Download G40UH(X) - HvacPartsShop.com
Transcript
TABLE 11 PROVE SWITCH SET POINTS −1 to −14 Units 0 − 4500ft (0 − 1372m) 4501’ − 7500’ 1373m − 7500m 7501’ − 10,000’ (2287 − 3048m) −045 0.47" (116Pa) 0.36" (89Pa) 0.36" (89Pa) −070 0.47" (116Pa) 0.36" (89Pa) 0.36" (89Pa) −090 0.51" (126Pa) 0.47" (116Pa) 0.43" (106Pa) −110 0.58" (.14Pa) 0.47" (116Pa) 0.43" (106Pa) −135 0.51" (126Pa) 0.47" (116Pa) 0.43" (106Pa) −155 0.51" (126Pa) 0.47 (116a) 0.43" (106Pa) All −15 and later models 0.40" (99pa) no change 0.36" (89Pa) NOTE−− −1 to −14 units require a high altitude prove switch kit if installed above 4500 ft (1370 m). NOTE−− −15 and later units require a high altitude prove switch kit if installed above 7500 ft (2286 m). II−PLACEMENT AND INSTALLATION Make sure unit is installed in accordance with installation instructions and applicable codes. III−START-UP A−Preliminary and Seasonal Checks 1 − Inspect electrical wiring, both field and factory installed for loose connections. Tighten as required. 2 − Check voltage at disconnect switch. Voltage must be within range listed on the nameplate. If not, consult the power company and have voltage condition corrected before starting unit. B−Heating Start-Up WARNING Turn knob on gas valve clockwise to OFF. Do not force. See figure 18. White Rodgers 36E/36F Gas Valve − Move gas valve switch to OFF position. 7 − Wait five minutes to clear out any gas. If you then smell gas, STOP! Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. If you do not smell gas go to next step. 8 − Honeywell VR8205 Gas Valve with On/Off Switch − Move gas valve switch to ON position. Do not force. See figure 17. Honeywell VR8205 Gas Valve with Control Knob − Turn knob on gas valve counterclockwise to ON. Do not force. White Rodgers 36E/36F Gas Valve − Move gas valve switch to ON position. 9 − Replace the upper access panel. 10− Turn on all electrical power to to the unit. 11− Set the thermostat to desired setting. NOTE − When unit is initially started, steps 1 through 11 may need to be repeated to purge air from gas line. 12− If the appliance will not operate, follow the instructions Turning Off Gas to Unit" and call your service technician or gas supplier. Turning Off Gas to Unit 1 − Set the thermostat to the lowest setting. 2 − Turn off all electrical power to the unit if service is to be performed. 3 − Remove the upper access panel. 4 − Honeywell VR8205 Gas Valve with On/Off Switch − Move gas valve switch to OFF position. Do not force. See figure 17. Honeywell VR8205 Gas Valve with Control Knob − Turn knob on gas valve clockwise to OFF. Do not force. See figure 18. White Rodgers 36E/36F Gas Valve − Switch gas valve lever to OFF. 5 − Replace the upper access panel. Shock and burn hazard. C−Safety or Emergency Shutdown G40UH(X) units are equipped with a hot surface ignition system. Do not attempt to light manually. Disconnect main power to unit. Close manual and main gas valves. Gas Valve Operation (Figures 16, 15, 17 and 18) 1 − STOP! Read the safety information at the beginning of this section. 2 − Set the thermostat to the lowest setting. 3 − Turn off all electrical power to the unit. 4 − This furnace is equipped with an ignition device which automatically lights the burners. Do not try to light the burners by hand. 5 − Remove the upper access panel. 6 − Honeywell VR8205 Gas Valve with On/Off Switch − Move gas valve switch to OFF position. Do not force. See figure 17. Honeywell VR8205 Gas Valve with Control Knob − D−Extended Period Shutdown Turn off thermostat or set to UNOCCUPIED" mode. Close all gas valves (both internal and external to unit) to guarantee no gas leak into combustion chamber. Turn off power to unit. All access panels and covers must be in place and secured. IV−HEATING SYSTEM SERVICE CHECKS A−C.S.A. Certification All units are C.S.A. (formally A.G.A. and C.G.A. combined) design certified without modifications. Refer to the G40UH(X) Installation Instruction. B−Gas Piping Gas supply piping should not allow more than 0.5"W.C. drop in pressure between gas meter and unit. Supply gas pipe must not be smaller than unit gas connection. Page 24