DESIGN
E Q U I P M E N T
N O T E B O O K
Installing Infrared Heaters
COMMISSIONING
OPERATION & MAINTENANCE
INSTALLATION
Proper installation guarantees safe and comfortable use
CAM MARKLOWITZ
MJM Associates Inc.
Englewood, Colo.
explosive or flammaGas supply line
ble fumes, especially
ast month, the sizing and selec- those where chloriManual gastion of commercial, gas-fired in- nated, halogenated, or
shutoff valve
Ground joint union
frared units was discussed. An- acidic vapors are preswith brass seat
other key factor in determining the ent.
Gas
correct type and size of a unit for an appli• Manufacturer re- supply
line
cation is to examine how the unit will be quirements for clearTo controls
installed. Proper installation is at least as ance to combustibles
Plugged 1/8-in. NPT
3-in. min.
important as sizing and selecting the type and recommended
test gauge connection
of infrared unit heater to be used in an ap- mounting heights
plication.
must be adhered to
Sediment trap
A number of general infrared installa- strictly.
tion requirements are common to all
• Installations must
commercial, gas-fired equipment:
conform not only to FIGURE 2.2 A ground joint union and manual shutoff valve
• The installation work must be done local and national should be installed in the gas supply line adjacent to the unit.
by a qualified installation agency.
building codes, but
• Gas-fired equipment should never be also to the requirements of the manufac- intensity infrared units reach temperainstalled in areas exposed to potentially turer described in the installation and tures in excess of 1,700o F, while low-intensity units can produce tube temperaservice manual.
Photos courtesy of Modine Manufacturing
When equipment is selected tures in excess of 1,000 o F near the
for a job, the sizing and selection burner. As a result of these high temperaprocess should produce a plan tures, clearances to combustibles must be
drawing that shows where each strictly adhered to. Be aware of clearances
Minimum clearance to
unit will be located in the build- to the following:
combustible materials
• Combustible materials.
ing. Make sure this plan drawing
• Stacked materials (signs are to be
is available before installing the
Mount
posted in locations with stacked materials
equipment.
height
No matter how neat and clean to indicate the maximum permissible
the installation, if the installation stacking height (Figure 2.1).
Stacking
• Lights.
does not comply with a properly
height
• Sprinkler heads.
designed plan, there will be heat
• Overhead cranes.
related complaints from the
• Objects on lifts (like automobiles inbuilding occupants. The plans
should include location, mount- side repair shops).
Infrared units, like all gas-fired equiping height, and angle of reflecFIGURE 2.1 Post maximum stacking heights below
ment, need clean combustion air to opertors.
infrared heaters.
Next, determine if the sup- ate. High-intensity units and unvented
porting structure is adequate to low-intensity units require a minimum
support the unit and ensure the required air displacement of 4 cfm per 1,000-Btuh
Cam Marklowitz is the vice president of
electric and gas utilities are available. For input for natural gas and 5 cfm per
sales for MJM Associates Inc. in Englevented applications, the unit must be lo- 1,000-Btuh input for propane gas. Not
wood, Colo., which represents 15 manucated so it is vented per the requirements all low-intensity installations can be unfacturers in the HVAC industry, offering
vented. Check the installation-and-servin the installation and service manual.
sales support, product training, applicaOperating temperature is also a factor ice manual provided by the manufaction assistance, and technical support to
that must be considered. High and low- turer. Ventilation and combustion-air
wholesale distributors, OEMs, engineers, intensity infrared units operate at high requirements for both vented and unand contractors.
temperatures. The ceramic tiles in high- vented applications must be adhered to.
L
2