51
Analog input for "sliding temperature" function (to reduce cold shock) for
intelligent Manager EC021.
H1 Interface for use in BACnet®
DMS502A51
Interface unit to allow communications between VRV and BMS. Operation and
monitoring of air-conditioning systems through BACnet® communications.
Optional DIII board
DAM411A1
Expansion kit, installed on DMS502A51, to provide 3 more DIII-NET
communication ports. Not usable independently.
Optional Di board
DAM412A1
Expansion kit, installed on DMS502A51, to provide 16 more wattmeter pulse
input points. Not usable independently.
H2 Interface for use in LON WORKS®
DMS504B51
Interface unit to allow communications between VRV and BMS. Operation and
monitoring of air-conditioning systems through
LON WORKS® communication.
Basic unit
DPF201A51
Enables ON/OFF command, operation and display of malfunction; can be used
in combination with up to 4 units.
Temperature
measurement units
DPF201A52
Enables temperature measurement output for 4 groups; 0-5VDC.
Temperature setting units
DPF201A53
Enables temperature setting input for 16 groups; 0-5VDC.
Parallel
interface
1
Part name
Unification adaptor for computerized
control
DCS302A52
Wiring adaptor for electrical
appendices (1)
KRP2A53, 61, 62
Wiring adaptor for electrical
appendices (2)
KRP4A51-54
External control adaptor for outdoor
unit (Must be installed on indoor units.)
DTA104A53, 61,
62
Interface between the central monitoring board and central control units
Simultaneously controls air-conditioning control computer and up to 64 groups of
indoor units.
To control the group of indoor units collectively, which are connected by the
transmission wiring of remote controller.
Cooling/Heating mode change over. Demand control and Low noise control are
available between the plural outdoor units.
Note:
H
1. BACnet® is a registered trademark of American Society of Heating, Refrigerating and AirConditioning Engineers (ASHRAE).
H2. LON WORKS® is a registered trade mark of Echelon Corporation.
302
: http://splitoff.ru/tehn-doc.html
Appendix
SiE39-404
4.2
Option List
Option Lists (Outdoor Unit)
RXYQ5 ~ 16MY1B
Optional accessories
RXYQ5MY1B
Distributive
Piping
Cool/Heat
Selector
Cool/Heat Selector
KRC19-26A
Fixing box
Refnet header
RXYQ12MY1B
RXYQ14MY1B
RXYQ16MY1B
RXYQ8MY1B
RXYQ10MY1B
KJB111A
KHRP26M22H,
KHRP26M33H
(Max. 4 branch)
(Max. 8 branch)
KHRP26M22H,
KHRP26M33H,
(Max. 4 branch)
(Max. 8 branch)
KHRP26M22H,
KHRP26M33H,
KHRP26M72H
(Max. 4 branch)
(Max. 8 branch)
(Max. 8 branch)
KHRP26M22T
KHRP26M22T,
KHRP26M33T,
KHRP26M22T,
KHRP26M33T,
KHRP26M72T
Refnet joint
Kit of air discharge duct
KPF26B160
KPF26B280
KPF26B450
Central drain pan kit
KWC26B160
KWC26B280
KWC26B450
Refrigerant leak detector kit
KFLD26A
3D039551A
RXYQ18 ~ 32MY1B
Optional accessories
RXYQ18MY1B
RXYQ20MY1B
RXYQ22MY1B
RXYQ24MY1B
RXYQ26MY1B
Distributive Cool/Heat
Piping
Selector
Cool/Heat Selector
RXYQ28MY1B
RXYQ30MY1B
RXYQ32MY1B
KRC19-26A
Fixing box
KJB111A
Refnet header
KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
(Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
Refnet joint
KHRP26M22T, KHRP26M33T, KHRP26M72T, KHRP26M73T
Outdoor unit multi connection piping kit
BHFP22M90
Pipe size reducer
KHRP26M73TP, KHRP26M73HP, BHFP22M90P
Kit of air discharge duct
KPF26B280 × 2
KPF26B280
KPF26B450
KPF26B450 × 2
KPF26B450 × 2
Central drain pan kit
KWC26B280 × 2
KWC26B280
KWC26B450
KWC26B450 × 2
KWC26B450 × 2
Refrigerant leak detector kit
KFLD26A
3D039552A
RXYQ34 ~ 48MY1B
Optional accessories
RXYQ34MY1B
RXYQ36MY1B
Distributive Cool/Heat
Piping
Selector
Cool/Heat Selector
RXYQ38MY1B
RXYQ40MY1B
RXYQ42MY1B
RXYQ44MY1B
RXYQ46MY1B
RXYQ48MY1B
KRC19-26A
Fixing box
KJB111A
Refnet header
KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
(Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
Refnet joint
KHRP26M22T, KHRP26M33T, KHRP26M72T, KHRP26M73T
Outdoor unit multi connection piping kit
BHFP22M135
Pipe size reducer
KHRP26M73TP, KHRP26M73HP, BHFP22M90P
Kit of air discharge duct
KPF26B280 × 2
KPF26B450
KPF26B280
KPF26B450 × 2
KPF26B280
KPF26B450 × 2
KPF26B450 × 3
Central drain pan kit
KWC26B280 × 2
KWC26B450
KWC26B280
KWC26B450 × 2
KWC26B280
KWC26B450 × 2
KWC26B450 × 3
Refrigerant leak detector kit
KFLD26A
3D039553A
Appendix
: http://splitoff.ru/tehn-doc.html
303
Piping Installation Point
SiE39-404
5. Piping Installation Point
5.1
Piping Installation Point
Max. 5m
Connection
Kit A
Connection
Kit B
Maximum length from a connection kit.
10m or less from first branch.
(Equivalent Piping Length 13m)
Since there is a possibility that oil may be collected on a stop machine side, install piping
between outdoor units to go to level or go up to an outdoor unit, and to make a slope.
(V3084)
The projection part between multi connection piping kits
When the piping length between the multi connection kits or between multi connection kit and
outdoor unit is 2m or more, prepare a vertical projection part (200mm or more as shown below) only
on the gas pipe line location less than 2m from multi connection kit.
In the case of 2m or less
Less than 2m
V3037
In the case of 2m or more
200~
300mm
Less than 2m
2m or more
Vertical
Projection
Vertical
Projection
200~300mm
Less than 2m
304
200~300mm
Less than 2m
: http://splitoff.ru/tehn-doc.html
(V3085)
Appendix
SiE39-404
5.2
Piping Installation Point
The Example of A Wrong Pattern
Wrong
×
Oil is collected to the outdoor
unit at the time of a stop,
because of bottom omission of
piping.
V3039
Wrong
×
Oil is collected to the low level outdoor
unit at the time of a stop, because of
downward slope of piping.
The example of installation on which oil is not collected.
Good
Good
Vertical projector
is required if this
distance is 2m
or more.
Vertical
Projection
200~
300mm
(V3086)
Outdoor Unit - Multi Connection Piping Kit
Max.allowable Multi Connection Piping Kit - Indoor Unit
Piping Length
REFNET Joint - Indoor Unit
Outdoor Unit - Outdoor Unit
Allowable
Level
Outdoor Unit - Indoor Unit
Difference
Indoor Unit - Indoor Unit
Appendix
Actual piping length 10m or less, equivalent length 13m or less
Actual piping length 150m or less, equivalent length 175m or
less, the total extension 300m or less
Actual piping length 40m or less
5m or less
50m or less
(when an outdoor unit is lower than indoor units : 40m or less)
15m or less
: http://splitoff.ru/tehn-doc.html
305
Selection of Pipe Size, Joints and Header
SiE39-404
6. Selection of Pipe Size, Joints and Header
6.1
RXYQ5MY1B, RXYQ8MY1B, RXYQ10MY1B,
RXYQ12MY1B, RXYQ14MY1B,
RXYQ16MY1B
6.1.1 How to select the REFNET Joint
How to select the REFNET Joint
Select the REFNET Joint from the following table when using REFNET Joints at the first branch
counted from the outdoor unit side.
