Download geoTHERM - Vaillant
Transcript
8 Control system Display shown Menu A: Installation assistant Installation Language selection Language Description Factory setting You will be guided through the Installation Assistant, Menus A1 and A2, during the initial commissioning of the heat pump. The Installation Assistant appears automatically during initial commissioning. Language : Set the local language A1 >GB English During the initial installation the controller always starts with this menu (Installation Assistant). >Select Installation assistant Hydraulic scheme Heat pump type Electric Wiring Diagram Accept change >Select A2 The hydraulic and electroplans must be set by the installer during initial commissioning. 3 The heat pump type has already been set at the fac5 tory and may not be changed! 1 Yes Hydraulic plan: 1 = no buffer cylinder, no DHW cylinder 2 = with buffer cylinder, no DHW cylinder 3 = no buffer cylinder, with DHW cylinder 4 = with buffer cylinder, with DHW cylinder See Figs. 6.8 to 6.11. Heat pump type: Type Description 29 VWS 61/2 230 V 30 VWS 81/2 230 V 31 VWS 101/2 230 V Electroplan: 1 = all on the high tariff (see Fig. 6.2). 2 = low tariff for the compressor (see Fig. 6.3). 3 = low tariff for the compressor and electric auxiliary heating (see Fig. 6.4). Accept change: Yes/No; "Yes" means that all the set values will be saved. Table 8.4 Parameters that can be set in the Code level (cont.) 62 Installation instructions geoTHERM VWS 0020046310_01