Transcript
2. Alarm Details and Countermeasures a. High Temperature Alarm (E1) If the cabinet temperature exceeds the setpoint temperature by 14.4°F (8°C) or more for more than x hours, "E1" is displayed. The default value of x is "2" (2 hours). The value of x can be changed under F3 on the Settings and Diagnostics Menu. (0=No delay; 1=1; 2=2; 3=3 hours) Note: • After the machine has been turned off and then turned back on, the high temperature alarm feature is not active until the cabinet temperature reaches the lower setpoint temperature differential. • The high temperature alarm feature operates even during defrost. Reset Options The alarm will automatically reset once the cabinet temperature reaches the lower setpoint temperature differential. Possible Causes • The door is opened frequently or is not completely closed. • Trouble with the compressor or a gas leak. • Trouble with the cabinet thermistor (black). 35