(Ex. : REFNET Joint A)
Outdoor Unit
RXYQ5MY1B
RXYQ8,10MY1B
RXYQ12-16MY1B
REFNET Joints (Kit Name)
KHRP26M22T
KHRP26M33T
KHRP26M72T
For REFNET Joints other than the first branch, select the proper ones based on the total
capacity index of the indoor units installed after the first branch using the following table :
Total capacity index of indoor
units
<200
≥200~<290
≥290
REFNET Joints (Kit Name)
KHRP26M22T
KHRP26M33T
KHRP26M72T
6.1.2 How to select pipe size
Between outdoor unit and uppermost stream REFNET Joint.
Pipe size connected to outdoor unit.
Outdoor Unit
RXYQ5MY1B
RXYQ8MY1B
RXYQ10MY1B
RXYQ12-16MY1B
Gas
φ15.9
φ19.1
φ22.2
φ28.6
Liquid
φ9.5
φ12.7
Piping Material
Select the piping material to be used from the next table according to piping size.
Piping Size (O / D)
φ15.9 or less
φ19.1 or more
Temper grade of Material
O
1 / 2H or H
Wall thickness of refrigerant pipe
(Unit : mm)
Temper grade
Copper tube O.D φ6.4
Copper tube W.T
0.80
(Minimum
requirement)
O Type
1/2H Type
φ9.5
φ12.7 φ15.9 φ19.1 φ22.2 φ25.4 φ28.6 φ31.8 φ34.9 φ38.1 φ41.3
0.80
0.80
0.99
0.80
0.80
0.88
0.99
1.10
1.21
1.32
1.43
∗The table shows the requirements of Japanese High Pressure Gas Control low. The thickness
and material shall be selected in accordance with local code. (As of Jan.2003)
306
: http://splitoff.ru/tehn-doc.html
Appendix
SiE39-404
Selection of Pipe Size, Joints and Header
6.1.3 How to select the REFNET header
When connecting the indoor unit larger than 250 or more, use with KHRP26M33T,M72T to
upper stream side.
(Do not connect downstream side)
Select the proper REFNET Header using the following table based on the total capacity index of
indoor units installed after the header.
Total capacity index of indoor units
<200
<290
≥290
REFNET Header (Kit Name)
KHRP26M22H (Max.4 Branches)
KHRP26M33H (Max.8 Branches)
KHRP26M72H (Max.8 Branches)
6.1.4 Piping between the REFNET Joints
Select the proper pipe size using the following table based on the total capacity index of indoor
units connected downstream.
Connection piping size should not exceed the refrigerant piping size selected by "the model with
combination units".
Total capacity index of indoor units
<200
≥200~<290
≥290~<420
≥420
Gas
φ15.9
φ22.2
φ28.6
φ28.6
Liquid
φ9.5
φ12.7
φ15.9
6.1.5 Piping between the REFNET Joints and indoor unit
Pipe size for direct connection to indoor unit must be the same as the connection size of indoor
unit.
Connection pipe size of indoor unit.
Appendix
Indoor Units
Gas
Liquid
20 · 25 · 32 · 40 · 50 Type
φ12.7
φ6.4
63 · 80 · 100 · 125 Type
φ15.9
200 Type
φ19.1
250 Type
φ22.2
φ9.5
: http://splitoff.ru/tehn-doc.html
307
Selection of Pipe Size, Joints and Header
6.2
SiE39-404
RXYQ18MY1B, RXYQ20MY1B, RXYQ22MY1B,
RXYQ24MY1B, RXYQ26MY1B, RXYQ28MY1B,
RXYQ30MY1B, RXYQ32MY1B, RXYQ34MY1B,
RXYQ36MY1B, RXYQ38MY1B, RXYQ40MY1B,
RXYQ42MY1B, RXYQ44MY1B, RXYQ46MY1B,
RXYQ48MY1B
6.2.1 How to select the REFNET Joint
How to select the REFNET Joint
Select the REFNET Joint from the following table.When using REFNET Joints at the first branch
counted from the outdoor unit side.
(Ex. : REFNET Joint A)
Outdoor Unit
RXYQ18MY1B-22MY1B
RXYQ24MY1B-48MY1B
REFNET Joint (Kit Name)
KHRP26M72T
KHRP26M73T
For REFNET Joints other than the first branch, select the proper ones based on the total
capacity index of the indoor units installed after the first branch using the following table :
Total capacity index of indoor units
<200
≥200~<290
≥290
≥640
REFNET Joints (Kit Name)
KHRP26M22T
KHRP26M33T
KHRP26M72T
KHRP26M73T
6.2.2 How to select pipe size
Main Piping (Between Multi connection piping kit and REFNET Joint)
Select the proper ones based on the following table :
Outdoor Unit
RXYQ18MY1B
RXYQ20MY1B
RXYQ22MY1B
RXYQ24MY1B
RXYQ26MY1B
RXYQ28MY1B
RXYQ30MY1B
RXYQ32MY1B
RXYQ34MY1B
RXYQ36MY1B
RXYQ38MY1B
RXYQ40MY1B
RXYQ42MY1B
RXYQ44MY1B
RXYQ46MY1B
RXYQ48MY1B
Gas
φ28.6
Liquid
φ15.9
φ34.9
φ19.1
φ41.3
Piping Material
Select the piping material to be used from the next table according to piping size.
Piping Size (O / D)
φ15.9 or less
φ19.1 or more
308
Temper grade of Material
O
1 / 2H or H
* O: Soft (Annealed)
* H: Hard (Drawn)
: http://splitoff.ru/tehn-doc.html
Appendix
SiE39-404
Selection of Pipe Size, Joints and Header
Wall thickness of refrigerant pipe
(Unit : mm)
Temper grade
Copper tube O.D
O Type
1/2H Type
φ6.4
φ9.5
φ12.7 φ15.9 φ19.1 φ22.2 φ25.4 φ28.6 φ31.8 φ34.9 φ38.1 φ41.3
Copper tube W.T
0.80
(Minimum
requirement)
0.80
0.80
0.99
0.80
0.80
0.88
0.99
1.10
1.21
1.32
1.43
∗The table shows the requirements of Japanese High Pressure Gas Control low. The thickness
and material shall be selected in accordance with local code. (As of Jan.2003)
6.2.3 How to select the REFNET header
Select the proper REFNET Header using the following table based on the total capacity index of
indoor units installed after the header.
Total capacity index of indoor units
<200
≥200~<290
≥290~<640
≥640
REFNET Header (Kit Name)
KHRP26M22H (Max.4 Branches)
KHRP26M33H (Max8 Branches)
KHRP26M72H (Max8 Branches)
KHRP26M73H (Max8 Branches)
KHRP26M73HP
When using REFNET Joints at the first branch counted from the outdoor unit side, use
KHRP26M73H for larger than RXYQ24MY1B.
6.2.4 Piping between the REFNET Joints.
Select the proper pipe size using the following table based on the total capacity index of indoor
units connected downstream.
Connection piping size should be larger than main piping size.
Connection piping size should not exceed the refrigerant piping size selected by "the model with
combination units".
Total capacity index of indoor units
<200
≥200~<290
≥290~<420
≥420~<640
≥640~<920
≥920
Gas
φ15.9
φ22.2
Liquid
φ9.5
φ28.6
φ12.7
φ15.9
φ34.9
φ41.3
φ19.1
6.2.5 Piping between the multi connection piping kit
Select the proper pipe size using the following table based on the total capacity index of outdoor
units connected upper stream.
Total capacity index of outdoor units
connected to upper stream
Less than RXYQ22MY1B
RXYQ24MY1B
RXYQ26MY1B or more~
Less than RXYQ32MY1B
Appendix
Gas
φ28.6
φ34.9
Liquid
φ15.9
Oil
φ6.4
φ19.1
: http://splitoff.ru/tehn-doc.html
309
Selection of Pipe Size, Joints and Header
SiE39-404
6.2.6 Outdoor Unit Multi Connection Piping Kit
Select the piping kit according to the No. of outdoor units
No. of outdoor units
Multi Connection Piping Kit
2 units
BHFP22M90
BHFP22M90P
BHFP22M135
BHFP22M135P
3 units
6.2.7 Piping between REFNET Joint and Indoor Unit
Pipe size for direct connection to indoor unit must be the same as the connection size of indoor
unit.
