Download Outdoor Unit
Transcript
SiE39-404 Troubleshooting by Indication on the Remote Controller 2.20 “F3” Outdoor Unit: Abnormal Discharge Pipe Temperature Remote Controller Display F3 Applicable Models RXYQ5~48M Method of Malfunction Detection Abnormality is detected according to the temperature detected by the discharge pipe temperature sensor. Malfunction Decision Conditions ! When the discharge pipe temperature rises to an abnormally high level ! When the discharge pipe temperature rises suddenly Supposed Causes ! Faulty discharge pipe temperature sensor ! Faulty connection of discharge pipe temperature sensor ! Faulty outdoor unit PCB Troubleshooting Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred. Discharge pipe temperature is 115°C or higher. YES Out of gas, compression defect, etc. Defect of the refrigerant system. NO Are the characteristics of the discharge pipe thermistor normal? (3.5~400KΩ) YES NO Replace the discharge pipe thermistor. Replace outdoor unit PC board A2P. (V3068) ∗2: Refer to thermistor resistance / temperature characteristics table on P311. Troubleshooting : http://splitoff.ru/tehn-doc.html 197