Download instruction manual for transformer differential
Transcript
DIELECTRIC TEST In accordance with IEC 255-5 and ANSI/IEEE C37.90-1989, one minute dielectric (high potential) tests may be performed as follows. All circuits to ground: 2121 Vdc Input to output circuits 1500 Vac or 2121 Vdc Note that this device employs decoupling capacitors to ground at all the output terminals, and at the power supply terminals (3, 4). Accordingly, a leakage current of approximately 15 milliamperes per 1000 Vac is to be expected. CONNECTIONS Incorrect wiring may result in damage to the relay. Be sure to check the model and Style Number against the options listed in the Style Number Identification Chart (Figure 1-1) before connecting and energizing a particular relay. NOTE Be sure the relay case is hard-wired to earth ground with no smaller than 12 AWG copper wire attached to the ground terminal on the rear of the relay case. When the relay is configured in a system with other protective devices, it is recommended to use a separate lead to the ground bus from each relay. Except as noted above, connections should be made with a minimum wire size of 14 AWG. Figures 4-7 through 4-10 show case terminals designations for four typical relay configurations. Figures 4-11 through 4-14 show the internal connections of the BE1-87T. Control circuit connections are shown in Figures 4-15 through 4-18. CAUTION To prevent possible false tripping, the upper connection plug should be in place prior to removing or installing the lower connection plug. BE1-87T 5 AUX N.O. 7 AUX COM 11 12 6 AUX N.C. 14 8 RESTRAINED COM 4 13 15 9 COMMON 5 16 10 UNRESTRAINED 19 POWER SUPPLY STATUS CONTACTS POWER 1 INPUTS 1 3 2 3 4 20 1 CONFIGURATION IS DEPENDENT ON STYLE SELECTED. OUTPUTS 1 BE1-87T D437-001 9-23-94 Figure 4-7. Case Terminals: Single-Phase 9171300990 Rev R BE1-87T Installation 4-9