Connection pipe size of indoor unit.
Indoor Units
20 · 25 · 32 · 40 · 50 Type
63 · 80 · 100 · 125 Type
200 Type
250 Type
Gas
φ12.7
φ15.9
φ19.1
φ22.2
Liquid
φ6.4
φ9.5
6.2.8 Piping between outdoor Unit and Multi Connection Piping Kit
Pipe size for direct connection to outdoor unit must be the same as the connection size of
outdoor unit.
Outdoor Units
RXYQ8MY1B
RXYQ10MY1B
RXYQ12-16MY1B
310
Gas
φ19.1
φ22.2
φ28.6
Liquid
φ9.5
Oil
φ6.4
φ12.7
: http://splitoff.ru/tehn-doc.html
Appendix
SiE39-404
Thermistor Resistance / Temperature Characteristics
7. Thermistor Resistance / Temperature
Characteristics
Indoor unit
For air suction
For liquid pipe
For gas pipe
R1T
R2T
R3T
Outdoor unit For outdoor air
For coil
For suction pipe
For Receiver gas pipe
T°C
-20
-19
-18
-17
-16
-15
-14
-13
-12
-11
-10
-9
-8
-7
-6
-5
-4
-3
-2
-1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
Appendix
R1T
R2T
R4T
R5T
0.0
197.81
186.53
175.97
166.07
156.80
148.10
139.94
132.28
125.09
118.34
111.99
106.03
100.41
95.14
90.17
85.49
81.08
76.93
73.01
69.32
65.84
62.54
59.43
56.49
53.71
51.09
48.61
46.26
44.05
41.95
39.96
38.08
36.30
34.62
33.02
31.50
30.06
28.70
27.41
26.18
25.01
23.91
22.85
21.85
20.90
20.00
19.14
18.32
17.54
16.80
16.10
0.5
192.08
181.16
170.94
161.36
152.38
143.96
136.05
128.63
121.66
115.12
108.96
103.18
97.73
92.61
87.79
83.25
78.97
74.94
71.14
67.56
64.17
60.96
57.94
55.08
52.38
49.83
47.42
45.14
42.98
40.94
39.01
37.18
35.45
33.81
32.25
30.77
29.37
28.05
26.78
25.59
24.45
23.37
22.35
21.37
20.45
19.56
18.73
17.93
17.17
16.45
15.76
T°C
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
0.0
16.10
15.43
14.79
14.18
13.59
13.04
12.51
12.01
11.52
11.06
10.63
10.21
9.81
9.42
9.06
8.71
8.37
8.05
7.75
7.46
7.18
6.91
6.65
6.41
6.65
6.41
6.18
5.95
5.74
5.14
4.96
4.79
4.62
4.46
4.30
4.16
4.01
3.88
3.75
3.62
3.50
3.38
3.27
3.16
3.06
2.96
2.86
2.77
2.68
2.60
2.51
: http://splitoff.ru/tehn-doc.html
(kΩ)
0.5
15.76
15.10
14.48
13.88
13.31
12.77
12.25
11.76
11.29
10.84
10.41
10.00
9.61
9.24
8.88
8.54
8.21
7.90
7.60
7.31
7.04
6.78
6.53
6.53
6.53
6.53
6.06
5.84
5.43
5.05
4.87
4.70
4.54
4.38
4.23
4.08
3.94
3.81
3.68
3.56
3.44
3.32
3.21
3.11
3.01
2.91
2.82
2.72
2.64
2.55
2.47
311
Thermistor Resistance / Temperature Characteristics
SiE39-404
Outdoor Unit
Thermistors for
Discharge Pipe
(R3T)
T°C
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
312
0.0
640.44
609.31
579.96
552.00
525.63
500.66
477.01
454.60
433.37
413.24
394.16
376.05
358.88
342.58
327.10
312.41
298.45
285.18
272.58
260.60
249.00
238.36
228.05
218.24
208.90
200.00
191.53
183.46
175.77
168.44
161.45
154.79
148.43
142.37
136.59
131.06
125.79
120.76
115.95
111.35
106.96
102.76
98.75
94.92
91.25
87.74
84.38
81.16
78.09
75.14
72.32
0.5
624.65
594.43
565.78
538.63
512.97
488.67
465.65
443.84
423.17
403.57
384.98
367.35
350.62
334.74
319.66
305.33
291.73
278.80
266.51
254.72
243.61
233.14
223.08
213.51
204.39
195.71
187.44
179.57
172.06
164.90
158.08
151.57
145.37
139.44
133.79
128.39
123.24
118.32
113.62
109.13
104.84
100.73
96.81
93.06
89.47
86.04
82.75
79.61
76.60
73.71
70.96
T°C
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
0.0
72.32
69.64
67.06
64.60
62.24
59.97
57.80
55.72
53.72
51.98
49.96
48.19
46.49
44.86
43.30
41.79
40.35
38.96
37.63
36.34
35.11
33.92
32.78
31.69
30.63
29.61
28.64
27.69
26.79
25.91
25.07
24.26
23.48
22.73
22.01
21.31
20.63
19.98
19.36
18.75
18.17
17.61
17.07
16.54
16.04
15.55
15.08
14.62
14.18
13.76
13.35
0.5
70.96
68.34
65.82
63.41
61.09
58.87
56.75
54.70
52.84
50.96
49.06
47.33
45.67
44.07
42.54
41.06
39.65
38.29
36.98
35.72
34.51
33.35
32.23
31.15
30.12
29.12
28.16
27.24
26.35
25.49
24.66
23.87
23.10
22.36
21.65
20.97
20.31
19.67
19.05
18.46
17.89
17.34
16.80
16.29
15.79
15.31
14.85
14.40
13.97
13.55
13.15
T°C
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
: http://splitoff.ru/tehn-doc.html
0.0
13.35
12.95
12.57
12.20
11.84
11.49
11.15
10.83
10.52
10.21
9.92
9.64
9.36
9.10
8.84
8.59
8.35
8.12
7.89
7.68
7.47
7.26
7.06
6.87
6.69
6.51
6.33
6.16
6.00
5.84
5.69
5.54
5.39
5.25
5.12
4.98
4.86
4.73
4.61
4.49
4.38
4.27
4.16
4.06
3.96
3.86
3.76
3.67
3.58
3.49
3.41
(kΩ))
0.5
13.15
12.76
12.38
12.01
11.66
11.32
10.99
10.67
10.36
10.06
9.78
9.50
9.23
8.97
8.71
8.47
8.23
8.01
7.78
7.57
7.36
7.16
6.97
6.78
6.59
6.42
6.25
6.08
5.92
5.76
5.61
5.46
5.32
5.18
5.05
4.92
4.79
4.67
4.55
4.44
4.32
4.22
4.11
4.01
3.91
3.81
3.72
3.62
3.54
3.45
3.37
Appendix
SiE39-404
Pressure Sensor
8. Pressure Sensor
PH = 1.38V-0.69
PL = 0.57V-0.28
PH : High pressure (MPa)
VL : Low pressure (MPa)
V : Voltage (V)
Detected Pressure
PH PL
(kg/cm²) MPa
51.0 5.0
PH : Detected Pressure [High Side] MPa
PL : Detected Pressure [Low Side] MPa
VH : Output Voltage [High Side] VDC
VL : Output Voltage [Low Side] VDC
45.9 4.5
High Pressure (PH)
40.8 4.0
35.7 3.5
30.6 3.0
25.5 2.5
20.4 2.0
Low Pressure (PL)
15.3 1.5
10.2 1.0
5.1 0.5
0
-5.1 -0.5
-0.5
0
0.5
1
1.5
2
Output Voltage (VH, VL)
2.5
3
3.5
4
Voc
(V3053)
Appendix
: http://splitoff.ru/tehn-doc.html
313
Method of Replacing The Inverter’s Power Transistors and Diode Modules
SiE39-404
9. Method of Replacing The Inverter’s Power
Transistors and Diode Modules
9.1
Method of Replacing The Inverter’s Power Transistors and Diode
Modules
Inverter P.C.Board
Inverter PC board (AIP)
PC0208
Fasten Tab
X10A
N3
P3 P2 P1
Pin
X11A
L1 L2 L3
U
V
W
N
Electronic circuit
DM
P1
P2 P3
IGBT
X10A
L1
L2
L3
N3
U
V
W
N
X11A
(V2895)
[Decision according to continuity check by analog tester]
! Before checking, disconnect the electric wiring connected to the power transistor and diode
module.
314
: http://splitoff.ru/tehn-doc.html
Appendix
SiE39-404
Method of Replacing The Inverter’s Power Transistors and Diode Modules
Power Transistor
IGBT (On Inverter
PC Board)
P3
"
"
"
U
V
W
N
N3
U Continuity
V
"
W
"
N (Approx. 100k)
P3 Approx. 4k "
"
"
U
V
W
N
N3
"
"
"
U
V
W
N
"
"
(Approx. 160k)
"
"
"
Approx. 4k "
"
(Approx. 250k)
Continuity
In the case of continuity,
the resistance must be
"
the same for all phases.
"
(Approx. 100k)
(Decision)
If other than given above, the power unit is defective and must be replaced.
Note:
If using a digital tester, ∞ and continuity may be reversed.
Diode Module
P1
P1
P1
L1
L2
L3
L1 Continuity
L2
"
L3
"
P1
P1
P1
N3
"
"
L1
L2
L3
L1
L2
L3
N3
"
"
Continuity
"
"
(Decision)
If other than given above, the diode module is defective and must be replaced.
Note:
Appendix
If using a digital tester, ∞ and continuity may be reversed.
: http://splitoff.ru/tehn-doc.html
315
Method of Replacing The Inverter’s Power Transistors and Diode Modules
316
: http://splitoff.ru/tehn-doc.html
SiE39-404
Appendix
SiE39-404
Part 9
Precautions for New
Refrigerant (R410)
1. Precautions for New Refrigerant (R410) .............................................318
1.1 Outline ..................................................................................................318
1.2 Refrigerant Cylinders............................................................................320
1.3 Service Tools........................................................................................321
Precautions for New Refrigerant (R410)
: http://splitoff.ru/tehn-doc.html
317
Precautions for New Refrigerant (R410)
SiE39-404
1. Precautions for New Refrigerant (R410)
1.1
Outline
1.1.1 About Refrigerant R410A
! Characteristics of new refrigerant, R410A
1. Performance
Almost the same performance as R22 and R407C
2. Pressure
Working pressure is approx. 1.4 times more than R22 and R407C.
3. Refrigerant composition
Few problems in composition control, since it is a Quasi-azeotropic mixture refrigerant.
Refrigerant name
Composing
substances
Design pressure
HFC units (Units using new refrigerants)
R407C
R410A
Non-azeotropic mixture Quasi-azeotropic mixture
of HFC32, HFC125 and of HFC32 and JFC125
HFC134a (*1)
(*1)
3.2 MPa (gauge pressure) 3.80 MPa (gauge pressure)
= 32.6 kgf/cm2
= 38.7 kgf/cm2
2.75MPa (gauge pressure)
= 28.0 kgf/cm2
Synthetic oil (Ether)
Mineral oil (Suniso)
Refrigerant oil
Ozone destruction
factor (ODP)
Combustibility
Toxicity
HCFC units
R22
Single-component
refrigerant
0
0
0.05
None
None
None
None
None
None
H1. Non-azeotropic mixture refrigerant: mixture of two or more refrigerants having different
boiling points.
H2. Quasi-azeotropic mixture refrigerant: mixture of two or more refrigerants having similar
boiling points.
H3. The design pressure is different at each product. Please refer to the installation manual for
each product.
(Reference) 1 MPa 10.19716 kgf / cm2
HFC-32/125 (50/50wt%)
20.0
10.0
5.0
2.0
P/MPa
1.0
0.5
0.2
0.1
0.05
0.02
0.01
0.005
50
100
150
200
250
300
350
400
450
500
550
600
650
h/kJ kg-1
Pressure-Enthalpy curves of HFC-32/125 (50/50wt%)
318
: http://splitoff.ru/tehn-doc.html
Precautions for New Refrigerant (R410)
SiE39-404
Precautions for New Refrigerant (R410)
! Thermodynamic characteristic of R410A
Temperature
(°C)
Steam pressure
(kPa)
Liquid
Vapor
Density
(kg/m3 )
Liquid
Vapor
Specific heat at constant
pressure (kJ/kgK)
Liquid
Vapor
Specific enthalpy
(kJ/kg)
Liquid
Vapor
DAIREP ver2.0
Specific entropy
(kJ/KgK)
Liquid
Vapor
-70
-68
-66
-64
-62
-60
-58
-56
-54
-52
36.13
40.83
46.02
51.73
58.00
64.87
72.38
80.57
89.49
99.18
36.11
40.80
45.98
51.68
57.94
64.80
72.29
80.46
89.36
99.03
1410.7
1404.7
1398.6
1392.5
1386.4
1380.2
1374.0
1367.8
1361.6
1355.3
1.582
1.774
1.984
2.213
2.463
2.734
3.303
3.350
3.696
4.071
1.372
1.374
1.375
1.377
1.378
1.379
1.380
1.382
1.384
1.386
0.695
0.700
0.705
0.710
0.715
0.720
0.726
0.732
0.737
0.744
100.8
103.6
106.3
109.1
111.9
114.6
117.4
120.1
122.9
125.7
390.6
391.8
393.0
394.1
395.3
396.4
397.6
398.7
399.8
400.9
0.649
0.663
0.676
0.689
0.702
0.715
0.728
0.741
0.754
0.766
2.074
2.066
2.058
2.051
2.044
2.037
2.030
2.023
2.017
2.010
-51.58
101.32
101.17
1354.0
4.153
1.386
0.745
126.3
401.1
0.769
2.009
-50
-48
-46
-44
-42
-40
-38
-36
-34
-32
109.69
121.07
133.36
146.61
160.89
176.24
192.71
210.37
229.26
249.46
109.51
120.85
133.11
146.32
160.55
175.85
192.27
209.86
228.69
248.81
1349.0
1342.7
1336.3
1330.0
1323.5
1317.0
1310.5
1304.0
1297.3
1290.6
4.474
4.909
5.377
5.880
6.419
6.996
7.614
8.275
8.980
9.732
1.388
1.391
1.394
1.397
1.401
1.405
1.409
1.414
1.419
1.424
0.750
0.756
0.763
0.770
0.777
0.785
0.792
0.800
0.809
0.817
128.5
131.2
134.0
136.8
139.6
142.4
145.3
148.1
150.9
153.8
402.0
403.1
404.1
405.2
406.2
407.3
408.3
409.3
410.2
411.2
0.779
0.791
0.803
0.816
0.828
0.840
0.852
0.863
0.875
0.887
2.004
1.998
1.992
1.987
1.981
1.976
1.970
1.965
1.960
1.955
-30
-28
-26
-24
-22
-20
-18
-16
-14
-12
271.01
293.99
318.44
344.44
372.05
401.34
432.36
465.20
499.91
536.58
270.28
293.16
317.52
343.41
370.90
400.06
430.95
463.64
498.20
534.69
1383.9
1277.1
1270.2
1263.3
1256.3
1249.2
1242.0
1234.8
1227.5
1220.0
10.53
11.39
12.29
13.26
14.28
15.37
16.52
17.74
19.04
20.41
1.430
1.436
1.442
1.448
1.455
1.461
1.468
1.476
1.483
1.491
0.826
0.835
0.844
0.854
0.864
0.875
0.886
0.897
0.909
0.921
156.6
159.5
162.4
165.3
168.2
171.1
174.1
177.0
180.0
182.9
412.1
413.1
414.0
414.9
415.7
416.6
417.4
418.2
419.0
419.8
0.899
0.911
0.922
0.934
0.945
0.957
0.968
0.980
0.991
1.003
1.950
1.946
1.941
1.936
1.932
1.927
1.923
1.919
1.914
1.910
-10
-8
-6
-4
-2
0
2
4
6
8
575.26
616.03
658.97
704.15
751.64
801.52
853.87
908.77
966.29
1026.5
573.20
613.78
656.52
701.49
748.76
798.41
850.52
905.16
962.42
1022.4
1212.5
1204.9
1197.2
1189.4
1181.4
1173.4
1165.3
1157.0
1148.6
1140.0
21.86
23.39
25.01
26.72
28.53
30.44
32.46
34.59
36.83
39.21
1.499
1.507
1.516
1.524
1.533
1.543
1.552
1.563
1.573
1.584
0.933
0.947
0.960
0.975
0.990
1.005
1.022
1.039
1.057
1.076
185.9
189.0
192.0
195.0
198.1
201.2
204.3
207.4
210.5
213.7
420.5
421.2
421.9
422.6
423.2
423.8
424.4
424.9
425.5
425.9
1.014
1.025
1.036
1.048
1.059
1.070
1.081
1.092
1.103
1.114
1.906
1.902
1.898
1.894
1.890
1.886
1.882
1.878
1.874
1.870
10
12
14
16
18
20
22
24
26
28
1089.5
1155.4
1224.3
1296.2
1371.2
1449.4
1530.9
1615.8
1704.2
1796.2
1085.1
1150.7
1219.2
1290.8
1365.5
1443.4
1524.6
1609.2
1697.2
1788.9
1131.3
1122.5
1113.5
1104.4
1095.1
1085.6
1075.9
1066.0
1055.9
1045.5
41.71
44.35
47.14
50.05
53.20
56.48
59.96
63.63
67.51
71.62
1.596
1.608
1.621
1.635
1.650
1.666
1.683
1.701
1.721
1.743
1.096
1.117
1.139
1.163
1.188
1.215
1.243
1.273
1.306
1.341
216.8
220.0
223.2
226.5
229.7
233.0
236.4
239.7
243.1
246.5
426.4
426.8
427.2
427.5
427.8
428.1
428.3
428.4
428.6
428.6
1.125
1.136
1.147
1.158
1.169
1.180
1.191
1.202
1.214
1.225
1.866
1.862
1.859
1.855
1.851
1.847
1.843
1.839
1.834
1.830
30
32
34
36
38
40
42
44
46
48
1891.9
1991.3
2094.5
2201.7
2313.0
2428.4
2548.1
2672.2
2800.7
2933.7
1884.2
1983.2
2086.2
2193.1
2304.0
2419.2
2538.6
2662.4
2790.7
2923.6
1034.9
1024.1
1012.9
1001.4
989.5
977.3
964.6
951.4
937.7
923.3
75.97
80.58
85.48
90.68
96.22
102.1
108.4
115.2
122.4
130.2
1.767
1.793
1.822
1.855
1.891
1.932
1.979
2.033
2.095
2.168
1.379
1.420
1.465
1.514
1.569
1.629
1.696
1.771
1.857
1.955
249.9
253.4
256.9
260.5
264.1
267.8
271.5
275.3
279.2
283.2
428.6
428.6
428.4
428.3
428.0
427.7
427.2
426.7
426.1
425.4
1.236
1.247
1.258
1.269
1.281
1.292
1.303
1.315
1.327
1.339
1.826
1.822
1.817
1.813
1.808
1.803
1.798
1.793
1.788
1.782
50
52
54
56
58
60
62
64
3071.5
3214.0
3361.4
3513.8
3671.3
3834.1
4002.1
4175.7
3061.2
3203.6
3351.0
3503.5
3661.2
3824.2
3992.7
4166.8
908.2
892.2
875.1
856.8
836.9
814.9
790.1
761.0
138.6
147.7
157.6
168.4
180.4
193.7
208.6
225.6
2.256
2.362
2.493
2.661
2.883
3.191
3.650
4.415
2.069
2.203
2.363
2.557
2.799
3.106
3.511
4.064
287.3
291.5
295.8
300.3
305.0
310.0
315.3
321.2
424.5
423.5
422.4
421.0
419.4
417.6
415.5
413.0
1.351
1.363
1.376
1.389
1.403
1.417
1.433
1.450
1.776
1.770
1.764
1.757
1.749
1.741
1.732
1.722
Precautions for New Refrigerant (R410)
: http://splitoff.ru/tehn-doc.html
319
Precautions for New Refrigerant (R410)
1.2
SiE39-404
Refrigerant Cylinders
! Cylinder specifications
2 The cylinder is painted refrigerant color (pink).
2 The cylinder valve is equipped with a siphon tube.
Cylinder
Refrigerant can be charged in liquid state with cylinder in
upright position.
Caution: Do not lay cylinder on its side during charging, since
it cause refrigerant in gas state to enter the system.
! Handling of cylinders
(1) Laws and regulations
R410A is liquefied gas, and the High-Pressure Gas Safety Law must be observed in
handling them. Before using, refer to the High-Pressure Gas Safety Law.
The Law stipulates standards and regulations that must be followed to prevent accidents
with high-pressure gases. Be sure to follow the regulations.
(2) Handing of vessels
Since R410A is high-pressure gas, it is contained in high-pressure vessels.
Although those vessels are durable and strong, careless handling can cause damage that
can lead to unexpected accidents. Do not drop vessels, let them fall, apply impact or roll
them on the ground.
(3) Storage
Although R410A is not flammable, it must be stored in a well-ventilated, cool, and dark place
in the same way as any other high-pressure gases.
It should also be noted that high-pressure vessels are equipped with safety devices that
releases gas when the ambient temperature reaches more than a certain level (fusible plug
melts) and when the pressure exceeds a certain level (spring-type safety valve operates).
320
: http://splitoff.ru/tehn-doc.html
Precautions for New Refrigerant (R410)
SiE39-404
1.3
Precautions for New Refrigerant (R410)
Service Tools
R410A is used under higher working pressure, compared to previous refrigerants (R22,R407C).
Furthermore, the refrigerating machine oil has been changed from Suniso oil to Ether oil, and if
oil mixing is occurred, sludge results in the refrigerants and causes other problems. Therefore,
gauge manifolds and charge hoses that are used with a previous refrigerant (R22,R407C) can
not be used for products that use new refrigerants.
Be sure to use dedicated tools and devices.
! Tool compatibility
Tool
Compatibility
HFC
HCFC
R410A
R407C
R22
Gauge manifold
Charge hose
5
"
5
5
"
Charging cylinder
Gas detector
Vacuum pump
(pump with reverse flow
preventive function)
Weighting instrument
"
2Do not use the same tools for R22 and
R410A.
2Thread specification differs for R410A
and R407C.
2Weighting instrument used for HFCs.
2The same tool can be used for HFCs.
2To use existing pump for HFCs,
vacuum pump adaptor must be
installed.
"
2Seal material is different between R22
and HFCs.
2Thread specification is different
between R410A and others.
2For R410A, flare gauge is necessary.
2Torque-up for 1/2 and 5/8
Charge mouthpiece
5
Flaring tool (Clutch type)
Torque wrench
Pipe cutter
Pipe expander
Pipe bender
"
"
"
"
"
Pipe assembling oil
5
Refrigerant recovery
device
Check your recovery device.
Refrigerant piping
Reasons for change
2Due to refrigerating machine oil
change. (No Suniso oil can be used.)
See the chart below.
2Only φ19.1 is changed to 1/2H material
while the previous material is "O".
As for the charge mouthpiece and packing, 1/2UNF20 is necessary for mouthpiece size of
charge hose.
! Copper tube material and thickness
Pipe size
φ6.4
φ9.5
φ12.7
φ15.9
φ19.1
φ22.2
φ25.4
φ28.6
φ31.8
φ38.1
φ44.5
Material
O
O
O
O
O
1/2H
1/2H
1/2H
1/2H
1/2H
1/2H
Ve-up
R407C
Thickness
[mm]
0.8
0.8
0.8
1.0
1.0
1.0
1.0
1.0
1.2
1.4
1.6
Material
O
O
O
O
1/2H
1/2H
1/2H
1/2H
1/2H
1/2H
1/2H
Ve-upII
R410A
Thickness
[mm]
0.8
0.8
0.8
1.0
1.0
1.0
1.0
1.0
1.1
1.4
1.6
* O: Soft (Annealed)
H: Hard (Drawn)
Precautions for New Refrigerant (R410)
: http://splitoff.ru/tehn-doc.html
321
Precautions for New Refrigerant (R410)
SiE39-404
1. Flaring tool
Flare gauge
! Specifications
2 Dimension A
Unit: mm
Nominal size
A +0
-0.4
Tube O.D.
Do
Class-2 (R410A)
Class-1 (Conventional)
1/4
6.35
9.1
9.0
3/8
9.52
13.2
13.0
1/2
12.70
16.6
16.2
5/8
15.88
19.7
19.4
3/4
19.05
24.0
23.3
! Differences
2 Change of dimension A
Dimension A
For class-1: R407C
For class-2: R410A
Conventional flaring tools can be used when the work process is changed.
(change of work process)
Previously, a pipe extension margin of 0 to 0.5mm was provided for flaring. For R410A air
conditioners, perform pipe flaring with a pipe extension margin of 1.0 to 1.5mm.
(For clutch type only)
Conventional tool with pipe extension margin adjustment can be used.
322
: http://splitoff.ru/tehn-doc.html
Precautions for New Refrigerant (R410)
SiE39-404
Precautions for New Refrigerant (R410)
2. Torque wrench
! Specifications
2 Dimension B
Nominal size
1/2
5/8
Unit:mm
Class-1
24
27
Class-2
26
29
Previous
24
27
No change in tightening torque
No change in pipes of other sizes
! Differences
2 Change of dimension B
Only 1/2", 5/8" are extended
For class-1: R407C
For class-2: R410A
Dimension B
3. Vacuum pump with check valve
Vacuum pump adapter
Reverse flow preventive
vacuum adapter
! Specifications
2 Discharge speed
) Maximum degree of vacuum
50 l/min (50Hz)
–100.7 kpa ( 5 torr – 755 mmHg)
60 l/min (60Hz)
2 Suction port UNF7/16-20(1/4 Flare)
UNF1/2-20(5/16 Flare) with adapter
! Differences
2 Equipped with function to prevent reverse oil flow
2 Previous vacuum pump can be used by installing adapter.
Precautions for New Refrigerant (R410)
: http://splitoff.ru/tehn-doc.html
323
Precautions for New Refrigerant (R410)
SiE39-404
4. Leak tester
! Specifications
2 Hydrogen detecting type, etc.
2 Applicable refrigerants
R410A, R407C, R404A, R507A, R134a, etc.
! Differences
2 Previous testers detected chlorine. Since HFCs do not contain chlorine, new tester detects
hydrogen.
5. Refrigerant oil (Air compal)
! Specifications
2 Contains synthetic oil, therefore it can be used for piping work of every refrigerant cycle.
2 Offers high rust resistance and stability over long period of time.
! Differences
2 Can be used for R410A and R22 units.
6. Gauge manifold for R410A
! Specifications
2 High pressure gauge
- 0.1 to 5.3 MPa (-76 cmHg to 53 kg/cm2)
2 Low pressure gauge
- 0.1 to 3.8 MPa (-76 cmHg to 38 kg/cm2)
2 1/4" → 5/16" (2min → 2.5min)
2 No oil is used in pressure test of gauges.
→ For prevention of contamination
324
: http://splitoff.ru/tehn-doc.html
Precautions for New Refrigerant (R410)
SiE39-404
Precautions for New Refrigerant (R410)
2 Temperature scale indicates the relationship between pressure and temperature in gas
saturated state.
! Differences
2 Change in pressure
2 Change in service port diameter
7. Charge hose for R410A
(Hose with ball valve)
!
2
2
2
Specifications
Working pressure 5.08 MPa (51.8 kg/cm2)
Rupture pressure 25.4 MPa (259 kg/cm2)
Available with and without hand-operate valve that prevents refrigerant from outflow.
!
2
2
2
Differences
Pressure proof hose
Change in service port diameter
Use of nylon coated material for HFC resistance
8. Charging cylinder
Can not be used
! Specifications
2 Use weigher for refrigerant charge listed below to charge directly from refrigerant cylinder.
! Differences
2 The cylinder can not be used for mixed refrigerant since mixing ratio is changed during
charging.
When R410A is charged in liquid state using charging cylinder, foaming phenomenon is
generated inside charging cylinder.
Precautions for New Refrigerant (R410)
: http://splitoff.ru/tehn-doc.html
325
Precautions for New Refrigerant (R410)
SiE39-404
9. Weigher for refrigerant charge
! Specifications
2 High accuracy
TA101A (for 10-kg cylinder) = ± 2g
TA101B (for 20-kg cylinder) = ± 5g
2 Equipped with pressure-resistant sight glass to check liquid refrigerant charging.
2 A manifold with separate ports for HFCs and previous refrigerants is equipped as standard
accessories.
! Differences
2 Measurement is based on weight to prevent change of mixing ratio during charging.
10. Charge mouthpiece
! Specifications
2 For R410A, 1/4"→ 5/16" (2min → 2.5min)
2 Material is changed from CR to H-NBR.
! Differences
2 Change of thread specification on hose connection side (For the R410A use)
2 Change of sealer material for the HFCs use.
326
: http://splitoff.ru/tehn-doc.html
Precautions for New Refrigerant (R410)
SiE39-404
Index
A
E
A0 .........................................................................173
A1 .........................................................................174
A3 .........................................................................175
A6 .........................................................................177
A7 .........................................................................178
A9 .........................................................................180
AF ........................................................................182
AJ .........................................................................183
Abnormal Discharge Pipe Temperature ...............197
Abnormal Outdoor Fan Motor Signal ...................199
About Refrigerant R410A .....................................318
Actuation of High Pressure Switch .......................189
Actuation of Low Pressure Sensor .......................190
Address Duplication of Central
Remote Controller .........................................231
Address Duplication, Improper Setting ....... 241, 248
Applicable range of Field setting ..........................123
Auto restart after power failure reset ....................124
E1 ........................................................................ 188
E3 ........................................................................ 189
E4 ........................................................................ 190
E5 ........................................................................ 191
E6 ........................................................................ 192
E7 ........................................................................ 193
E9 ........................................................................ 195
Electronic Expansion Valve PI Control .................. 83
Emergency Operation ......................................... 100
Error of External Protection Device ..................... 173
Excessive Number of Indoor Units ...................... 230
B
Basic Control ..........................................................76
C
C4 ........................................................................184
C5 ........................................................................185
C9 ........................................................................186
CJ .........................................................................187
Centralized Control Group No. Setting ................128
Check No. 12 .......................................................256
Check No. 8 .........................................................255
Check No. 9 .........................................................255
Check Operation ..................................................115
Check Operation not executed ............................221
Compressor Motor Lock .......................................191
Compressor Motor Overcurrent/Lock ...................192
Compressor PI Control ..........................................77
Contents of Control Modes ..................................130
Cool/Heat Mode Switching ...................................142
Cooling Operation Fan Control ..............................84
Current Sensor Malfunction .................................201
F
F3 ........................................................................ 197
F6 ........................................................................ 198
Fan Motor (M1F) Lock, Overload ........................ 177
Field Setting ........................................................ 119
Field Setting from Outdoor Unit .......................... 132
Field Setting from Remote Controller .................. 119
Filter Sign Setting ................................................ 124
Freeze Prevention ............................................... 108
Functional Parts Layout ........................................ 57
RXYQ14, 16M ................................................ 59
RXYQ5M ........................................................ 57
RXYQ8, 10, 12M ............................................ 58
H
H7 ....................................................................... 199
H9 ....................................................................... 200
Heating operation prohibition .............................. 102
High Pressure Protection Control .......................... 94
I
Improper Combination of Optional Controllers for
Centralized Control .............................. 239, 246
Inverter Compressor Abnormal ........................... 210
Inverter Current Abnormal .................................. 211
Inverter Over-Ripple Protection ........................... 215
Inverter Protection Control .................................... 97
Inverter Start up Error ......................................... 212
D
J
Defrosting Operation ..............................................88
Demand Operation ...............................................102
Detailed Explanation of Setting Modes ................124
Discharge Pipe Protection Control .........................96
Display “Under Host Computer Integrate Control”
Blinks (Repeats Double Blink) ......................254
Display “Under Host Computer Integrate Control”
Blinks (Repeats Single Blink) ........................251
Drain Level above Limit .......................................182
Drain Pump Control .............................................103
J2
J3
J5
J6
J8
J9
JA
JC
........................................................................ 201
........................................................................ 202
........................................................................ 203
........................................................................ 204
........................................................................ 205
........................................................................ 206
........................................................................ 207
........................................................................ 208
L
L4 ........................................................................ 209
L5 ........................................................................ 210
Index
: http://splitoff.ru/tehn-doc.html
i
SiE39-404
L8 .........................................................................211
L9 .........................................................................212
LC ........................................................................213
List of Electrical and Functional Parts ..................293
Indoor Unit .....................................................295
Outdoor Unit ..................................................293
Louver Control for Preventing Ceiling Dirt ...........105
Low Pressure Drop Due to Refrigerant Shortage or
Electronic Expansion Valve Failure ..............217
Low Pressure Protection Control ...........................95
M
M1 ............................................................... 237, 244
M8 ............................................................... 238, 245
MA ............................................................... 239, 246
MC .............................................................. 241, 248
Malfunction code indication by
outdoor unit PCB ..........................................171
Malfunction of Capacity Determination Device ....183
Malfunction of Discharge Pipe
Pressure Sensor ...........................................207
Malfunction of Discharge Pipe Thermistor
(R3, R31~33T) ..............................................202
Malfunction of Drain Level Control System
(S1L) .............................................................175
Malfunction of Inverter Radiating Fin Temperature
Rise ...............................................................209
Malfunction of Inverter Radiating Fin Temperature
Rise Sensor ..................................................216
Malfunction of Moving Part of Electronic Expansion
Valve (20E) ...................................................180
Malfunction of Moving Part of Electronic Expansion
Valve (Y1E, Y2E) ..........................................195
Malfunction of Oil Equalizing Pipe
Thermistor (R7T) ..........................................205
Malfunction of Outdoor Unit Fan Motor ................193
Malfunction of Receiver Gas Pipe
Thermistor (R5T) ..........................................206
Malfunction of Suction Pipe Pressure Sensor ......208
Malfunction of Swing Flap Motor (MA) .................178
Malfunction of System, Refrigerant System
Address Undefined .......................................235
Malfunction of Thermistor (R1T)
for Suction Air ...............................................186
Malfunction of Thermistor (R2T)
for Heat Exchanger .......................................184
Malfunction of Thermistor (R2T)
for Suction Pipe ............................................203
Malfunction of Thermistor (R3T)
for Gas Pipes ................................................185
Malfunction of Thermistor (R4T)
for Outdoor Unit Heat Exchanger .................204
Malfunction of Thermistor for
Outdoor Air (R1T) .........................................200
Malfunction of Thermostat Sensor in Remote
Controller ......................................................187
Malfunction of Transmission Between Central
Remote Controller and
Indoor Unit ...................................232, 236, 242
Malfunction of Transmission Between
Indoor Units ..................................................222
ii
Malfunction of Transmission Between Indoor and
Outdoor Units in the Same System .............. 228
Malfunction of Transmission Between Inverter and
Control PC Board ......................................... 213
Malfunction of Transmission Between Master and
Slave Remote Controllers ............................ 227
Malfunction of Transmission Between Optional
Controllers for Centralized Control ....... 238, 245
Malfunction of Transmission Between
Outdoor Units ............................................... 225
Malfunction of Transmission Between Remote
Controller and Indoor Unit ............................ 224
Method of Replacing The Inverter’s Power
Transistors and Diode Modules ................... 314
O
Oil Return Operation ............................................. 86
Operation Lamp Blinks ........................................ 249
Operation Mode .................................................... 75
Operation When Power is Turned On ................. 117
Option List ........................................................... 301
Other Control ........................................................ 99
Outdoor Air Processing Unit-Field Setting .......... 127
Outdoor Unit PC Board Layout ........................... 118
Outdoor Unit Rotation ........................................... 99
P
P1 ........................................................................ 215
P4 ........................................................................ 216
PC Board Defect ........................ 174, 188, 237, 244
Piping Installation Point ....................................... 304
The Example of A Wrong Pattern ................. 305
Power Supply Insufficient or
Instantaneous Failure .................................. 219
Precautions for New Refrigerant (R410) ............. 318
Pressure Equalization prior to Startup .................. 93
Pressure Sensor ................................................. 313
Procedure and Outline ........................................ 114
Protection Control ................................................. 94
Pump-down Residual Operation ........................... 89
R
Refrigerant Circuit ................................................. 50
FXMQ125~250MFV1 ...................................... 56
RXYQ14, 16M ................................................ 54
RXYQ5M ........................................................ 50
RXYQ8, 10, 12M ............................................ 52
Refrigerant Cylinders .......................................... 320
Refrigerant Flow for Each Operation Mode ........... 60
RXYQ14, 16M ................................................ 68
RXYQ5M ........................................................ 60
RXYQ8, 10, 12M ............................................ 64
Refrigerant Overcharged .................................... 198
Refrigerant System not Set, Incompatible
Wiring/Piping ................................................ 234
Replacement procedure for INV compressor,
VRV II (RXYQ5M-48M) ................................ 258
Restart Standby .................................................... 90
Reverse Phase, Open Phase ............................. 218
: http://splitoff.ru/tehn-doc.html
Index
SiE39-404
S
STD Compressor Overload Protection ..................98
Selection of Pipe Size, Joints and Header ...........306
Service Tools .......................................................321
Setting Contents and Code No. ...........................122
Setting by dip switches ........................................132
Setting by pushbutton switches ...........................134
Setting of Low Noise Operation and Demand
Operation ......................................................147
Setting of Refrigerant Additional
Charging Operation ......................................153
Special Control .......................................................85
Specifications .........................................................10
Indoor Units .....................................................21
Outdoor Units ..................................................10
Startup Control .......................................................85
Stopping Operation ................................................91
T
Test Operation .....................................................114
Thermistor Resistance / Temperature
Characteristics ..............................................311
Thermostat Sensor in Remote Controller ............106
Troubleshooting (OP
Central Remote Controller) ............................236
Schedule Timer) ............................................242
Unified ON/OFF Controller) ...........................249
U
U0
U1
U2
U3
U4
U5
U7
U8
U9
UA
UC
UE
UF
UH
........................................................................217
........................................................................218
........................................................................219
........................................................................221
........................................................................222
........................................................................224
........................................................................225
........................................................................227
........................................................................228
........................................................................230
........................................................................231
.......................................................232, 236, 242
........................................................................234
........................................................................235
Index
: http://splitoff.ru/tehn-doc.html
iii
SiE39-404
iv
: http://splitoff.ru/tehn-doc.html
Index
SiE39-404
Drawings & Flow Charts
A
Abnormal Discharge Pipe Temperature ...............197
Abnormal Outdoor Fan Motor Signal ...................199
Actuation of High Pressure Switch .......................189
Actuation of Low Pressure Sensor .......................190
Address Duplication of Central
Remote Controller .........................................231
Address Duplication, Improper Setting ........ 241, 248
C
Centralized Control Group No. Setting
BRC1A Type ..................................................128
BRC7C Type .................................................129
Group No. Setting Example ...........................129
Charge hose for R410A .......................................325
Charge mouthpiece ..............................................326
Charging cylinder .................................................325
Check No. 12 .......................................................256
Check No. 8 .........................................................255
Check No. 9 .........................................................255
Check Operation not executed ............................221
Compressor Motor Lock .......................................191
Compressor Motor Overcurrent/Lock ...................192
Contents of Control Modes
How to Select Operation Mode ......................131
Current Sensor Malfunction .................................201
D
Discharge air temperature control
Cooling operations .........................................110
Heating operations ........................................111
Display “Under Host Computer Integrate Control”
Blinks (Repeats Double Blink) ......................254
Display “Under Host Computer Integrate Control”
Blinks (Repeats Single Blink) ........................251
Display of sensor and address data .....................167
Drain Level above Limit .......................................182
Drain Pump Control
When the Float Switch is Tripped and “AF” is
Displayed on the
Remote Controller ............................104
When the Float Switch is Tripped During
Cooling OFF by Thermostat .............103
When the Float Switch is Tripped During
Heating Operation ............................104
When the Float Switch is Tripped While the
Cooling Thermostat is ON ................103
E
Error of External Protection Device ......................173
Excessive Number of Indoor Units .......................230
F
Fan Motor (M1F) Lock, Overload .........................177
Drawings & Flow Charts
Field Setting From Outdoor Unit
Mode changing procedure ............................ 134
Setting by pushbutton switches .................... 134
Field Setting from Outdoor Unit
Setting by dip switches ................................. 132
Flaring tool .......................................................... 322
Forced fan ON ..................................................... 167
Freeze Prevention ............................................... 108
Functional Parts Layout ........................................ 57
RXYQ14, 16M ................................................. 59
RXYQ5M ......................................................... 57
RXYQ8, 10, 12M ............................................. 58
G
Gauge manifold for R410A .................................. 324
H
How to Enter the Service Mode .......................... 166
I
Improper Combination of Optional Controllers
for Centralized Control ......................... 239, 246
Individual setting ................................................. 167
Inverter Compressor Abnormal ........................... 210
Inverter Current Abnormal ................................... 211
Inverter Over-Ripple Protection ........................... 215
Inverter Start up Error ......................................... 212
L
Leak tester .......................................................... 324
Low Pressure Drop Due to Refrigerant Shortage
or Electronic Expansion Valve Failure ......... 217
M
Malfunction hysteresis display ............................ 167
Malfunction of Capacity Determination Device ... 183
Malfunction of Discharge Pipe
Pressure Sensor .......................................... 207
Malfunction of Discharge Pipe
Thermistor (R3, R31~33T) ........................... 202
Malfunction of Drain Level
Control System (S1L) ................................... 175
Malfunction of Inverter Radiating Fin
Temperature Rise ........................................ 209
Malfunction of Inverter Radiating Fin
Temperature Rise Sensor ............................ 216
Malfunction of Moving Part of Electronic
Expansion Valve (20E) ................................ 180
Malfunction of Moving Part of Electronic
Expansion Valve (Y1E, Y2E) ....................... 195
Malfunction of Oil Equalizing Pipe
Thermistor (R7T) .......................................... 205
Malfunction of Outdoor Unit Fan Motor ............... 193
Malfunction of Receiver Gas Pipe
Thermistor (R5T) .......................................... 206
: http://splitoff.ru/tehn-doc.html
v
SiE39-404
Malfunction of Suction Pipe Pressure Sensor ......208
Malfunction of Swing Flap Motor (MA) .................178
Malfunction of System, Refrigerant
System Address Undefined ..........................235
Malfunction of Thermistor (R1T)
for Suction Air ...............................................186
Malfunction of Thermistor (R2T)
for Heat Exchanger .......................................184
Malfunction of Thermistor (R2T)
for Suction Pipe .............................................203
Malfunction of Thermistor (R3T)
for Gas Pipes ................................................185
Malfunction of Thermistor (R4T)
for Outdoor Unit Heat Exchanger ..................204
Malfunction of Thermistor for
Outdoor Air (R1T) .........................................200
Malfunction of Thermostat Sensor in Remote
Controller ......................................................187
Malfunction of Transmission Between
Central Remote Controller and
Indoor Unit ................................... 232, 236, 242
Malfunction of Transmission Between Indoor
and Outdoor Units in the Same System ........228
Malfunction of Transmission
Between Indoor Units ....................................222
Malfunction of Transmission Between Inverter
and Control PC Board ...................................213
Malfunction of Transmission Between Master
and Slave Remote Controllers ......................227
Malfunction of Transmission Between Optional
Controllers for Centralized Control ....... 238, 245
Malfunction of Transmission Between
Outdoor Units ................................................225
Malfunction of Transmission Between Remote
Controller and Indoor Unit .............................224
Method of Replacing The Inverter’s
Power Transistors and Diode Modules .........314
Diode Module ................................................315
Power Transistor IGBT
(On Inverter PC Board) .....................315
RXYQ8, 10, 12M ............................................. 52
Refrigerant Cylinders .......................................... 320
Refrigerant Flow for Each Operation Mode ........... 60
RXYQ14, 16M ................................................. 68
RXYQ5M ......................................................... 60
RXYQ8, 10, 12M ............................................. 64
Refrigerant oil (Air compal) ................................. 324
Refrigerant Overcharged ..................................... 198
Refrigerant R410A .............................................. 318
Refrigerant System not Set, Incompatible
Wiring/Piping ................................................ 234
Replacement procedure for INV compressor,
VRV II (RXYQ5M-48M) ................................ 258
Reverse Phase, Open Phase .............................. 218
O
U
Operation Lamp Blinks .........................................249
Outdoor Unit PC Board Layout ............................118
Unit No. transfer .................................................. 167
P
PC Board Defect ......................... 174, 188, 237, 244
Piping Diagrams ...................................................260
Indoor Unit .....................................................263
Outdoor Unit ..................................................260
Piping Installation Point ........................................304
The Example of A Wrong Pattern ..................305
Power Supply Insufficient or
Instantaneous Failure ...................................219
Pressure Sensor ..................................................313
R
S
Selection of Operation Mode ............................... 109
Setting of Air Flow Direction
Adjustment Range ....................................... 126
Setting of Demand Operation
Image of operation in the case of A .............. 150
Image of operation in the case of A and B .... 150
Image of operation in the case of B .............. 150
Setting of Low Noise Operation
Image of operation in the case of A .............. 148
Image of operation in the case of A, B .......... 148
Image of operation in the case of B .............. 148
Simplified Remote Controller .............................. 121
BRC2A51 ...................................................... 121
T
Test Operation .................................................... 115
Thermostat Sensor in Remote Controller
Cooling .......................................................... 106
Heating ......................................................... 107
Torque wrench .................................................... 323
Troubleshooting (OP
Central Remote Controller) ........................... 236
Schedule Timer) ........................................... 242
Unified ON/OFF Controller) .......................... 249
V
Vacuum pump with check valve .......................... 323
W
Weigher for refrigerant charge ............................ 326
Wired Remote Controller ..................................... 119
Wireless Remote Controller - Indoor Unit ........... 120
BRC7C type .................................................. 120
Wiring Diagrams for Reference ........................... 269
Field Wiring ................................................... 272
Indoor Unit .................................................... 275
Outdoor Unit ................................................. 269
Refrigerant Circuit ..................................................50
FXMQ125~250MFV1 .......................................56
RXYQ14, 16M .................................................54
RXYQ5M .........................................................50
vi
: http://splitoff.ru/tehn-doc.html
Drawings & Flow Charts
Daikin Europe N.V. is approved by LRQA for its Quality
Management System in accordance with the ISO9001
standard. ISO9001 pertains to quality assurance
regarding design, development, manufacturing as well
as to services related to the product.
Daikin units comply with the European regulations that
guarantee the safety of the product.
ISO14001 assures an effective environmental
management system in order to help protect human
health and the environment from the potential impact
of our activities, products and services and to assist in
maintaining and improving the quality of the
environment.
VRV products are not within the scope of the Eurovent
certification programme.
SiE39-404 • 01/2005
Prepared in Belgium by Lannoo
Specifications are subject to change without prior notice
Zandvoordestraat 300
B-8400 Ostend - Belgium
www.daikineurope.com
: http://splitoff.ru/tehn-doc.html